Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Manual mx2s en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 68

Original instructions

User manual
MX² 30–95S

Desiccant dehumidifier
with steam heater for reactivation
Applies to all units manufactured
from week 01, 2015.

190TEN–1089–G1412 © Munters Europe AB 2015


Important user information
Intended use Safety
Munters dehumidifiers are intended to be used for the Information about dangers are in this manual indicated
dehumidification of air. Any other use of the unit, or by the common hazard symbol:
use which is contrary to the instructions given in this
manual, can cause personal injury and damage to the unit WARNING!
and other property. Indicates a possible danger that can lead to personal injury.

No modification of the unit is allowed without prior


approval by Munters. Attachment or installation
CAUTION!
Indicates a possible danger that can lead to damage to the
of additional devices is only allowed after written
unit or other property, or cause environmental damage.
agreement by Munters.

Warranty NOTE! Highlights supplementary information for optimal


The warranty period is valid from the date the unit use of the unit.
left our factory, unless otherwise stated in writing.
The warranty is limited to a free exchange of parts or
Conformity with Directives
The dehumidifier is in conformity with the essential
components which have failed as a result of defects in
safety requirements of the Machinery Directive
materials or workmanship.
2006/42/EC, and in conformity with the provisions
All warranty claims must include proof that the
of the Ecodesign Directive (ErP) 2009/125/EC, the
fault has occurred within the warranty period and
Ecodesign Directive for electric motors 2005/32/EC
that the unit has been used in accordance with the
and of the EMC Directive 2014/30/EU. The
specifications. All claims must specify the unit type and
dehumidifier is manufactured by an organization
fabrication number. This information is stamped on the
certified according to ISO 9001 and ISO 14001.
identification plate, see section Marking.
It is a condition of the warranty that the unit for the full Copyright
warranty period is serviced and maintained by a qualified The contents of this manual can be changed without
Munters engineer or Munters approved engineer. prior notice.
Access to specific and calibrated test equipment is NOTE! This manual contains information which is
necessary. The service and maintenance must be protected by copyright laws. It is not allowed to reproduce or
documented for the warranty to be valid. transmit any part of this manual without written consent from
Always contact Munters for service or repair. Operating Munters.
faults can occur if the unit is maintained insufficiently or
incorrectly. Please send any comments regarding this manual to:
Munters Europe AB
Technical Documentation
P.O. Box 1150
SE- 164 26 KISTA Sweden
e-mail: t-doc@munters.se

ii Important user information 190TEN–1089–G1412


Table of contents
Important user information . .. .. .. .. .. .. .. ii 3.8 Steam regulation . .. .. .. .. .. .. .. .. .. .. . 20
Intended use . .. .. .. .. .. .. .. .. .. .. .. .. .. ii 3.9 Steam heater – recommendations for
Warranty . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ii installation .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 20
Safety .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ii 3.10 Set-up and running checks .. .. .. .. .. . 23
Conformity with Directives .. .. .. .. .. .. ii 3.11 Duct installation .. .. .. .. .. .. .. .. .. .. .. . 23
Copyright .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ii 3.11.1 General recommendations .. . 23
Table of contents . .. .. .. .. .. .. .. .. .. .. .. .. .. iii 3.11.2 Duct for outdoor air inlet .. .. .. . 25
1 Introduction . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 1 3.11.3 Duct for wet air outlet .. .. .. .. .. . 25
1.1 General .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 1 3.11.4 Duct connection dimensions,
1.2 About this manual . .. .. .. .. .. .. .. .. .. .. 1 air inlets . .. .. .. .. .. .. .. .. .. .. .. . 26
1.3 Safety and cautions . .. .. .. .. .. .. .. .. .. 3.11.6 Duct connection dimensions
1
(unit without process fan) . .. .. . 27
1.3.1 Safety labels . .. .. .. .. .. .. .. .. .. 2
3.11.7 Duct connection dimensions,
1.4 Operation monitoring . .. .. .. .. .. .. .. .. 2
process fan . .. .. .. .. .. .. .. .. .. . 28
1.5 Application limitations . .. .. .. .. .. .. .. .. 3
3.11.8 Duct connection dimensions,
1.6 Fault indications . .. .. .. .. .. .. .. .. .. .. .. 3
reactivation fan . .. .. .. .. .. .. .. . 29
1.7 Steam supply .. .. .. .. .. .. .. .. .. .. .. .. .. 4 3.12 Electrical connections . .. .. .. .. .. .. .. . 30
1.8 Marking .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 4 3.13 External humidity transmitter .. .. .. .. . 30
1.8.1 Identification plate . .. .. .. .. .. .. 4 4 Commissioning .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 31
1.8.2 Pressure test points . .. .. .. .. .. 4 4.1 Pre-start checks .. .. .. .. .. .. .. .. .. .. .. . 31
2 Dehumidifier design . .. .. .. .. .. .. .. .. .. .. .. 6 4.2 Airflow adjustment . .. .. .. .. .. .. .. .. .. . 31
2.1 Product description . .. .. .. .. .. .. .. .. .. 6 4.2.1 General .. .. .. .. .. .. .. .. .. .. .. .. . 31
2.2 Principle of operation .. .. .. .. .. .. .. .. .. 6 4.2.2 Setting the rated airflows . .. .. . 32
2.3 Main components, MX² 30 .. .. .. .. .. .. 8 4.2.3 Base configuration settings .. . 32
2.4 Main components, MX² 35–95 . .. .. .. 10 4.3 Set-up and test of steam heater . .. .. . 33
2.5 Configuration features .. .. .. .. .. .. .. .. 13 5 Operation . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 34
2.5.1 Insulated process air inlet . .. .. 13 5.1 Control panel . .. .. .. .. .. .. .. .. .. .. .. .. . 34
2.5.2 Process fan control .. .. .. .. .. .. 13 5.2 General . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 35
2.5.3 Bypass damper .. .. .. .. .. .. .. .. 14 5.3 Quick stop . .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 35
2.5.4 Energy Recovery Purge and 5.4 Operating the unit .. .. .. .. .. .. .. .. .. .. . 36
Energy Efficiency Purge . .. .. .. 15 5.4.1 Initial start–up, Manual mode
2.5.5 Low Dewpoint Purge .. .. .. .. .. 16 (MAN) .. .. .. .. .. .. .. .. .. .. .. .. .. . 36
3 Installation . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 17 5.4.2 Inital start-up, Automatic mode
3.1 Safety .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 17 (AUTO) – regulating to set
3.2 Moving the dehumidifier .. .. .. .. .. .. .. 17 point . .. .. .. .. .. .. .. .. .. .. .. .. .. . 36
3.3 Inspection of delivery .. .. .. .. .. .. .. .. .. 6 Service and maintenance .. .. .. .. .. .. .. .. . 37
17
6.1 Safety . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 37
3.4 Scope of delivery – steam reactivation
system . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 6.2 Regular service and maintenance .. . 37
18
3.5 Storing the dehumidifier .. .. .. .. .. .. .. 6.3 Service options . .. .. .. .. .. .. .. .. .. .. .. . 38
18
3.6 Site requirements . .. .. .. .. .. .. .. .. .. .. 6.4 Extended warranty . .. .. .. .. .. .. .. .. .. . 38
18
3.7 Foundation .. .. .. .. .. .. .. .. .. .. .. .. .. .. 19 6.5 Service indicator lamp . .. .. .. .. .. .. .. . 38

190TEN–1089–G1412 Table of contents iii


6.6 Service and maintenance schedule 8.1 Capacity diagrams . .. .. .. .. .. .. .. .. .. . 48
(0–24000 hours) . .. .. .. .. .. .. .. .. .. .. .. 39 8.2 Noise data .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 50
6.7 Service and maintenance schedule 8.2.1 Noise to room . .. .. .. .. .. .. .. .. . 50
(28000–48000 hours) . .. .. .. .. .. .. .. .. 40 8.2.2 Noise in ducts . .. .. .. .. .. .. .. .. . 52
6.8 Maintenance of steam reactivation 8.3 Dimensions and service space .. .. .. . 54
heater .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 41 8.3.1 Dimensions . .. .. .. .. .. .. .. .. .. . 54
6.9 Air filter replacement .. .. .. .. .. .. .. .. .. 42 8.3.2 Dimensions (unit without
7 Fault tracing . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 44 process fan) . .. .. .. .. .. .. .. .. .. . 55
7.1 Safety .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 44 8.3.3 Service space . .. .. .. .. .. .. .. .. . 57
7.2 Fault tracing list, dehumidifier .. .. .. .. 45 8.4 Technical data .. .. .. .. .. .. .. .. .. .. .. .. . 58
7.3 Fault tracing list, steam heater unit . .. 47 9 Scrapping . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 60
8 Technical specification .. .. .. .. .. .. .. .. .. .. 48 10 Contact Munters . .. .. .. .. .. .. .. .. .. .. .. .. .. . 61

iv Table of contents 190TEN–1089–G1412


1 Introduction
1.1 General
Munters manufactures a wide range of efficient dehumidifiers designed for different uses and applications.
Contact your nearest Munters office if you have any questions regarding the installation or the use of your
dehumidifier.
For product data, see section Technical specification.

1.2 About this manual


This manual contains necessary information for how to install and use the dehumidifier in a safe and
efficient way. Operation instructions for the control system can be found in a separate supplement, also
delivered with the dehumidifier.
NOTE! Make sure to read all relevant parts of this manual before operating or performing any work on the
dehumidifier. This manual should be stored in a permanent location close to the dehumidifier.

1.3 Safety and cautions


Every measure has been taken in the design and manufacture of the dehumidifier to ensure that it meets the
safety requirements of the directives and standards listed in the EC Declaration of Conformity.
The information in this manual shall in no way take precedence over individual responsibilities or local
regulations.
During operation and other work with a machine it is always the responsibility of the individual to consider:
■ The safety of all persons concerned.
■ The safety of the unit and other property.
■ The protection of the environment.

The types of dangers that are indicated in this manual are described in section Important user information.

WARNING!
- The unit must not be splashed with or immersed in water.

- The unit must never be connected to a voltage or frequency other than that for which it was designed. Refer to the
identification plate. Line voltage that is too high can cause an electrical shock hazard and damage to the unit.

- Do not insert fingers or any other objects into the air vents.

- All electrical installations must be carried out by a qualified electrician and in accordance with local regulations.

- The dehumidifier can restart automatically after a power cut. Always set and lock the main power switch in the
OFF position before carrying out any service work.

- Use only approved lifting equipment to prevent personal injury and damage to the equipment.

- Always contact Munters for service or repair.

190TEN–1089–G1412 Introduction 1
1.3.1 Safety labels
The safety labels below are attached to the unit. Make sure that all personnel working with or near the unit
are aware of the meaning of each label.

Figure 1.1 Risk of personal injury due to electric shock. Figure 1.2 Risk of personal injury due to hot surfaces.

1.4 Operation monitoring


The dehumidifier is controlled and monitored from the control panel on the front of the unit, see section
5.1, Control panel. The HMI (Human Machine Interface) is used to display values and parameters, and to
input settings and commands to the control system. The HMI is described in the separate supplement.

2 Introduction 190TEN–1089–G1412
1.5 Application limitations
The dehumidifier conforms to the emission limits of residential, commercial and light-industrial
environments except for the emission limits for harmonics emission (EN 61000-3-12).
As the equipment exceeds the limits for harmonics it must not be used in residential, commercial or
light-industrial environment without taking proper steps regarding the power installation like supplying the
equipment from a dedicated transformer connected to the high or medium voltage network.
The dehumidifier conforms to Rsce 33, see Table 1.1.
Harmonic, number Limit (%) 1) Measured value (%)
1 8 0,32
3 4 0,24
4 10,7 4,00
5 2,67 0,05
6 7,2 2,09
7 2 0,05
9 1,6 0,02
10 3,1 0,56
11 1,33 0,01
12 2 0,54
PWHD 2) 22 3,1
1) Measured values valid for Rsce=33

2) Partial Weighted Harmonic Distortion

Table 1.1

The dehumidifier must only be used in industrial environments (class A) when the HMI is equipped with a
touch panel. If the HMI is equipped with a text panel, the dehumidifier can be used in all environments
since the text panel is approved according to class B.
The dehumidifier is intended for indoor installation only.

1.6 Fault indications


Any faults are indicated by the red light on the control panel. The cause of the alarm is indicated on the
display.

190TEN–1089–G1412 Introduction 3
1.7 Steam supply
The quality of water determines the quality of steam produced. It is important that a good quality steam
supply, at the correct temperature and pressure, is available for a reliable operation of the steam heater.
Disregarding this can lead to degradation of the heater performance and eventually to failure.
The following impurities are common in the feed water:
■ Dissolved solids – which can cause scale to form on equipment. The principal dissolved solids are
carbonate and sulphates of calcium and magnesium.
■ Suspended solids – these can cause sludge to form in the boiler. Suspended solids are usually solid
mineral or organic particles carried in suspension in the water.
■ Dissolved gases – these can cause corrosion in equipment. The dissolved gases are oxygen and carbon
dioxide.
■ Frothing substances that can cause contamination and corrosion of the equipment. The frothing
substances creates a foam that usually contains soda in the form of carbonates, chlorides or sulphates.
Correct water treatment is required to remove the impurities in the feed water. If the impurities are not
removed there could be an overflow of boiler water into the steam system.

1.8 Marking

1.8.1 Identification plate

Type MX² 55S


Fabr. No. 1005 170XXX XXXXX
Fabr. year 2010
3 ~ 400V 50 Hz
M 4,1 kW STEAM
Max 4,6 kW IP33
Made in Sweden
Munters Europe AB
Isafjordsgatan 1
MX² 30S MX² 35-95S 164 26 Kista, Sweden

Figure 1.3 Position of identification plate Figure 1.4 Identification plate, example

Explanation of "Fabr. No" on the identification plate:


10 Year of manufacture 170XXX Article number
05 Week of manufacture XXXXX Serial number

1.8.2 Pressure test points


The built-in pressure test points are used for measuring pressure drop across components during
basic installation work and inspection of the rotor condition. For airflow adjustment, refer to section
4.2, Airflow adjustment .

4 Introduction 190TEN–1089–G1412
MX² 30S MX² 35-95S TP1 TP2 TP3 TP4

Figure 1.5 Label position Figure 1.6 Pressure test points

TP1. Process air TP1–TP4. Differential pressure, process air


TP2. Wet air TP2–TP3. Differential pressure, reactivation air
TP3. Reactivation air
TP4. Dry air

190TEN–1089–G1412 Introduction 5
2 Dehumidifier design
2.1 Product description
The desiccant dehumidifier has been designed to effectively dehumidify the air in environments requiring
low air humidity.
All functional components are enclosed in a corrosion resistant Aluzink® casing (standard) or stainless steel
casing (option) which makes installation and maintenance easy. The unit is constructed on a steel base frame
which allows the use of a fork-lift truck during transportation and installation.
The electrical control system complies with standard EN 60204-1. The electrical components are mounted
on bus bars. The dehumidifier is manufactured according to European standards and the established
requirements for CE-marking.

2.2 Principle of operation

1 2

1. Process air
2. Dry air
4 3. Reactivation air
3
4. Wet air

Figure 2.1 Rotor principle

The desiccant rotor is the adsorption dehumidifying component in the unit. The rotor structure is
comprised of a large number of small air channels.
The desiccant rotor is made of a composite material that is highly effective in attracting and retaining water
vapour. The rotor is divided in two zones. The airflow to be dehumidified, process air, passes through the
largest zone of the rotor and then leaves the rotor as dry air. Since the rotor rotates slowly, the incoming air
always meets a dry zone on the rotor, thus creating a continuous dehumidification process.

The airflow that is used to dry the rotor, reactivation air, is heated. The reactivation air passes through
the rotor in the opposite direction to the process air and leaves the rotor as wet air (warm, moist air). This
principle enables the dehumidifier to work effectively, even at freezing temperatures.

6 Dehumidifier design 190TEN–1089–G1412


A
3
A
4 1. Process air
A
5 A
2 2. Dry air
3. Reactivation air
4. Wet air
5. Reactivation fan
A
7
6. Rotor
7. Process fan

A
6
A
1

Figure 2.2 Airflow overview

190TEN–1089–G1412 Dehumidifier design 7


2.3 Main components, MX² 30

2
6

7
5

4 8
1
3
9
10

11

13
12
14
16
15
Figure 2.3 Exploded view

14

18 19

17

Figure 2.4 Front view

8 Dehumidifier design 190TEN–1089–G1412


Item No. Description
1. Reactivation fan
2. Filter, reactivation air
3. Filter, process air
4. Steam coil
5. Cooling fan with filter
6. Filter, cooling fan
7. Connector, RJ45
8. Main power switch
9. Pressure sensor
10. Process fan
11. Duct, bypass damper 1)
12. Rotor
13. Drive motor, rotor
14. Electrical panel
15. Control system display
16. Control panel
17. Pressure sensor 1)
18. Filter guard
19. Sensor, rotor stop
1) Option

Table 2.1 Main components, MX² 30

190TEN–1089–G1412 Dehumidifier design 9


2.4 Main components, MX² 35–95

3
1
17
2
4
16
5

15 6

14

12 11 10
13 9 8 7
Figure 2.5 Exploded view

18

19

6 20
21

Figure 2.6 Front view

10 Dehumidifier design 190TEN–1089–G1412


Item No. Description
1. Control system display
2. Control panel
3. Process fan
4. Duct, bypass damper 1)
5. Duct, purge, right 1)
6. Electrical panel
7. Drive motor, rotor
8. Rotor cassette
9. Duct, purge, left 1)
10. Filter guard
11. Plate, bypass
12. Pressure sensor 1)
13. Filter, process air
14. Reactivation fan (left) 2)
15. Reactivation fan
16. Filter, reactivation air
17. Steam coil
18. Connector, RJ45
19. Main power switch
20. Pressure sensor
21. Sensor, rotor stop
1) Option

2) Only used for reversed assemblies

Table 2.2 Main components, MX² 35–95

190TEN–1089–G1412 Dehumidifier design 11


2.5 Configuration features
This chapter includes information about functions and components that can be added when ordering an
MX² dehumidifier.

2.5.1 Insulated process air inlet


All dehumidifier units supplied with pre-cooled process air should have insulated process air inlet. The
process air sector in front of the rotor has an internal lining of isolation to prevent condensation on the unit.

2.5.2 Process fan control


The process fan is equipped with a frequency converter for controlling the fan speed. The process fan
control can be configured as fixed speed or variable speed according to below:
Fixed speed
The frequency converter for the process fan is pre-set at the factory and the process fan always runs with a
constant speed that gives the rated process airflow.
Variable speed
The frequency converter for the process fan is controlled either by flow or pressure.
At flow control, a pressure sensor measures the pressure difference over the inlet cone on the process fan. At
pressure control, a pressure sensor measures the air pressure in the dry air duct.
The actual value from the pressure sensor is calculated, together with the fan coefficient, by the PLC in the
control system. The PLC compares the actual value with the set point value and changes the command
signal to the frequency converter if there is a difference between the values.

190TEN–1089–G1412 Dehumidifier design 13


2.5.3 Bypass damper

MX² 30 MX² 35-95


Figure 2.7 Handle for bypass damper

An installed bypass damper kit allows a fixed airflow to be used when the process airflow exceeds the
maximum rotor flow capacity. The bypass function consists of an adjustable damper positioned in the
bypass airflow channel. The bypass airflow channel is integrated with the unit and passes under the rotor.
NOTE! The bypass damper should only be adjusted by specially trained personnel.

4 5

1. Reactivation air
2. Heated reactivation air
3. Wet air
4. Process air
3 2 1 5. Dry air
6. Bypassed process air

Figure 2.8 Bypass principle

14 Dehumidifier design 190TEN–1089–G1412


2.5.4 Energy Recovery Purge and Energy Efficiency Purge

4 5
1. Reactivation air
2. Heated reactivation air
3. Wet air
6
7 4. Process air
3 2 1 5. Dry air
6 6. Purge air
7. Warm purge air

Figure 2.9 Principle for Energy Recovery Purge and Energy Efficiency Purge

Energy Recovery Purge (ERP) and Energy Efficiency Purge (EEP) are two energy saving solutions that
recycles heat from the rotor, after the reactivation section in the rotational direction of the rotor. A minor
part of the reactivation airflow is bypassed to the warm sector of the rotor, before the airflow enters the
reactivation heater. The airflow is heated up by the rotor and then mixed with the reactivation airflow, after
the reactivation heater. The recycled heat from the rotor increases the efficiency and reduces the energy
consumption.
Compared to a standard unit, ERP will give the same dehumidification capacity with reduced reactivation
heater energy. With EEP, the reactivation heater energy is the same as in a standard unit, while the
dehumidification capacity is increased.
The purge airflow duct on MX² 30 is installed on the rear side of the unit. The purge airflow (ERP, EEP,
LDP) can be adjusted with a damper installed on the duct.

MX² 30

Figure 2.10 Purge airflow duct

The purge airflow duct on MX² 35–95 is located inside the unit and the purge airflow (ERP, EEP) cannot be
adjusted. An adjustable damper for Low Dewpoint Purge is located on top of the unit.

190TEN–1089–G1412 Dehumidifier design 15


2.5.5 Low Dewpoint Purge

4 5
1. Reactivation air
2. Heated reactivation air
7
6 3. Wet air
4. Process air
3 2 1 5. Dry air
6. Warm purge air
7. Adjustable damper

Figure 2.11 Low Dewpoint Purge principle

Low Dewpoint Purge (LDP) is used to enable extra low dewpoints. A minor part of the process airflow is
forced through a smaller sector of the rotor which, according to the rotor rotation direction, is positioned
directly after the reactivation sector. The result is that a part of the process air is taken off (purge air) and the
rotor material is cooled down before it is exposed to the dry air outlet sector. The warm purge airflow which
is drawn from the smaller sector of the rotor passes an adjustable damper and enters the reactivation air just
before the reactivation heater. This makes drying of the rotor more efficient.
NOTE! The purge airflow setting is application dependent and should only be adjusted by specially trained
personnel during the commissioning to obtain the desired dry air dewpoint. A general recommendation is that the
purge airflow represents 10 % of the total process airflow.

MX² 30 MX² 35-95


Figure 2.12 Adjustable damper for Low Dewpoint Purge

NOTE! The adjustable damper is set from the factory and should only be adjusted by specially trained personnel.

16 Dehumidifier design 190TEN–1089–G1412


3 Installation
3.1 Safety
WARNING!
To prevent personal injury or damage to the dehumidifier, always use approved lifting equipment.

CAUTION!
Never climb on, or place any objects on the dehumidifier.

WARNING!
Installation, adjustments, maintenance and repairs must only be carried out by qualified personnel who are
aware of the risks involved when working with equipment operating with high electrical voltage and high machine
temperatures.

3.2 Moving the dehumidifier


The dehumidifier must be handled with care. All panel doors must be closed during transportation. Use
a fork lift or pallet loader to move the dehumidifier. The forklift/pallet loader must be equipped with
extended forks to ensure even weight distribution.

Figure 3.1 Correct length on forklift arms

See section 8.4, Technical data for weight data.

WARNING!
Move the dehumidifier carefully as there is a risk of the dehumidifier tipping over.

3.3 Inspection of delivery


1. Inspect the delivery and compare with the delivery note, order confirmation or other delivery
documentation. Make sure that everything is included and nothing is damaged.
2. Contact Munters immediately if the delivery is not complete in order to avoid installation delays.
3. Remove all packaging material from the unit, and make sure that no damage has occurred during
transportation.
4. Any visible damage must be reported in writing to Munters within 5 days and prior to installation of
the unit.
5. Dispose of the packaging material according to local regulations.
If the unit is to be put into storage prior to installation, see section 3.5, Storing the dehumidifier.

190TEN–1089–G1412 Installation 17
3.4 Scope of delivery – steam reactivation system
The following steam components are included with the delivery:

Component MX² 30 MX² 35 MX² 40 MX² 55 MX² 60 MX² 80 MX² 95

Steam valve, VUG015F324 VUG015F324 VUG015F324 VUG015F324 VUG015F314 VUG015F304 VUG015F314


(Sauter)

Actuator (Sauter) AVM234S F132

Steam battery screw flanges (supplied loose): Carbon steel, PN16, DIN 2566, hubbed threaded.

The steam valve is delivered without companion flange (DN15)

Data sheets for the valve and actuator are delivered with the components. Contact Munters for additional
information.

3.5 Storing the dehumidifier


Follow these instructions if the dehumidifier is to be stored prior to installation:
■ Place the dehumidifier in an upright position on a horizontal surface.
■ Re-use the packaging material to provide protection for the unit.
■ Protect the dehumidifier from physical damage.
■ Store the dehumidifier under cover and protect it from dust, frost, rain and aggressive contaminants.
See section 8.4, Technical data for correct storage temperature.

3.6 Site requirements


NOTE! It is important that the intended installation site meets the requirements in order to achieve the best
possible performance and trouble-free operation.

NOTE! It is important for both maintenance and service purposes that the minimum service space requirements
are complied with.

The dehumidifier is only intended for indoor installation. Avoid installing the dehumidifier in a damp
environment where there is a risk of water entering the unit, or in a very dusty environment. Refer to
Munters for advice if in doubt.
NOTE! If there is a need for reduction of vibrations from the dehumidifier, contact Munters for instructions. Refer
to standard EN1299+A1:2008.

See section 8.3, Dimensions and service space for unit and service dimensions.

18 Installation 190TEN–1089–G1412
3.7 Foundation
The dehumidifier must be installed on a level floor, or platform, which has been designed with a floor
loading capacity capable of supporting the machine’s weight. If the maximum floor loading weight is not
exceeded, special foundations are not required.
When the dehumidifier has been installed, it should be checked that it is level. If local regulations require that
the unit is permanently fixed in position, the fixing holes can be used for bolting the unit to the floor.

B C G Ø 13,5

A
E

A/2

74 74
F
D

Figure 3.2 Mounting base


MX² 30 MX² 35–55 MX² 60–95
Dimension (mm) Dimension (mm) Dimension (mm)
A 600 880 970
B 110 94 151
C 26 25 25
D 800 1063 1063
E 811 1068 1272
F 101 94 151
G Centerline

Table 3.1 Mounting base dimensions

190TEN–1089–G1412 Installation 19
3.8 Steam regulation
NOTE! Steam regulation setting must only be changed by authorised personnel. Contact Munters for more
information.

For dehumidifiers with steam reactivation heater, the dehumidification capacity/reactivation heater effect
can be regulated according to the two different principles described below.
1. Steam pressure regulation: The steam pressure in the steam heater is regulated by a modulating
reducing valve on the steam inlet. As this regulating principle result in a narrow regulating range for
the reactivation temperature, it is not suitable if the dehumidifier will run for long periods with low
dehumidification need.
2. Variable reactivation flow: Steam pressure and condensation temperature remains constant all the
time. The steam control valve is operated with an ON/OFF-function. Dehumidification capacity and
reactivation power is controlled by varying reactivation flow, this by means of variable-speed control on
the reactivation fan. The reactivation flow can be down-regulated from rated flow to a small flow limited
by the fan motor's minimum speed, or the air distribution in the reactivation sector.
When the steam control valve closes, the steam flow to the heater is shut-off. This can be selected when
there is no need for dehumidification, or when the dehumidifier is turned off.
In order to limit the reactivation temperature when the reactivation airflow is low, the steam supply
pressure must not exceed 4–5 barg.

The default setting from the factory is variable reactivation flow.

3.9 Steam heater – recommendations for installation


NOTE! When the unit is delivered, the flanges are only tightened by hand. The flanges must be fully sealed
and tightened before the steam supply is connected.

See 8.3, Dimensions and service space for dimensions. See 8.4, Technical data for steam data.
The following components must be installed as part of the steam supply system to ensure problem-free
operation:
■ A separator for removing contaminants and fluid from incoming steam. The separator removes fluids
that can negatively affect the heat transmission surface or cause erosion damage.
■ A steam control valve for opening and closing the steam flow through the heater. When regulating
with steam pressure, the valve is used for adjusting the steam flow. For all types of control valves, it is
important that they open slowly to reduce the risk of hydraulic shock, thermal strains and erosion that
can damage the heat exchanger. It is recommended to use an equal percentage valve to obtain a slow
opening action. The valve actuator must have an opening time of no less than 120 seconds.
■ When the steam control valve has a modulating function, the pressure drop across the valve affects
the steam pressure to the steam heater, and therefore the temperature that can be achieved. Obey this
when designing a control valve.
■ A vacuum breaker shall be installed on the steam inlet to make it possible to drain condensate upon
shut-down and when operating with low power consumption.
■ The steam trap must be a float type, preferably with built-in thermal de-aerator. A thermostatic trap
must not be used.

20 Installation 190TEN–1089–G1412
■ A non-return valve must be installed in the condensate return line to prevent condensate from returning
to the heater and to protect against any hammering in the condensate system. This applies if the
condensate return line has condensate from more than one steam trap as there could be differing
pressures and temperatures and/or to protect against return flow when condensate is "lifted" to the
condensate tank.
■ Both the inlet and outlet lines must have expansion bends to compensate for thermal expansion. All
pipework must be independently supported close to the dehumidifier to prevent strain on the steam
heater.
■ If the air temperature drops below +7 °C and there is a risk of freezing, a thermostat must be installed
directly after the heater in the airflow direction. The thermostat must be a two-stage type with a long,
temperature sensing capillary tube. The capillary tube is active along its entire length, and must be
installed so it covers the sectional area efficiently. The thermostat reacts to the lowest temperature
present along the capillary tube length, that is where the gas in the thermostat system condensates.
At the air temperature +7 °C, the reactivation effect should increase and a warning-type of alarm
be triggered. If the temperature drops further to +3 °C, the thermostat should switch off the
dehumidification system so that the reactivation airflow ceases and an alarm is triggered.

In addition to the above, installation of the following components is recommended to facilitate operation
and maintenance:
■ De-aerator to ventilate any oxygen or other gases in the steam supply.
■ Shut-off valves.
■ A manometer to indicate the steam pressure at the heater.
■ A thermometer, capable of withstanding the line pressure, to indicate the full scale of the steam supply.
■ Filters to restrict unwanted impurities.
■ An extra shut-off valve downstream of the condensate trap. This to facilitate installation of a
manometer, which would quickly indicate any counter pressure in the condensate system in the event
of any malfunctions during operation.
NOTE! If a manometer is installed in the steam line, the full scale reading must be 1,5 times the line pressure
where it is installed.

190TEN–1089–G1412 Installation 21
>0.5 %
B
1 2 3 4 5 6 7

A
>0.5 %
C

E 8 9 10 11

18 19

F >0.5 %

15 16 17
D

>0.5 %

B
12
B

13 14

Figure 3.3 Installation of steam heater.

A. Steam supply D. Condensate drainage


B. Condensate return, dehumidifier E. Closed condensate return
C. Condensate return, drainage F. Open condensate return

1. Thermal de-aerator 11. Ball valve


2. Vacuum valve 12. Steam trap (float)
3. Manometer 13. Condensate tank
4. Modulating steam valve 14. Pump
5. Mushroom valve 15. Steam trap (float)
6. Separator 16. Electromechanical valve
7. Steam filter 17. Non-return valve
8. Ball valve 18. Ball valve (shut-off valve)
9. Steam trap (float) 19. Ball valve (for connecting manometer)
10. Non-return valve

NOTE! Components marked in bold must always be installed.

22 Installation 190TEN–1089–G1412
NOTE! All pipework must be supported to ensure minimal strain on the connections.

NOTE! It is important that the control valve does not open too quickly, including during "On/Off" control as this
might damage the steam heater and other components.

WARNING!
When the steam control valve opens, no condensate must remain in the steam heater. During downtime, the
pressure in the heater must not prevent draining of the heater.

NOTE! It is important that the condensate return line does not have too high counter pressure, and that it is
installed at a downward slope from the steam heater outlet all the way to the open condensate tank. This to make
drain of condensate easier.
If this is not possible due to external conditions, the risk of stalling must be minimised by installing a condensate
pump or a component with the same function.

3.10 Set-up and running checks


1. Ensure the shut-off valves are closed.
2. Connect the reactivation heater to the steam supply.
3. Open the steam supply valves.
4. Check that correct steam supply pressure is indicated on the manometer.
5. Check that there are no leaks from the coil or the pipe connections.
6. Check that the thermometer is indicating a temperature relevant to the line pressure.
7. Open the control valve manually, very slowly, to test the condensation evacuation system.

3.11 Duct installation

3.11.1 General recommendations


The connections for process and reactivation air are designed in accordance with the recommendations in
ISO 13351. The rectangular duct connections contain tapped inserts for M8 screws.
NOTE! The dehumidifier has been designed to operate at specific process airflows corresponding to the fan
sizes installed.

When installing ductwork between the dehumidifier and the inlet and outlet connections, the following
recommendations should be observed:
■ The length of ductwork should be kept as short as possible to minimise static air pressure losses.
■ To maintain performance, all rigid process or reactivation air ductwork joints must be air and vapour
tight.
■ The process air ductwork must be insulated to prevent condensation developing on the outside of the
duct, whenever the temperature of the air within the duct falls below the dewpoint temperature of the
ambient air through which the ductwork is routed.
■ The ducts must always be insulated when there is a risk of freezing.
■ The wet air leaving the dehumidifier will, because of high moisture content, condense on the inside duct
walls. By insulating the ducts, the amount of condensate is reduced.

190TEN–1089–G1412 Installation 23
■ Horizontal wet air ducts must be installed with a slight decline (away from the dehumidifier) to drain
away possible condensation. Suitable condensation drains should be installed at low points in the wet
air outlet duct, see Figure 3.5 .
■ Ensure that access for operation and servicing is not restricted when designing and installing ducting.
For more information, see section 8.3, Dimensions and service space.
■ To reduce noise and/or vibrations being transmitted along rigid ducts, good quality, airtight flexible
connections can be fitted.
■ Ducts mounted directly onto the dehumidifier should be adequately supported to minimise the load and
stress due to the weight and movement of the ducting.
■ The total pressure drop in the process and reactivation ductwork must not exceed the available pressure
of the fans fitted to the dehumidifier. For details of minimum available static pressure, see section
8.4, Technical data.

24 Installation 190TEN–1089–G1412
3.11.2 Duct for outdoor air inlet
When bringing ambient air from outdoors into the dehumidifier, the inlet duct opening must be located
sufficiently high above ground level to prevent dust and debris from entering.
The ducting must be designed to prevent rain and snow from being drawn into the dehumidifier. The air
inlet must be located away from possible contaminants such as engine exhaust gases, steam and harmful
vapours.
To prevent the wet (outlet) air from humidifying the reactivation (inlet) air, the air inlet for reactivation must
be located at least 2 m from the wet air outlet.
Attach a wire net with a mesh width of approximately 10 mm in the outer end of the duct to prevent animals
from entering the dehumidifier ducting.

A B A. Rectangular ducting
B. Round ducting
C. Wire netting

C C
Figure 3.4 Outdoor air inlet design

3.11.3 Duct for wet air outlet


The material for the wet air duct must withstand corrosion and temperatures of up to 100 °C. The wet air
ducting must always be insulated if there is a risk of condensation. The wet air leaving the dehumidifier will
easily cause condensation on the inside of the duct walls due to the high moisture content.
Horizontal ducts must be installed sloping downwards (away from the dehumidifier) to drain away possible
condensation. The duct slope must be at least 2 cm/m. In addition, drainage holes (5 mm) should be made at
low points in the duct to prevent water accumulation.
Attach a wire net with a mesh width of approximately 10 mm in the outer end of the duct to prevent animals
from entering the dehumidifier ducting.

A. Horizontal wet air outlet


A B B. Vertical wet air outlet
D C. Wire netting
C D. Downward slope
C E. Condensate drainage

D E
Figure 3.5 Wet air outlet design

190TEN–1089–G1412 Installation 25
3.11.4 Duct connection dimensions, air inlets

A
A

B B

MX² 30S MX² 35-95S

22 160 160 160 160


24 145 145 145

138
170

A B
138

467
380

MX² 30 MX² 30
170

138

527 M6 (10x)
20

771 M6 (14x)
33

22
43 150 200 (3x)
120 200 (2x)
120

200 (2x)

A B
200

480

590

630
MX² 35-55 MX² 35-55
95
120

M8 (14x)
640 M8 (18x)
900
20

770
1075

20 120 200 (4x)


22 120 200 (2x)
200 (2x)
200 120

A B
480

640

680

MX² 60-95 MX² 60-95


120

120

640 M8 (14X)
20

770
20

1040 M8 (20x)
1199

Figure 3.6 Reactivation air inlet (A) and process air inlet (B)

26 Installation 190TEN–1089–G1412
3.11.6 Duct connection dimensions (unit without process fan)

C D C D

MX² 30S MX² 35-95S

160 160
108 160 160 M6 (14x)
138

414
138

C D C D
138

640
158

MX² 30 MX² 35-55

120
138 200 (4x) M8 (20x)
200 (2x)

C D
640
120

1040
123

MX² 60-95
Figure 3.7 Dry air outlet (C) and process air inlet without filter (D)

190TEN–1089–G1412 Installation 27
3.11.7 Duct connection dimensions, process fan

A
MX² 30-95S

283
M8 (8x) 222
C
218
460
414

218
12

12 A
128 128
MX² 30

307
M8 (8X) 247 C M8(10x) 333
243 (2x)

273 23,5
25

C
175 (3x)
510
450

560
500
12

141,5 (2x)
12

12 154,5 (2x) 12

MX² 35-55
A MX² 60-95
A
Figure 3.8 Process air outlet (dry air outlet)

C. Use hexagon head bolts (M8 x 25).

28 Installation 190TEN–1089–G1412
3.11.8 Duct connection dimensions, reactivation fan

MX² 30-95S

170 C
126
214
M8 (6x) 190
C
154

12
130
222
284

130

310
250

143 (2x)
12

B M8(8x) B
12 95 (2x) 12
73
MX² 30 73 MX² 35-55

291
M8(8x) 231 110,5 (2x) 12
12

C
C
239 (2x)

460
400
502
450

218 (2x)

B
23

B M8(8x) 185 27,5


133,5 (2x) 12
12

245
MX² 60
MX² 80 MX² 95
Figure 3.9 Reactivation air outlet (wet air outlet)

C: Use hexagon head bolts (M8 x 25)

190TEN–1089–G1412 Installation 29
3.12 Electrical connections
The dehumidifier is designed for operation with a three-phase four wire system. All dehumidifiers are
delivered complete with all internal wiring installed and configured in accordance with the voltage and
frequency specified on the identification plate.
The mains power supply is connected directly to the main power switch in the unit. The supply cable
and main fuses must be dimensioned to suit the unit being installed. For connection details, refer to the
identification plate and wiring diagram, or to section 8.4, Technical data.
NOTE! The supply voltage must not differ from specified operating voltage by more than +/- 10%.

3.13 External humidity transmitter


The dehumidifier can be delivered without a humidity transmitter, but is normally delivered with one of the
humidity transmitters described below.
■ Combined humidity and temperature transmitter in wall mounted version (standard):
The measurement range for humidity is 0–100 % RH as standard. The measurement range for
temperature is -5...+55 °C as standard.
■ Combined humidity and temperature transmitter in duct mounted version (standard):
The measurement range for humidity is 0–99 % RH as standard. The measurement range for
temperature is -20...+80 °C as standard.
■ Humidity transmitter for dewpoint (optional):
The measurement range for dewpoint temperature is -80...+20 °C.
■ Humidity transmitter for absolute humidity (optional):
The measurement range is 0...99% RH (non condensing), -40 °C...60 °C, with display -30...60°C.
The humidity transmitter is mounted externally and connected according to the wiring diagram provided
with the unit. The humidity transmitter controls the dehumidifier when the mode switch is in AUTO
position, i.e. automatic operation, and also indicates the current humidity.
To ensure correct operation, the humidity transmitter should be connected with NOVOFLEX NCY
(shielded 4G, 0,75 mm²) electric cable, or equal.

When placed on a wall, the humidity transmitter should be mounted 1–1,5 m above the floor. It should be
positioned so that it is not directly exposed to dry air from the unit, or moist air flowing in through doors that
are opened and closed. It should not be placed close to a heat source or be exposed to direct sunlight.
For more information, see the wiring diagram delivered with the unit and the assembly instruction delivered
with the humidity transmitter.

30 Installation 190TEN–1089–G1412
4 Commissioning

WARNING!
Commissioning and initial start-up of the unit must be carried out by authorized personnel only.

WARNING!
The mains power supply is permanently connected to the main power switch of the unit. Risk of electric shock.

4.1 Pre-start checks


1. Make sure that the main power switch on the control panel is set to position 0.
2. Make sure that the air intake filters are undamaged and correctly installed and that all areas inside the
different unit sections are clean.
3. Examine all ducts and duct connections and make sure that all connections have been correctly installed,
and that there are no signs of damage. Make sure that all ducts are free from unwanted material blocking
the air passage.
4. Make sure that the humidity transmitter is correctly positioned in the room, and correctly connected to
the dehumidifier.
5. Open the cover for the electrical panel and make sure that no circuit breakers or automatic fuses have
tripped. For more information, refer to the wiring diagram provided with the unit.
6. Make sure that the incoming power supply voltage is correct and that the cables are correctly connected.
7. Set the main power switch to position 1.
8. Start the unit by setting the mode switch to position MAN.
9. Make sure that the rotor rotates in the direction indicated by the arrows. If the direction of rotation is
wrong, interchange the connections for the incoming wires in the main power switch.
10. Switch off the unit and continue with the procedure in section 4.2, Airflow adjustment.

4.2 Airflow adjustment

4.2.1 General
To obtain optimal performance, the process and reactivation airflows must be correctly adjusted in
accordance with the rated airflows, see 8.4, Technical data. It is recommended to set the airflows in the control
system display without using dampers.
For more information about the control system, parameters and settings, see the control system
supplement.
Contact Munters for help with installation and settings. For contact addresses, see section
10, Contact Munters.
NOTE! The application software settings for the frequency converter are set at the factory. The frequency control
range is limited to correspond to an acceptable fan speed.

WARNING!
Rotating hazard – to prevent access to the fan impellers the dehumidifier must only be run with the wet and dry air
ducts connected.

190TEN–1089–G1412 Commissioning 31
CAUTION!
Failure to correctly adjust the airflows can cause malfunction of the unit.

Any damage to the unit resulting from incorrect adjustment of the airflows can invalidate the warranty of the unit.

The airflows must never be set above the rated airflows without consulting Munters for verification.

4.2.2 Setting the rated airflows


Process fan control with fixed speed
1. Calculate the corresponding differential pressures for the actual process and reactivation airflows. Use
the formula and the fan coefficients in section 4.2.3, Base configuration settings.
2. Start the unit by setting the mode switch in position MAN.
3. Connect a manometer to the pressure nipple on the process fan. Measure and record the differential
pressure.
4. Compare the measured differential pressure with the calculated value.
5. Adjust the settings for the process airflow in the control system, so the measured differential pressure
value corresponds to the calculated value.
6. Connect the manometer to the pressure nipple on the reactivation fan. Repeat the procedure in step 3–5
to set the actual reactivation airflow.
NOTE! The actual airflow is dependant on the temperature at the fan outlet.

Process fan control with variable speed


1. Start the unit by setting the mode switch in position AUTO.
2. Set the required process airflow or process air pressure in the control system.
3. Measure the actual process airflow external to the dehumidifier using external, calibrated test
equipment.
4. If necessary, adjust the settings for process airflow or process air pressure in the control system.
5. Set the required reactivation airflow in the control system.
6. Measure the actual reactivation airflow external to the dehumidifier using external, calibrated test
equipment.
7. If necessary, adjust the settings for the reactivation airflow in the control system.

4.2.3 Base configuration settings

2
q
Δ p= k () p = Differential pressure (Pa)
q = Air flow (m3/h)
k = Fan coefficient

Figure 4.1 Formula for calculation of differential pressure

32 Commissioning 190TEN–1089–G1412
Fan coefficient Air flow Differential Fan speed
(m3/h pressure (rpm)
(Pa)
Process fan 140 2700 372 3000
MX² 30
Reactivation fan 47 900 367 3000
Process fan 222 3500 249 2400
MX² 35
Reactivation fan 94 1080 132 2550
Process fan 222 4000 325 2770
MX² 40
Reactivation fan 94 1260 180 3000
Process fan 222 5500 614 3000
MX² 55
Reactivation fan 94 1080 132 2550
Process fan 390 6000 237 2330
MX² 60
Reactivation fan 147 1980 181 2930
Process fan 390 8000 421 2820
MX² 80
Reactivation fan 150 2520 282 2940
Process fan 390 9500 593 3000
MX² 95
Reactivation fan 147 1800 150 2540

Table 4.1 Base configuration settings

4.3 Set-up and test of steam heater


1. Make sure that the shut-off valves are closed.
2. Connect the reactivation heater to the steam supply.
3. Open the steam supply valves.
4. Check that correct steam supply pressure is indicated on the manometer.
5. Check that there are no leaks from the coil or the pipe connections.
6. Check that the thermometer is indicating a temperature relevant to the line pressure.
7. Open the control valve manually, very slowly, to test the condensation evacuation system.

190TEN–1089–G1412 Commissioning 33
5 Operation
5.1 Control panel

1 ON
RUN ALARM SERVICE
o
OFF
0
o

OFF
SIEMENS

Figure 5.2 Main power switch

1 2 3 4

Figure 5.1 Control panel

Item Switch/Indicator Function

Main power switch (see Figure 5.2 ) When the main power switch is in position 0, the unit is not powered
beyond the switch.
When the main power switch is in position 1, the dehumidifier can be
started.

Control and regulation system (HMI) See the supplement for information on HMI operation.

1 Mode switch When the mode switch is in position MAN, the dehumidifier runs
continuously (full capacity). There is a brief delay before the unit starts.
When the mode switch is in position AUTO, the dehumidifier is regulated
by an internal adjustable humidity level set point, or via an external input
signal.

2 White lamp (RUN) Lights when one of the fans is running.

3 Red lamp (ALARM) Illuminates with a steady glow when an alarm has been triggered. Check
which alarm has been triggered.

4 Yellow lamp (SERVICE) Lights when a filter change is required, or when the dehumidifier has
reached the number of operating hours or the date at which mainte-
nance should be carried out, see section 6.5, Service indicator lamp.

Table 5.1 Control panel functions

34 Operation 190TEN–1089–G1412
5.2 General
The mode switch on the control panel has two operating positions:
■ AUTO (Automatic position): The dehumidifier’s fans, rotor and reactivation heater are activated only
when the humidity exceeds the desired value (the set point). If continual process air operation is selected
in the control system, the process air fan continues to run even after the unit has stopped dehumidifying.
■ MAN (Max effect position): The dehumidifier’s fans, rotor and reactivation heater operate continuously
at full capacity.

Remote start/stop
If remote start/stop is connected, the mode switch must be set to position AUTO in order to run the
dehumidifier.
External control
If the dehumidifier is regulated via an external signal, the fans and drive motor start when the "remote start"
switch is closed, regardless of the present humidity. In order to operate the dehumidifier, the external signal
must be >1 V. The reactivation heater is regulated via the input signal.
On delivery the dehumidifier is set to restart automatically after a power cut.

5.3 Quick stop


Under normal working conditions, the mode switch is used to stop and start the unit (see ). In case of an
emergency, use the main power switch on the dehumidifier.

190TEN–1089–G1412 Operation 35
5.4 Operating the unit

5.4.1 Initial start–up, Manual mode (MAN)


1. Set the main power switch to position 1 and check that the display lights up.
2. Set the mode switch to MAN position. Check that:
■ The white lamp which indicates that the dehumidifier is in operational mode lights. A few seconds
delay is normal.
■ The fans have started..
■ The airflows for the process and reactivation air are correct, see section 8.4, Technical data.
3. Run the unit for about 10 minutes to allow the operating conditions to stabilise. Check that:
■ The steam valve is fully opened and the temperature is increasing.
■ The reactivation heater temperature is correct.
4. Set the mode switch on the control panel to position 0. In order to dissipate any residual heat, the
reactivation air fan will continue to run after the unit has been switched off. The fan will run until the
temperature has fallen below preset temperature, or according to preset time. The default temperature
value is 50 °C and the time value is 30 s.

5.4.2 Inital start-up, Automatic mode (AUTO) – regulating to set point


In order to operate the unit in automatic mode to a desired set point, a humidity transmitter must be
connected. If the system is equipped with "remote start", this switch must be closed.
If remote start is not used, ensure that the jumper between terminal blocks 9 and 10 in row XT1 is fitted.
The following steps applies irrespective of whether the unit is controlled by set points entered via the unit's
display or by external means.
1. Set the main power switch to position 1; electrical connection is confirmed by the display lighting up.
2. Adjust the humidity set point to the lowest possible value, internally or externally.
3. Set the mode switch to AUTO position. Check that:
■ The white lamp which indicates that the unit is in operational mode lights. A few seconds delay
is normal.
■ The fans have started.
■ The heater is switched on.
■ Reactivation temperature increases.
4. a) Frequency controlled reactivation fan: Slowly increase the humidity set point and check that the
reactivation airflow decreases to minimum flow when the set point coincide with the actual humidity.
b) Analogue controlled steam valve: Slowly increase the humidity set point and check that the
reactivation air temperature decreases to minimum temperature when the set point coincide with the
actual humidity.
5. Set the mode switch to position 0. In order to dissipate any residual heat, the reactivation air fan will
continue to run after the unit has been switched off. The fan will run until the temperature has fallen
below preset temperature, or according to preset time. The default temperature value is 50 °C and the
time value is 30 s.

36 Operation 190TEN–1089–G1412
6 Service and maintenance
6.1 Safety
WARNING!
Installation, adjustments, maintenance and repairs must only be carried out by qualified personnel who are
aware of the risks involved when working with equipment operating with high electrical voltage and high machine
temperatures.

WARNING!
The mains power supply is permanently connected to the main power switch of the unit. Risk of electric shock.

WARNING!
The dehumidifier can restart automatically after a power cut. Always switch off and lock the main power switch
before carrying out any service work.

6.2 Regular service and maintenance


Munters dehumidifiers are designed to run reliably in continuous operation for long periods. Regular
service and maintenance is required to ensure that the dehumidifier is operating as efficient and economical
as possible.
Service and maintenance interval lengths are primarily determined by operating conditions and the
environment in which the unit is installed. For example, if the process air contains a lot of dust, preventative
maintenance should be carried out at shorter intervals. The same also applies if the dehumidifier works
intensively.
The service levels for a standard service and maintenance programme are described in section
6.3, Service options.
The dehumidifier's control system is equipped with a service indicator. During installation and
commissioning, an estimate should be made of a suitable number of operating hours until the next service,
or the date for the next service. This value is programmed by Munters personnel at initial start-up of the unit.

190TEN–1089–G1412 Service and maintenance 37


6.3 Service options
In addition to commissioning of the unit there are four service options (A - D) as standard.
S. Commissioning/start-up.
A. Inspection and if necessary change of filter. General function check.
B. In addition to A, safety check and capacity, temperature and humidity regulation measurements.
C. In addition to B, preventive replacement of some components after 3 years of operation.
D. In addition to C, preventive replacement of some components after 6 years of operation.
NOTE! Always contact Munters for service or repair. Operating faults can occur if the unit is maintained
insufficiently or incorrectly.

NOTE! Commissioning/Start-up inspection "S" by Munters is mandatory to validate the full warranty.

Munters service engineers have special equipment and rapid spare parts access to handle service on all
Munters products. All test equipment used by our personnel to ensure proper system balancing is certified
for accuracy.
Munters Service can offer a service plan adapted to suit the conditions of a specific installation. See contact
addresses on the back page of this manual.
The service options comprises service efforts indicated in Table 6.1 and Table 6.2.

6.4 Extended warranty


Munters offers an extended warranty to the standard terms when the Customer signs a service contract with
Munters. Details are available on request.

6.5 Service indicator lamp


The yellow service indicator lamp indicates one of the following:
■ Filter replacement required
■ Humidity level too high
■ Service requirements
The reason for the service alarm is shown on the control system display.

38 Service and maintenance 190TEN–1089–G1412


6.6 Service and maintenance schedule
(0–24000 hours)

Service level S A B A B A C

Service work Operating time in hours 0 4000 8000 12000 16000 20000 24000

Calendar time in months 0 6 12 18 24 30 36

Filter inspection, filter replacement if necessary, operational


X X X X X X X
checks

Preventive inspection, safety checks X X X X

Capacity monitoring, rotor inspection X X X X

Replacement of HTCO Thermostats 1) X

Inspection of electric heater / steam heater X

Replacement of drive belt and belt lock X

Replacement of rotor drive motor

Inspection of fans (impellers, motors, bearings)

Operational check of electric panel and control system X X X X

Calibration of humidity control equipment, sensors, valves, SSR X X X X

Calibration of temperature control equipment and sensors X X X X

Replacement of rotor seals

1) Not required for units with steam reactivation heater.

Table 6.1 Service and maintenance schedule (0–24000 hours)

NOTE! Commissioning/Start-up inspection "S" by Munters is mandatory to validate the full warranty.

NOTE! Service work should be performed at indicated operating hours or calendar time, whichever is reached
first.

NOTE! The desiccant rotor will not be replaced preventively, capacity monitoring will indicate rotor replacement.

190TEN–1089–G1412 Service and maintenance 39


6.7 Service and maintenance schedule
(28000–48000 hours)

Service level A B A B A D

Service work Operating time in hours 28000 32000 36000 40000 44000 48000

Calendar time in months 42 48 54 60 66 72

Filter inspection, filter replacement if necessary, operational checks X X X X X X

Preventive inspection, safety checks X X X

Capacity monitoring, rotor inspection X X X

Replacement of HTCO Thermostats 1) X

Inspection of electric heater / steam heater X

Replacement of drive belt and belt lock X

Replacement of rotor drive motor X

Inspection of fans (impellers, motors, bearings) X

Operational check of electric panel and control system X X X

Calibration of humidity control equipment, sensors, valves, SSR X X X

Calibration of temperature control equipment and sensors X X X

Replacement of rotor seals X

1) Not required for units with steam reactivation heater.

Table 6.2 Service and maintenance schedule (28000–48000 hours)

NOTE! Maintenance schedule restarts again after maintenance type D.

40 Service and maintenance 190TEN–1089–G1412


6.8 Maintenance of steam reactivation heater
Adjustment, maintenance and repairs should only be carried out by qualified personnel who are aware of the
hazards of operating and maintaining equipment operating with high voltages and high steam temperatures.
Before attempting to carry out any inspection or maintenance in the heater compartment, the reactivation
heater must be allowed to cool down.
The following must be carried out before the dehumidifier is re-started:
1. Examine all ductwork and duct insulation for correct connection and for general signs of damage and
leaks.
2. Examine the steam connections to ensure that all pipes are correctly installed and secured.

Service interval Service work

Weekly Make sure that correct pressure is indicated on the manometer.

Examine all steam connections for leaks.

Monthly Examine the heater compartment for signs of corrosion and scale build-up.
All signs of corrosion must be treated immediately. Any scale deposits or dirt accumulated on the
bottom of the heater compartment should be removed.

Make sure that the electrical connections for the modulating valve are secure.

Six-monthly Examine the modulating valve. Refer to manufacturer's technical documentation.

Examine all finned surfaces for corrosion. Repair if necessary.

Annually Drain the heater. Examine the water for minute magnetic deposits.

Table 6.3 Periodic maintenance for steam heater unit.

190TEN–1089–G1412 Service and maintenance 41


6.9 Air filter replacement

MX² 30 MX² 35-95


Figure 6.1 Tools required

The procedure for filter replacement is the same for process filter and reactivation filter. Replacement of
reactivation filter on MX² 55 shown as an example. The numbers within brackets refer to Figure 6.2 and
Figure 6.3 .
1. Set the mode switch to position 0.
2. Wait 60 seconds for the heater to cool down.
3. Set the main power switch to position 0 and lock the switch.
4. Open the filter box door by turning the lock counter clockwise (1).
5. Lift off the door (2).
6. Push the upper and lower filter clamp to release the filter (3).
7. Pull out the filter (4).

1 2

3 4

Figure 6.2

42 Service and maintenance 190TEN–1089–G1412


8. Clean the filter clamps and filter box using a vacuum cleaner.
9. Put the new filter between the filter clamps and push the filter fully into the filter box . Make sure that the
arrow on the filter points in the same direction as the air stream (5).
10. Pull the upper and lower filter clamp out towards the opening in the filter box, until the clamps click into
a locked position (6).
11. Install the door (7).
12. Tighten the lock (8).

5 6

7 8

Figure 6.3

190TEN–1089–G1412 Service and maintenance 43


7 Fault tracing
7.1 Safety
WARNING!
Installation, adjustments, maintenance and repairs must only be carried out by qualified personnel who are
aware of the risks involved when working with equipment operating with high electrical voltage and high machine
temperatures.

WARNING!
The mains power supply is permanently connected to the main power switch of the unit. Risk of electric shock.

WARNING!
The dehumidifier can restart automatically after a power cut. Always switch off and lock the main power switch
before carrying out any service work.

44 Fault tracing 190TEN–1089–G1412


7.2 Fault tracing list, dehumidifier
Before contacting Munters, go through the fault tracing list below. Investigate the cause of alarm and rectify
if possible. The list provides help in identifying faults that can often be rectified without the assistance of
specially trained personnel.
NOTE! Other alarm indications are possible. Consult Munters service in these cases.

Fault symptom Indicators Possible cause Corrective action

The unit has stopped. The display window is not lit. Power supply failure. Check the power supply to the unit.

A fuse and/or circuit breaker has Investigate the cause of the fault and rectify.

tripped. Reset the fuse and circuit breaker. If the fault

re-occurs, contact Munters service.

The unit is in AUTO mode and has The display window is lit. Dehumidification is not required. Check if the current humidity level is lower than

stopped. the setpoint.

Check the function by setting the setpoint

lower than the actual humidity value and noting

whether the unit starts.

Verify that the value given by the humidity

sensor is correct.

Remote start not connected. Check the wire jumper on the remote start

circuit.

The unit has stopped. The red alarm lamp on the

control panel is lit. The following

text is shown on the display:

– Modbus comm Communication faults to the Stop the unit via the mode switch and restart.

frequency converter. Reset the alarm.

– React Fan Fault Low power supply. Check flows, fan motor and circuit breaker.

Remedy any faults, reset the circuit breaker.

– Process Fan Fault Low power supply. Check flows, fan motor and circuit breaker.

Remedy any faults, reset the circuit breaker.

– Rotor Drive Fault Drive belt error. Check the tension and condition of the drive

belt.

Drive motor overheating; rotor Check the motor, drive and rotor seals. Reset

runs with difficulty. the circuit breaker.

– Damper Open/close Fault Damper actuator error. Check actuator and gears.

190TEN–1089–G1412 Fault tracing 45


Fault symptom Indicators Possible cause Corrective action

The unit has stopped. – React Heater HTCO The air flow is too low. One For units with electric heater: Check that the

of the high temperature airflow is correct. Reset the circuit breakers

cut-outs has tripped, either and the high temperature cut-out.

due to an obstruction in the


For units with gas heater: Check that the
reactivation airflow or because
airflow is correct. Reset the high temperature
the reactivation airflow has been
cut-out.
set too low.

Broken PT1000 sensor. Check that the sensor is working.

Power failure. Check the power supply to the unit.

– React Heater Fault Reactivation heater error. Contact Munters Service.

Yellow alarm when the unit is in The yellow alarm lamp on the

operation. control panel is lit. The following

text is shown on the display:

– React Filter 1 Reactivation filter clogged. Change the filter and reset the alarm.

– React Filter 2 Reactivation filter clogged. Change the filter and reset the alarm.

– Process Pre Filter 1 Process filter clogged. Change the filter and reset the alarm.

– Process Pre Filter 2 Process filter clogged. Change the filter and reset the alarm.

– Humidity Deviation Alarm The humidity exceeds the Reset the alarm.

setpoint. This is probably due

to some other fault in the unit or

temporary excessive humidity in

the space.

– Temperature Deviation Alarm No cooling/heating medium Verify medium supply

supply to coils, unusual heat/cool

load (open window, too much

people).

– Service message Preset data for date and/or Contact Munters service.

operating hours for next service

has passed.

– React Heater Gas Low For units with gas burner: Gas Check the gas supply up to the unit.

pressure is too low.

The unit is running but is not – Humidity Deviation Reactivation and process Check and adjust the reactivation and process

reducing the humidity. airflows do not correspond to the air flow, see the basic manual for the unit.

rated airflows.

The humidity transmitter is not Check that the humidity transmitter works

working properly. properly and is correctly connected as

described in the recommendations.

46 Fault tracing 190TEN–1089–G1412


Fault symptom Indicators Possible cause Corrective action

The unit is running but is not – Humidity Deviation P-band, I-time or hysteresis are Check these parameters.

reducing the humidity. incorrectly set.

The rotor is worn out. Contact Munters service.

Table 7.1 Fault tracing list, dehumidifier

7.3 Fault tracing list, steam heater unit


The fault tracing list below provides help in identifying faults related to the steam heater unit.

Before contacting Munters service, go through the list below and rectify the fault if possible.

Fault symptom Possible cause Corrective action

General

Low or no reactivation heat. Incorrect steam pressure. Check that pressure indicated on manometer is within the

working limits

(<10 barg overpressure).

Blocked steam trap. Check the function of the steam trap and replace it if

necessary.

Incorrect steam temperature. Check that the temperature indicated on the thermometer

corresponds to the line pressure.

Closed shut-off valve. Check that the shut-off valves are open.

The modulating steam valve remains closed. Check that the modulating valve is operating correctly.

Blocked steam pipes. Check the steam pipe work for blockage.

Leaking steam pipes. Check the steam pipe works for leaks.

Loss of performance

The unit is operating, but is not controlling air Steam reactivation heater malfunction. Check the steam pressure and temperature in the heater.

humidity.
Check that the steam pipe work is not blocked or leaking.

The modulating steam valve does not open Check the controller for regulation of the modulating valve

fully. and the signal to the modulating valve.

Clogged filter or clogged steam trap. Clean the filter and steam trap.

Performance variations

The unit is operating, but air humidity varies. The steam pressure varies. Stabilise the steam pressure.

Other cause Contact Munters service.

Table 7.2 Fault tracing list, steam heater unit

190TEN–1089–G1412 Fault tracing 47


8 Technical specification
8.1 Capacity diagrams
NOTE! The figures in the diagrams are based on a rated airflow (1/1).

kg/h
3 MX² 30 kg/h MX² 35
30 40

80 % RH

60 % RH
80 % RH
30 60 % RH
40 % RH
20

40 % RH

20

10

1 10

0 0
-10 0 10 20 30 °C -10 0 10 20 30 °C

kg/h MX² 40 kg/h MX² 55


50 40

80 % RH
40 80 % RH
60 % RH
30
60 % RH

40 % RH 40 % RH
30

20

20

10
10

0 °C 0 °C
-10 0 10 20 30 -10 0 10 20 30

1. Process air temperature (°C)

2. Process air relative humidity (%RH)

3. Dehumidification capacity (moisture removal) (kg/h)

48 Technical specification 190TEN–1089–G1412


kg/h MX² 60 kg/h MX² 80
70 90

80 % RH 80 80 % RH
60
60 % RH 60 % RH
70

50 40 % RH 40 % RH
60

40 50

40
30

30
20
20

10
10

0 °C 0 °C
-10 0 10 20 30 -10 0 10 20 30

kg/h
MX² 95
60

80 % RH
60 % RH
50
40 % RH

40

30

20

10

0 °C
-10 0 10 20 30

190TEN–1089–G1412 Technical specification 49


8.2 Noise data

8.2.1 Noise to room

A B C D
3 1 3 1 3 1 3 1
4 4 4 4
2 2 2 2
Figure 8.1 Duct connection setups
Setup A: All ducts connected 1. Ductwork for dry air
Setup B: Process inlet not connected to duct 2. Ductwork for process air
Setup C: Reactivation inlet not connected to duct 3. Ductwork for reactivation air
Setup D: Reactivation and process inlet not connected to duct 4. Ductwork for wet air

Lp(A) 100 m2 = Rated pressure sound level at 100 m2 room absorption (A–weighted).
Lwt = Total sound power level (db) (rel. 10 –12 W)
Kok = Correction for calculating Lw (Lw = Lwt + Kok)
MX² 30E Correction Kok dB at ISO-band centre frequency, Hz

Setup Lp(A) 100 m2 Lwt 63 125 250 500 1000 2000 4000 8000
(dB)

A 68 88 -13 -5 -3 -10 -14 -15 -16 -22

B 69 89 -14 -3 -5 -10 -14 -14 -16 -22

C 69 90 -8 -5 -5 -11 -14 -15 -16 -22

D 69 90 -11 -4 -5 -10 -14 -14 -17 -22

MX² 35E Correction Kok dB at ISO-band centre frequency, Hz

Setup Lp(A) 100 m2 Lwt 63 125 250 500 1000 2000 4000 8000
(dB)

A 67 84 -10 -6 -7 -9 -6 -14 -16 -14

B 68 87 -8 -5 -8 -8 -9 -17 -20 -18

C 68 86 -10 -5 -9 -10 -5 -16 -18 -16

D 69 88 -7 -4 -10 -9 -8 -18 -20 -18

Table 8.1 Noise to room

50 Technical specification 190TEN–1089–G1412


MX² 40E Correction Kok dB at ISO-band centre frequency, Hz

Setup Lp(A) 100 m2 Lwt 63 125 250 500 1000 2000 4000 8000
(dB)

A 71 90 -9 -5 -8 -7 -11 -14 -17 -18

B 73 93 -8 -4 -10 -6 -14 -17 -20 -22

C 71 91 -8 -4 -7 -10 -12 -14 -16 -20

D 72 92 -6 -5 -9 -8 -13 -16 -17 -19

MX² 55E Correction Kok dB at ISO-band centre frequency, Hz

Setup Lp(A) 100 m2 Lwt 63 125 250 500 1000 2000 4000 8000
(dB)

A 71 90 -7 -4 -10 -9 -9 -14 -15 -19

B 72 93 -7 -3 -9 -9 -11 -15 -19 -22

C 70 91 -10 -3 -8 -10 -12 -14 -16 -20

D 72 93 -6 -3 -11 -10 -12 -17 -18 -22

MX² 60E Correction Kok dB at ISO-band centre frequency, Hz

Setup Lp(A) 100 m2 Lwt 63 125 250 500 1000 2000 4000 8000
(dB)

A 73 92 -6 -7 -6 -10 -10 -16 -14 -14

B 75 94 -7 -8 -7 -5 -12 -18 -16 -15

C 73 93 -6 -6 -7 -11 -11 -17 -14 -15

D 75 94 -7 -8 -7 -6 -12 -16 -16 -15

MX² 80E Correction Kok dB at ISO-band centre frequency, Hz

Setup Lp(A) 100 m2 Lwt 63 125 250 500 1000 2000 4000 8000
(dB)

A 76 95 -5 -7 -7 -10 -10 -15 -14 -16

B 78 97 -6 -8 -8 -5 -11 -17 -16 -16

C 76 96 -5 -6 -8 -11 -10 -15 -15 -16

D 78 97 -6 -8 -8 -6 -12 -15 -16 -16

MX² 95E Correction Kok dB at ISO-band centre frequency, Hz

Setup Lp(A) 100 m2 Lwt 63 125 250 500 1000 2000 4000 8000
(dB)

A 76 97 -5 -5 -9 -12 -12 -13 -15 -19

B 79 98 -5 -7 -9 -8 -12 -13 -18 -20

C 76 97 -5 -4 -9 -10 -13 -14 -18 -19

D 79 98 -5 -6 -8 -8 -12 -13 -17 -21

Table 8.2 Noise to room

190TEN–1089–G1412 Technical specification 51


8.2.2 Noise in ducts

A B C D
3 1 3 1 3 1 3 1
4 4 4 4
2 2 2 2
Figure 8.2 Duct connection setups
Setup A: All ducts connected 1. Ductwork for dry air
Setup B: Process inlet not connected to duct 2. Ductwork for process air
Setup C: Reactivation inlet not connected to duct 3. Ductwork for reactivation air
Setup D: Reactivation and process inlet not connected to duct 4. Ductwork for wet air

Lwt = Total sound power level (db) (rel. 10 –12 W)


Kok = Correction for calculating Lw (Lw = Lwt + Kok)

MX² 30E Correction Kok dB at ISO-band centre frequency, Hz

Ductwork Lwt (dB) 63 125 250 500 1000 2000 4000 8000

1. Dry air 105 -18 -18 0 -15 -23 -28 -34 -40

2. Process air 87 -2 -11 -6 -14 -25 -30 -37 -47

3. Reactivation air 87 0 -12 -19 -29 -36 -39 -45 -53

4. Wet air 93 -9 -11 -2 -8 -13 -20 -25 -32

MX² 35E Correction Kok dB at ISO-band centre frequency, Hz

Ductwork Lwt (dB) 63 125 250 500 1000 2000 4000 8000

1. Dry air 96 -8 -6 -4 -7 -15 -21 -28 -36

2. Process air 85 -1 -11 -16 -13 -24 -34 -41 -51

3. Reactivation air 93 -1 -7 -21 -38 -42 -45 -52 -57

4. Wet air 100 -7 -11 -2 -18 -24 -29 -37 -42

MX² 40E Correction Kok dB at ISO-band centre frequency, Hz

Ductwork Lwt (dB) 63 125 250 500 1000 2000 4000 8000

1. Dry air 100 -8 -4 -7 -9 -14 -17 -23 -31

2. Process air 86 -1 -8 -13 -11 -22 -28 -35 -47

3. Reactivation air 88 -2 -4 -16 -24 -31 -36 -43 -64

4. Wet air 100 -8 -9 -3 -9 -16 -22 -31 -35

Table 8.3 Noise in ducts

52 Technical specification 190TEN–1089–G1412


MX² 55E Correction Kok dB at ISO-band centre frequency, Hz

Ductwork Lwt (dB) 63 125 250 500 1000 2000 4000 8000

1. Dry air 103 -9 -4 -8 -5 -13 -17 -23 -29

2. Process air 88 -2 -8 -13 -11 -20 -27 -34 -46

3. Reactivation air 87 -1 -7 -17 -32 -36 -38 -44 -49

4. Wet air 96 -5 -7 -4 -13 -18 -23 -32 -35

MX² 60E Correction Kok dB at ISO-band centre frequency, Hz

Ductwork Lwt (dB) 63 125 250 500 1000 2000 4000 8000

1. Dry air 104 -6 -4 -9 -9 -14 -21 -27 -34

2. Process air 87 -2 -7 -10 -13 -19 -27 -37 -44

3. Reactivation air 84 -2 -7 -8 -18 -26 -31 -38 -48

4. Wet air 100 -8 -6 -5 -7 -17 -20 -27 -34

MX² 80E Correction Kok dB at ISO-band centre frequency, Hz

Ductwork Lwt (dB) 63 125 250 500 1000 2000 4000 8000

1. Dry air 109 -6 -4 -9 -8 -13 -19 -25 -32

2. Process air 93 -1 -8 -13 -15 -22 -28 -35 -45

3. Reactivation air 84 -1 -9 -9 -22 -25 -28 -34 -44

4. Wet air 100 -13 -9 -2 -11 -18 -22 -28 -31

MX² 95E Correction Kok dB at ISO-band centre frequency, Hz

Ductwork Lwt (dB) 63 125 250 500 1000 2000 4000 8000

1. Dry air 110 -8 -4 -8 -9 -12 -18 -23 -29

2. Process air 94 -2 -8 -13 -13 -22 -27 -35 -43

3. Reactivation air 82 -1 -12 -9 -23 -29 -33 -40 -47

4. Wet air 98 -6 -5 -6 -10 -17 -23 -28 -35

Table 8.4 Noise in ducts

190TEN–1089–G1412 Technical specification 53


8.3 Dimensions and service space

8.3.1 Dimensions

C
A B D F Q
E

O
M
G

P
N

R
J

K
I

H L
Figure 8.3 MX² 30S

A B C D E F Q

O
M

P
G

R
K
J
I

H L

Figure 8.4 MX² 35–95S

54 Technical specification 190TEN–1089–G1412


8.3.2 Dimensions (unit without process fan)

C
A B F Q
E

O
M
G

P
N

R
K
T

U
S V

Figure 8.5 MX² 30S without process fan

A B C E F Q

O
M

P
G

R
K

U
T

S
V

Figure 8.6 MX² 35–95S without process fan

190TEN–1089–G1412 Technical specification 55


Dimensions
MX² 30S MX² 35S MX² 40S MX² 55S MX² 60S MX² 80S MX² 95S
(mm)

A 810 1091 1091 1091 1307 1307 1307

B 455 518 518 518 561 634 561

C 800 1068 1068 1068 1068 1068 1068

D 641 711 711 711 787 787 787

E 74 63 63 63 52 61 62

F1) 400 667 657 667 636 621 636

F2) 400 682 667 682 666 651 666

G 1882 1899 1899 1899 2204 2204 2204

H 381 541 541 541 629 629 626

I 365 450 450 450 500 500 500

J 666 753 753 753 853 853 853

K 586 737 737 737 921 891 921

L1) 189 177 177 177 177 177 177

L2) 650 602 602 602 602 602 602

M1) 469 405 405 405 436 436 436

M2) 469 412 405 412 436 436 436

N 1058 1284 1284 1284 1589 1589 1589

48,7 (1½” 48,7 (1½” 48,7 (1½” 48,7 (1½” 48,7 (1½” 48,7 (1½” 48,7 (1½”
O
BSP) BSP) BSP) BSP) BSP) BSP) BSP)

P 33,7 (1” BSP) 33,7 (1” BSP) 33,7 (1” BSP) 33,7 (1” BSP) 33,7 (1” BSP) 33,7 (1” BSP) 33,7 (1” BSP)

Q 177 165 165 165 181 204 181

R 958 1100 1100 1100 1304 1322 1304

S 381 510 510 510 649 649 649

T 365 417 417 417 443 443 443

U 348 417 417 417 443 443 443

V 381 509 509 509 648 648 648

F1): 3 barg

F2): 5 barg

L1): G4 filter

L2): F7 filter (option)

M1): 3 barg

M2): 5 barg

Table 8.5 Dimensions

56 Technical specification 190TEN–1089–G1412


8.3.3 Service space

1000

200
500
500
1200

Figure 8.7 Required service space (S)

190TEN–1089–G1412 Technical specification 57


8.4 Technical data

MX² 30S MX² 35S MX² 40S MX² 55S MX² 60S MX² 80S MX² 95S

Process air

Figures quoted are rated, based on a fan inlet

temperature of 20 °C and an air density of 1,2 kg/m3.

Rated airflow (m3/s) 0,750 0,972 1,111 1,528 1,667 2,222 2,639

Rated airflow (m3/h) 2700 3500 4000 5500 6000 8000 9500

Minimum available static pressure (Pa) 300 300 300 300 300 300 300

Fan motor power (kW) 2,2 3,0 3,0 3,0 7,5 7,5 7,5

Reactivation air

Rated airflow (m3/s) 0,250 0,300 0,350 0,300 0,550 0,700 0,500

Rated airflow (m3/h) 900 1080 1260 1080 1980 2520 1800

Minimum available static pressure (Pa) 300 300 300 300 300 300 300

Fan motor power (kW) 0,75 1,1 1,1 1,1 1,5 2,2 1,5

Rated current with

process and reactivation fan, Standard/EEP

Current (Amps/Phase) at 380 V, 50/60 Hz (A) 7 10 10 10 19 20 19

Current (Amps/Phase) at 400 V, 50/60 Hz (A) 7 9 9 9 18 19 18

Current (Amps/Phase) at 415 V, 50/60 Hz (A) 7 9 9 9 17 18 17

Current (Amps/Phase) at 440 V, 50/60 Hz (A) 6 8 8 8 16 17 16

Rated current with

process and reactivation fan, ERP

Current (Amps/Phase) at 380 V, 50/60 Hz (A) 7 10 10 10 19 21 19

Current (Amps/Phase) at 400 V, 50/60 Hz (A) 7 9 9 9 18 20 18

Current (Amps/Phase) at 415 V, 50/60 Hz (A) 7 9 9 9 18 19 18

Current (Amps/Phase) at 440 V, 50/60 Hz (A) 6 9 9 9 17 18 17

Reactivation heater

Temperature increase across heater (°C) 100 100 100 100 100 100 100

Reactivation heater power (kW) 30 36 42 36 66 84 60

Reactivation heater power, ERP (kW) 25 36 36 36 60 78 60

Total required power (50 Hz)

With process and reactivation fans (kW) 3,4 4,6 4,6 4,6 9,5 10,2 9,5

Without process fan (kW) 1,2 1,6 1,6 1,6 2,0 2,7 2,0

58 Technical specification 190TEN–1089–G1412


MX² 30S MX² 35S MX² 40S MX² 55S MX² 60S MX² 80S MX² 95S

Steam data

Steam consumption (g/s) at 3 barg 14,1 14,1 19,7 16,9 30,9 39,4 28,1

Steam consumption (g/s) at 5 barg 14,4 14,4 20,1 17,3 31,6 40,3 28,8

Steam consumption, ERP (g/s) at 3 barg 11,7 14,1 16,9 16,9 28,1 36,6 28,1

Steam consumption, ERP (g/s) at 5 barg 12,0 14,4 17,3 17,3 28,8 37,4 28,8

Maximum steam working pressure (bar) 7 7 7 7 7 7 7

Miscellaneous data

Drive motor power (W) 10 10 10 10 10 10 10

IEC protection class, unit IP33 IP33 IP33 IP33 IP33 IP33 IP33

IEC protection class, electrical panel IP54 IP54 IP54 IP54 IP54 IP54 IP54

Fan motor winding insulation class Class F Class F Class F Class F Class F Class F Class F

Drive motor winding insulation class Class F Class F Class F Class F Class F Class F Class F

Contactor coil voltage (V AC) 230 230 230 230 230 230 230

External (potential-free) output contacts 8 A, 250 V 8 A, 250 V 8 A, 250 V 8 A, 250 V 8 A, 250 V 8 A, 250 V 8 A, 250 V

AC (max.) AC (max.) AC (max.) AC (max.) AC (max.) AC (max.) AC (max.)

Moisture removal at 20 °C, RH 60 % (kg/24 h) 535 520 768 660 1220 1550 1150

Weight (kg) 407 488 557 492 721 729 673

Weight without process fan (kg) 385 412 481 416 599 607 551

Corrosion class, outside casing C4 (painted, AluZink 150, ISO 12944)

Corrosion class, inside casing C3 (unpainted, AluZink 150, ISO 12944)

Environmental conditions

Operating temperature (°C) -20... +40

Maximum installation altitude, above sea level (m) 2000

Transport and storage temperature (°C) -20... +70

Table 8.6 Technical data for units with steam heater

190TEN–1089–G1412 Technical specification 59


9 Scrapping
The unit must be scrapped in accordance with applicable legal requirements and regulations. Contact your
local authorities.
The rotor material is not combustible, and should be deposited like glass fibre materials.
If the rotor has been exposed to chemicals that are dangerous to the environment the risk must be assessed.
The chemicals can accumulate in the rotor material. Take the necessary precautions to comply with
applicable legal requirements and regulations.

WARNING!
If the rotor is to be cut in pieces, wear a suitable CE marked face mask selected and fitted in accordance with the
applicable safety standards to protect from the dust.

60 Scrapping 190TEN–1089–G1412
10 Contact Munters
AUSTRIA Munters GmbH Eduard-Kittenberger-Gasse 56, Tel: +43 1 616 4298–92 51
Air Treatment Obj. 6 luftentfeuchtung@munters.at
Zweigniederlassung Wien A-1235 Wien www.munters.at

BELGIUM Munters Belgium nv Blarenberglaan 21c Tel: +3215285611


Air Treatment B-2800 Mechelen service@muntersbelgium.be
www.muntersbelgium.be

CZECH REPUBLIC Munters CZ, organizacni slozka Slevacská 2368/68 Tel: +420 775 569 657
Air Treatment CZ-615 00 BRNO info@munters-odvlhcovani.cz
www.munters-odvlhcovani.cz

DENMARK Munters A/S Ryttermarken 4 Tel: +4544953355


Air Treatment DK-3520 Farum info@munters.dk
www.munters.dk

FINLAND Munters Finland Oy Hakamäenkuja 3 Tel: +358 207 768 230


Kuivaajamyynti FI-01510 VANTAA laitemyynti@munters.fi
www.munters.fi

FRANCE Munters France SAS 106, Boulevard Héloise Tel: +33 1 34 11 57 57


Air Treatment F-95815 Argenteuil Cedex dh@munters.fr
www.munters.fr

GERMANY Munters GmbH Hans-Duncker-Str. 8 Tel: +49 (0) 40 879 690 - 0


Air Treatment-Zentrale D-21035 Hamburg mgd@munters.de
www.munters.de

ITALY Munters Italy S.p.A Strada Piani 2 Tel: +39 0183 521377
Air Treatment I-18027Chiusavecchia marketing@munters.it
IM www.munters.it

NETHERLANDS Munters Vochtbeheersing Energieweg 69 Tel: +31 172 43 32 31


NL-2404 HE Alphen a/d Rijn vochtbeheersing@munters.nl
www.munters.nl

POLAND Munters Sp. z o.o. ul. Swietojanska 55/11 Tel.: + 48 58 305 35 17


Oddzial w Polsce 81-391 Gdynia dh@munters.pl
Air Treatment www.munters.com.pl

SPAIN Munters Spain SA Europa Epresarial. Edificio Londres. Tel: +34 91 640 09 02
Air Treatment C/Playa de Liencres 2. marketing@munters.es
28230 Las Matas. Madrid www.munters.es

SWEDEN Munters Europe AB P O Box 1150 Tel: +46 8 626 63 00


Air Treatment S-164 26 Kista avfuktning@munters.se
www.munters.se

SWITZERLAND Munters GmbH Glattalstr. 501 Tel: +41 52 343 88 86


Air Treatment CH-8153 Rümlang info.dh@munters.ch
Zweigniederlassung Rümlang www.munters.ch

UNITED KINGDOM Munters Ltd Pathfinder Place 10 Ramsay Court Tel: +44 1480 432 243
Air Treatment Hinchingbrooke Business Park info@munters.co.uk
Huntingdon PE29 6FY Cambs www.munters.co.uk

AUSTRALIA Tel:+61 288431588 MEXICO Tel:+52 722 270 40 29


dh.info@munters.com.au munters@munters.com.mx

BRAZIL Tel: +55 11 5054 0150 SINGAPORE Tel:+65 6744 6828


www.munters.com.br singapore@muntersasia.com

CANADA Tel: +1-800-843-5360 SOUTH AFRICA Tel:+27 11 997 2000


dhinfo@munters.com info@munters.co.za

CHINA Tel: +86 10 804 18000 TURKEY Tel:+90 216 548 14 44


marketing@munters.cn info@muntersform.com

INDIA Tel:+91 20 668 18 900 UAE (Dubai) Tel:+971 4 881 3026


info@munters.in middle.east@munters.com

JAPAN Tel:+81 3 5970 0021 USA Tel: +1-800-843-5360


mkk@munters.jp dhinfo@munters.com

KOREA Tel:+82 2 761 8701


munters@munters.kr

190TEN–1089–G1412 Contact Munters 61


.
www.munters.com

You might also like