Hve 3
Hve 3
Hve 3
Examples:
Electron microscopes and x-ray units require high d.c. voltages of the order of 100 kV or more.
Electrostatic precipitators, particle accelerators in nuclear physics, etc. require high voltages
(d.c.) of several kilovolts and even megavolts.
High a.c. voltages of one million volts or even more are required for testing power apparatus
rated for extra high transmission voltages (400 kV system and above)
High impulse voltages are required for testing purposes to simulate over voltages that occur in
power systems due to lightning or switching surges.
For electrical engineers, the main concern of high voltages is for the insulation testing of
various components in power systems for different types of voltages, namely, power frequency
a.c., high frequency, switching or lightning impulses.
Different forms of high voltages mentioned above are classified as:
1. high d.c. voltages
2. high a.c. voltages of power frequency
3. high a.c. voltages of high frequency
4. high transient or impulse voltages of very short duration such as lightning Over
voltages, and
5. transient voltages of longer duration such as switching surges
When a full wave or a half wave rectifier is used along with the smoothing
capacitor C, the voltage on no load will be the maximum a.c. voltage.
But when on load, the capacitor gets charged from the supply voltage and
discharges into load resistance RL whenever the supply voltage waveform varies
from peak value to zero value.
These waveforms are shown in Fig.
When loaded, a fluctuation in the output d.c. voltage δV appears, and is called a
ripple.
The ripple voltage δV is larger for a half wave rectifier than that for a full wave
rectifier, since the discharge period in the case of half wave rectifier is larger.
The ripple δV depends on :
(a) the supply voltage frequency f,
(b) the time constant CRL , and
(c) the reactance of the supply transformer XL .
For half wave rectifiers, the ripple frequency is equal to the supply frequency
and for full wave rectifiers, it is twice that value.
The ripple voltage is to be kept as low as possible with the proper choice of the
filter condenser and the transformer reactance for a given load RL.
Full-Wave Rectifier Circuit
A full wave rectifier circuit is shown in Fig.
In the positive half cycle, the rectifier A conducts and charges the capacitors Vmax,
while in the negative half cycle the rectifier B conducts and charges the capacitor.
Hence a full wave rectified output voltage is obtained.
The source transformer requires a centre tapped secondary with a peak voltage
rating of 2 V.
Both full wave and half wave rectifiers produce d.c. voltages less than the
maximum a.c. input voltage due to the presence of ripples.
Also, ripple or the voltage fluctuation will be present, and this has to be kept
within a resonable limit by means of filters.
Ripple frequency is twice the
input a.c. Supply frequency and
ripple is less as compared to half
wave rectifier.
Disadvantages of Rectifier Circuits Methods:
The size of circuit and capacitor will be large for high DC voltage generation.
Not suitable for high current applications.
In case of full wave rectifier circuit, source transformer requires center-tapped
secondary with rating 2V.
Voltage Doubler Circuits
Both full wave and half wave rectifier circuits produce a d.c. voltage less than the a.c.
maximum voltage.
When higher d.c. voltages are needed, a voltage doubler or cascaded rectifier doubler
circuits are used.
The schematic diagram of voltage doubler is given.
Functioning of simple voltage doubler circuit:
In voltage doubler circuit shown in Fig. the capacitor C1 is charged through
rectifier R1 to a voltage of +Vmax during the negative half cycle.
As the voltage of the transformer rises to positive +Vmax during the next half
cycle, the potential of the other terminal of C1 rises to a voltage of +2Vmax .
Thus, the capacitor C2 is charged through R2 to +2Vmax.
The d.c. Output voltage on load will be less than +2Vmax , depending on the
time constant C2 RL and the charging time constant.
The ripple voltage of these circuits will be about 2% for RL /r ≤10 and X/r ≤0.25,
where X and r are the reactance and resistance of the input transformer.
The rectifiers are rated to a peak inverse voltage of 2Vmax, and the condensers
C1 and C2 must also have the same rating i.e. 2Vmax.
The ripple voltage increases with increase in load current.
Cascaded voltage doublers are used when larger output voltages are needed
without changing the input transformer voltage level.
A typical cascaded voltage doubler is shown Fig.
Operation:
Rectifiers D1, D3, .......D2n-1 conduct during the negative half cycle.
Rectifiers D2, D4, .......D2n conduct during the positive half cycle.
Typical current and voltage waveforms of such a circuit are shown in fig 6.4c &
6.4d.
The voltage on C2 is the sum of the input a.c. voltage, Vac and the voltage across
capacitor C1 ,Vc1).
The mean voltage on C2 is less than the positive peak charging voltage (Vac +
Vc1).
The voltages across other capacitors C2 to C2n can be derived in the same
manner, (i.e.) from the difference between voltage across the previous
capacitor and the charging voltage.
Finally the voltage after 2n stages will be Vac (n1 + n2 + ...), where n1, n2,... are
factors when ripple and regulation are considered in the next rectifier.
The ripple voltage δV and the voltage drop ∆V in a cascaded voltage multiplier
unit are shown in Fig. 6.4e.
Ripple In Cascaded Voltage Multiplier Circuits:
For n-stages, the total ripple will be,
Where,
IL = Load current from rectifier
f = supply frequency
C = equal value of capacitors in each stage
n = total number of stages
∆V
Optimum number of stages for the minimum voltage drop:
Where,
I = load current.
Vmax = Peak rated transformer secondary voltage
Maximum possible output voltage:
Electrostatic Machines
In electromagnetic machines, current carrying conductors are moved in a
magnetic field, so that the mechanical energy is converted into electrical
energy.
Basic Principle of Electrostatics Machines:
In electrostatic machines charged bodies are moved in an electric field against
an electrostatic field in order that mechanical energy is converted into electrical
energy.
Thus, if an insulated belt with a charge density δ moves in an electric field
“E(x)”between two electrodes with separation ‘S’ then
1. the charge on the strip of belt at a distance dx is dq = δ. b. dx where b is the
width of the belt, and
2. The force on the belt, F is,
If the belt moves with a velocity, v, then the mechanical power P, required to
move the belt is
https://www.youtube.com/watch?v=y20lKZB5BR0
Functioning of Van De Graaff Generator:
The generator is usually enclosed in an earthed metallic cylindrical vessel and is
operated under pressure or in vacuum.
Charge is sprayed on to an insulating moving belt from corona points at a
potential of 10 to 100 kV above earth and is removed and collected from the
belt connected to the inside of an insulated metal electrode through which the
belt moves.
The belt is driven by an electric motor at a speed of 1000 to 2000 meters per
minute.
The potential of the high voltage electrode above the earth at any instant is
V=Q/C , where, Q is the charge stored and C is the capacitance of the high
voltage electrode to earth.
The potential of the high voltage electrodes rises at a rate ,
Introduction:
Van de Graaff generators are essentially high voltage but low power devices,
and their power rating seldom exceeds few tens of kilowatts.
As such electrostatic machines which effectively convert mechanical energy
into electrical energy using variable capacitor principle were developed.
These are essentially duals of electromagnetic machines and are constant
voltage variable capacitance machines.
An electrostatic generator consists of a stator with interleaved rotor vanes
forming a variable capacitor and operates in vacuum.
E- Line voltage output
V- Rotor plate voltage
1. Stator with vanes
2. Rotor shaft
3. Rotor vanes
A, B – Rectifiers
where,
V1 – Input voltage
V2 – Output voltage
g – Insulation support
aa’ – LV primary winding
bb’ – HV secondary winding
cc’ – Excitation winding
bd – Meter winding
(200 to 500 V)
In the cascade transformer units, the first transformer is at the ground
potential along with its tank.
The primary of the first stage transformer is connected to a low voltage supply.
The second transformer is kept on insulators and maintained at a potential of
V2, the output voltage of the first unit above the ground.
The high voltage winding of the first unit is connected to the tank of the second
unit.
The low voltage winding of this unit is supplied from the excitation winding of
the first transformer, which is in series with the high voltage winding of the first
transformer at its high voltage end.
The rating of the excitation winding is almost identical to that of the primary or
the low voltage winding.
The high voltage connection from the first transformer winding and the
excitation winding terminal are taken through a bushing to the second
transformer.
In a similar manner, the third transformer is kept on insulators above the
ground at a potential of 2V2 and is supplied likewise from the second
transformer.
The number of stages in this type of arrangement are usually two to four, but
very often, three stages are adopted to facilitate a three-phase operation so
that √(3V2) can be obtained between the lines.
Supply to the units can be obtained from a motor-generator set or through an
induction regulator for variation of the output voltage.
The rating of the primary or the low voltage winding is usually 230 or 400 V for
small units up to 100 kVA.
For larger outputs the rating of the low voltage winding may be 3.3kV, 6.6 kV or
11 kV.
Resonant Transformer
The equivalent circuit of a high voltage testing transformer consist of the leakage
reactances of the windings, the windings resistances, the magnetizing reactance,
and the shunt capacitance across the output terminal due to the bushing of the
high voltage terminal and also that of the test object.
Also, for testing electrical apparatus for switching surges, high frequency high
voltage damped oscillations are needed which need high voltage high frequency
transformers.
The primary is fed form a.d.c. or a.c. supply through the capacitor C1.
A spark gap G connected across the primary is triggered at the desired voltage
V1 which induces a high self excitation in the secondary.
The primary and the secondary windings L1 and L2 are wound on an insulated
former with no core (air cored) and are immersed in oil.
The windings are tuned to a frequency of 10 to 100kHz by means of the
capacitors C1 and C2.
The output voltage V2 is a function of the parameters L1, L2, C1, C2, and the
mutual inductances M.
Usually, the windings resistance will be small and contribute only for damping
of the oscillations.
The analysis of the output waveform can be done in a simple manner neglecting
the winding resistance.
Let the capacitor C1 be charged to a voltage V1 when the spark gap is triggered.
Let a current i1 flow through the primary windings L1 and produce a current i2
through L2 and C2.
Then,
Where,
From this,