13-01-955
PED-category: SEP Index Description Date
Fluid group: 2 01.06.13
Product line a CO2 gaseous 18.05.18
Sinorix ™ Pressure reducer (L10/200 LabLine) b EN562-> ISO 5171 18.11.19
SAP 8 bar output
A5Q00060861
PRED-200 8
2014/68/EU
Technical data
Usage
This pressure reducer may be used for selector valves with (blue) drive gear type Airtorque AT only.
It reduces the control cylinder pressure to 8bar.
1/3
Smart Infrastructure 13-01-955 E
Installation
Warning!
Do not use oil or grease with this product.
Ensure the pilot cylinder valve is isolated (e.g. remove the solenoid from the cylinder valve) before installing
and adjusting the pressure regulator.
CO2 pilot cylinder always without diptube. Inlet from CO2 distribution pipe network to extinguishing nozzles
forbidden.
Fit the pressure regulator to a solid vibrations free surface close to the pilot cylinder ensuring that the inlet port
is orientated towards the pilot cylinder. Use pipe clamps (STAUFF) to fix the tube just before the inlet
connection and just after the outlet connection.
Warning!
All flexible hoses and any fittings which may have been exposed to contamination by particulate matter must
be blown through with dry gas before assembly.
Ensure that the test cylinder has a hand valve and the cylinder pressure is equal to the pilot cylinder.
1. Connect a pilot tubing to the outlet port of the pressure reduction regulator and close it.
2. Secure the test cylinder and briefly open the hand valve without connecting it to the pressure regulator.
(to be sure there will be no dirt into the pressure regulator)
3. Connect the test cylinder to the pressure regulator high pressure inlet.
4. Slowly open the test cylinder valve.
5. Close the test cylinder valve.
6. Vent the connecting hose and any other devices fitted between the pressure regulator and the test
cylinder.
7. Disconnect the test equipment from the pressure regulator.
8. Refit the hose from the pilot cylinder.
Maintenance
Ensure that the test cylinder has a hand valve and the cylinder pressure is equal to the pilot cylinder.
Spare parts:
The regulators are maintenance free.
In case of leakage tighten the connections or change the complete regulator.
After an extinguishing release check the internal filter.
2/3
Smart Infrastructure 13-01-955 E
The frequency of the product inspection is subject to applicable local regulations. For more
information, refer to the maintenance documentation.
Every 10 years
● Replace the pressure reducer.
3/3