Jacuzzi Design Calculation
Jacuzzi Design Calculation
Jacuzzi Design Calculation
The design of Jacuzzi is same as the design of swimming pool but with small change
in it there is Air Blower, Domestic Booster Pump , Skimmer, Jet Nozzle
According to Egyptian code for Swimming Pool 1 Skimmer for each 46.5 m2 from
Surface Water for Swimming Pool
Got No. of Skimmer = 1 Unit
Assuming 50% of water suck from skimmer & 50% will suck from floor drains outlet
Got Flow Rate will discharge in pipes = 0.275 m3/min
Suction pipe maximum velocity will be 1.2 m/s from skimmer & drain outlet
Pump flow rate = 16.5 m3/hr
No. Of outlet = 2 Outlet
Each outlet give flow rate = 8.25 m3/hr
NOTE :-
No. of pipe will be taken according to No. of outlet for 2 outlet in series take to Dia 2
Supply pipe maximum velocity will be 2 m/s
Pump flow rate = 16.5 m3/hr
No. Of inlets = 1 Inlets
Each Inlet give flow rate = 16.5 m3/hr
NOTE :-
No. of pipe will be taken according to No. of outlet for 2 outlet in series take to Dia 2
Heater is required for heating purposes at winter seasons if required take inconsideration that
it's not particle to heat the pool without covers at coldest winter months
For calculation purposes the following conditions to be considered:-
The recommended Pool water temperature is around 28 º C deg.
Outdoor air condition : 46 / 30 deg º C DB/WB –summer condition, max 122deg F (50 C)
: 6/ 10 deg º C BD/WB -winter condition
From SPATA p5, Sec3, the Average Daily heat loss (DH) in KWhr / m2 of pool surface area
Correction Value Will be Changed According to type of Swimming Pool And it`s Location
= Heater required Pool Volume * 1000 * ( Tc2 - Tc1) / ( 860 * Available Heating Hour)
= 9.9 * 1000 * ( 28 - 10 ) / 860 * 24
= 10.8 Kw
For cooling purpose in summer seasons chilled water is required to cooling the water
temperature in summer to recommended temperatures
The recommended Pool water temperature is around 28 deg º C
Outdoor air condition : 46 / 30 deg º C DB/ WB - summer condition , Max 122 deg º F
: 10 / 06 deg º C DB/ WB - winter condition
During summer time the outdoor air temperature will be around 45 deg º C and hence the
water temperature will be the same
So to estimate the cooling load required for the chiller to reduce water temperature to
28 deg º C will be two part as following
The first part is the cooling load required to reduce the water temperature
to 28 deg º C as following
from SPATA tables there is no information about heat loss from pool areas the gulf area
condition the available data only at 15deg º C out door temp which is = 3.48 KWhr/m 2
Assuming linearity condition the excepted heat loss at 45deg º C =
(45/15) x 3.48 = 10.44 KWhr/m2
Q2 =1.25 * 11 * 10.44 / 72
= 2 Kw
Assuming Booster pump Capacity equal to 80% from Filtration pump Capacity
Filtration Pump Capacity = 0.55 m3/min
Suction pipe maximum velocity will be 1.2 m/s from skimmer & drain outlet
Pump flow rate = 26.4 m3/hr
No. Of outlet Floor Drains = 3 Outlet
Each outlet give flow rate = 8.8 m3/hr
NOTE :-
No. of pipe will be taken according to No. of outlet for 2 outlet in series take to Dia 2
NOTE :-
No. of pipe will be taken according to No. of outlet for 2 outlet in series take to Dia 2
NOTE :-
No. of pipe will be taken according to No. of jet nozzel for 2 nozzel in series take to Dia 2