VRV - Daikin - HW - Fxaq
VRV - Daikin - HW - Fxaq
VRV - Daikin - HW - Fxaq
FXAQ-AVM
60 Hz
FXAQ-AVM VRV INDOOR UNIT
FXAQ-AVM
Wall Mounted Type
60 Hz
1. Lineup..........................................................................................................2
2. Specifications..............................................................................................3
3. Dimensions..................................................................................................6
4. Piping Diagrams..........................................................................................9
5. Wiring Diagrams........................................................................................10
6. Electric Characteristics..............................................................................11
7. Safety Devices Setting..............................................................................12
8. Capacity Tables.........................................................................................13
8.1 Cooling Capacity for Te: Auto..........................................................13
8.2 Cooling Capacity for Te: 6°C...........................................................13
8.3 Cooling Capacity for Te: 9°C...........................................................14
8.4 Heating Capacity..............................................................................14
9. Sound Levels.............................................................................................15
10.Centre of Gravity.......................................................................................18
1
FXAQ-AVM VRV INDOOR UNIT
1. Lineup
VM : 1 phase, 220-230 V, 60 Hz
2
FXAQ-AVM VRV INDOOR UNIT
2. Specifications
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB, 15°CWB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m,
kcal/h=kW×860
level difference: 0 m. Btu/h=kW×3412
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
+4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During l/s=m³/min×1000/60
actual operation, these values are normally somewhat higher as a result of ambient conditions.
3
FXAQ-AVM VRV INDOOR UNIT
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB, 15°CWB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m,
kcal/h=kW×860
level difference: 0 m. Btu/h=kW×3412
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
+4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During l/s=m³/min×1000/60
actual operation, these values are normally somewhat higher as a result of ambient conditions.
4
FXAQ-AVM VRV INDOOR UNIT
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB, 15°CWB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m,
kcal/h=kW×860
level difference: 0 m. Btu/h=kW×3412
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
+4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During l/s=m³/min×1000/60
actual operation, these values are normally somewhat higher as a result of ambient conditions.
5
FXAQ-AVM VRV INDOOR UNIT
3. Dimensions
3D122217
6
FXAQ-AVM VRV INDOOR UNIT
FXAQ40AVM / FXAQ50AVM
Unit: mm
3D122237
7
FXAQ-AVM VRV INDOOR UNIT
FXAQ63AVM
Unit: mm
3D122240
8
FXAQ-AVM VRV INDOOR UNIT
4. Piping Diagrams
4D034245R
Unit: mm
Model Gas Liquid
FXAQ20AVM / FXAQ25AVM / FXAQ32AVM / FXAQ40AVM / FXAQ50AVM φ12.7 φ6.4
FXAQ63AVM φ15.9 φ9.5
9
FXAQ-AVM VRV INDOOR UNIT
5. Wiring Diagrams
3D120333A
10
FXAQ-AVM VRV INDOOR UNIT
6. Electric Characteristics
3D122088A
11
FXAQ-AVM VRV INDOOR UNIT
12
FXAQ-AVM VRV INDOOR UNIT
8. Capacity Tables
8.1 Cooling Capacity for Te: Auto
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
13
FXAQ-AVM VRV INDOOR UNIT
For VRV indoor units only at Te: 9°C / mixed combination of VRV and residential indoor units
Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXAQ20AVM 20 1.0 1.0 1.2 1.2 1.5 1.5 1.7 1.6 1.7 1.5 1.9 1.6 1.9 1.6
FXAQ25AVM 25 1.3 1.3 1.6 1.6 1.9 1.9 2.1 1.9 2.2 1.8 2.4 1.8 2.5 1.7
FXAQ32AVM 32 1.7 1.6 2.0 1.9 2.5 2.2 2.7 2.2 2.8 2.1 3.0 2.2 3.2 2.1
FXAQ40AVM 40 2.0 2.0 2.5 2.5 3.1 2.9 3.5 3.0 3.6 2.9 3.9 2.9 4.1 2.7
FXAQ50AVM 50 2.6 2.5 3.1 3.0 3.9 3.5 4.3 3.6 4.6 3.6 4.8 3.5 5.0 3.2
FXAQ63AVM 63 3.3 3.1 3.9 3.8 5.0 4.3 5.6 4.6 5.8 4.5 6.2 4.4 6.4 4.0
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
14
FXAQ-AVM VRV INDOOR UNIT
9. Sound Levels
FXAQ20AVM
4D122383A
FXAQ25AVM
4D122384A
15
FXAQ-AVM VRV INDOOR UNIT
FXAQ32AVM
4D122385A
FXAQ40AVM
4D122386A
16
FXAQ-AVM VRV INDOOR UNIT
FXAQ50AVM
4D122387A
FXAQ63AVM
4D122388A
17
FXAQ-AVM VRV INDOOR UNIT
10.Centre of Gravity
Unit: mm
4D112526
18
FXAQ-AVM VRV INDOOR UNIT
Unit: mm
EDTFMT391910
4D112525
19