C LC Catalogue
C LC Catalogue
C LC Catalogue
International Standards
Series C-LC cooling towers have been designed according to the international standards featuring light weight
structure, easy transport, easy lifting and easy site installation.
Low Noise & Easy Maintenance
Series C-LC cooling towers use high tension V-belt reducers, which correspond to the low noise axial flow fans
featuring silent operation and easy maintenance.
Light Weight, Less Space and Multi-Cell Installation
Comparing with other types of closed circuit cooling tower, C-LC features lighter operational weight and less
installation space. Also the combinative multi-cell structure is suitable for large cooling requirement and future
expansion.
Unique Distribution System & Efficient Heat Exchange
Gravitational distribution systems features low pressure and slow water flow which can prolong cooling duration
and ensure cooling efficiency.
Efficient Performance
Unique design of vacuum-formed and round-chorded filling with ripple surface facilitate even spread and long
duration of water drop and free of deposits and scales.
Low Electrical Power Consumption
The high efficient hydrodynamic "venturi-tube" fan stack with high efficient low-resistance filling facilitates good
ventilation and reduction of fan motor power to save electrical power.
Long Service Life
C-LC tower components are made of weatherproof and anticorrosive materials. Casing is constructed of anti
ultraviolet P.V.C. which features soundproof and non-decayed merits with fine streamline outlook. Fan stack,
basin and access door are made by F.R.P. Filling and inlet louvers are made of P.V.C. Supporting rack is made
of light weight steel. All the steel parts are hot dip galvanized so as to prolong the service life.
Easy Inner Piping Arrangement & Low Piping Cost
Instead of outer piping arrangement, C-LC provides an inner piping arrangement, which keeps the outer
maintenance area pipe free so that it is easier and safer for people to maintain the tower, and it can save the
cost of outer piping work.
Heat Exchange Coil Pack
Heat exchange coil packs are made of seamless deoxidized copper tubes with best heat transfer efficiency and
anticorrosion. The copper construction offers a non corrosive coil for extended service life. Instead of single heat
exchange coil pack in each side of tower, it is divided into 4~5 sets of heat exchange packs so that they are light
in weight which is easy to be dismantled and offer a flexible operation that in case one or some of them need to
be repaired the rest of coil packs can still work normally.
Structure and Standard Materials
Motor Support(Hot Dip Gal Steel)
Fan Guard(Hot Dip Gal Steel)
Expansion Tank(F.R.P)
Fan Stack(F.R.P)
Speed Reducer
Motor
Flow Control Valve(ABS+ST.S)
Distribution Box(F.R.P)
Hot Water Basin(F.R.P) Ladder(Hot Dip Gal Steel)
Eliminator
Fan
Coil(CU)
Infill(P.V.C)
Sump(F.R.P)
Walkway(Hot Dip Gal Steel)
-1-
Recommended Concrete Foundations
-2-
Dimensions and Standard Specifications
C-LC-02101~05103
C-LC-07201~10203
-3-
C-LC-10204~15205
C-LC-15206~20207
-4-
Dimensions
Model Internal
Nominal Fan Dia. Fan Motor
Number Coil Flow Rate Width(mm) Length(mm) Height(mm)
Ton*1 (mm) (HP)
(LPM)
C-LC- W L h H
02101 50 650 2745 2360 3690 4510 1300 2
05102 60 780 2845 2660 3690 4500 1500 5
05103 67 871 2845 2960 3690 4500 1500 5
07201 104 1352 4080 2360 3690 4550 1700 7 1/2
07202 122 1586 4380 2660 3690 4570 2000 7 1/2
10203 135 1755 4380 2960 3690 4570 2000 10
10204 195 2535 4780 2960 4370 5730 2360 10
15205 210 2730 4780 2960 4370 5795 2360 15
15206 255 3315 5580 3770 4370 5895 2970 15
20207 275 3575 5580 3770 4370 6005 2970 20
(KG) (KG)
C-LC- (H1) (C1) (D) (O) (A) (M)
02101 4B(100A) 4B(100A) 2B(50A) 2B(50A) 1/2B(15A) 1/2B(15A) 1150 2950
05102 4B(100A) 4B(100A) 2B(50A) 2B(50A) 1/2B(15A) 1/2B(15A) 1450 3350
05103 4B(100A) 4B(100A) 2B(50A) 2B(50A) 3/4B(20A) 3/4B(20A) 1750 3750
07201 5B(125A) 5B(125A) 2B(50A) 2B(50A) 3/4B(20A) 3/4B(20A) 2000 4400
07202 5B(125A) 5B(125A) 2B(50A) 2B(50A) 3/4B(20A) 3/4B(20A) 2400 5200
10203 6B(150A) 6B(150A) 2B(50A) 2B(50A) 1B(25A) 1B(25A) 2600 5600
10204 6B(150A) 6B(150A) 2B(50A) 2B(50A) 1B(25A) 1B(25A) 3680 7490
15205 6B(150A) 6B(150A) 2B(50A) 2B(50A) 1B(25A) 1B(25A) 3700 7510
15206 8B(200A) 8B(200A) 2B(50A)×2 2B(50A)×2 3/4B(20A)×2 3/4B(20A)×2 5810 11480
20207 8B(200A) 8B(200A) 2B(50A)×2 2B(50A)×2 1B(25A)×2 1B(25A)×2 6000 11770
-6-
-7-
-8-
-9-
-10-