3G3RX-E1F Discontinue Notice
3G3RX-E1F Discontinue Notice
3G3RX-E1F Discontinue Notice
Correction Reissue
2
[ Body color ]
Product discontinuation Recommendable replacement
Model 3G3RX-[]-E1F Model 3G3RX2-[]
3G3RX-[]-E1F 3G3RX2-[]
Black. Black.
[ Wire connection ]
Product discontinuation Recommendable replacement
Model 3G3RX-[]-E1F Model 3G3RX2-[]
3G3RX-[]-E1F 3G3RX2-[]
Circuit Diagram Main Circuit Diagram
3
[ Difference of Terminal Block ]
Control Circuit Terminal Block
Product discontinuation Recommendable replacement
Item
Model 3G3RX-[]-E1F Model 3G3RX2-[]
By factory default, the terminal FW and the
multi-function input terminals are set to sink logic
Changing (NPN).
You can switch between the sink logic and
input To change the input control logic to source logic
source logic for input terminals by using SW6.
control (PNP), remove the short-circuit bar between the
(The default setting is source logic.)
logic terminals P24 and PLC on the control circuit
terminal block, and connect it between the
terminals PLC and CM1.
- Backup 24 V power supply terminal
Additional
- 1a relay terminal
function
- Function safety terminal
4
[ Difference of Terminal Block ]
Product discontinuation Recommendable replacement
Model 3G3RX-[]-E1F Model 3G3RX2-[] Remarks
Terminal Terminal name Terminal Terminal name
1 1
2 2
3 3
4 4
Multi-function input
5 5
6 6 Input terminal
7 7
8 8
Forward RUN On 3G3RX2, FW signal is set on the input
FW 9
command terminal terminal ”9”.
Multi-function input Common for input
PLC COM
common terminal
11 11
12 12
Multi-function
13 13 Output terminal
output
14 14
15 15
Multi-function Common for output
CM2 CM2
output common terminal
On 3G3RX-E1F, By factory default,
AL2 AL0 Multi-function Relay Output (AL2, AL1)
Multi-function relay
Operation Selection (C036) is set at NC
output Select
AL1 AL1 contact between AL2 and AL0, and NO
1c relay terminal contact between AL1 and AL0.
On 3G3RX2, by factory default,
Multi-function relay Relay output terminal function selection
AL0 AL2 a/b (NO/NC) selection (CC-17) is set at
output common
NO contact between AL0 and AL2.
External thermistor External thermistor
TH TH+
input terminal Input
- 16A NO contact relay added to 3G3RX2.
- 1a relay terminal You can select the function by setting the
- 16C parameter of output terminal 16.
[ Mounting dimensions ]
Product discontinuation Recommendable replacement
Model 3G3RX-[]-E1F Model 3G3RX2-[]
Mounting dimensions for 3G3RX-[]-E1F and 3G3RX2-[] are same.
Model Width Height Screw
A2004/A2007/A2015/A2022/A2037/A4004(3G3RX)/A4007/A4015/A4022/A4037 130 241 M5
A2055/A2075/A2110/A4055/A4075/A4110 189 246 M6
A2150/A2185/A2220/A4150/A4185/A4220 229 376 M6
A2300/A4300 265 510 M8
A2370/A2450/A4370/A4450/A4550 300 520 M10
A2550 380 670 M10
B4750/B4900 300 670 M10
B411K/B413K 380 710 M10
5
[ Dimensions ]
Product discontinuation Recommendable replacement
Model 3G3RX-[]-E1F Model 3G3RX2-[]
3G3RX-A2004-E1F/A2007-E1F/A2015-E1F/ 3G3RX2-A2004/A2007/A2015/A2022/A2037/A4007/
A2022-E1F/A2037-E1F/A4004-E1F/ A4015/A4022/A4037
A4007-E1F/A4015-E1F/A4022-E1F/
A4037-E1F
6
[ Dimensions ]
Product discontinuation Recommendable replacement
Model 3G3RX-[]-E1F Model 3G3RX2-[]
3G3RX-A2055-E1F/A2075-E1F/A2110-E1F/ 3G3RX2-A2055/A2075/A2110/A4055/A4075/A4110
A4055-E1F/A4075-E1F/A4110-E1F
7
[ Dimensions ]
Product discontinuation Recommendable replacement
Model 3G3RX-[]-E1F Model 3G3RX2-[]
3G3RX-A2150-E1F/A2185-E1F/A2220-E1F/ 3G3RX2-A2150/A2185/A2220/A4150/A4185/A4220
A4150-E1F/A4185-E1F/A4220-E1F
8
[ Dimensions ]
Product discontinuation Recommendable replacement
Model 3G3RX-[]-E1F Model 3G3RX2-[]
3G3RX-A2300-E1F/A4300-E1F 3G3RX2-A2300/A4300
9
[ Dimensions ]
Product discontinuation Recommendable replacement
Model 3G3RX-[]-E1F Model 3G3RX2-[]
3G3RX-A2370-E1F/A2450-E1F/A4370-E1F/ 3G3RX2-A2370/A2450/A4370/A4450/A4550
A4450-E1F/A4550-E1F
10
[ Dimensions ]
Product discontinuation Recommendable replacement
Model 3G3RX-[]-E1F Model 3G3RX2-[]
3G3RX-A2550-E1F 3G3RX2-A2550
11
[ Dimensions ]
Product discontinuation Recommendable replacement
Model 3G3RX-[]-E1F Model 3G3RX2-[]
3G3RX-B4750-E1F/B4900-E1F 3G3RX2-B4750/B4900
12
[ Dimensions ]
Product discontinuation Recommendable replacement
Model 3G3RX-[]-E1F Model 3G3RX2-[]
3G3RX-B411K-E1F/B413K-E1F 3G3RX2-B411K/B413K
13
[ Characteristics ]
Product discontinuation Recommendable replacement
Item Model 3G3RX-[]-E1F Model 3G3RX2-[]
A2004 A2007 A2015 A2022 A2004 A2007 A2015 A2022
Applicable motor CT 0.4 0.75 1.5 2.2 ND 0.4 0.75 1.5 2.2
(4-pole) capacity VT 0.75 1.5 2.2 3.7 LD 0.75 1.5 2.2 3.7
[kW] VLD 0.75 1.5 2.2 3.7
Rated input 3-phase: 200 V -15% to 240 V 10%, 3-phase: 200 V -15% to 240 V 10%,
voltage 50/60 Hz ±5% 50/60 Hz ±5%
CT 3.3 5.5 8.3 12 ND 3.8 6.0 9.5 13.1
Rated input
VT 3.9 7.2 10.8 13.9 LD 4.4 7.5 11.2 14.3
current [A]
VLD 5.2 9.5 12.4 18.6
Rated output 3-phase (3-wire) 200 to 240 V 3-phase (3-wire) 200 to 240 V
voltage (depending on receiving voltage) (depending on receiving voltage)
CT 3.0 5.0 7.5 10.5 ND 3.2 5.0 8.0 11.0
Rated output
VT 3.7 6.3 9.4 12 LD 3.7 6.3 9.4 12.0
current [A]
VLD 4.4 8.0 10.4 15.6
CT (Heavy Load) -10 to 50°C ND (Normal Duty) -10 to 50°C
Operating ambient
VT (Light Load) -10 to 40°C LD (Low Duty) -10 to 45°C
temperature
VLD (Very Low Duty) -10 to 40°C
Storage ambient
-20 to 65°C -20 to 65°C
temperature
Operating ambient 20% to 90%RH 20% to 90%RH
humidity (location free of condensation) (location free of condensation)
14
[ Characteristics ]
Product discontinuation Recommendable replacement
Item Model 3G3RX-[]-E1F Model 3G3RX2-[]
A2150 A2185 A2220 A2300 A2150 A2185 A2220 A2300
Applicable motor CT 15 18.5 22 30 ND 15 18.5 22 30
(4-pole) capacity VT 18.5 22 30 37 LD 18.5 22 30 37
[kW] VLD 18.5 22 30 37
Rated input 3-phase: 200 V -15% to 240 V 10%, 3-phase: 200 V -15% to 240 V 10%,
voltage 50/60 Hz ±5% 50/60 Hz ±5%
CT 70 84 105 133 ND 76.2 90.5 113.1 145.2
Rated input
VT 80 94 120 150 LD 86.9 101.2 134.5 166.7
current [A]
VLD 95.2 110.7 147.6 182.1
Rated output 3-phase (3-wire) 200 to 240 V 3-phase (3-wire) 200 to 240 V
voltage (depending on receiving voltage) (depending on receiving voltage)
CT 64 76 95 121 ND 64.0 76.0 95.0 122
Rated output
VT 73 85 113 140 LD 73.0 85.0 113 140
current [A]
VLD 80.0 93.0 124 153
CT (Heavy Load) -10 to 50°C ND (Normal Duty) -10 to 50°C
Operating ambient
VT (Light Load) -10 to 40°C LD (Low Duty) -10 to 45°C
temperature
VLD (Very Low Duty) -10 to 40°C
Storage ambient
-20 to 65°C -20 to 65°C
temperature
Operating ambient 20% to 90%RH 20% to 90%RH
humidity (location free of condensation) (location free of condensation)
15
[ Characteristics ]
Product discontinuation Recommendable replacement
Item Model 3G3RX-[]-E1F Model 3G3RX2-[]
A4004 A4007 A4015 A4022 - A4007 A4015 A4022
Applicable motor CT 0.4 0.75 1.5 2.2 ND - 0.75 1.5 2.2
(4-pole) capacity VT 0.75 1.5 2.2 3.7 LD - 1.5 2.2 3.7
[kW] VLD - 1.5 2.2 3.7
Rated input 3-phase: 380 V -15% to 480 V 10%, 3-phase: 380 V -15% to 500 V 10%,
voltage 50/60 Hz ±5% 50/60 Hz ±5%
CT 1.8 2.8 4.2 5.8 ND - 3.0 4.8 6.5
Rated input
VT 2.1 4.3 5.9 8.1 LD - 3.7 5.7 8.0
current [A]
VLD - 4.9 6.4 9.9
Rated output 3-phase (3-wire) 380 to 480 V 3-phase (3-wire) 380 to 500 V
voltage (depending on receiving voltage) (depending on receiving voltage)
CT 1.5 2.5 3.8 5.3 ND - 2.5 4.0 5.5
Rated output
VT 1.9 3.1 4.8 6.7 LD - 3.1 4.8 6.7
current [A]
VLD - 4.1 5.4 8.3
CT (Heavy Load) -10 to 50°C ND (Normal Duty) -10 to 50°C
Operating ambient
VT (Light Load) -10 to 40°C LD (Low Duty) -10 to 45°C
temperature
VLD (Very Low Duty) -10 to 40°C
Storage ambient
-20 to 65°C -20 to 65°C
temperature
Operating ambient 20% to 90%RH 20% to 90%RH
humidity (location free of condensation) (location free of condensation)
16
[ Characteristics ]
Product discontinuation Recommendable replacement
Item Model 3G3RX-[]-E1F Model 3G3RX2-[]
A4150 A4185 A4220 A4300 A4150 A4185 A4220 A4300
Applicable motor CT 15 18.5 22 30 ND 15 18.5 22 30
(4-pole) capacity VT 18.5 22 30 37 LD 18.5 22 30 37
[kW] VLD 18.5 22 30 37
Rated input 3-phase: 380 V -15% to 480 V 10%, 3-phase: 380 V -15% to 500 V 10%,
voltage 50/60 Hz ±5% 50/60 Hz ±5%
CT 35 42 53 64 ND 38.1 46.4 57.1 72.6
Rated input
VT 41 47 63 77 LD 44.0 51.2 67.9 83.3
current [A]
VLD 47.6 56.0 73.8 91.7
Rated output 3-phase (3-wire) 380 to 480 V 3-phase (3-wire) 380 to 500 V
voltage (depending on receiving voltage) (depending on receiving voltage)
CT 32 38 48 58 ND 32.0 39.0 48.0 61.0
Rated output
VT 37 43 57 70 LD 37.0 43.0 57.0 70.0
current [A]
VLD 40.0 47.0 62.0 77.0
CT (Heavy Load) -10 to 50°C ND (Normal Duty) -10 to 50°C
Operating ambient
VT (Light Load) -10 to 40°C LD (Low Duty) -10 to 45°C
temperature
VLD (Very Low Duty) -10 to 40°C
Storage ambient
-20 to 65°C -20 to 65°C
temperature
Operating ambient 20% to 90%RH 20% to 90%RH
humidity (location free of condensation) (location free of condensation)
17
[ Characteristics ]
Product discontinuation Recommendable replacement
Item Model 3G3RX-[]-E1F Model 3G3RX2-[]
B4900 B411K B413K B4900 B411K B413K
Applicable motor CT 90 110 132 ND 90 110 132
(4-pole) capacity VT 110 132 160 LD 110 132 160
[kW] VLD 110 132 160
Rated input 3-phase: 380 V -15% to 480 V 10%, 3-phase: 380 V -15% to 500 V 10%,
voltage 50/60 Hz ±5% 50/60 Hz ±5%
CT 194 239 286 ND 214.3 258.3 309.5
Rated input
VT 199 253 300 LD 232.1 273.8 345.2
current [A]
VLD 253.6 300.0 376.2
Rated output 3-phase (3-wire) 380 to 480 V 3-phase (3-wire) 380 to 500 V
voltage (depending on receiving voltage) (depending on receiving voltage)
CT 176 217 260 ND 180 217 260
Rated output
VT 195 230 290 LD 195 230 290
current [A]
VLD 213 252 316
CT (Heavy Load) -10 to 50°C ND (Normal Duty) -10 to 50°C
Operating ambient
VT (Light Load) -10 to 40°C LD (Low Duty) -10 to 45°C
temperature
VLD (Very Low Duty) -10 to 40°C
Storage ambient
-20 to 65°C -20 to 65°C
temperature
Operating ambient 20% to 90%RH 20% to 90%RH
humidity (location free of condensation) (location free of condensation)
[ Operation ratings ]
Product discontinuation Recommendable replacement
Model 3G3RX-[]-E1F Model 3G3RX2-[]
Item
A2004 to A2550 B4750 to A2004 to A2550 B4750 to
A4004 to A4550 B413K A4007 to A4550 B413K
CT 0.5 to 15 kHz 0.5 to 10 kHz ND 0.5 to 16.0 kHz 0.5 to 10.0 kHz
Carrier frequency
VT 0.5 to 12 kHz 0.5 to 8 kHz LD 0.5 to 12.0 kHz 0.5 to 8.0 kHz
change range
VLD 0.5 to 10.0 kHz 0.5 to 8.0 kHz
Output frequency
0.1 to 400 Hz 0.00 to 590.00 Hz
range
Digital command ±0.01% and Digital command ±0.01% and
Frequency
analog command ±0.2% (25°C±10°C) analog command ±0.2% (25°C±10°C)
precision
against the maximum frequency against the maximum frequency
Frequency Digital setting: 0.01 Hz Digital setting: 0.01 Hz
resolution Analog setting: maximum frequency/4000 Analog setting: maximum frequency/4000
Acceleration/
0.01 to 3600.0 s 0.00 to 3600.00 s
Deceleration time
[ Operation methods ]
There are some differences of operator, parameters, terminal blocks, default settings and options between
3G3RX-E1F and 3G3RX2.
Please refer to “Replace Guide From 3G3RX to 3G3RX2" (Man. No.: I922-E1), “High-function
General-purpose Inverter RX Series User’s Manual" (Man. No.: I560-E2) and “High-function
General-purpose Inverter RX2 Series User’s Manual" (Man. No.: I620-E1).
Specifications and prices in this product news are as of the issue date and are subject to change without notice.
Only main changes in specifications are described in this document. Please be sure to read the relevant catalogs, datasheets, product
specifications, instructions, and manuals for precautions and necessary information when using products.