160kw VFD Panel
160kw VFD Panel
160kw VFD Panel
INFORMATION SHEET
A A
GOLA SOLUTIONS
At Post - MIA Desoola Industrial Area
Dist. Alwar - 301030 ,RAjasthan, Bharat
E-mail: gajendra.golasolutions@gmail.com
Tel : +91 6350443830
B B
PROJECT -
C
CUSTOMER Carlsberg India Pvt Ltd (Raj Brewery) C
JOB NUMBER -
PANEL SR. NO. GS/LTS/P-021
MANUFACTURER GOLA SOLUTIONS , RAJASTHAN-301030
D D
Number of pages 5
A A
50 295 50
125
B B
345
215
334,8 R-PHASE Y-PHASE B-PHASE MAIN TRIP
75
ENERGY METER
92
MFM
92
150
VFD Display
MCB
PVC (25X60) EMG. STOP
C C
150
1300
VFD VFD
VFD TRIP
PANEL
1400
STOP START
PVC (25X60)
AC
855
MCCB
500A
MCCB
TERMI A
D D
207
930
1000
600 1000 600
75
MOUNTING
E R.H.S. VIEW PLATE E
FRONT VIEW L.H.S. VIEW
A A
Q1,MCB
Q2,MCB
DP,16A
DP,02A
B B
MFM
C C
160kW,3Ø
VFD
500A,36kA
MCCB ,FP
LAMP
R,Y,B
D D
E E
MAIN INCOMMER 160KW 220VAC 220VAC
415VAC,3PH+N VFD Air CONTROL
Conditioning SUPPLY
SUPPLY TO LOAD
N
A A
415VAC
B
0701
R
AUX. SUPPLY
2
EMG.STOP
220VAC
N
R
B
R
R
Y
0AC
1
B B
V3
V2
V1
Q4 Q6
N
L
VFD-1
STOP
6A 6A
220VAC
N
R
Y
MFM 1.5SQMM
2.5SQMM
I1
I2
I3
0702
220VAC
220AC
S1
S2
S1
S2
S1
S2
1AC
0AC
220VAC
5.6D
VFD 220V AC
3S1
3S2
2S1
2S2
1S1
1S2
C 160kW C
CONTROL
0R1
START
VFD-1
SUPPLY 6.2E 9
S1
125/5A, 5.6D
5 1
0CT3 0AC
S2
S1
125/5A,
0CT2
S2
0DC
0703
S1
220VAC
0AC
1Y2
125/5A,
1B2
1R2
D 0CT1 D
S2
8 6 4 2
TRIP INDICATOR
MCCB
MCCB TRIP A1
CONTACT
0R1
X1
X2
NC R
7 5 3 1
X2:1
Ø X2:2
X2:3
A2
X1
X2
TO PANEL TO 220VAC
Ø
0AC
X1
X2
E E
AC POWER SUPPLY VFD
START/ STOP
X1
X2
NØ
BØ
RØ
YØ
R,Y,B 5
LAMP 1 9
6
1.0SQMM
Ø
X1:3 Ø
2 10
X1:4
X1:1
X1:2
MAIN INCOMMER
415VAC,3Ø+N
F *Do not modify Manually* F
2 Start Date 15-05-2024 PROJECT: 160kV VFD panel GOLA SOLUTIONS Dwg.No: GS/LTS/P-021
=
1 Drawn by GSG CUSTOMER: Carlsberg India Pvt Ltd (Raj Brewery) At Post - MIA Desoola Industrial Area Page 4
0 Checked by GSG Dist. Alwar - 301030 ,RAjasthan, Bharat Page Title: Scheme total Page 4
E-mail: gajendra.golasolutions@gmail.com POWER AND CONTROL WIRING
Rev Change Date Name Approved by GSG Total Page 5
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
B B
0704
220AC
220AC
0707
0708
0709
0705
0706
C C
10
0R1
2
24DC
D D
4.5D
X1 X1 X1
TO 4-20mA
FROM FIELD X2 X2 X2
E E
0AC 0AC
INDICATION
INDICATION
INDICATION
VFD TRIP
VFD STOP
VFD RUN