DC System Sizing Calculation
DC System Sizing Calculation
ANNEXURE - 1
220V DC LOAD
S. 599 to 600
Description KW Amps 0-1 Minute 1-120 Minute 1-10 hrs Remarks Load Classification
No. miniute
Note:
1.For asterisk (*) marked loads, a ten (10) percent loading is considered as momentary loading during the first one minute period of the duty cycle.
2. For (D) marked loads, the Momentary Load is arrived based on operation criteria & Indication load is taken as constant load throughout it's duty cycle.
3. 400KV & 220KV switchyard loads are not included since these are catered by dedicated DC systems.
4. Loads marked thus (#) are included for float charger sizing.
5. In Loads marked ($) Load factor of 0.9 are considered only in Continious running condition.
6. No random Load is assumed as insertion of load is known to us.
Rev R0
2 x 300MW JSW Power Plant
ANNEXURE - 2
CALCULATION FOR MINIMUM END CELL VOLTAGE
1. Nominal System Voltage = 220 V
2. Minimum allowable system voltage (-15% of the System voltage) = 187 V
3. Maxm. Voltage drop from battery upto load terminals @5% of 220V = 11 V
4. Minimum voltage required at battery terminals = (2)+(3) 198 V
5. Number of cells assumed = 110 V
6. Minimum end cell voltage required = (4)/(5) 1.80 V
7. Leaving a little margin, minimum End cell voltage considered = 1.85 V
8. Minimum number of cells required for ECV of 1.85V =(4)/(7) 107.03
Therefore Min Number of cell rounded-off to next higher whole No. 108
Hence, consideration of 110 cells is correct.
(a) (b) © (d) = (a) x (c) (e) = (h) (f) = (d) - (e) (g)=(e) + (h) = (a) x (i) = (g) -
(f) (b) / 60 (h)
611.14 1 1.3 794.48 0 794.48 794.48 10.19 784.29
425.86 59 2.55 1085.95 784.29 301.66 1085.95 418.77 667.19
60.64 540 9.3 563.92 667.19 667.19 545.73 121.46
NB:- Since Selected battery rating is higher than calculated battery hence design is safe
Rev R0
0-1 Minute 1-60 61-120 120 -599 599 -600
Upto 1Min Minute Minute min min
Rev R1
11 kV Breakers Closing coils Intermittent 180 1 1 1 1 4 0.72 3.27 0.82 0.82 3.27
Diff Relay 87T Intermittent 5 1 1 2 0.01 0.05 0.00
Diff Relay 87M Intermittent 5 0 0.00 0.00
Feeder 50+51/Motor Relay 99 Intermittent 6 1 1 2 0.01 0.05 0.03 0.03 0.03
Auxiliary relays Intermittent 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 14 0.04 0.19 0.19 0.19 0.19
Antpumping relay 94 Continous Load 1.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 14 0.02 0.10 0.01 0.01 0.01 0.01
CB Contact Multiplier Intermittent 65 1 1 1 1 1 1 1 1 1 1 1 1 1 1 14 0.46 2.07 0.30 0.30 0.30 0.30
DC fail Relay (80DCF) Continous Load 1.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 15 0.02 0.10 0.10 0.10 0.10 0.10
U/V Relay & It's Contact Multiplier Continous Load 7.5 1 1 2 0.02 0.07 0.07 0.07 0.07 0.07
Syn relay Continous Load 12 1 1 2 0.02 0.11 0.11 0.11 0.11
TCS Relay, 74 Continous Load 3.24 1 1 1 1 1 1 1 1 1 1 1 1 1 1 14 0.05 0.21 0.21 0.21 0.21 0.21
Tripping Relay, 86 (Operation of 50%
0 1 1 1 1 1 1 1 1 1 1 1 0 0 1
Relay/Switchboard Sim.) Intermittent 9 12 0.05 0.25 0.25 0.25 0.25 0.25
Rev R1
Coal OCCW Coal Coal
Coal Mill- Coal Coal TDBFP BWCP BWCP CWCP Coal Coal Mill- CWCP TDBFP- OCCWP- BWCP-
6.6KV Unit Auxiliary Switchboard UA-1 I/C-1 Mill-1G P-1A B/C Mill- Mill- I/C-2
1A Mill-1C Mill-1E -1A -1A -1C (S) M-1A Mill-1F 1D M-1B 1B 1B 1B
(S) (S) 1B(S) 1(SP)
6.6 kV Breakers tripping coils Intermittent 180 1 1 1 1 4 0.72 3.27 0.82 0.82 0.33
6.6 kV Breakers Closing coils Intermittent 180 1 1 2 0.36 1.64 0.82 0.82 1.64 1.64
Diff Relay 87UAT 5 1 1 0.01 0.02
Diff Relay 87M 5 1 1 1 1 1 5 0.03 0.11
Feeder 50+51/Motor Relay 99 6 1 1 1 1 1 1 1 1 1 9 0.05 0.25 0.03 0.03 0.03
Auxiliary relays 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 15 0.05 0.20 0.20 0.20 0.20 0.20
Antpumping relay 94 1.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 15 0.02 0.10 0.01 0.01 0.01 0.01
CB Contact Multiplier (Operation of 50%
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Relay/Switchboard Sim.) 65 15 0.49 2.22 0.30 0.30 0.30 0.30
DC fail Relay (80DCF) 1.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 15 0.02 0.10 0.10 0.10 0.10 0.10
U/V Relay & It's Contact Multiplier 7.5 0 0.00 0.00 0.00 0.00 0.00
Syn relay 12 1 1 0.01 0.05 0.05 0.05 0.05 0.05
TCS Relay, 74 3.24 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 15 0.05 0.22 0.22 0.22 0.22 0.22
Tripping Relay, 86 (Operation of 50%
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Relay/Switchboard Sim.) 9 15 0.07 0.31 0.31 0.31 0.31
TOTAL
400 KV Switchyard Separate DC System is considered for Switchyard Purpose 0 0.00 0.00 0.00 0.00 0.00
ELECTRICAL OPERATED SOLENOID VALVE Fed from UPS Supply 0 0.00 0.00 0.00 0.00 0.00
Rev R1
Total Plant Load 1192.55 925.81 921.44 77.54 20.67
Rev R1
COASTAL ENERGEN PRIVATE LIMITED Doc Ref.No.
2 X 600 MW 1013-3VYN591603-01
THERMAL POWER PLANT
ABB LIMITED DC SYSTEM (BATTERY & BATTERY CHARGER) Section
BANGALORE SIZING CALCULATION Sheet 4 of 5
ANNEXURE - 2
CALCULATION FOR MINIMUM END CELL VOLTAGE
1. Nominal System Voltage = 220 V
2. Minimum allowable system voltage (-15% of the System voltage) = 187 V
3. Maxm. Voltage drop from battery upto load terminals @5% of 220V = 8.8 V
4. Minimum voltage required at battery terminals = (2)+(3) 195.8 V
5. Number of cells assumed = 108 V
6. Minimum end cell voltage required = (4)/(5) 1.81 V
7. Leaving a little margin, minimum End cell voltage considered = 1.85 V
8. Minimum number of cells required for ECV of 1.85V =(4)/(7) 105.84
9. Therefore Min Number of cell rounded-off to next higher whole No. 108
10. Max system Voltage = 10% of the system Voltage 242
(a) (b) © (d) = (a) x (c) (e) = (h) (f) = (d) - (e) (g)=(e) + (h) = (a) x (i) = (g) - (h)
(f) (b) / 60
1192.55 1 1.169 1394.09 0 1394.09 1394.09 19.88 1374.22
925.81 59 1.863 1724.78 1374.22 350.56 1724.78 910.38 814.40
921.44 60 1.8721 1725.04 814.40 910.63 1725.04 921.44 803.59
77.54 479 8.261 640.55 803.59 -163.04 640.55 619.02 21.53
20.67 1 1.169 24.17 21.53 2.64 24.17 0.34 23.82
NB:- Since Selected battery rating is higher than calculated battery hence design is safe
Rev R1
2 x 300 MW JSW Power Plant
1192.55
925.81
921.44
77.54
20.67
0 1 60 120 599 600
DURATION (IN MIN.)
Rev R1
NO. EQ. NAME
FEEDER quantity/per
NOTE INCOMER BREAKER'S
CAPABILITY unit RATING CURRENT
2 Turbine DC jacking oil pump 30KW 1 220VDC ONE FEEDER PER UNIT.starting time IS 30ms
3 Turbine DC emergency oil pump 55KW 1 220VDC ONE FEEDER PER UNIT.starting time IS 30ms
ELECTRICAL
4 Generator air side seal standby pump 22KW 1 220VDC ONE FEEDER PER UNIT.starting time IS 30ms
5 5.5KW
Generator hydrogen seal oil standby pump 1 220VDC ONE FEEDER PER UNIT.starting time IS 30ms
6 BFPT DC emergence oil pump 10KW 2 220VDC ONE FEEDER PER UNIT.starting time IS 30ms
7 SCANNER AIR FAN 20KW 1 220VDC ONE FEEDER PER UNIT.starting time IS 30ms