Tecb Riy3 MF RF 104

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

NORTH DIRECTION

H
RT
NO
6 7 8 9 10 11 12 13 14 15 16 18 19 20 21 22 23 24 26 27
NOVEC CLEAN AGENT
17 25
SYSTEM-71
2 CYLINDER ( 2X180 KG) =360 KG
WITH STEEL ENCLOSURE
NOVEC CLEAN AGENT SYSTEM- 70
1 CYLINDER (1 X140 KG) =140 KG
WITH STEEL ENCLOSURE

A A
FE-1 FE-1 FE-1 FE-1
FE-1
Ø50 RN Ø25 mm Ø32 mm Ø40 mm Ø50 mm Ø40 mm Ø32 mm Ø25 mm Ø50 mm

EMERGENCY STAIR Ø50 mm


B B

Ø50 mm

Ø50 mm
C N/S C
NOVEC SYSTEM NO. 70 NOVEC CLEAN AGENT SYSTEM- 72
FE-2 2 CYLINDER ( 2X180 KG) =360 KG
D FE-1 N/S D
WITH STEEL ENCLOSURE CORRIDOR
Ø25 mm Ø32 mm Ø40 mm Ø50 mm Ø50 mm Ø50 mm
NOVIC CLEAN AGENT SYSTEM- 69

Ø50 mm
1 CYLINDER (1 X70 KG) =70 KG

Ø50 mm
E CORRIDOR Ø50 mm E
WITH STEEL ENCLOSURE

Ø80 mm
Ø25 mm

Ø25 mm
F FE-1 FE-2 F
FE-2
IT CLOSET
CORRIDOR

FE-1
STORAGE

Ø50 mm
Ø80 mm
SPARE AREA

Ø50 mm
G G

N/S N/S
1 2 3 4 5
NOVEC SYSTEM NO. 71 NOVEC SYSTEM NO. 72

POWER ROOM POD-8 FE-1


FE-2

Ø50 mm

Ø50 mm
POD-8
H H

FE-1 N/S N/S


H* CORRIDOR H*
I NOVIC CLEAN AGENT SYSTEM- 85 NOVEC SYSTEM NO. 73 NOVEC SYSTEM NO. 74 I
J 3 CYLINDER (3X165 KG) =495 KG J
WITH STEEL ENCLOSURE NOVEC CLEAN AGENT SYSTEM- 73

Ø50 mm
2 CYLINDER ( 2X180 KG) =360 KG

Ø50 mm
WITH STEEL ENCLOSURE

K NOVEC SYSTEM NO. 85 NOVEC CLEAN AGENT SYSTEM- 75 K


1 CYLINDER (1 X140 KG) =140 KG
L N/S WITH STEEL ENCLOSURE L
FE-2

Ø50 mm
FE-2

Ø80 mm
M NOVEC CLEAN AGENT SYSTEM- 74 M

Ø50 mm
N FE-1 2 CYLINDER ( 2X180 KG) =360 KG N
FE-2 FE-1 WITH STEEL ENCLOSURE

NOVEC SYSTEM NO. 75 FE-1

N/S
FE-1 FE-1

Ø50 mm
O O
P P
NOVEC SYSTEM NO. 76

N/S
FE-1 FE-1
Q Q

Ø80 mm
FE-1

Ø50 mm
R NOVEC CLEAN AGENT SYSTEM- 78 R

Ø50 mm
2 CYLINDER ( 2X180 KG) =360 KG
FE-1 WITH STEEL ENCLOSURE
FE-2
NOVEC SYSTEM NO. 84 FE-2 FE-2
S S
NOVEC CLEAN AGENT SYSTEM- 76
N/S
1 CYLINDER (1 X140 KG) =140 KG
WITH STEEL ENCLOSURE
S* S*

Ø50 mm

Ø50 mm
POWER ROOM POD-9 NOVEC CLEAN AGENT SYSTEM- 77
T 2 CYLINDER ( 2X180 KG) =360 KG T
WITH STEEL ENCLOSURE
N/S N/S
POD-9
NOVIC CLEAN AGENT SYSTEM- 84 NOVEC SYSTEM NO. 77 NOVEC SYSTEM NO. 78
3 CYLINDER (3X165 KG) =495 KG
WITH STEEL ENCLOSURE FE-1

Ø50 mm
U U

Ø50 mm
V V

FE-1
CORRIDOR
FE-1
FE-2 N/S

1 2 3 4 5 N/S NOVEC SYSTEM NO. 80

Ø50 mm
NOVEC SYSTEM NO. 79

Ø50 mm
W FE-1 NOVEC CLEAN AGENT SYSTEM- 81 W
1 CYLINDER (1 X140 KG) =140 KG
WITH STEEL ENCLOSURE
X X
2 AUGUST. 2023 SCHEMATIC DESIGN M.M. A.Y. I.M. -- -- H.I.
IT CLOSET STAGING ROOM
Y Y
NOVIC CLEAN AGENT SYSTEM- 83
FE-2 FE-2 JULY. 2023 M.M. A.Y. I.M. -- -- H.I.
Ø80 mm

1 CYLINDER (1 X25 KG) =25 KG 1 SCHEMATIC DESIGN


Ø50 mm

N/S NOVEC CLEAN AGENT SYSTEM- 80

Ø50 mm
WITH STEEL ENCLOSURE N/S
2 CYLINDER ( 2X180 KG) =360 KG
FE-2
Z WITH STEEL ENCLOSURE Z 0 JUNE. 2023 CONCEPT DESIGN M.M. A.Y. I.M. -- -- H.I.

CORRIDOR FE-2
Ø25 mm Ø32 mm Ø40 mm Ø50 mm

ED
ED
AA AA

D
D

D
Ø80 mm

WE
NE

KE
N

OV
ITT
REV.NO. DATE DESCRIPTION

AW

SIG

EC

VIE

PR
BM
NOVIC CLEAN AGENT SYSTEM- 82 Ø50 mm NOVEC SYSTEM NO. 81 N/S

DR
Ø50 mm

CH
DE

AP
RE
Ø50 mm

SU
1 CYLINDER (1 X31 KG) =31 KG
WITH STEEL ENCLOSURE FE-1 FE-1
BB Ø50 mm Ø50 mm BB
Ø80 mm
Ø25 mm Ø32 mm Ø40 mm Ø50 mm Ø50 mm Ø40 mm Ø32 mm Ø25 mm Ø50 mm
FHS CORRIDOR FE-1 FE-1
FE-1 FE-1 FE-1
EMERGENCY STAIR
CC CC

∅150mm COMBINED FIRE STANDPIPE RISER NOVEC CLEAN AGENT SYSTEM- 79 FE-1
& SPRINKLER RISERS 2 CYLINDER ( 2X180 KG) =360 KG
DD VALVE
∅ 80mm OS & Y GATE WITH STEEL ENCLOSURE DD
WITH TAMPER SWITCH
∅ 80mm FLOW SWITCH F
∅ 80mm CHECK VALVE
∅ 25mm DRAIN & TEST LINE
∅ 65mm LANDING VALVE
02

17 25
ETIHAD ETISALAT (Mobily)
6 7 8 9 10 11 12 13 14 15 16 18 19 20 21 22 23 24 26 27
∅ 40mm FHR/FE
∅ 50 DRAIN STACK CONSULTANT

ARCHITECTURE AND STRICTURE CONSULTANT


FOR CONTRACTOR :

MAIN CONTRACTOR

MOHAMMED MANSOUR AL RUMAIH


TRADING COMPANY (JOINT STOCK)

LEAD CONSULTANT FOR CONTRACTOR

ABBREVIATIONS ABBREVIATIONS
SYMBOLS SYMBOLS

ABBREVIATION MEANING SYMBOL ABBREVIATION SYMBOL ABBREVIATION


ABBREVIATION MEANING

G GV CHECK VALVE PORTABLE 6kg FIRE EXTINGUISHER


GATE VALVE FE-1
A AAV AUTOMATIC AIR VENT DRY POWDER (A,B,C)
HDPE HIGH DENSITY POLY ETHYLENE C CONTROL PANEL
H
HIGH LEVEL P PORTABLE 6kg FIRE EXTINGUISHER
B B.O.P BOTTOM OF PIPE H/L CLEAN AGENT CYLINDER FE-2
CO2 PROJECT:
M MM MILEMETER
PENDENT SPRINKLER HEAD (K factor= 5.65)
N/S NON SPRINKLERED
C CH.V CHECK VALVE N
NTS NOT TO SCALE
FIRE HOSE STATION(FHS)
DESIGN & BUILD DATA CENTERS
FB FIRE BLANKET F S SIAMESE CONNECTION
F/A FROM ABOVE
P
PG PRESSURE GAUGE FIRE HYDRANT TIER III IN RIYADH & JEDDAH
FE-1 DRY POWDER EXTINGUISHER
F PRV PRESSURE REDUCING VALVE U UPRIGHT SPRINKLER HEAD (K factor= 5.65)
FE-2
FE-3
CO2 FIRE EXTINGUISHER
FOAM EXTINGUISHER M MULTI DETECTOR
RIYADH 3
R R/N RISER NIPPLE
FHR FIRE HOSE REEL Z ZONE CONTROL VALVES
FHS FIRE HOSE STATION S SP SPRINKLER
N/S NON SPRINKLERED
TITLE:
F/B FROM BELOW T/A TO ABOVE
FS FLOW SWITCH N O (O.S.&.Y) GATE VALVE WITH TAMPER SWITCH
T T/B TO BELOW
FM FLOW METER
TYP. TYPICAL
NOZZLE SPRINKLER FOR NOVEC SYSTEM Firefighting System Layout
U U/G UNDERGROUND Roof Floor Plan

Firefighting System Layout-Roof Floor Plan-Sprinkler system CONTRACT No.


068/2022 DATE: JUNE. 2023
1 1 : 150 SCALE: DRAWING No. REV.

1:150 TECB - RIY3 - MF - RF - 104 2