Schneider - Electric METSEPM1200 Datasheet
Schneider - Electric METSEPM1200 Datasheet
Schneider - Electric METSEPM1200 Datasheet
Main
Range of product PowerLogic PM1000
Device short name PM1200
Product or component Power meter
type
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Complementary
Type of measurement Power factor
Active and reactive energy
Active and reactive power
Frequency
Voltage
Current
Supply voltage 44...277 V DC
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
44...277 V AC (50/60 Hz)
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Network frequency 50/60 Hz
Power consumption in VA < 3 VA at 240 V AC
Display type LED, digital
Display resolution 3 lines with 4 digits
Sampling rate 20 samples/cycle
Measurement current 50 mA...6 A
Input type Current 0...1 A (impedance <= 0.1 Ohm)
Current 0...5 A (impedance <= 0.1 Ohm)
Measurement voltage 0 V...999 kV AC 50/60 Hz with external VT
80...480 V AC 50/60 Hz phase to phase
Measurement accuracy 1 % apparent power
1 % power factor
0.1 % frequency
1 % energy
1 % voltage
1 % current
1 % power
Accuracy class Class 1 (active energy according to IEC 62053-21)
Class 2 (reactive energy according to IEC 62053-23)
Communication port protocol Modbus
Communication port support RS485
Transmission rate 19.2 kbauds
Mar 9, 2013
1
Environment
Electromagnetic compatibility Immunity to microbreaks and voltage drops, conforming to IEC 61000-4-11
Conducted and radiated emissions class A, conforming to CISPR 11
1.2/50 µs shock waves immunity test, conforming to IEC 61000-4-5
Conducted RF disturbances, conforming to IEC 61000-4-6
Electrical fast transient/burst immunity test, conforming to IEC 61000-4-4
Susceptibility to electromagnetic fields, conforming to IEC 61000-4-3
Electrostatic discharge immunity test, conforming to IEC 61000-4-2
Immunity to impulse waves, conforming to IEC 61000-4-12
Mounting mode Flush-mounted
Type of installation Indoor installation
Overvoltage category III
IP degree of protection IP40 (back) conforming to IEC 60529
IP51 (front face) conforming to IEC 60529
Relative humidity 5...95 %
Ambient air temperature for operation -10...60 °C
Ambient air temperature for storage -25...70 °C
Operating altitude 0...2000 m
Standards IEC 62053-21
IEC 62052-11
Width 96 mm
Depth 80 mm (embedded)
Height 96 mm
Product weight 0.4 kg