Finite Element Analysis of Transformer
Finite Element Analysis of Transformer
The losses due to transformer leakage field comprise a small percentage of the power in a transformer.
Yet these losses produce localized heating which can compromise its operation. The stray field
strength increases rapidly with growing rating. The stray flux intruding into the structural parts
gives rise to eddy currents in them. The resulting eddy current losses may be considerable, thereby
increasing the load loss of transformer [1, 5]. The objective of this work is to calculate stray losses
in magnetic structures of 400 MVA 1-phase, 500–230 kV auto transformer and study the effect of
copper shield on structural losses and winding eddy losses, using commercial software package Magnet
(Infolytica Corp.) based on finite element method (FEM). Due to presence of non linear magnetic
materials, the sinusoidal source with 60 Hz frequency induces non-sinusoidally varying magnetic
fields. A transient solution (which calculates time varying magnetic field) is required for calculating
fields in non-linear materials. However, this requires more computational resources. Therefore Time
harmonic solution (which calculates field at 60 Hz frequency) with linear magnetic materials is
used for this analyses. Further, 3D time harmonic analysis has been done to analyze the effect of
varying Cu shield thickness on loss density and finally its effect on winding eddy losses has been
investigated.
The paper investigates effects of Cu shield on the Transformer is the most efficient machine in
stray losses occurring in core clamping structure power system with efficiency more than 99%.
of the core and how it affects leakage field pattern However, manufacturers want to attain even higher
which in turn changes eddy losses occurring in efficiency and in turn become more competitive
winding of power transformer. The 3D geometric in the market of power transformers hence it is
model of power transformer was made and solved important to calculate transformer performance
with finite element method. The time harmonic as accurately as possible. Accurate calculations
analysis is used to investigate the discussed of stray losses of a power transformer based on
problem. On this basis, we calculated the leakage numerical model may also improve transformer
magnetic field around the coils at nominal current structure in terms of reduced losses and increased
loadings. Further, radial and axial field values are overall efficiency [4].
calculated inside each conductor and eddy losses
in common winding are calculated with and The stray losses in the power transformer are
without Cu shield. composed of additional losses in windings and
*Global R&D Centre, Crompton Greaves Ltd., Kanjur Marg E, Mumbai - 400 042, Maharastra, India.
E-mail: ram.mishra@cgglobal.com, saravanan.selvaraj@cgglobal.com.
142 The Journal of CPRI, Vol. 9, No. 1, March 2013
of losses which are originated in transformer’s to small depth of magnetic field penetration in to
structural parts (Figure 1). The losses in the conducting parts [2–3]. Dimensions of each finite
windings are the subject to a power and voltage element in tank walls and clamps should be in
level of the power transformer. The additional the size class below millimeter. So the number
losses in the windings and in the construction, due of finite element would increase above software
to leakage magnetic field can not be separately computational possibilities. For this purpose, so-
measured. called surface impedance is introduced [7–8].
This will significantly reduce the number of finite
elements and allow the calculation of losses in the
tank walls and other transformer’s construction
parts. Leontovich [9] presented a simple form
of the boundary condition for highly conducting
bodies, which relates the electric field intensity
(E) and the magnetic field intensity (H) at each
point on the conductor surface as
n × E = Zn n × (n × H) .... (1)
H 02 ⎡ eξ − e −ξ − 2sin ξ ⎤
Pe = .... (5)
σδ ⎢⎣ eξ + e −ξ + 2 cos ξ ⎥⎦
Where ξ = 2b/δ.
fluctuate by first harmonic. This is not the case (Table 1) because of its closer proximity to
when we deal with non-linear characteristic of windings.
iron. Because of this magnetic non-linearity the
magnetic field in the material has non-sinusoidal The plot for total loss for the case when Cu shield is
form. Nevertheless, the losses are calculated used is shown in Figure 4. It is clearly visible from
relatively accurate. Figure 4 that a Cu shield considerably reduces the
effect of stray field and losses occurring in frame
5.0 RESULTS and tie rods are significantly reduced [10].
TABLE 1
COMPARISON OF LOSSES OCCURRING IN TOP FRAME, BOTTOM FRAME,
TIE RODS AND Cu SHIELDS
Bottom
Top frame Tie rods Cu shields
frame
HV Side (kW) 17.5 28.73 2.01 –
Without Cu shield
LV Side (kW) 14.38 24.4 1.78 –
HV Side (kW) 4.67 7.81 2.1 7.98
With Cu shield
LV Side (kW) 3.19 5.66 7.86 7.29
The Journal of CPRI, Vol. 9, No. 1, March 2013 145
Inaccuracy of calculations can be mainly ascribed IEE Science Measurement and Technology,
to mathematical simplifications and to material’s Vol. 144, No.1, pp.34–38, 1997.
nonlinear magnetic properties description. The
[4] Kralj L, Miljavec D. “Stray losses in power
results show the difference in eddy current losses
transformer tank walls and construction
occurring in top frame, bottom frame, tie rods
parts”, ICEM, 2010.
and Cu shields and it can be deduced that the
eddy current losses in transformer frame and tie [5] Karsai K, Kerenyl D and Kiss L. “Large
rods can be reduced drastically with the use of power transformers”, New York, Elsevier
shielding techniques. However metallic shielding Science Publishing Company, 1987.
has adverse effect on winding eddy losses and
[6] Ahuja R and Robert M Del Vecchio,
overall cost of material so it should be chosen
“Transformer Stray loss and Flux Distribution
judiciously keeping rating of the transformer in
Studies using 3D Finite Element Analysis”,
mind.
Trafotech, 2006.