FT Motor Diagnosis

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

FT Menu B85 Motor Diagnosis

***Dornier Service Card needed to access this data!***

Menu B85 Motor Diagnosis


Backup Eplan
LVM = Main Power Supply G1
EWM1 = Main Drive Motor M1 Main Drive Motor
Loom
FBM1 = Shedding Drive Motor M2 Shedding Drive
(Jacquard)
TU = Takeup ECT = Takeup
WLO = Warp-Let-Off EWL = Warp-Let-Off
SSMCC = Start Stop Module Kuppling / Clutch
clutch
SSMBR = Start Stop Module Bremse / Brake
Brake

From software version FT01.002.001:


Explanation:
In the Acopos, B & R constantly monitors the measured resolver signal as to whether the amplitude is
within the valid tolerance range. An amplitude of 100% is expected, whereby the coupling factor of 0.5
is already included.
If the amplitude falls below the 80% limit, the error becomes
****** 9805, angular position sensor defective, B & R code 7032, signal amplitude too small *****

If amplitude exceeds 115% limit we the error


****** 9805, angular position sensor defective, B & R code 7031, signal amplitude too high *****

Resolver Signal
ex. 95,0 = 95.0 %
FT Menu B85 Motor Diagnosis

Resolver Signal
ex. 635 = 63.5%

Variations in the amplitude occur naturally. But to have enough distance to the error
limits,
The measured values should be in the range for each engine
90% - 105% lie
This gives us 10% reserve for the error limits.
In addition, minimum and maximum values should not differ more than 5% while the
engine is running.
Reasons for a greater deviation could be:
- magnetic interference brake <-> resolver
- bad mounting of the resolver
- Bearing damage in the engine
By the way:
Only the diagnostic values of the currently selected drive are written into the backup
If a new drive is selected, the minimum,

Either the resolver in the motor has a problem or it is due to the resolver card card of the module
-A1 in the control cabinet or the wiring, especially the plug, between motor resolver and module -
A1 have a contact problem.