POINT I/O Input Modules: Installation Instructions
POINT I/O Input Modules: Installation Instructions
POINT I/O Input Modules: Installation Instructions
Table of Contents
Topic Page
Important User Information 2
Specifications 23
2 POINT I/O Input Modules
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the
many variables and requirements associated with any particular installation, Rockwell Automation, Inc.
cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or
motor) to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or
motor) to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of
the product.
D s rk
O atu o
S et t w
N
E:
N
1
2
0
10
4
9
8
5
7
45720
Description Description
1 Module locking mechanism 6 1734-TB or 1734-TBS mounting base
4 Removable terminal block (RTB) handle 9 DIN rail locking screw (orange)
ATTENTION: This product is grounded through the DIN rail to chassis ground.
Use zinc plated chromate-passivated steel DIN rail to assure proper grounding.
The use of other DIN rail materials (for example, aluminum or plastic) that can
corrode, oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail
properly. Refer to Industrial Automation Wiring and Grounding Guidelines,
Rockwell Automation publication 1770-4.1, for more information.
1. Position the mounting base vertically above the installed units (adapter, power
supply, or existing module).
46014
2. Slide the mounting base down allowing the interlocking side pieces to engage the
adjacent module or adapter.
3. Press firmly to seat the mounting base on the DIN rail.
The mounting base snaps into place.
WARNING: When you insert or remove the module while backplane power is
on, an electrical arc can occur. This could cause an explosion in hazardous
location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create electrical
resistance that can affect module operation.
1. Use a bladed screwdriver to rotate the keyswitch on the mounting base clockwise
until the number required for the type of module you are installing aligns with
the notch in the base.
2. Verify the DIN rail locking screw is in the horizontal position.
You cannot insert the module if the locking mechanism is unlocked.
1734-TB Base
45696
3. Insert the module straight down into the mounting base and press to secure.
The module locks into place.
tu ule
s
Sta od
M
D tus ork
Sta etw
N
E:
O
N
1. Insert the end opposite the handle into the base unit.
This end has a curved section that engages with the wiring base.
2. Rotate the terminal block into the wiring base until it locks itself in place.
3. If an I/O module is installed, snap the RTB handle into place on the module.
tu ule
s
Sta od
M
D tus ork
Sta etw
N
E:
O
N
WARNING: For 1734-RTBS and 1734-RTB3S, to latch and unlatch the wire,
insert a bladed screwdriver (catalog number 1492-N90 – 3 mm diameter blade)
into the opening at approximately 73° (blade surface is parallel with top surface
of the opening) and push up gently.
73° 85°
WARNING: When you insert or remove the module while backplane power is
on, an electrical arc can occur. This could cause an explosion in hazardous
location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create electrical
resistance that can affect module operation.
WARNING: To comply with the CE Low Voltage Directive (LVD), this equipment
must be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
C C C C Input 4 Input 5
V V V V Input 6 Input 7
45721 45722 45723
0 1
In 0 In 1
2 3
Prox NC NC Prox
2-wire 3-wire
4 5
C C
6 7
V = 12/24V DC
V V
C = Common
0 1
In 0 In 1
2-wire 3-wire 2 3
In 2 In 3
Prox Prox Prox Prox
4 5
C C
6 7
V = 12/24V DC
V V
C = Common
V C C V
Note: When connecting more than one wire in a termination point, make sure that both
wires are the same gauge and type.
Module Module
Status Status
Network Network
Status Status
DeviceNet
0 4 0 4
1 5 1 5
2 6 2 6
System
Power
3 7 3 7
DeviceNet
Power
1734 1734
OB8E IB8
Prox
Prox
Prox
Prox
Prox
Prox
Prox
Prox
24V DC return
24V DC
45724
Terminal block with bus connector strip
Module Module
Status Status
Network Network
DeviceNet Status Status
0 4 0 4
1 5 1 5
2 6 2 6
System
Power
3 7 3 7
DeviceNet
Power
1734 1734
OB8E IB8
Prox
Prox
Prox
Prox
Prox
Prox
Prox
Prox
24V DC return
24V DC
Status of 1 Status of
input 1 Status of input 1 1
inputs 1 & 5
1 5
Status of
Status of input 2 2
inputs 2 & 6 2 6
Status of
Status of input 3 3
inputs 3 & 7 3 7
1734 1734 1734
IB2 45721 IB4 45722 IB8 45723
Specifications
POINT I/O Input Module – 1734-IB2, 1734-IB4, 1734-IB4K, 1734-IB8,
1734-IB8K
Attribute Value
Inputs per module 1734-IB2 – 2 (1 group of 2), sinking
1734-IB4, 1734-IB4K – 4 (1 group of 4), sinking
1734-IB8, 1734-IB8K – 8 (1 group of 8), sinking
Voltage, on-state, min 10V DC
Voltage, on-state, nom 24V DC
Voltage, on-state, max 28.8V DC
Current, on-state, min 2 mA
Current, on-state, nom 4 mA @ 24V DC
Current, on-state, max 5 mA
Voltage, off-state, max 5V DC
Current, off-state, min 1.5 mA
Impedance, input, nom 3.6 kΩ
Impedance, input, max 4.7 kΩ
(1)
Input filter time
OFF to ON 0.5 ms hardware plus 0...63 ms (user-selectable)
ON to OFF 0.5 ms hardware plus 0...63 ms (user-selectable)
Field wiring terminations 1734-IB2 1734-IB4, 1734-IB4K 1734-IB8, 1734-IB8K
0 – Input 0 0 – Input 0 0 – Input 0
1 – Input 1 1 – Input 1 1 – Input 1
2 – No connection 2 – Input 2 2 – Input 2
3 – No connection 3 – Input 3 3 – Input 3
4 – Common 4 – Common 4 – Input 4
5 – Common 5 – Common 5 – Input 5
6 – User supply 6 – User supply 6 – Input 6
7 – User supply 7 – User supply 7 – Input 7
(1)
Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off time is the
time from a valid input signal to recognition by the module.
General Specifications(1)
Attribute Value
Terminal base screw torque 0.8 Nm (7 lb-in.)
Module location 1734-TB or 1734-TBS wiring base assembly
Indicators, network status 1 green/red, logic side
Indicators, module status 1 green/red, logic side
Indicators, input status 1734-IB2 – 2 yellow, logic side
1734-IB4, 1734-IB4K – 4 yellow, logic side
1734-IB8, 1734-IB8K – 8 yellow, logic side
POINTBus current, max 75 mA @ 5V DC
Power dissipation @ 28.8V DC, 1734-IB2 – 0.7 W
max 1734-IB4, 1734-IB4K – 1.0 W
1734-IB8, 1734-IB8K – 1.6 W
Thermal dissipation @ 28.8V DC, 1734-IB2 – 2.4 BTU/hr
max 1734-IB4, 1734-IB4K – 3.4 BTU/hr
1734-IB8, 1734-IB8K – 5.5 BTU/hr
Isolation voltage 50V (continuous), Reinforced Insulation Type
Tested @ 2500V DC for 60 s, field-side to system
Field power supply voltage, nom 24V DC
Field power voltage range 10...28.8V DC
Dimensions, HxWxD, approx. 56 x 12 x 75.5 mm
(2.2 x 0.47 x 2.97 in.)
Wiring category(2) (3) 1 – on signal ports
Wire size Determined by installed terminal block.
Weight, approx. 1734-IB2 – 30.9 g (1.09 oz)
1734-IB4, 1734-IB4K – 31.8 g (1.12 oz)
1734-IB8, 1734-IB8K – 32.3 g (1.14 oz)
Enclosure type rating None (open-style)
Keyswitch position 1
North American Temp Code T4A
ATEX Temp Code T4
(3)
Use this Conductor Category information for planning conductor routing as described in the appropriate System Level
Installation Manual.
At the end of its life, this equipment should be collected separately from any
unsorted municipal waste.
Environmental Specifications
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...55 °C (-4...131 °F)
Temperature, surrounding air, 55 °C (131 °F)
max.
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40...85 °C (-40...185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):
5...95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10...500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions IEC 61000-6-4
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
1V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
EFT/B immunity IEC 61000-4-4:
±4 kV @ 5 kHz on signal ports
Surge transient immunity ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Certifications
(1)
See the Product Certification link at http://www.rockwellautomation.com/global/certification/overview.page for
Declaration of Conformity, Certificates, and other certification details.
(2)
Applies to 1734-IB2, 1734-IB2K, 1734-IB4, and 1734-IB4K only.
Notes:
For an additional level of technical phone support for installation, configuration and troubleshooting, we
offer TechConnect support programs. For more information, contact your local distributor or Rockwell
Automation representative, or visit http://www.rockwellautomation.com/support/.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's
contained in this manual. You can also contact a special Customer Support number for initial help in getting
your product up and running.
United States Contact your distributor. You must provide a Customer Support case number
(call the phone number above to obtain one) to your distributor to complete
the return process.
Outside United States Please contact your local Rockwell Automation representative for the return
procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to
improve this document, complete this form, publication RA-DU002, available at
http://www.rockwellautomation.com/literature/.
Rockwell Automation maintains current product environmental information on its website at
http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Allen-Bradley, POINT I/O, Rockwell Automation, Rockwell Software, RSLogix 5000, and TechConnect are trademarks of Rockwell
Automation, Inc.
ControlNet, DeviceNet, and EtherNet/IP are trademarks of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.