BMS Point Schedule

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

BMS Point Schedule

I/O POINTS PERIPHERAL DEVICES Cables


S/N DESCRIPTION
AI DI AO DO Type/description Model No QTY Type
Package Units 2
Return Air Temp/RH 4 Duct Temp Sensor TB/TI-S 2 Single twisted pair-22AWG
Cooling Coil off Temp 2 Duct Temp Sensor TB/TI-S 2 Single twisted pair-22AWG
Heater coil off Temp 2 Duct Temp Sensor TB/TI-S 2 Single twisted pair-22AWG
Room Air Temp/RH 8 Space Temp sensor TB/TS 8 Single twisted pair-22AWG
Supply fan run status 2 ADPS DPSA-400 2 Single twisted pair-22AWG
Supply fan trip status 2 VFC from PACU Ctrl Pannel Single twisted pair-22AWG
Filter status 2 ADPS DPSA-400 2 Single twisted pair-22AWG
Stage ‐01 Run status 2 VFC from PACU Ctrl Pannel
Twisted, twin pair - 22AWG
Stage ‐02 Run Status 2 VFC from PACU Ctrl Pannel
Stage ‐03 Run status 2 VFC from PACU Ctrl Pannel
Twisted, twin pair - 22AWG
Stage ‐04 Run Status 2 VFC from PACU Ctrl Pannel
Stage ‐01 Trip status 2 VFC from PACU Ctrl Pannel
Twisted, twin pair - 22AWG
Stage ‐02 Trip Status 2 VFC from PACU Ctrl Pannel
Stage ‐03 Trip status 2 VFC from PACU Ctrl Pannel
Twisted, twin pair - 22AWG
Stage ‐04 Trip Status 2 VFC from PACU Ctrl Pannel
Stage-01 high pressure status 2 VFC from PACU Ctrl Pannel
Twisted, twin pair - 22AWG
stage-01 low pressure status 2 VFC from PACU Ctrl Pannel
Stage-02 high pressure status 2 VFC from PACU Ctrl Pannel
Twisted, twin pair - 22AWG
DMS 600x2 stage-02 low pressure status 2 VFC from PACU Ctrl Pannel
Stage-03 high pressure status 2 VFC from PACU Ctrl Pannel
Twisted, twin pair - 22AWG
stage-03 low pressure status 2 VFC from PACU Ctrl Pannel
Stage-04 high pressure status 2 VFC from PACU Ctrl Pannel
Twisted, twin pair - 22AWG
stage-04 low pressure status 2 VFC from PACU Ctrl Pannel
Packaged A/C Stage‐01 On/Off Ctrl 2 relay output from DDC 1.5mm2Single core flexible cables - 2 nrs
Packaged A/C Stage‐02 On/Off Ctrl 2 relay output from DDC 1.5mm2Single core flexible cables - 2 nrs
Packaged A/C Stage‐03 On/Off Ctrl 2 relay output from DDC 1.5mm2Single core flexible cables - 2 nrs
Packaged A/C Stage‐04 On/Off Ctrl 2 relay output from DDC 1.5mm2Single core flexible cables - 2 nrs
Duct Heater Stage‐01 On/Off Ctrl 2 relay output from DDC 1.5mm2Single core flexible cables - 2 nrs
Duct Heater Stage‐02 On/Off Ctrl 2 relay output from DDC 1.5mm2Single core flexible cables - 2 nrs
Duct Heater Stage‐03 On/Off Ctrl 2 relay output from DDC 1.5mm2Single core flexible cables - 2 nrs

1/4
BMS Point Schedule

I/O POINTS PERIPHERAL DEVICES Cables


S/N DESCRIPTION
AI DI AO DO Type/description Model No QTY Type
Duct Heater Stage‐04 On/Off Ctrl 2 relay output from DDC 1.5mm2Single core flexible cables - 2 nrs
Freez Stat 8 Twisted, twin pair - 22AWG
Exhaust fan A/M 2 Twisted, twin pair - 22AWG
Exhaust fan trip status 2 VFC from Exh.Fan Ctrl Pannel Single twisted pair-22AWG
Exhaust fan Run status 2 VFC from Exh.Fan Ctrl Pannel Single twisted pair-22AWG
Exhaust Fan On/Off Ctrl 2 relay output from DDC 1.5mm2Single core flexible cables - 2 nrs
Total 16 46 0 8 2650

2/4
BMS Point Schedule

Cables
Model

Beldon - 8761/Eqv.
Beldon - 8761/Eqv.
Beldon - 8761/Eqv.
Beldon - 8761/Eqv.
Beldon - 8761/Eqv.
Beldon - 8761/Eqv.
Beldon - 8761/Eqv.
Beldon - 8723/Eqv.

Beldon - 8723/Eqv.

Beldon - 8723/Eqv.

Beldon - 8723/Eqv.

Beldon - 8723/Eqv.

Beldon - 8723/Eqv.

Beldon - 8723/Eqv.

Beldon - 8723/Eqv.

1.5mm2Single core flexible cables - 2 nrs


1.5mm2Single core flexible cables - 2 nrs
1.5mm2Single core flexible cables - 2 nrs
1.5mm2Single core flexible cables - 2 nrs
1.5mm2Single core flexible cables - 2 nrs
1.5mm2Single core flexible cables - 2 nrs
1.5mm2Single core flexible cables - 2 nrs

3/4
BMS Point Schedule

Cables
Model
2
1.5mm Single core flexible cables - 2 nrs
Beldon - 8723/Eqv.
Beldon - 8723/Eqv.
Beldon - 8761/Eqv.
Beldon - 8761/Eqv.
2
1.5mm Single core flexible cables - 2 nrs