Lecture 1-4
Lecture 1-4
Electric Machines
Class EEE-5B
Lecture No.1-3
1
31/10/2023
1. Electrical Machine
A device that can convert either mechanical energy to electrical energy or electrical energy to mechanical energy
Almost all practical motors and generators convert energy from one form to another through the action of a
magnetic field
It converts ac electrical energy at one voltage level to ac electrical energy at another voltage level
These three types of electric devices are ubiquitous in modern daily life
Electric motors in the home run refrigerators, freezers, vacuum cleaners, blenders, air conditioners, fans, and
many similar appliances
Generators are necessary to supply the power used by all these motors
Almost all electric machines rotate about an axis, called the shaft of the machine
Angular Position ϴ
The angular position 9 of an object is the angle at which it is oriented, measured from some arbitrary reference
point
Angular position is usually measured in radians or degrees
Angular Velocity ω
Angular velocity (or speed) is the rate of change in angular position/angular displacement with respect to time
If the units of angular position are radians, then angular velocity is measured in radians per second.
2
31/10/2023
Angular Acceleration α
Angular acceleration is the rate of change in angular velocity with respect to time
If the units of angular velocity are radians per second, then angular acceleration is measured in radians per second
square
3
31/10/2023
Four basic principles describe how magnetic fields are used in these devices:
2. A time-changing magnetic field induces a voltage in a coil of wire if it passes through that coil. (This is the basis
of transformer action.)
3. A current-carrying wire in the presence of a magnetic field has a force induced on it. (This is the basis of motor
action.)
4. A moving wire in the presence of a magnetic field has a voltage induced in it.
(This is the basis of generator action.)
B=μH
B= μNi/lc
Ø=BA
Ø=μNiA/lc
A simple magnetic core
4
31/10/2023
Reluctances in parallel-
=flux, R=reluctance
1/Req=1/R1+R2+R3+…..
Flux in a core
Calculation of flux in a core performed by using magnetic circuit concepts
are approximation due to following reasons:
Small fraction of flux escapes from core to surrounding low permeability
air-Leakage flux
Calculation of reluctances assumes a certain path length and cross-
sectional area of core –not good especially at corners
In ferromagnetic materials, the permeability varies with the amount of
flux already in the material- Reluctances used in magnetic circuit
calculation depend on the permeability of material
If there are air gaps in the flux path in a core, the effective cross-
sectional area will be larger than the iron-core on either side-Fringing
effect
Fringing effect
Problem 1. A ferromagnetic core is shown in Figure. The depth of the core is 5 cm. The other dimensions of the core are as
shown in the figure. Find the value of the current that will produce a flux of 0.005 Wb. With this current, what is the flux
density at the top of the core? What is the flux density at the right side of the core? Assume that the relative permeability of
the core is 1000.
10
5
31/10/2023
Sol:
11
Problem 2: A ferromagnetic core with a relative permeability of 1500 is shown in Figure. The dimensions are
as shown in the diagram, and the depth of the core is 7 cm. The air gaps on the left and right sides of the core
are 0.070 and 0.020 cm, respectively. Because of fringing effects, the effective area of the air gaps is 5
percent larger than their physical size. If there are 400 turns in the coil wrapped around the center leg of
the core and if the current in the coil is 1.0 A, what is the flux in each of the left, center, and right legs of
the core? What is the flux density in each air gap?
12
6
31/10/2023
Solution:
13
Although permeability is constant in free space, this most certainly is not true for iron and other ferromagnetic
materials
To illustrate the behavior of magnetic permeability in a ferromagnetic material, apply a direct current to the
core shown in Figure
14
7
31/10/2023
15
8
31/10/2023
Faraday's law states that if a flux passes through a turn of a coil of wire, a voltage will be induced in the turn of
wire that is directly proportional to the rate of change in the flux with respect to time. In equation form,
where
eind = voltage induced in the coil
N = number of turns of wire in coil
ø= flux passing through coil
The minus sign in the equations is an expression of Lenz's law. Lenz's law states that the direction of the voltage
buildup in the coil is such that if the coil ends were short circuited, it would produce current that would cause a
flux opposing the original flux change.
The magnitude of the voltage in the ith turn of the coil is always given by
If there are N turns in the coil of wire, the total voltage on the coil is
Where
17
where
i = magnitude of current in wire
l= length of wire, with direction of l defined to be in the direction of
current flow
B = magnetic flux density vector
F = il BSinϴ
Where ϴ is the angle between the wire and flux density vector
18
9
31/10/2023
If a wire with the proper orientation moves through a magnetic field, a voltage is induced in it
eind = (v X B) • l
where
v = velocity of the wire
B = magnetic flux density vector
l = length of conductor in the magnetic field
19
2. Transformers
A transformer is a device that changes ac electric power at one frequency and voltage level to ac electric
power at the same frequency and another voltage level through the action of a magnetic field
It consists of two or more coils of wire wrapped around a common ferromagnetic core
These coils are (usually) not directly connected and the only connection between the coils is the common
magnetic flux present within the core
One of the transformer windings is connected to a source of ac electric power, and the second (and perhaps
third) transformer winding supplies electric power to loads
The transformer winding connected to the power source is called the primary winding or input winding, and
the winding connected to the loads is called the secondary winding or output winding
20
10
31/10/2023
120-V dc system invented by Thomas A. Edison in 1882- low voltage, large current
Huge Voltage drop and power losses in transmission line
If a transformer steps up the voltage level of a circuit, it must decrease the current to keep the power into
the device equal to the power out of it
Voltage stepped up for transmission over long distances at very low losses, and its voltage stepped down
again for final us
The transmission losses in the lines of a power system are proportional to the square of the current in the
lines, raising the transmission voltage
Reducing the resulting transmission currents by a factor of 10 with transformers reduces power transmission
losses by a factor of 100
21
In either case, the core is constructed of thin laminations electrically isolated from each other in order to
minimize eddy currents
The primary and secondary windings in a physical transformer are wrapped one on top of the other with the low-
voltage winding innermost, Two purposes
1. It simplifies the problem of insulating the high-voltage winding from the core.
2. It results in much less leakage flux than would be the case if the two windings were separated by a distance on
the core.
22
11
31/10/2023
Unit transformer: A transformer connected to the output of a generator and used to step its voltage up to
transmission levels (110 + kV)
Substation transformer: The transformer at the other end of the transmission line, which steps the voltage down
from transmission levels to distribution levels (from 2.3 to 34.5 kV)
Distribution transformer: The transformer that takes the distribution voltage and steps it down to the final
voltage at which the power is actually used (110, 208, 220 V, etc.)
In addition to the various power transformers, two special-purpose transfomer are used to measure voltage
and current in electric machinery and power systems.
The first of these special transformers is a device specially designed to sample a high voltage and produce a
low secondary voltage directly proportional to it. Such a transformer is called a potential transformer
A power transformer also produces a secondary voltage directly proportional to its primary voltage
The difference between a potential transformer and a power transformer is that the potential transformer is
designed to handle only a very small current
The second type of special transformer is a device designed to provide a secondary current much smaller than
but directly proportional to its primary current. This device is called a current transformer
23
1. If the primary voltage is positive at the dotted end of the winding with respect
to the undotted end, then the secondary voltage will be positive at the dotted
end also. Voltage polarities are the same with respect to the dots on each side
of the core.
2. If the primary current of the transformer flows into the dotted end of the primary
winding, the secondary current will flow out of the dotted end of the
secondary winding.
24
12
31/10/2023
The real power Pin supplied to the transformer by the primary circuit is given by the equation
The real power P out supplied by the transformer secondary circuit to its loads is given by the equation
Apply
Thus, the output power of an ideal transformer is equal to its input power
25
If the secondary current is called Is and the secondary voltage Vs, then the impedance of the load is given by
26
13
31/10/2023
Problem 1:A single-phase power system consists of a 480-V 60-Hz generator supplying a load Zload=4+j3Ω through
a transmission line of impedance Zline = 0.18 + j0.24Ω. Answer the following questions about this system.
(a) If the power system is exactly as described above as shown in Figure a?, what will the voltage at the load be?
What will the transmission line losses be?
(b) Suppose a 1: 10 step-up transformer is placed at the generator end of the transmission line and a 10:1 step-down
transformer is placed at the load end of the line (as shown in Figure b). What will the load voltage be now? What
will the transmission line losses be now?
27
Solution
Here IG = Iline =Iload
The line current in this system is given by
28
14
31/10/2023
(b) Figure b shows the power system with the transformers. To analyze this system, it is necessary to convert it to a common
voltage level. This is done in two
steps:
1. Eliminate transformer T2 by referring the load over to the transmission line's voltage level
2. Eliminate transformer T1 by referring the transmission line's elements and the equivalent load at the transmission line's
voltage over to the source side.
29
30
15
31/10/2023
If the total flux linkage in all the turns of the coils is λ and if there are N turns, then the average flux per
turn is given by
31
32
16
31/10/2023
The other component of the no-load current in the transformer is the current required to supply power to make
up the hysteresis and eddy current losses in the core. This is the core-loss current.
Assume that the flux in the core is sinusoidal.
Since the eddy currents in the core are proportional to dø/dt, the eddy currents are largest when the flux in the
core is passing through 0 Wb. Therefore, the core-loss current is greatest as the flux passes through zero
The total no-load Current in the core is called the excitation current of the transformer. It is just the sum of the
magnetization current and the core-loss current in the core:
In a well-designed power transformer, the excitation current is much smaller than the full-load current of the
transformer
33
A current flowing into the dotted end of a winding produces a positive magnetomotive force F
A current flowing into the undotted end of a winding produces a negative magnetomotive force
Two currents flowing into the dotted ends of their respective windings produce magnetomotive forces that add
If one current flows into a dotted end of a winding and one flows out of a dotted end, then the magnetomotive
forces wil1 subtract from each other
34
17
31/10/2023
1. Copper (I2R) losses. Copper losses are the resistive heating losses in the primary and secondary windings of
the transformer. They are proportional to the square of the current in the windings.
2. Eddy current losses. Eddy current losses are resistive heating losses in the core of the transformer. They are
proportional to the square of the voltage applied to the transformer.
3. Hysteresis Losses. Hysteresis losses are associated with the rearrangement of the magnetic domains in the core
during each half-cycle. They are a complex, nonlinear function of the voltage applied to the transformer.
4. Leakage flux. The fluxes øLP and øLS which escape the core and pass through only one of the transformer
windings are leakage fluxes.
35
The Transformer model referred to its primary voltage The transformer model referred to its secondary voltage
level level
36
18
31/10/2023
Approximate transformer models. (a) Referred to the primary side; (b) referred to the secondary side; (c) with no
excitation branch, referred to the primary side; Cd} with no excitation branch, referred to the secondary side
37
Electric Machines
Class EEE-5B
Lecture No.4
September , 2021
Abbottabad
38
38
19
31/10/2023
It is possible to experimentally determine the values of the inductances and resistances in the transformer model
39
In the short-circuit test, the low-voltage terminals of the transformer are short circuited, and the high-voltage
terminals are connected to a variable voltage source
This measurement is normally done on the high-voltage side of the transformer, since currents will be lower on
that side, and lower currents are easier to work with
The input voltage is adjusted until the current in the short circuited windings is equal to its rated value
Be sure to keep the primary voltage at a safe level. It would not be a good idea to burn out the transformer's
windings while trying to test it
Since the input voltage is so low during the short-circuit test, negligible current flows through the excitation
branch
If the excitation current is ignored, then all the voltage drop in the transformer can be attributed to the series
elements in the circuit
40
20
31/10/2023
41
Full-load voltage regulation is a quantity that compares the output voltage of the transformer at no load with
the output voltage at full load. It is defined by the equation
42
21
31/10/2023
Transformers are also compared and judged on their efficiencies. The efficiency of a device is defined by the
equation
43
44
22
31/10/2023
45
The voltage on the high side of the The current relationship between the two sides of the
autotransformer is given by transformer can be found by noting that
46
23
31/10/2023
It is interesting to note that not all the power traveling from the primary to the secondary in the
autotransformer goes through the windings
As a result, if a conventional transformer is reconnected as an autotransformer, it can handle much
more power than it was originally rated for
47
Problem 1
48
24
31/10/2023
49
50
25
31/10/2023
51
52
26
31/10/2023
References
1. Electrical Machinery Fundamentals by Stephen J. Chapman, 4th Edition
2. Electric Machines by Charles. I. Hubert (2nd Edition)
3. Electric Machines by Fitz Gerald
53
Thank You
Q & A Session
54
27