Evaluationn of A 3bolted Short-Circuit
Evaluationn of A 3bolted Short-Circuit
Evaluationn of A 3bolted Short-Circuit
I. INTRODUCTION
the first few cycles after the short. The machines are assumed Thereafter, for simplification, we neglected in (3) and
to have squirrel cage rotors. made . Equation (3) becomes
Although very simple and useful, this approach does not com-
pletely describe the event, because it does not take into consid- (4)
eration the dc component of the stator currents associated with
the short-circuit phenomena. Also, it does not include the effect In retrospect, this procedure is justified by the validity of the
of the resistance of the machine stator, or the resistance of results, as demonstrated in Sections III–VI of the paper.
the feeder/transformer. Equation (4) suggests that the first current peak may exceed
An approach that does take into account the effect of the dc the amplitude of the ac component by as much as a factor of
stator currents on the total short-circuit current is described in 2. The initial magnitude of the ac component itself can be de-
IEEE Standards C37.010-1999 and C37-013-1997 [2], [3]; in termined in terms of the transient reactance (1). In practice,
the IEC Standard 60909-0 [4]; in a book by St. Pierre [5]; and , and . Therefore
in a paper by Huening [6]. Procedures are presented there that
describe in detail how to calculate short-circuit currents of in- (5)
duction machines following a short-circuit at the terminals. A
sample calculation is presented in Section VI. The voltage behind the transient reactance is a voltage pro-
A third approach, one that underlies the work of this paper, portional to the rotor flux linkage [1], [5]. When the machine
uses as a starting point for evaluating bolted short-circuit operates as a generator, the pre-short-circuit terminal phase-
currents for an induction generator, the governing equations for voltage . Therefore, using would yield a con-
the generator. These are formulated in terms of the flux linkages servative solution. The value of the short-circuit inductance is
between stator and rotor [7]. Using this approach, the equation .
for the short-circuit current finally becomes Concerning the time constant of the dc component—At
normal machine startup, the stationary rotor sees a synchro-
nously rotating magnetic field. In the present instance, the rotor
(2) is spinning, but it also sees a synchronously rotating magnetic
field, this time established by the set of 3 dc stator currents.
The coefficients , , and depend mainly on what Therefore, for the dc components, the equivalent circuit in Fig. 2
Nasar terms the transient, sub-transient, and synchronous was used, but with . That is
reactances of the induction generator [7]; , , and are
time-constants; is the line frequency; and is a reference (6)
angle. The first term in (2) is the dc component, which is
especially important during the first few cycles.
The time constant of the ac component is given by (1).
The envelope (upper boundary) for the current peaks of the
Since ; and , that equation
oscillatory waveform (2) would be (conservatively assuming
may be simplified as follows:
)
(3) (7)
Although it is an accurate representation of the short circuit From (6) and (7)
current, (3) utilizes internal parameters of the machine that are
not available to the customer. Furthermore, it is seen that several
(8)
time constants are involved, so that a single time constant, by
itself, is not sufficient to represent the current decay during a
short. and are generally of the same order, as suggested by the
Sections II–VI discuss: peak currents during a short-circuit; entries in Table I. However, one might expect that the difference
simulation techniques; laboratory experiment test results; between the two would depend on the design class, as defined
sample calculations; and some concluding remarks. in NEMA Standard MG1-2006, “Motors and Generators.” To
be definite, we shall assume that for the sake of anal-
II. CALCULATION OF THE PEAK CURRENTS DURING A SHORT ysis. The value of depends on the feeder and the line trans-
To estimate the relative values of the coefficients , , and former, but it would be of the same order as . That suggests
in [7, Eq. 5. 80], sample data on p. 204 were used, thus: a practical range for : .
(here , , and are the “sub-transient,” “transient,” and Here, the emphasis is on urban systems. In rural systems,
“synchronous” inductances) however, where long feeders may be encountered, would
be larger, and the value of correspondingly greater.
Finally, from (4), the envelope of the upper boundary of the
peak currents during a bolted short-circuit may be rewritten
as
(9)
SULAWA et al.: EVALUATION OF A BOLTED SHORT-CIRCUIT 1967
TABLE I
MACHINE AND LINE PARAMETERS
Fig. 6. Laboratory test results for the line currents following a 3 0 bolted
short-circuit on the feeder of machine #1 in Table I.
Fig. 4. MATLAB simulation results for the line currents following a 3 0 That means, the peak value of the current of the third cycle
bolted short-circuit on the feeder of machine #1 in Table I. decayed to 15% of its first cycle value in the laboratory, com-
pared to 13% in the computer simulation (13).
The close agreement, for machine #1, between experi-
mental results and the MATLAB simulation, suggested that the
Simulink code was a valid way of predicting the bolted
short-circuit currents. Therefore, it appeared to be worthwhile
to use it for different size machines, for comparison with results
obtained using (9).
This result is in close agreement with the simulation result (12). (16)
The ratio of the third current peak to the first is
was defined for the first five peaks. Here, is the differ-
(15) ence between the two th peak currents as obtained by the two
SULAWA et al.: EVALUATION OF A BOLTED SHORT-CIRCUIT 1969
TABLE II
SUMMARY OF RESULTS FOR ALL 16 MACHINES
TABLE III
SIMULATION VS. (9) RESULTS FOR I
to obtain that first peak current using an ratio multiplied circuit, it may take about one cycle for the breaker to open, but
by a correcting factor, where is the operating phase-voltage the current arc may not be extinguished until the 5th cycle.
at the fault, is the system reactance leading to the fault, and Table III quantifies the difference between the 5th current
a correcting multiplier adjusts for the dc component during the peaks as calculated by simulation and by (9) using the
fault. The simplified methods of Sect. 6.4.1, Table 7, and Sect. actual value of . It is seen that the largest difference is 30%,
6.3.1 of the Standard were used here. except for machine #3 (60%) for which .
Locked rotor reactance
VII. MITIGATION OPTIONS
Our study also suggested that the contribution of the induc-
Modified reactance for closing and latching duty, for the tion generator during a short could be reduced by the use of two
size and r/min of the machine mitigation techniques.
1) Parallel connection of generators. The smaller the power
rating of an induction generator, the shorter the duration
of the current decay. For instance, a bolted short
Feeder/transformer reactance circuit on a 4 MW generator (machine #15 in Table II)
System reactance leading to the fault leads to a current ratio , but for a fault on
a 1 MW generator (machine #12 in Table II) that current
ratio is . Therefore, connecting four 1 MW
ratio: generators instead of a single 4 MW unit would provide an
To account for the asymmetry caused by the dc component, the improvement of about 12%.
peak current in the first 0.5-cycle is (Table 7 in the Standard, 2) Addition of series reactance. Connecting a reactance
footnote d) per-phase in series with the terminals of the induction
generator (on the customer side) would reduce the initial
value of both the ac and the dc components ((5), leading to
smaller short-circuit current peaks. For instance, following
This, then, is the peak current that is contributed by induction a short on a 4 MW generator (machine #15 in Table II),
generator #7 to the fault, in accordance with the IEEE Standard. the first current peak, our simulation indicates, is 1515 A
Additional details are presented in Sect. 6.3.2 of the IEEE (not shown in the paper); with a series reactance that is
Standard. equal to the stator leakage reactance, the peak was only
2) Short-Circuit Calculations Using (9) of This Paper: The 1059 A (a 30% improvement).
procedure offered here (assuming in (9) provides the There are three additional effects associated with an added
following. series reactance that should be noted.
DC time constant is (6) 1) DC time constant will increase (6). For instance, without
considering any power-factor correcting capacitors, an
added series reactance equal to the stator leakage re-
actance increased the time constant by about 30% (not
AC coefficient is (5) shown in paper).
2) Terminal voltage of the induction generator will need to
be smaller to maintain rated value at the PCC (point of
common coupling).
First current peak at 7 ms is (9) 3) Reactor itself would be a bulky construction, and may
need capacitors to supply reactive power.
These findings suggest that (9) might serve as a helpful ad- [9] F. Goodman, Engineering Guide for Integration of Distributed Genera-
junct to the methods outlined in the current IEEE and IEC Stan- tion and Storage into power Distribution Systems EPRI Rep. 1000419,
Palo Alto, CA, 2000.
dards for calculating bolted short-circuit currents for in- [10] R. Stern and D. W. Novotny, “A simplified approach to the determina-
duction machines. tion of induction machine dynamic response,” IEEE Trans. Power App.
Syst., vol. PAS-97, no. 4, pp. 1430–1439, Jul./Aug. 1978.
ACKNOWLEDGMENT
T. Sulawa, photograph and biography not available at the time of publication.
The authors would like to express their deep appreciation to
E. Chebli of Con Edison for his skillful guidance.
REFERENCES Z. Zabar (SM’81), photograph and biography not available at the time of pub-
[1] A. E. Fitzgerald, C. Kingsley, and S. D. Umans, Electric Machinery, lication.
5th ed. New York: McGraw-Hill, 1990, ch. 6.
[2] IEEE Standard for AC High-Voltage Generator Circuit Breakers Rated
on a Symmetrical Current Basis, IEEE Std. C37.013, 1997, Sec. 7 “Ap-
plication guide”. D. Czarkowski (M’97), photograph and biography not available at the time of
[3] IEEE Application Guide for AC High-Voltage Circuit Breakers Rated publication.
on a Symmetrical Current Basis, IEEE Std. C37.010, 1999, Sec. 6:
“Short-circuit considerations”.
[4] IEC Short-Circuit Currents in Three-Phase A.C. Systems—Part 0: Cal-
culation of Currents IEC 60909-0, 2001-07, Sec. 3.8 & 4.7; also IEC Y. TenAmi (M’04), photograph and biography not available at the time of pub-
TR 60909-1, 2002-07, Sect. 2.9. lication.
[5] C. S. Pierre, A Practical Guide to Short-Circuit Calculations Thomson-
Shore, 2001, Sec. 4.4, 6.5, 9.7.
[6] W. C. Huening, “Calculating short-circuit currents with contributions
from induction motors,” IEEE Trans. Ind. Appl., vol. IA-18, no. 2, pp.
85–92, Mar./Apr. 1982. L. Birenbaum (SM’02), photograph and biography not available at the time of
[7] S. A. Nasar and J. Boldea, Electric Machines, Dynamics. New York: publication.
Macmillan, 1986, ch. 5.
[8] Asynchronous Machine in MATLAB Mathworks [Online]. Available:
http://www.mathworks.com/access/helpdesk/help/toolbox/physmod/
powersys/asynchronousmachine.html. S. Lee, photograph and biography not available at the time of publication.