FIELD DEVICES – ***POSITIONERS***

Product Specifications
08.2018 PSS EVE0102 A-(en)

SRI986 Electro-Pneumatic Positioner

The SRI986 Positioner is for operation of pneumatic valve actuators from control systems and electrical
controllers with electric control signals. It is used to reduce the adverse effects of valve friction, for higher thrust
and shorter positioning time.

FEATURES
• Independent adjustment of stroke range and zero • Stroke 8 to 260 mm (0.3 to 10.2 in) with standard
• Adjustable amplification and damping lever; larger stroke with special lever
• Split range up to 3-fold possible • Explosion protection:
II 2 G Ex ia IIC T6 according to ATEX or intrinsic
• Input signal 0/4 to 20 mA, 0/2 to 10 V
safety acc. to FM, CSA, CU TR, INMETRO
• Supply pressure up to 6 bar (90 psig)
• EMC in accordance with the international
• Low vibration effect in all directions standards and laws
• Mounting according to IEC 534, part 6 (NAMUR) • Modular system of additional equipment
• Rotation adapter for angles up to 120 - Limit switches
- Position transmitter
- Booster
- Connection manifold

Equipment should be installed, operated, serviced, and maintained


only by qualified personnel.
No responsibility is assumed by Schneider Electric for any
consequences arising from the use of this material.
PSS EVE0102 A-(en)
Page 2 TECHNICAL DATA SRI986

TECHNICAL DATA
Input Response characteristic 2)
Signal range ......................... 4 to 20 mA or Amplification ....................... adjustable
0 to 20 mA or Sensitivity ........................... < 0.1 % F.S.
2 to 10 V (On request) or Non-linearity (terminal
0 to 10 V (On request) based adjustment) ............. < 1.0 % F.S.
Input resistance ...................... < 200 Ohms at 20 °C Hysteresis ......................... < 0.3 % F.S.
Stroke range ......................... 8 to 100 mm (0.3 to 4 in) Supply air dependency ......... < 0.3 % / 0.1 bar (1.5 psi)
Angular range Temperature effect ............... < 0.5 % / 10 K
Linear ................................... 30 ° to 120 °
Equal percentage.................. 90 °; from 70 ° linear Air consumption
Air consumption single acting
Output Supply air 1.4 bar (20 psig) 200 ln/h ( 7.1 scfh)
Output to actuator . . . . . . . . . 0 to 100 % supply air pressure Supply air 3.0 bar (45 psig) 400 ln/h (12.4 scfh)
Supply air 6.0 bar (90 psig) 600 ln/h (21.2 scfh)
Supply Air consumption double acting
Supply air 1.4 bar (20 psig) 350 ln/h (10.6 scfh)
Supply air pressure ............... 1.4 to 6 bar (20 to 90 psig)
Supply air 3.0 bar (45 psig) 550 ln/h (17.7 scfh)
Air supply ............................. according to ISO 8573-1
Supply air 6.0 bar (90 psig) 750 ln/h (33.5 scfh)
- Solid particle size and density class 2
- Oil rate............................. class 3
Air output
- Pressure dew point 10 K under ambient temperature
Load effect 3) ........................ –3 % for delivery flow
The use of filter regulator for air supply of positioner is 2350 ln/h (83 scfh)
strongly recommended. It reduces the air pressure to ........................... +3 % for exhausted flow
actuator’s maximum pressure and keeps it constant. 1900 ln/h (67 scfh)

Ambient conditions Capacity at max. deviation

Ambient temperature 1) ......... –40 to 80°C (–40 to 176°F) Supply air


1.4 2 4 6
Relative humidity .................. up to 100 % pressure
(20) (30) (60) (90)
Operating conditions bar (psig)
According to IEC 654-1 ....... The device can be operated without
2 700 3 500 5 500 7 500
at a class D2 location booster
(95) (124) (194) (265)
Transport and ln/h (scfh)
Storage temperature ........... –50 to 80°C (–58 to 176°F) with booster
18 000 24 000 40 000 55 000
Storage conditions VKXG-FN/GN
acc. to IEC 60 721-3-1 ........ 1K5, 1B1, 1C2, 1S3, 1M2 (636) (847) (1 492) (1 942)
ln/h (scfh)
Protection class ...................... IP 54; IP65 as an option with booster
IP65 protection class can be selected from model code 36 000 48 000 80 000 110 000
VKXG-HN
option –FA or can be retrofit on existing device by ordering (1 271) (1 695) (2 825) (3 884)
ln/h (scfh)
the kit EW 411 406 301.

Electromagnetic compatibility EMC


Operating conditions ............. industrial environment
Immunity according to
- EN 61326, EN 61000-6-2 .... fulfilled
Emission according to
- EN 61326, Class A,
- EN 61000-6-3 ..................... fulfilled
NAMUR recommendation ..... fulfilled

CE marking
Electromagnetic compatibility 2004/108/EC
Low-voltage regulation........... not applicable
1) Note the section “Explosion protection” on pages 6 and 7 with respect
to explosion-protected equipment
2) Data based on the following parameters:
stroke 30 mm (1.28 in), range spring FES 628/1,
feedback lever 117.5 mm (4.63 in), max. amplification,
supply air pressure 3 bar (45 psig)
3) Measured at air supply 1.4 bar (20 psig) and 50 % of the signal range
PSS EVE0102 A-(en)
SRI986 TECHNICAL DATA Page 3

Materials Connection
Housing ................................ Aluminum (Alloy No. 230) Pneumatic ........................... Female threads
finished with DD-varnish G 1/8 acc. to ISO 228
blue Electric
All moving parts of Line entry............................. 1 or 2 cable glands
feedback system .............. 1.4305 / 1.4571 M20 x 1.5 or 1/2-14 NPT
Mounting bracket ................. Aluminum (Alloy No. 230) (others with Adapter AD-...)
Cable diameter .................... 6 to12 mm (0.24 to 0.47 in)
Weight Screw terminals ................... Screw terminals for wires
single acting ......................... approx. 1.5 kg (3.3 lbs) up to 2.5 mm (AWG 14)
double acting ........................ approx. 1.8 kg (3.9 lbs)
Attachment kit Mounting
for diaphragm actuators ..... approx. 0.3 kg (0.6 lbs) Type of mounting ................. for attaching to diaphragm
for rotary actuators ............. approx. 0.5 kg (1.1 lbs) actuators acc. to IEC 534-6
(NAMUR) and to rotary
actuators
Mounting orientation ............. any
PSS EVE0102 A-(en)
Page 4 ADDITIONAL EQUIPMENT SRI986

ADDITIONAL EQUIPMENT Limit Switch Assembly with Micro-switches


Code V
Additional equipment is installed by the manufacturer, but
some types can also be put in later on. Therefore special Input ............................. Stroke / angle from actuator
part sets are available. via positioner feedback lever
Output .......................... 2 micro switches 2) 5)
Inductive Limit Switch, two wire system Connected load, alternating current
Code T, U Switching capacity ...... max. 250 VA
Switching voltage ........ max. 250 V
Input . . . . . . . . . . . . . . . . . . . . . Stroke / angle from actuator
Switching current with
via positioner feedback lever
ohmic resistance ....... max. 5 A
Output ............................ 2 inductive proximity sensors
inductive resistance ... max. 2 A
acc. to DIN 19 234 resp.
Bulb metal filament .... max. 0.5 A
NAMUR for connection to
Connected load, direct current
a switching amplifier with
an intrinsically safe control Switching Ohmic Inductive
circuit 1) 2) 3) Voltage, load load
Current consumption max. V A A
Vane clear .................... > 3 mA 30 5 3
50 1 1
Vane interposed ............ < 1 mA
75 0.75 0.75
for control circuit with the following electrical values
125 0.5 0.03
Supply voltage............... DC 8 V, Ri approx. 1 kOhm
250 0.25 0.03
Residual ripple............... < 5 % permissible
line resistance ............... < 100 Ohms
Response characteristic 6)
Response characteristic 6)
Gain ........................... continuously adjustable
Gain ............................... continuously adjustable
from 1:1 to approx. 7:1
from 1:1 to approx. 7:1
Switching differential... < 2.5 %
Switching differential ....... < 1 %
Switching point
Switching point
repeatability ............... < 0.2 %
Repeatability .................. < 0.2 %
Part set for later installation EW 420 421 026
EMC .................................. acc. to EN 60 947-5-2
Part set for later installation
Code P, Q ..................... not available Connection Manifold with Gauges
Code T .......................... EW 419 510 343 Code JN, MN, RN, SN
Code U .......................... EW 419 510 361
Indicating range ............ 0 to 10 bar (0 to 150 psig)
Inductive Limit Switch, three wire system Error limit ...................... class 1.6
Code R Pneum. Connections ..... Female threads
Q1/4-18 NPT
Input ..................................... Stroke / angle from actuator
acc. to DIN 45 141
via positioner feedback lever
Output .................................. 2 inductive proximity sensors,
three wire system,
LED indication, contact, pnp 2) 4)
Supply voltage US ................ DC 10 to 30 V
Residual ripple ...................... ± 10 %, Us = 30 V
Switching frequency .............. 2 kHz
Constant current ................... 100 mA
Response characteristics 6)
Gain .................................. continuously adjustable
from 1:1 to approx. 7:1 1) For the standard version Code T, one switching amplifier is required
Switching differentia ........... < 1 % For the security version Code U, a fail-safe amplifier for each
inductive proximity sensor is required
Switching point 2) Operating mode min. (=low) / max. (=high) selectable by adjustment
Repeatability ...................... < 0.2 % of switch vanes
3) Operating mode normally closed circuit / normally open circuit
Part set for later installation.... EW 419 510 307 selectable at switch amplifier output
4) Contact closed within the positive range
5) Contact open within the positive range
6) For feedback lever effective length 117.5 mm (4.63 in),
stroke 30 mm (1.28 in) and maximum gain
PSS EVE0102 A-(en)
SRI986 ADDITIONAL EQUIPMENT Page 5

Electrical Position Transmitter Common data 2)


Code F Ambient conditions
Sensor ................................. resistive precision Ambient temperature 3) 4) .. . –25 to 80 °C (–13 to 176 °F)
Conductive plastic element Relative humidity ............... up to 100 %
Input ..................................... Stroke / angle from actuator Operating conditions
acc. to IEC 654-1 .............. The device can be operated
via positioner feedback lever
at a class D2 location
Stroke range ......................... 8 to 100 mm (0.3 to 4 in) Transport and
Angular range ....................... 60° to 120 ° storage temperature .......... –40 to 80 °C (–40 to 176 °F)
Output .................................. two-wire system Protection class................. IP 54, IP65
Signal range ......................... 4 to 20 mA
Mounting ................................. attachment to positioner
Permitted load .................... RBmax = (Us -12 V) / 0.02 A
(US = Supply voltage)
Electrical connections
Power supply Line entry............................. 1 or 2 cable glands
M20x 1.5 or 1/2-14 NPT
Supply voltage....................... DC 12 to 36 V
(others with Adapter AD- ...)
Permitted ripple ..................... < 10 % p.p.
Cable diameter .................... 6 to 12 mm (0.24 to 0.47 in)
Supply voltage
dependency........................ < 0.2 % Screw terminals ................... Screw terminals for wires
2
up to 2.5 mm (AWG 14)
Optionally .............................. Screwed gland made of
Response characteristic 1)
Stainless steel 1.4305
Non-linearity with
Materials
terminal based setting ...... < 1.0 % F.S.
Base plate ............................ galvanized Steel
Hysteresis .......................... < 0.5 % F.S. Control vane ........................ Aluminum
External resistance Setting mechanism.............. Fiber glass reinforced
dependency .................... < 0.2 % / RB max Polyamide
Temperature effect ............. < 0.3 % / 10 K

Part set for later installation


Code F .............................. EW 420 661 124

1) For feedback lever with effective length 117.5 mm (4.63 in) and
stroke 30 mm (1.28 in)
2) Except manifold with gauges
3) Note the section “Explosion protection” on pages 6 and 7 with respect
to explosion-protected equipment.
4) –40 to 80 °C (–40 to 176 °F) for the fail-safe version of inductive
limit switch Code Q, U
PSS EVE0102 A-(en)
Page 6 SAFETY REQUIREMENTS SRI986

SAFETY REQUIREMENTS Limit Switch Code T, U (additional equipment)


Type of protection Intrinsic safety Ex ib/ia IIB/IIC
Safety with the following maximum values:
acc. to EN 61 010-1 Ui ..................................... 16 V
(resp. IEC 1010-1) ................ safety class III, Ii....................................................................... 25 mA
pollution degree 2, Pi ...................................... 64 mW
overvoltage category I Internal inductance ............ 100 µH
Limit Switch Code V Internal capacitance .......... 30 nF
(additional equipment) ........... safety class II,
The signal circuits are galvanically separate from earth,
pollution degree 2,
from each other and from all other electric circuits.
overvoltage category II
Position Transmitter Code F (additional equipment)
Explosion protection type Ex ia/ib 1) Type of protection Intrinsic safety Ex ib/ia IIB/IIC
Basic device Type ............... AI 633 with the following maximum values:
Type of protection ............ II 2 G Ex ib/ia IIB/IIC T4/T6 For temperature class T4 and a maximally permissible
Certificate of conformity .... PTB 02 ATEX 2153 outside ambient temperature of 80 °C:
For operation in certified intrinsically safe circuits with the Ui ..................................... 30 V
following maximum values of input circuit: Ii ................................... 130 mA
Ui .................................... 30 V Pi ...................................... 0.9 W
Ii .................................. 150 mA
For temperature class T4 and a maximally permissible
Pi ..................................... refer to following table:
outside ambient temperature of 60 °C:
Pi [W] T6 [°C] T4 [°C] Ui ...................................... 22 V
2 40 90 Ii ................................... 66 mA
1.5 50 90
1 57.5 90 Pi ...................................... 0.5 W
Internal inductance ........... negligible The effective internal inductance Li left amounts to 9 µH,
Internal capacitance ......... negligible the effective capacity Ci against earth amounts to 10 nF
and/or differential 6 nF.
The control circuit is galvanically separate from earth and all
The supply and signal circuits are galvanically separate
other electric circuits.
from earth and from all other electric circuits.

1) National installation regulations must be observed


The national regulations must be strictly observed when retrofitting the
electrical position transmitter type AI 633 in the electro-pneumatic
positioner of type AI 633 or the inductive limit switch type AI 633 K in the
electro-pneumatic positioner of type AI 633 (SRI986-BIDS2EBB and
SRI986-CIDS2EBB).
The following regulations apply to the Federal Republic of Germany:
The installation must be carried out by the manufacturer, or the product
must be tested by a qualified inspector as a special version in
accordance with ElexV.
PSS EVE0102 A-(en)
SRI986 SAFETY REQUIREMENTS Page 7

Explosion protection Zone 2 1)


It is recommended that the instrument version for protection
type Ex ia is used.
In the Federal Republic of Germany, these instruments
may be operated in Zone 2 with non-intrinsically safe
circuits if the operating values do not exceed the maximum
reference values.

Explosion protection according to FM and CSA 1)


Electro-pneumatic positioner type BIM 633
Intrinsically safe, Class I, Division 1,
Groups A, B, C, D, hazardous locations

Explosion protection according to INMETRO


see certificate

Explosion protection according to CU TR


EAC marking see certificate

1) National installation regulations must be observed


PSS EVE0102 A-(en)
Page 8 MODEL CODES SRI986

MODEL CODES SRI986


230819

Electro-Pneumatic Positioner SRI986


Version
Single acting ........................................................................... -B
Double acting ......................................................................... -C
Input
Signal range 4 – 20 mA ..................................................................... I
Mode of Action
Direct Version: Increasing input increases output ................................. D
Reverse Version: Increasing input decreases output .................. (z) ......... R
Built-In Limit Switch / Position Transmitter
Without ................................................................................................................. S
Inductive limit switch three-wire technique, without Explosion Protection (a) ......... R
Inductive limit switch (Standard version) ...................................... (a) ................... T
Inductive limit switch (Security version)........................................ (a) ................... U
Two micro switches, without Explosion Protection ....................... (a) ................... V
Position Transmitter 4 – 20 mA .................................................... (a) ................... F
Cable Entry
1/2"-14 NPT (with Adapter(s) M20x1.5 to 1/2"-14 NPT)................................................ 6
M20 x 1.5 with one plastic cable gland, color gray ....................................................... 7
Electrical Certification: (Only Standard Device)
II 2 G Ex ia IIC T6 Gb according to ATEX .................................... (d) .................................... EAA
FM approved for intrinsic safety Cl. I, Div. 1, groups A, B, C, D hazardous locations Indoors ......... FAA
CSA approved for intrinsic safety Cl. I, Div. 1, groups A, B, C, D hazardous locations Indoors ....... CAA
GOST approved for intrinsic safety ......................................................................................................... GAA
EAC approved for intrinsic safety ............................................................................................................ EAC
INMETRO approved for intrinsic safety .................................................................................................. BAA
Without.........................................................................................................................................................ZZZ
Attachment Kit
Order as auxiliary .............................................................................................................................. N
Manifold
Order as auxiliary ........................................................................................................................................ A
Options
Amplifier free of nonferrous metals ............................................. (a) ................................................................... -C
Protection Class IP65 made with non return valve exhaust ........... .................................................................... -FA
Certificate EN 10204-2.1 certificate of compliance with the order ........................................................................ -1
Tag No. Labeling
Stamped with water resistant color ...................................................................................................................... -G
Stainless steel label fixed with wire ....................................................................................................................... -L

a) Not available with FAA & CAA


d) Not available with limit switch codes R, V
PSS EVE0102 A-(en)
SRI986 MODEL CODES Page 9

MODEL CODES Accessories


Attachment kit EBZG
for diaphragm actuators with casting yoke acc. to NAMUR (incl. standard Couple lever) (for SRI986) ............. -HN
for diaphragm actuators with pillar yoke acc. to NAMUR (incl. standard Couple lever) (for SRI986) ................. -KN
for rotary actuators, without flange, 3 drill holes 6.5 mm (for SRP981, SRI983, SRI986, SMP981, SMI983, SGE985) . -PN
for rotary actuators, without flange, 4 threads M6 (for SRP981, SRI983, SRI986, SMP981, SMI983, SGE985) ...... -NN
for rotary actuators, with flange (for SRP981, SRI983, SRI986, SMP981, SMI983, SGE985) ..................................-JN
for rotary actuators, with shaft (for SRP981, SRI983, SRI986, SMP981, SMI983, SGE985) ................................... -ZN
for Masoneilan type Camflex II (for SRP981, SRI983, SRI986, SMP981, SMI983, SGE985).................................. -RN
Further Attachment kits on request. See also our website.

Couple lever / cam


Standard (a = 72 mm) . ........................................................................................................................................ -AN
Extended (a = 91 mm) . ........................................................................................................................................ -BN
Inverse equal percentage cam for rotary actuators ................................................................................................ -CN

Spring set FESG


Range springs (4 pcs) .......................................................................................................................................... -FN

Manifold (Connection 1/4-18NPT) LEXG


staggered connections (for SRP981, SRI986) ....................................................................................................... -BN
connections same level (for SRP981, SRI986)...................................................................................................... -CN
with gauges for supply air, y, for version single acting (for SRP981, SRI986) ......................................................... -JN
with gauges for supply air, y1, y2, for version double acting (for SRP981, SRI986) ................................................ -MN
gauge manifold without gauge, for version single acting (for SRP981, SRI986) ...................................................... -RN
gauge manifold without gauge, for supply air, y1, y2, for version double acting (for SRP981, SRI986) .................... -SN

Booster (Connection 1/4-18NPT) VKXG


for version single acting (for SRP981, SRI986) ................................................................................................................ -FN
for version double acting (for SRP981, SRI986) .............................................................................................................. -GN
for version single acting with double output capacity (for SRP981, SRI986) ................................................................. -HN

Adapter (Material SS) AD


Adapter ½” NPT to ¾” NPT ................................................................................................................................................ -A3
Adapter (Stainless steel) M20x1.5 to 1/2"-14NPT (internal thread) ................................................................................ -A6
Adapter (Stainless steel) M20x1.5 to PG 13.5 (internal thread) .............................................................................. -A7
Adapter (Stainless steel) M20x1.5 to G 1/2" (internal thread) ................................................................................. -A8
Adapter (Plastic) M20x1.5 to PG 13.5 (internal thread) .......................................................................................... -A9

Cable gland BUSG


M20x1.5 Plug connector for Fieldbus (ss/ threaded connection 7/8 - UN) .................................................................... -F2
M20x1.5 plastics, color gray ................................................................................................................................. -K6
M20x1.5 plastics, color blue ................................................................................................................................. -K7
M20x1.5 plastics, color black ........................................................................................................................... -K8
M20x1.5 plastics, color white ................................................................................................................................ -K9
M20x1.5 Plug connector for Fieldbus (ss/ threaded connection M12) ................................................................ -P3
M20x1.5 HF cable gland for Fieldbus (ss) .......................................................................................................... -P4
M20x1.5 Stainless steel ..................................................................................................................................... -S6
PSS EVE0102 A-(en)
Page 10 DIMENSIONS SRI986

DIMENSIONS SRI986

5 2 4

3 9 1 0 5 ,5
1 .5 4 4 .1 5
1 2 ,5 8 0
.4 9 3 .1 5
1 2 ,5
.4 9
1 .9 3
4 9

4 .0 6
1 0 3
m a x . 3 9

2 .0 5
5 2
m in . 4
1 1 4 ,5
4 .5 1

2 .8 3
7 2
3 .1 5
8 0

M 6

1 8 ,5
.7 3
2 4 2 2 2 2
.9 4 .8 7 .8 7
9
.3 5
3
.1 2
6 3
2 .4 8

6 7 8 9 1 0 6 ,7 ,8 3 1 2

1 Cable gland 6 Female thread G1/8 for output II (y2)


2 Dummy plug, can be replaced with 1 (only on double-acting valve positioners)
3 Ground connection resp. potential equalization 7 Female thread G1/8 for air supply
4 Ground connection resp. potential equalization 8 Female thread G1/8 for output I (y1)
5 Screw terminals (+/–) for signal input (w) 9 Feedback lever
PSS EVE0102 A-(en)
SRI986 DIMENSIONS Page 11

DIMENSIONS Additional Equipment

Built-in Limit Switch Code P, Q, R, T, U, V

144
1 A B 2 5.67

Built-in Limit Switch Code


P, Q, T, U R V
A A
A B B B A B A B

42 41 52 51 1 2 3 4 42 41 52 51

41/51 2 41
3/4 42
DC DC
51
42/52 1 52

Built-in Position Transmitter Code F

3 1 3 2

1 4 4
1 4 2 5 .6 7

1 Cable gland
2 Dummy plug, can be replaced with 1
3 Connection terminals (+/–)
4 Ground connection
A Limit switch
B Limit switch
PSS EVE0102 A-(en)
Page 12 DIMENSIONS SRI986

DIMENSIONS Attachment Kit for Diaphragm Actuators

Feedback lever Carrier bolt for attachment


Code EBZG - HN, - KN, - AN to valve stem

7,8 -0,05
.31 -.002
2,5
.10

M6
6 83 72 14
.24 3.27 2.83 .55
10
65 .39
7,9 +0,2
.31 +.01

2.56

.78
20
10
.39
91
3.58

Dimensions of Mounting bracket acc. to IEC 534-6 (NAMUR)


for Code EBZG - HN, - KN
43
1.69
3.54
90
1.69
43

55,5
2.19
11
.43

102 102
4.02 4.02

Attachment to casting yoke Attachment to casting yoke


acc. to IEC 534-6 (NAMUR) acc. to IEC 534-6 (NAMUR)
Code EBZG - HN Code EBZG - HN

63,5 63,5
2.50 2.50
20 ... 35
.79 ... 1.38
1.69
43
2.19

55,5
2.19
.41 55,5
10,4

10,4
.41
105,5

105,5
4.15

4.15
PSS EVE0102 A-(en)
SRI986 DIMENSIONS Page 13

DIMENSIONS Attachment Kit for Rotary Actuators

with shaft (acc. to VDI/VDE 3845) with flange


Code EBZG - ZN Code EBZG - JN

.47
12
.39
10
2.95 .01
75 0,2

2.36 .01
60 0,2
136,5
5.37

62,5
2.46

50

.2 ,5
1.97

6
6
1.10 +.02
28 +0,5

176,5
6.95

Detail Z M6 x 14 (2 x)
DIN 912

14
.5 5
2.76
70

M6 x 30 (2 x)
4,5
.18

.20
5
DIN 912
.31

.12

6
8

4 .24
47
.16 1.85

.39
10
6 54
.5 3 2.13
63
2.48
86
3.39
13, 5
. 53

with flange Housing dimensions


Code EBZG – NN, -PN Attachment kit with shaft -ZN resp. without flange -N
43 95
1.69 3.74

50 M6
1.97
136,5
5.37

62,5
2.46

2.52
64
.47
12

3.90
99
16 H8
1.18

.63
30

167
6.57

Housing dimensions
Detail Y
11
Attachment kit without
43
flange 95-PN
.43 1.69 3.74
45 0,2
1,2
.05

6,5 14 - 6 1.77 .01


/
.26 .55 - .24
.59 .01
15 0,2

2.52
64

3.90
99
.47
12

22
.87

M6 14 ... 15,5
.47
12

16 .55 ... .61


.63

167
6.57

Adaption of the actuator drive shaft end


and correct axial location by customer!
PSS EVE0102 A-(en)
Page 14 DIMENSIONS SRI986

DIMENSIONS Booster

Booster single acting Booster single acting with double capacity


Code VKXG -FN Code VKXG -HN

1 3 2 6 1 5 2 6
65,5
2.58

3.43
87
88 91
3.46 3.58

104 108
4.09 4.25

Booster double acting


Code VKXG -GN

4 1 3 2 6
3.35
85

104 83
4.09 3.27

1 Female thread 1/4-18 NPT for supply air


2 Female thread 1/4-18 NPT not used
3 Female thread 1/4-18 NPT for output I (y1)
4 Female thread 1/4-18 NPT for output II (y2)
5 Female thread 1/2-14 NPT for output I (y1)
6 Fixing screws 17 mm A/F
PSS EVE0102 A-(en)
SRI986 DIMENSIONS Page 15

DIMENSIONS Connection Manifold

Connection Manifold Connection Manifold


Code LEXG-BN Code LEXG-CN

4 1 3 2 4 1 3 2

6 6

28,5
1.12
28,5
1.12

88 30 88 30
3.46 1.18 3.46 1.18

1 Female thread 1/4-18 NPT for supply air


2 Female thread 1/4-18 NPT not used
3 Female thread 1/4-18 NPT for output I (y1)
4 Female thread 1/4-18 NPT for output II (y2)
6 Fixing screws 17 mm A/F

Connection Manifold with Gauges


Code LEXG-JN, -MN

6 1

5 2

3
4 3 ,5
1 .7 2

8 7 0
2 .7 6
1 0 2
4 .0 2
4

Connection
5 6 7
Manifold single double
Code Gauge for Gauge for Gauge for
acting acting
Supply Output I (y / y1) Output II (y2)
JN air air
Supply Output (y) without yes -
MN Supply air Output I (y1) Output II (y2) - yes
RN without without without yes -
SN Supply air Output I (y1) Output II (y2) - yes

1 Female thread 1/4-18 NPT for supply air


2 Female thread 1/4-18 NPT not used
3 Female thread 1/4-18 NPT for output I (y1)
4 Female thread 1/4-18 NPT for output II (y2)
(not for Connection Manifold LEXG - JN)
8 Fixing screws 17 mm A/F
PSS EVE0102 A-(en)
Page 16

Schneider Electric Systems USA, Inc. Global Customer Support Copyright 2010-2018 Schneider Electric
38 Neponset Avenue Inside U.S.: 1-866-746-6477 Systems USA, Inc. All rights reserved.
Foxboro, MA 02035 Outside U.S.:1-508-549-2424
United States of America https://pasupport.schneider-electric.com **Schneider Electric is a trademark** of
http://www.schneider-electric.com Schneider Electric Systems USA, Inc., its
subsidiaries, and affiliates. All other trademarks
are the property of their respective owners.

DOKT 535 735 022