CIENTIFICO3
CIENTIFICO3
CIENTIFICO3
Email: federico.milano@ucd.ie
Dublin, Ireland
• AC voltages are first converted into dc, the power is then transmitted on a high voltage
dc line, and finally converted again into ac at the other side of the HVDC link.
AC transfs. AC transfs.
AC AC filters AC/DC DC filters Transmission DC filters DC/AC AC filters AC
system Protections Protections system
Converter Protections Line Protections Converter
1 Reactive Reactive 2
Power Power
Converter Converter
Controls Controls
System
Control
Vdc
T T
4 6 2 4 6 2 −
Anode
1 3 5 1 3 5
R S R S
T T
4 6 2 4 6 2
1 3 5 1 3 5
R S R S
T T
4 6 2 4 6 2
on off
T5 R1 S3 T5 R1 S3 T5 R1
Cathode
Neutral
Anode
S6 T2 R4 S6 T2 R4 S6 T2
Anode
id
+
vd
−
+
vg
−
Cathode
T5 R1 S3 T5 R1 S3 T5 R1
Cathode
α
Neutral
Anode
S6 T2 R4 S6 T2 R4 S6 T2
T S RS RT ST SR T R T S RS RT ST SR T R
Reference
vdc anode busbar
T5 R1 S3 T5 R1 S3 T5 R1
Cathode
Neutral
Anode
S6 T2 R4 S6 T2 R4 S6 T2
α = 90◦
T S RS RT ST SR T R T S RS RT ST SR T R
Reference
vdc = 0 anode busbar
T5 R1 S3 T5 R1 S3 T5 R1
Cathode
Neutral
Anode
S6 T2 R4 S6 T2 R4 S6 T2
α = 180◦
T S RS RT ST SR T R T S RS RT ST SR T R
Reference
anode busbar
vdc
• The transformer reactance xc and the constant current lead to commutation problems:
β
1 idc = const.
vc,S vc,R vc,T
+ xc,R +
i1
ic
vc,R α
xc,S 3 vdc µ
+ idc = const.
vc,S i1 i3
− − i3 − neutral
T S RS RT ST SR T R T S RS RT ST SR T R T S
vdc
i5 i1 i3 i5 i1 i3 i5 i1 Thyristor 1
idc current
i6 i2 i4 i6 i2 i4 i6 i2
idc
i1 i1 i1 Phase R
iR current
−i4 −i4
• Definitions:
◦ α Firing angle
◦ µ Overlap angle
◦ β On angle
◦ γ Extinction angle:
γ = 180◦ − α − µ
• The value of angle γ is associated with the valve extinction angle , i.e. the time these
valves have to turn off.
• As Idc is constant, the ac current has large harmonic content, as previously shown.
• This can be reduced by connecting in series two phase-shifter 6-pulse converters:
dc line
T1
ac grid
T2
• iac = iT 1 + iT 2
−π −π/2 idc π/2 π
iT 1
√
√ 2idc / 3
idc / 3
iT 2
√
idc / 3 π/3
idc
√ 2π/3
idc / 3 π/2
−π −π/2 0 π
iac
• The harmonic content in this signal is reduced by eliminating the 5th and 7th
harmonics:
1
2 3
amp · √
π
0
1 11 13 23 25
harmonic #
dc line
ac grid
• More terminals can be added leading to Multi-terminal HVDC links (e.g. Quebec-New
England, ±450 kV, 2000 MW, at least 3 terminals, 1990).
• Back-to-back (e.g. connection between Finnish and Russian high voltage systems,
Vyborg, 12-pulse, ±85 kV, 1420 MW, 1980-2001).
Source: http://en.wikipedia.org/wiki/File:HVDC_Europe.svg
+ +
vR,dc vI,dc
− −
1 : mR mI : 1 v̄k
v̄h
Rectifier Inverter
• Ac/dc devices not only separates the ac grid side from the dc one.
• They also fully separate the ac quantities and bases from dc ones.
• In the following, dc bases are considered fully decoupled from ac ones and base
conversions are taken into account in the equations of ac/dc devices.
ac ac
• All ac quantities are in pu with respect to ac bases, i.e., Vbase and Sbase , and all dc
dc dc
quantities are in pu with respect to dc bases, i.e., Vbase and Ibase .
ac
• Furthermore, Sbase = Sn ≈ Vndc Indc = Sbase
dc
holds to avoid inconsistencies.
• The rectifier scheme with current and voltage sign notation is shown below.
ph + jqh iR,dc
+
vR,dc
−
vh ∠θh 1 : mR
α
• Where φh is the angle between the average ac voltage and the ac current of the
rectifier, mR is the transformer tap ratio, and:
dc
Sbase
k̂s = ac (2)
Sbase
√ ac
2 Vbase
k̂v = 0.9995 · 3 dc
(3)
π Vbase
• Two additional equations are required to complete the converter model. These
equations model the controllers of the transformer tap ratio mR and the firing angle α
• The inverter scheme with current and voltage sign notation is shown below.
iI,dc pk + jqk
+
vI,dc
−
mI : 1 vk ∠θk
γ
• Equations (1) and (4) have to be rewritten to take into account the extinction angle or
commutation margin γ and the sign of the dc current on the inverter dc side.
• For the two-terminal scheme above: iI,dc = −iR,dc , hence one has:
where φk is the angle between the ac voltage and the ac current of the inverter.
• Since iI,dc < 0, the inverter injects active power and consumes reactive power at the
ac bus k .
• Observe that the ac power and voltage bases (as well as the system frequency) have
not to be necessarily the same as those used for recitifier ac-side quantities.
• As for the rectifier, two equations are required to complete the model. These equations
model the controllers of the transformer tap ratio mI and the extinction angle γ .
• HVDC controllers have to coordinate the operations of the rectifier and the inverter
devices.
• The controlling variables are the transformer tap ratio and the firing angle on the
rectifier side and the transformer tap ratio and the extinction angle on the inverter side.
• Tap ratio controls are necessarily slower than those of firing/extinction angles.
• The firing and extinction angles, which are characterized by fast dynamics, are
considered algebraic variables, while the tap ratio, whose dynamic is relatively slow,
are considered state variables.
• Inverter-side regulators maintain constant the extinction angle γ = γ ref ≥ γ min and
control the dc voltage vI,dc through the tap ratio mI .
0 = xR,α + Kp (iref
dc − idc ) − α
0 = γ ref − γ
• The PI control undergoes an anti-windup limiter in order to maintain the firing angle
within its limits.
• Rectifier-side regulators maintain constant the firing angle α = αmin and control the
dc voltage vR,dc through the tap ratio mR .
0 = xI,γ + Kp (iref m
dc + idc − idc ) − γ
where ides
dc = pref /vdc is the current that provides the desired reference power pref
and vdc is the dc voltage at one of the two converter terminals, and ilim
dc is defined
based on the dc voltage value, as follows:
min min
i
dc
, if v dc < v dc
ilim
dc = imin
dc + c(v dc − v min
dc ), if v min
dc ≤ v dc ≤ v max
dc
(10)
imin max min max
dc + c(vdc − vdc ), if vdc > vdc
Inverter
im
dc
0
0 iref
dc idc
• In RCCM, to obtain an operating point, the inverter can operate only in the constant
extinction angle γ control mode of operation.
• However, if the AC voltage at the rectifier bus drops, the αmin characteristics will fall
below the constant extinction angle γ characteristics.
• In this case, the inverter-side dc voltage is too high for the rectifier to be able to force a
current through the dc circuit.
• However, if the inverter is provided with a current control mode, there exists a new
operating point.
• This basic control mode for HVDC has been called the current margin control.
• in practice, im
dc ≈ 10%.
• We conclude from the discussion above that with the use of the current margin control:
• The station with the highest maximum voltage will control the current.
• The station with the lowest will determine the voltage.
• The VDCOL is a control mode that reduces the reactive power demand of the converter
when ac voltages are too low, and thus decreases the risk of a commutation failure.
• If vdc is too low, the VDCOL reduces idc , which lead to a in a reduction in p, and as a
result in a q reduction as well.
im
dc Inverter
OLi
VDC
OLr
VDC
0
0 iref
dc idc
B C
im
dc
Inverter
0
0 iref
dc idc
• The positive slope is important for the stability of the current control system.
• When the inverter is operating in the constant γ mode, the rectifier sees the inverter as
a negative impedance.
• For lower frequencies in the dc current fluctuations the characteristics A-C in the
previous figure has a negative slope.
• This means that the voltage across the inverter decreases with an increasing current.
• The exclusive use of the basic controls often gives rise to unwanted interaction
between the AC and DC systems, which is manifested in a variety of voltage, harmonic
and power instabilities.
• When full advantage is taken of the fast and adaptable converter controllability a more
useful interaction can be achieved which manifests itself in stable AC and DC system
operation.
• Voltage stability criteria are used to determine the type of voltage control and of
reactive power supply.
• The level of temporary overvoltage (TOV) influences station design, including thyristor
valve and surge arrester ratings. The TOV levels will increase with decreasing values
of the short-circuit ratio (SCR), the ratio of the AC system MVA fault at the converter
terminals to the nominal DC power.
• Shunt capacitors are used in converter stations as part of the AC filters and VAR
compensation. The larger the ratio of shunt capacitor MVAR to AC system short-circuit
MVA, the lower will be the resonant frequency.
• Recoveries from AC and DC faults are slower with weak systems (i.e. high-impedance
source), although modern controls are less affected by the system impedance than
those used in earlier schemes.
• The rectifier and the inverter consume reactive power, which can be typically 60% of
the power transmitted at full load.
• Following a voltage drop in the AC network, the initial effect is a fall in power.
• The power controller of the DC link then increases the current reference to try and
restore the ordered power; the extra current increases the reactive demand and tends
to reduce the AC system voltage further.
• With very weak AC systems this could lead to voltage collapse; however, power
controllers always have limits built in to avoid excessive action.
• An example of dynamic instability [15] is the northern and southern parts of the
Western US power system, which are connected by the parallel Pacific AC and DC
Interties with ratings of 2500 and 1400 MW, respectively.
• The AC Intertie has a long history of negatively damped 1/3 Hz oscillations resulting
from interactions between generators with automatic voltage regulators and system
loads.
• Damping in the Pacific Intertie was produced by small signal modulation of the DC
power in proportion to the frequency difference across the AC Intertie.
• An HVDC link, on the other hand, even with the basic controls, shields one system
from disturbances on the other.
• Although the specified power flow can continue, the option is available to vary the
power setting to help the system in difficulty to the extent which the healthy system can
allow, without putting itself in difficulty, and subject to the rating on the link.
• With the addition of series capacitor compensation in the AC network, however, the
negative damping contribution of the AC system is dramatically increased when the
electrical and mechanical resonant frequencies are close.
• Under these conditions the torsional modes of vibration can become unstable, a
phenomenon which is commonly referred to as sub-synchronous resonance (SSR).
• However, the interaction with DC systems can be solved relatively simply by providing
power modulation control to cancel the negative damping impact of the basic constant
power control loop.
• Active and Reactive Power Coordination: Coordination between the active and reactive
power modulation can be achieved by DC system voltage modulation. An increase in
DC voltage will increase the DC power transfer as well as the power factor at both
terminals, and hence decrease the reactive consumption as a percentage of active
power transmitted.