Designation: C39/C39M − 21

Standard Test Method for


Compressive Strength of Cylindrical Concrete Specimens1
This standard is issued under the fixed designation C39/C39M; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.

1. Scope* 2. Referenced Documents


1.1 This test method covers determination of compressive 2.1 ASTM Standards:2
strength of cylindrical concrete specimens such as molded C31/C31M Practice for Making and Curing Concrete Test
cylinders and drilled cores. It is limited to concrete having a Specimens in the Field
density in excess of 800 kg/m3 [50 lb/ft3]. C42/C42M Test Method for Obtaining and Testing Drilled
Cores and Sawed Beams of Concrete
1.2 The values stated in either SI units or inch-pound units
C125 Terminology Relating to Concrete and Concrete Ag-
are to be regarded separately as standard. The inch-pound units
gregates
are shown in brackets. The values stated in each system may
C192/C192M Practice for Making and Curing Concrete Test
not be exact equivalents; therefore, each system shall be used
Specimens in the Laboratory
independently of the other. Combining values from the two
C617/C617M Practice for Capping Cylindrical Concrete
systems may result in non-conformance with the standard.
Specimens
1.3 This standard does not purport to address all of the C670 Practice for Preparing Precision and Bias Statements
safety concerns, if any, associated with its use. It is the for Test Methods for Construction Materials
responsibility of the user of this standard to establish appro- C873/C873M Test Method for Compressive Strength of
priate safety, health, and environmental practices and deter- Concrete Cylinders Cast in Place in Cylindrical Molds
mine the applicability of regulatory limitations prior to C943 Practice for Making Test Cylinders and Prisms for
use.(Warning—Means should be provided to contain concrete Determining Strength and Density of Preplaced-
fragments during sudden rupture of specimens. Tendency for Aggregate Concrete in the Laboratory
sudden rupture increases with increasing concrete strength and C1077 Practice for Agencies Testing Concrete and Concrete
it is more likely when the testing machine is relatively flexible. Aggregates for Use in Construction and Criteria for
The safety precautions given in R0030 are recommended.) Testing Agency Evaluation
1.4 The text of this standard references notes which provide C1176/C1176M Practice for Making Roller-Compacted
explanatory material. These notes shall not be considered as Concrete in Cylinder Molds Using a Vibrating Table
requirements of the standard. C1231/C1231M Practice for Use of Unbonded Caps in
1.5 This international standard was developed in accor- Determination of Compressive Strength of Hardened Cy-
dance with internationally recognized principles on standard- lindrical Concrete Specimens
ization established in the Decision on Principles for the C1435/C1435M Practice for Molding Roller-Compacted
Development of International Standards, Guides and Recom- Concrete in Cylinder Molds Using a Vibrating Hammer
mendations issued by the World Trade Organization Technical C1604/C1604M Test Method for Obtaining and Testing
Barriers to Trade (TBT) Committee. Drilled Cores of Shotcrete
E4 Practices for Force Verification of Testing Machines
E18 Test Methods for Rockwell Hardness of Metallic Ma-
terials
1
This test method is under the jurisdiction of ASTM Committee C09 on
Concrete and Concrete Aggregates and is the direct responsibility of Subcommittee
2
C09.61 on Testing for Strength. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved March 1, 2021. Published March 2021. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
approved in 1921. Last previous edition approved in 2020 as C39/C39M – 20. DOI: Standards volume information, refer to the standard’s Document Summary page on
10.1520/C0039_C0039M-21. the ASTM website.

*A Summary of Changes section appears at the end of this standard


Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States

&RS\ULJKWE\$670,QW O DOOULJKWVUHVHUYHG 7KX$XJ*07


1
'RZQORDGHGSULQWHGE\
0XTHHP.KDQ $UDE&HQWHUIRU(QJLQHHULQJ6WXGLHV$&(6 SXUVXDQWWR/LFHQVH$JUHHPHQW1RIXUWKHUUHSURGXFWLRQVDXWKRUL]HG
C39/C39M − 21
E74 Practices for Calibration and Verification for Force- C943, C1176/C1176M, C1231/C1231M, and C1435/C1435M,
Measuring Instruments and Test Methods C42/C42M, C873/C873M, and C1604/
R0030 Manual of Aggregate and Concrete Testing C1604M.
5.3 The results of this test method are used as a basis for
3. Terminology quality control of concrete proportioning, mixing, and placing
3.1 Definitions—For definitions of terms used in this operations; determination of compliance with specifications;
practice, refer to Terminology C125. control for evaluating effectiveness of admixtures; and similar
3.2 Definitions of Terms Specific to This Standard: uses.
3.2.1 bearing block, n—steel piece to distribute the load 5.4 The individual who tests concrete cylinders for accep-
from the testing machine to the specimen. tance testing shall meet the concrete laboratory technician
3.2.2 lower bearing block, n—steel piece placed under the requirements of Practice C1077, including an examination
specimen to distribute the load from the testing machine to the requiring performance demonstration that is evaluated by an
specimen. independent examiner.
3.2.2.1 Discussion—The lower bearing block provides a NOTE 1—Certification equivalent to the minimum guidelines for ACI
readily machinable surface for maintaining the specified bear- Concrete Laboratory Technician, Level I or ACI Concrete Strength
ing surface. The lower bearing block may also be used to adapt Testing Technician will satisfy this requirement.
the testing machine to various specimen heights. The lower
bearing block is also referred to as bottom block, plain block, 6. Apparatus
and false platen. 6.1 Testing Machine—The testing machine shall be of a type
3.2.3 platen, n—primary bearing surface of the testing having sufficient capacity and capable of providing the rates of
machine. loading prescribed in 8.5.
3.2.3.1 Discussion—The platen is also referred to as the 6.1.1 Verify the accuracy of the testing machine in accor-
testing machine table. dance with Practices E4, except that the verified loading range
shall be as required in 6.4. Verification is required:
3.2.4 spacer, n—steel piece used to elevate the lower bear-
ing block to accommodate test specimens of various heights. 6.1.1.1 Within 13 months of the last calibration,
3.2.4.1 Discussion—Spacers are not required to have hard- 6.1.1.2 On original installation or immediately after
ened bearing faces because spacers are not in direct contact relocation,
with the specimen or the retainers of unbonded caps. 6.1.1.3 Immediately after making repairs or adjustments
that affect the operation of the force applying system or the
3.2.5 upper bearing block, n—steel assembly suspended values displayed on the load indicating system, except for zero
above the specimen that is capable of tilting to bear uniformly adjustments that compensate for the mass of bearing blocks or
on the top of the specimen. specimen, or both, or
3.2.5.1 Discussion—The upper bearing block is also re-
6.1.1.4 Whenever there is reason to suspect the accuracy of
ferred to as the spherically seated block and the suspended
the indicated loads.
block.
6.1.2 Design—The design of the machine must include the
following features:
4. Summary of Test Method
6.1.2.1 The machine must be power operated and must
4.1 This test method consists of applying a compressive apply the load continuously rather than intermittently, and
axial load to molded cylinders or cores at a rate which is within without shock. If it has only one loading rate (meeting the
a prescribed range until failure occurs. The compressive requirements of 8.5), it must be provided with a supplemental
strength of the specimen is calculated by dividing the maxi- means for loading at a rate suitable for verification. This
mum load attained during the test by the cross-sectional area of supplemental means of loading may be power or hand oper-
the specimen. ated.
6.1.2.2 The space provided for test specimens shall be large
5. Significance and Use enough to accommodate, in a readable position, an elastic
5.1 Care must be exercised in the interpretation of the calibration device which is of sufficient capacity to cover the
significance of compressive strength determinations by this test potential loading range of the testing machine and which
method since strength is not a fundamental or intrinsic property complies with the requirements of Practice E74.
of concrete made from given materials. Values obtained will NOTE 2—The types of elastic calibration devices most generally
depend on the size and shape of the specimen, batching, mixing available and most commonly used for this purpose are the circular
procedures, the methods of sampling, molding, and fabrication proving ring or load cell.
and the age, temperature, and moisture conditions during 6.1.3 Accuracy—The accuracy of the testing machine shall
curing. be in accordance with the following provisions:
5.2 This test method is used to determine compressive 6.1.3.1 The percentage of error for the loads within the
strength of cylindrical specimens prepared and cured in accor- proposed range of use of the testing machine shall not exceed
dance with Practices C31/C31M, C192/C192M, C617/C617M, 61.0 % of the indicated load.

&RS\ULJKWE\$670,QW O DOOULJKWVUHVHUYHG 7KX$XJ*07


2
'RZQORDGHGSULQWHGE\
0XTHHP.KDQ $UDE&HQWHUIRU(QJLQHHULQJ6WXGLHV$&(6 SXUVXDQWWR/LFHQVH$JUHHPHQW1RIXUWKHUUHSURGXFWLRQVDXWKRUL]HG
C39/C39M − 21
6.1.3.2 The accuracy of the testing machine shall be verified 6.2 Bearing Blocks—The upper and lower bearing blocks
by applying five test loads in four approximately equal shall conform to the following requirements:
increments in ascending order. The difference between any two 6.2.1 Bearing blocks shall be steel with hardened bearing
successive test loads shall not exceed one third of the differ- faces (Note 3).
ence between the maximum and minimum test loads. 6.2.2 Bearing faces shall have dimensions at least 3 %
6.1.3.3 The test load as indicated by the testing machine and greater than the nominal diameter of the specimen.
the applied load computed from the readings of the verification 6.2.3 Except for the inscribed concentric circles described
device shall be recorded at each test point. Calculate the error, in 6.2.4.7, the bearing faces shall not depart from a plane by
E, and the percentage of error, Ep, for each point from these more than 0.02 mm [0.001 in.] along any 150 mm [6 in.] length
data as follows: for bearing blocks with a diameter of 150 mm [6 in.] or larger,
E5A2B (1) or by more than 0.02 mm [0.001 in.] in any direction of smaller
bearing blocks. New bearing blocks shall be manufactured
E p 5 100~ A 2 B ! /B within one half of this tolerance.
where: NOTE 3—It is desirable that the bearing faces of bearing blocks have a
A = load, kN [lbf] indicated by the machine being verified, Rockwell hardness at least 55 HRC as determined by Test Methods E18.
and NOTE 4—Square bearing faces are permissible for the bearing blocks.
B = applied load, kN [lbf] as determined by the calibrating 6.2.4 Upper Bearing Block—The upper bearing block shall
device. conform to the following requirements:
6.1.3.4 The report on the verification of a testing machine 6.2.4.1 The upper bearing block shall be spherically seated
shall state within what loading range it was found to conform and the center of the sphere shall coincide with the center of the
to specification requirements rather than reporting a blanket bearing face within 65 % of the radius of the sphere.
acceptance or rejection. In no case shall the loading range be 6.2.4.2 The ball and the socket shall be designed so that the
stated as including loads below the value which is 100 times steel in the contact area does not permanently deform when
the smallest change of load estimable on the load-indicating loaded to the capacity of the testing machine.
mechanism of the testing machine or loads within that portion
of the range below 10 % of the maximum range capacity. NOTE 5—The preferred contact area is in the form of a ring (described
as preferred bearing area) as shown in Fig. 1.
6.1.3.5 In no case shall the loading range be stated as
including loads outside the range of loads applied during the 6.2.4.3 Provision shall be made for holding the upper
verification test. bearing block in the socket. The design shall be such that the
6.1.3.6 The indicated load of a testing machine shall not be bearing face can be rotated and tilted at least 4° in any
corrected either by calculation or by the use of a calibration direction.
diagram to obtain values within the required permissible 6.2.4.4 If the upper bearing block is a two-piece design
variation. composed of a spherical portion and a bearing plate, a
mechanical means shall be provided to ensure that the spherical
portion is fixed and centered on the bearing plate.
6.2.4.5 The diameter of the sphere shall be at least 75 % of
the nominal diameter of the specimen. If the diameter of the
sphere is smaller than the diameter of the specimen, the portion
of the bearing face extending beyond the sphere shall have a
thickness not less than the difference between the radius of the
sphere and radius of the specimen (see Fig. 1). The least
dimension of the bearing face shall be at least as great as the
diameter of the sphere.
6.2.4.6 The dimensions of the bearing face of the upper
bearing block shall not exceed the following values:
Nominal Diameter Maximum Diameter Maximum Dimensions
of Specimen, of Round Bearing of Square Bearing
mm [in.] Face, mm [in.] Face, mm [in.]
50 [2] 105 [4] 105 by 105 [4 by 4]
75 [3] 130 [5] 130 by 130 [5 by 5]
100 [4] 165 [6.5] 165 by 165 [6.5 by 6.5]
150 [6] 255 [10] 255 by 255 [10 by 10]
200 [8] 280 [11] 280 by 280 [11 by 11]

T≥R–r 6.2.4.7 If the diameter of the bearing face of the upper


r = radius of spherical portion of upper bearing block bearing block exceeds the nominal diameter of the specimen by
R = nominal radius of specimen more than 13 mm [0.5 in.], concentric circles not more than 0.8
T = thickness of upper bearing block extending beyond the mm [0.03 in.] deep and not more than 1 mm [0.04 in.] wide
sphere shall be inscribed on the face of upper bearing block to
FIG. 1 Schematic Sketch of Typical Upper Bearing Block facilitate proper centering.

&RS\ULJKWE\$670,QW O DOOULJKWVUHVHUYHG 7KX$XJ*07


3
'RZQORDGHGSULQWHGE\
0XTHHP.KDQ $UDE&HQWHUIRU(QJLQHHULQJ6WXGLHV$&(6 SXUVXDQWWR/LFHQVH$JUHHPHQW1RIXUWKHUUHSURGXFWLRQVDXWKRUL]HG
C39/C39M − 21
6.2.4.8 At least every six months, or as specified by the exceed the clear distance between the smallest graduations.
manufacturer of the testing machine, clean and lubricate the The scale shall be provided with a labeled graduation line load
curved surfaces of the socket and of the spherical portion of the corresponding to zero load. Each dial shall be equipped with a
upper bearing block. The lubricant shall be a petroleum-type zero adjustment located outside the dial case and accessible
oil such as conventional motor oil or as specified by the from the front of the machine while observing the zero mark
manufacturer of the testing machine. and dial pointer.
NOTE 6—To ensure uniform seating, the upper bearing block is NOTE 9—Readability is considered to be 0.5 mm [0.02 in.] along the arc
designed to tilt freely as it comes into contact with the top of the specimen. described by the end of the pointer. If the spacing is between 1 and 2 mm
After contact, further rotation is undesirable. Friction between the socket [0.04 and 0.08 in.], one half of a scale interval is considered readable. If
and the spherical portion of the head provides restraint against further the spacing is between 2 and 3 mm [0.08 and 0.12 in.], one third of a scale
rotation during loading. Pressure-type greases can reduce the desired interval is considered readable. If the spacing is 3 mm [0.12 in.] or more,
friction and permit undesired rotation of the spherical head and should not one fourth of a scale interval is considered readable.
be used unless recommended by the manufacturer of the testing machine.
Petroleum-type oil such as conventional motor oil has been shown to 6.4.4 If the load is displayed in digital form, the numbers
permit the necessary friction to develop. must be large enough to be read. The numerical increment shall
6.2.5 Lower Bearing Block—The lower bearing block shall not exceed 0.1 % of the full scale load of a given loading range.
conform to the following requirements: Provision shall be made for adjusting the display to indicate a
6.2.5.1 The lower bearing block shall be solid. value of zero when no load is applied to the specimen.
6.2.5.2 The top and bottom surfaces of the lower bearing 6.5 Documentation of the calibration and maintenance of
block shall be parallel to each other. the testing machine shall be in accordance with Practice
6.2.5.3 The lower bearing block shall be at least 25 mm C1077.
[1.0 in.] thick when new, and at least 22.5 mm [0.9 in.] thick
after resurfacing. 7. Specimens
6.2.5.4 The lower bearing block shall be fully supported by 7.1 Specimens shall not be tested if any individual diameter
the platen of the testing machine or by any spacers used. of a cylinder differs from any other diameter of the same
6.2.5.5 If the testing machine is designed that the platen cylinder by more than 2 %.
itself is readily maintained in the specified surface condition, a
lower bearing block is not required. NOTE 10—This may occur when single use molds are damaged or
deformed during shipment, when flexible single use molds are deformed
NOTE 7—The lower bearing block may be fastened to the platen of the during molding, or when a core drill deflects or shifts during drilling.
testing machine.
NOTE 8—Inscribed concentric circles as described in 6.2.4.7 are 7.2 Prior to testing, neither end of test specimens shall
optional on the lower bearing block. depart from perpendicularity to the axis by more than 0.5°
6.3 Spacers—If spacers are used, the spacers shall be placed (approximately equivalent to 1 mm in 100 mm [0.12 in. in 12
under the lower bearing block and shall conform to the in.]). The ends of compression test specimens that are not plane
following requirements: within 0.050 mm [0.002 in.] shall be sawed or ground to meet
6.3.1 Spacers shall be solid steel. One vertical opening that tolerance, or capped in accordance with either Practice
located in the center of the spacer is permissible. The maxi- C617/C617M or, when permitted, Practice C1231/C1231M.
mum diameter of the vertical opening is 19 mm [0.75 in.]. The diameter used for calculating the cross-sectional area of
6.3.2 The top and bottom surfaces of the spacer shall be the test specimen shall be determined to the nearest 0.25 mm
parallel to each other. [0.01 in.] by averaging two diameters measured at right angles
6.3.3 Spacers shall be fully supported by the platen of the to each other at about midheight of the specimen.
test machine. 7.3 The number of individual cylinders measured for deter-
6.3.4 Spacers shall fully support the lower bearing block mination of average diameter is not prohibited from being
and any spacers above. reduced to one for each ten specimens or three specimens per
6.3.5 Spacers shall not be in direct contact with the speci- day, whichever is greater, if all cylinders are known to have
men or the retainers of unbonded caps. been made from a single lot of reusable or single-use molds
6.4 Load Indication—The testing machine shall be equipped which consistently produce specimens with average diameters
with either a dial or digital load indicator. within a range of 0.5 mm [0.02 in.]. When the average
6.4.1 The verified loading range shall not include loads less diameters do not fall within the range of 0.5 mm [0.02 in.] or
than 100 times the smallest change of load that can be read. when the cylinders are not made from a single lot of molds,
6.4.2 A means shall be provided that will record, or indicate each cylinder tested must be measured and the value used in
until reset, the maximum load to an accuracy within 1.0 % of calculation of the unit compressive strength of that specimen.
the load. When the diameters are measured at the reduced frequency, the
6.4.3 If the load is displayed on a dial, the graduated scale cross-sectional areas of all cylinders tested on that day shall be
shall be readable to at least the nearest 0.1 % of the full scale computed from the average of the diameters of the three or
load (Note 9). The dial shall be readable within 1.0 % of the more cylinders representing the group tested that day.
indicated load at any given load level within the loading range. 7.4 If the purchaser of the testing services or the specifier of
The dial pointer shall be of sufficient length to reach the the tests requests measurement of the specimen density, deter-
graduation marks. The width of the end of the pointer shall not mine the specimen density before capping by either 7.4.1

&RS\ULJKWE\$670,QW O DOOULJKWVUHVHUYHG 7KX$XJ*07


4
'RZQORDGHGSULQWHGE\
0XTHHP.KDQ $UDE&HQWHUIRU(QJLQHHULQJ6WXGLHV$&(6 SXUVXDQWWR/LFHQVH$JUHHPHQW1RIXUWKHUUHSURGXFWLRQVDXWKRUL]HG
C39/C39M − 21
(specimen dimension method) or 7.4.2 (submerged weighing will vary depending on the machine manufacturer. Consult your owner’s
method). For either method, use a balance or scale that is manual or compression machine calibrator for the proper technique.
accurate to within 0.3 % of the mass being measured. 8.4.2 Verification of Alignment When Using Unbonded
7.4.1 Remove any surface moisture with a towel and mea- Caps—If using unbonded caps, verify the alignment of the
sure the mass of the specimen. Measure the length of the specimen after application of load, but before reaching 10 % of
specimen to the nearest 1 mm [0.05 in.] at three locations the anticipated specimen strength. Check to see that the axis of
spaced evenly around the circumference. Compute the average the cylinder does not depart from vertical by more than 0.5°
length and record to the nearest 1 mm [0.05 in.]. (Note 13) and that the ends of the cylinder are centered within
7.4.2 Remove any surface moisture with a towel and deter- the retaining rings. If the cylinder alignment does not meet
mine the mass of the specimen in air. Submerge the specimen these requirements, release the load, and carefully recenter the
in water at a temperature of 23.0 °C 6 2.0 °C [73.5 °F 6 specimen. Reapply load and recheck specimen centering and
3.5 °F] for 15 6 5 sec. Then, determine the apparent mass of alignment. A pause in load application to check cylinder
the specimen while submerged under water. alignment is permissible.
7.5 When density determination is not required and the NOTE 13—An angle of 0.5° is equal to a slope of approximately 1 mm
length to diameter ratio is less than 1.8 or more than 2.2, in 100 mm [1⁄8 inches in 12 inches]
measure the length of the specimen to the nearest 0.05 D. 8.5 Rate of Loading—Apply the load continuously and
without shock.
8. Procedure 8.5.1 The load shall be applied at a rate of movement (platen
8.1 Compression tests of moist-cured specimens shall be to crosshead measurement) corresponding to a stress rate on
made as soon as practicable after removal from moist storage. the specimen of 0.25 MPa/s 6 0.05 MPa/s [35 psi/s 6 7 psi/s]
(see Note 14). The designated rate of movement shall be
8.2 Test specimens shall be kept moist by any convenient
maintained at least during the latter half of the anticipated
method during the period between removal from moist storage
loading phase.
and testing. They shall be tested in the moist condition.
NOTE 14—For a screw-driven or displacement-controlled testing
8.3 Tolerances for specimen ages are as follows: machine, preliminary testing will be necessary to establish the required
Test AgeA Permissible Tolerance rate of movement to achieve the specified stress rate. The required rate of
24 h ±0.5 h movement will depend on the size of the test specimen, the elastic
3 days ±2 h modulus of the concrete, and the stiffness of the testing machine.
7 days ±6 h
28 days ±20 h 8.5.2 During application of the first half of the anticipated
90 days ±2 days loading phase, a higher rate of loading shall be permitted. The
higher loading rate shall be applied in a controlled manner so
A
For test ages not listed, the test age tolerance is ±2.0% of the specified age. that the specimen is not subjected to shock loading.
8.3.1 Unless otherwise specified by the specifier of tests, for 8.5.3 Make no adjustment in the rate of movement (platen to
this test method the test age shall start at the beginning of crosshead) as the ultimate load is being approached and the
casting specimens. stress rate decreases due to cracking in the specimen.
8.4 Placing the Specimen—Place the lower bearing block, 8.6 Apply the compressive load until the load indicator
with the hardened face up, on the table or platen of the testing shows that the load is decreasing steadily and the specimen
machine. Wipe clean the bearing faces of the upper and lower displays a well-defined fracture pattern (Types 1 to 4 in Fig. 2).
bearing blocks, spacers if used, and of the specimen. If using For a testing machine equipped with a specimen break detector,
unbonded caps, wipe clean the bearing surfaces of the retainers automatic shut-off of the testing machine is prohibited until the
and center the unbonded caps on the specimen. Place the load has dropped to a value that is less than 95 % of the peak
specimen on the lower bearing block and align the axis of the load. When testing with unbonded caps, a corner fracture
specimen with the center of thrust of the upper bearing block. similar to a Type 5 or 6 pattern shown in Fig. 2 may occur
before the ultimate capacity of the specimen has been attained.
NOTE 11—Although the lower bearing block may have inscribed Continue compressing the specimen until the user is certain
concentric circles to assist with centering the specimen, final alignment is
made with reference to the upper bearing block. that the ultimate capacity has been attained. Record the
maximum load carried by the specimen during the test, and
8.4.1 Zero Verification and Block Seating—Prior to testing
note the type of fracture pattern according to Fig. 2. If the
the specimen, verify that the load indicator is set to zero. In
fracture pattern is not one of the typical patterns shown in Fig.
cases where the indicator is not properly set to zero, adjust the
2, sketch and describe briefly the fracture pattern. If the
indicator (Note 12). After placing the specimen in the machine
measured strength is lower than expected, examine the frac-
but prior to applying the load on the specimen, tilt the movable
tured concrete and note the presence of large air voids,
portion of the spherically seated block gently by hand so that
evidence of segregation, whether fractures pass predominantly
the bearing face appears to be parallel to the top of the test
around or through the coarse aggregate particles, and verify
specimen.
end preparations were in accordance with Practice C617/
NOTE 12—The technique used to verify and adjust load indicator to zero C617M or Practice C1231/C1231M.

&RS\ULJKWE\$670,QW O DOOULJKWVUHVHUYHG 7KX$XJ*07


5
'RZQORDGHGSULQWHGE\
0XTHHP.KDQ $UDE&HQWHUIRU(QJLQHHULQJ6WXGLHV$&(6 SXUVXDQWWR/LFHQVH$JUHHPHQW1RIXUWKHUUHSURGXFWLRQVDXWKRUL]HG
C39/C39M − 21

FIG. 2 Schematic of Typical Fracture Patterns

9. Calculation NOTE 15—Correction factors depend on various conditions such as


moisture condition, strength level, and elastic modulus. Average values are
9.1 Calculate the compressive strength of the specimen as given in the table. These correction factors apply to low-density concrete
follows: weighing between 1600 and 1920 kg/m3 [100 and 120 lb/ft3] and to
SI units: normal-density concrete. They are applicable to concrete dry or soaked at
the time of loading and for nominal concrete strengths from 14 to 42 MPa
4000P max [2000 to 6000 psi]. For strengths higher than 42 MPa [6000 psi] correction
f cm 5 (2)
πD 2 factors may be larger than the values listed above3.
Inch-pound units: 9.3 If required, calculate the specimen density to the nearest
10 kg/m3 [1 lb/ft3] using the applicable method.
4 P max
f cm 5 (3) 9.3.1 If specimen density is determined based on specimen
π D2
dimensions, calculate specimen density as follows:
where: SI units:
ƒcm = compressive strength, MPa [psi], 4 3 109 3 W
Pmax = maximum load, kN [lbf], and ρs 5 (4)
L 3 D2 3 π
D = average measured diameter, mm [in.].
Inch-pound units:
Use at least five digits for the value of π, that is, use 3.1416
or a more precise value.
9.2 If the specimen length to diameter ratio is 1.75 or less,
F ρs 5
6912 3 W
L 3 D2 3 π G (5)

correct the result obtained in 9.1 by multiplying by the where:


appropriate correction factor shown in the following table: ρs = specimen density, kg/m3 [lb ⁄ft3],
L/D: 1.75 1.50 1.25 1.00
Factor: 0.98 0.96 0.93 0.87
3
Bartlett, F.M. and MacGregor, J.G., “Effect of Core Length-to-Diameter Ratio
Use interpolation to determine correction factors for L/D on Concrete Core Strength,”ACI Materials Journal, Vol 91, No. 4, July-August,
values between those given in the table. 1994, pp. 339–348.

&RS\ULJKWE\$670,QW O DOOULJKWVUHVHUYHG 7KX$XJ*07


6
'RZQORDGHGSULQWHGE\
0XTHHP.KDQ $UDE&HQWHUIRU(QJLQHHULQJ6WXGLHV$&(6 SXUVXDQWWR/LFHQVH$JUHHPHQW1RIXUWKHUUHSURGXFWLRQVDXWKRUL]HG
C39/C39M − 21

W = mass of specimen in air, kg [lb], Coefficient of Acceptable Range4 of


L = average measured length, mm [in.], and Variation4 Individual Cylinder Strengths
2 cylinders 3 cylinders
D = average measured diameter, mm [in.]. 150 by 300 mm
[6 by 12 in.]
9.3.2 If the specimen density is based on submerged Laboratory conditions 2.4 % 6.6 % 7.8 %
weighing, calculate the specimen density as follows: Field conditions 2.9 % 8.0 % 9.5 %
100 by 200 mm
W 3 γw [4 by 8 in.]
ρs 5 (6) Laboratory conditions 3.2 % 9.0 % 10.6 %
W 2 Ws
11.1.2 The single-operator coefficient of variation repre-
where: sents the expected variation of measured strength of compan-
ρs = specimen density, kg/m3 [lb ⁄ft3], ion cylinders prepared from the same sample of concrete and
W = mass of specimen in air, kg [lb], tested by one laboratory at the same age. The values given for
Ws = apparent mass of submerged specimen, kg [lb], and the single-operator coefficient of variation of 150 by 300 mm
γw = density of water at 23 °C [73.5 °F] = 997.5 kg/
[6 by 12 in.] cylinders are applicable for compressive strengths
m3 [62.27 lb/ft3].
between 15 to 55 MPa [2000 to 8000 psi] and those for 100
mm by 200 mm [4 in. by 8 in.] cylinders are applicable for
10. Report compressive strengths between 17 to 32 MPa [2500 and 4700
10.1 Report the following information: psi]. The single-operator coefficients of variation for 150 by
10.1.1 Specimen identification, 300 mm [6 by 12 in.] cylinders are derived from CCRL
concrete proficiency sample data for laboratory conditions and
10.1.2 Serial number of delivery ticket, if available, a collection of 1265 test reports from 225 commercial testing
10.1.3 Average measured diameter (and measured length, if laboratories in 1978.5 The single-operator coefficient of varia-
outside the range of 1.8 D to 2.2 D), in millimetres [inches], tion of 100 by 200 mm [4 by 8 in.] cylinders are derived from
10.1.4 Cross-sectional area, in square millimetres [square CCRL concrete proficiency sample data for laboratory condi-
inches], tions.
10.1.5 Maximum load, in kilonewtons [pounds-force], 11.1.3 Multilaboratory Precision—The multi-laboratory co-
efficient of variation for compressive strength test results of
10.1.6 Compressive strength rounded to the nearest 0.1 MPa
150 by 300 mm [6 by 12 in.] cylinders has been found to be
[10 psi],
5.0 %4; therefore, the results of properly conducted tests by
10.1.7 If the average of two or more companion cylinders two laboratories on specimens prepared from the same sample
tested at the same age is reported, calculate the average of concrete are not expected to differ by more than 14 %4 of the
compressive strength using the unrounded individual compres- average (see Note 17). A strength test result is the average of
sive strength values. Report the average compressive-strength two cylinders tested at the same age.
rounded to the nearest 0.1 MPa [10 psi].
NOTE 17—The multilaboratory precision does not include variations
10.1.8 Type of fracture (see Fig. 2), associated with different operators preparing test specimens from split or
10.1.9 Defects in either specimen or caps, independent samples of concrete. These variations are expected to
increase the multilaboratory coefficient of variation.
10.1.10 Age of specimen at time of testing. Report age in
days for ages three days or greater, report age in hours if the 11.1.4 The multilaboratory data were obtained from six
age is less than three days, separate organized strength testing round robin programs
where 150 by 300 mm [6 by 12 in.] cylindrical specimens were
NOTE 16—If software limitations prevent reporting the specimen age in prepared at a single location and tested by different laborato-
hours, the age of the specimen in hours may be included in a note in the ries. The range of average strength from these programs was
report. 17.0 to 90 MPa [2500 to 13 000 psi].
10.1.11 If determined, the density to the nearest 10 kg/ NOTE 18—Subcommittee C09.61 will continue to examine recent
concrete proficiency sample data and field test data and make revisions to
m [1 lb ⁄ft3].
3
precisions statements when data indicate that they can be extended to
cover a wider range of strengths and specimen sizes.
11. Precision and Bias 11.2 Bias—Since there is no accepted reference material, no
11.1 Precision statement on bias is being made.
11.1.1 Single-Operator Precision—The following table pro-
vides the single-operator precision of tests of 150 mm by 300 4
These numbers represent respectively the (1s %) and (d2s %) limits as
mm [6 in. by 12 in.] and 100 mm by 200 mm [4 in. by 8 in.] described in Practice C670.
5
Supporting data have been filed at ASTM International Headquarters and may
cylinders made from a well-mixed sample of concrete under be obtained by requesting Research Report RR:C09-1006. Contact ASTM Customer
laboratory conditions and under field conditions (see 11.1.2). Service at service@astm.org.

&RS\ULJKWE\$670,QW O DOOULJKWVUHVHUYHG 7KX$XJ*07


7
'RZQORDGHGSULQWHGE\
0XTHHP.KDQ $UDE&HQWHUIRU(QJLQHHULQJ6WXGLHV$&(6 SXUVXDQWWR/LFHQVH$JUHHPHQW1RIXUWKHUUHSURGXFWLRQVDXWKRUL]HG
C39/C39M − 21
12. Keywords
12.1 concrete core; concrete cylinder; concrete specimen;
concrete strength; compressive strength; core; cylinder; drilled
core; strength

SUMMARY OF CHANGES

Committee C09 has identified the location of selected changes to this standard since the last issue
(C39/C39M–20) that may impact the use of this standard. (Approved March 1, 2021)

(1) 10.1.1 was revised. (2) 10.1.2 was added.

Committee C09 has identified the location of selected changes to this standard since the last issue
(C39/C39M–18) that may impact the use of this standard. (Approved Feb. 1, 2020)

(1) Revised 9.1 to specify the minimum precision of π.

ASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentioned
in this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the risk
of infringement of such rights, are entirely their own responsibility.

This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and
if not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standards
and should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of the
responsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you should
make your views known to the ASTM Committee on Standards, at the address shown below.

This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,
United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the above
address or at 610-832-9585 (phone), 610-832-9555 (fax), or service@astm.org (e-mail); or through the ASTM website
(www.astm.org). Permission rights to photocopy the standard may also be secured from the Copyright Clearance Center, 222
Rosewood Drive, Danvers, MA 01923, Tel: (978) 646-2600; http://www.copyright.com/

&RS\ULJKWE\$670,QW O DOOULJKWVUHVHUYHG 7KX$XJ*07


8
'RZQORDGHGSULQWHGE\
0XTHHP.KDQ $UDE&HQWHUIRU(QJLQHHULQJ6WXGLHV$&(6 SXUVXDQWWR/LFHQVH$JUHHPHQW1RIXUWKHUUHSURGXFWLRQVDXWKRUL]HG

You might also like