FCU Installation Guide
FCU Installation Guide
FCU Installation Guide
Air discharge
Grill
Control box panel
Feet
Air intake
Dimension(mm)
Model
A B
1
Installation Instruction
Physical data
Condition:
Cooling mode: entering air temperature 27°C db/19°C wb, entering/leaving water temperature 7/12°C, high fan speed.
Heating mode (2-pipe coil): entering air temperature 20°C, entering water temperature 50°C, high fan speed, water flow rate as
cooling mode.
Electrical data
Fan Motor
Model
Type Qty Type Qty Power input(w) Current input(A)
FCU150 1 1 27 0.11
FCU200 1 1 31 0.15
FCU300 1 1 35 0.16
Operating limits
Water circuit Water- side maximum pressure Minimum entering water temperature: + 4℃
1400 kPa (142 m w.c.) Maximum entering water temperature: + 65℃
Indoor temperature Minimum temperature: 5℃
Maximum temperature 32℃
Power supply Nominal single phase voltage 230V ~ 50 Hz
Operating voltage limits min. 198V - max. 264V
2
Installation Instruction
Warning avoid
3
Installation Instruction
4
Installation Instruction
Installation
Screw anchors
5
Installation Instruction
Water connection
Water piping can enter either from the floor or from the wall. Leave the space shown in the figure
above.
The unit coil can be supplied with water connections positioned as requested.
NOTE:
The connection pipes must be insulated with a condensation-proof material such as polyurethane,
propylene or neoprene of 5 to 10 mm thickness.
6
Installation Instruction
Electrical connections
1 2 3 4 5 6
Wiring box
IMPORTANT:
y Make earth connection prior to any other electrical connections.
y Disconnect the power supply to all circuits prior to handling any electrical components.
y Before proceeding with the unit connection to the mains supply locate live L and neutral N,
then make connections as shown in the wiring diagram.
y Ensure that the mains supply connection is made through a switch that disconnects all poles,
with contact gap of a least 3 mm.
y The fan coil connecting cable as well as accessory wires must be H07 RN-F type (or higher),
synthetic rubber insulation with Neoprene coating, according to EN 60335-2-40 and
HD277.S1 codes and located in a proper rigid conduit.
y For the unit power supply, it is recommended to use cables with a minimum size of 1.5 mm2.
Control box panel. The control box panel is always positioned opposite the water
connections.
y Two different control box panels are available: one for a unit without electric heater, and one
for a unit with electric heater. Inside each control box panel there is a terminal block for the
electrical connections (see wiring diagrams). After connections have been completed, cables
must be secured with the cable holders supplied.
y If the unit is fitted with an electric heater, this must have a separate power supply.
Control
7
Installation Instruction
Wiring diagram
FM fan motor
Cap capacitance
SS three-speed on-off
TB connecting terminal
- - - - - - - - -going to be connected
__________ connected
y Turning the unit ON and OFF.
y Changing the operation modes.
y Temperature selection.
y Leave the installation manual with the owner for future use during maintenance operations or for
any other needs.
Maintenance
Air filter
Check and make sure that the filter is cleaned at least once a month or more often if unit is located
in a dusty room. A dirty filter reduces the air flow and unit efficiency.
To inspect filter proceed as follows:
y switch the unit OFF;
y loosen the two screws located at the base of the unit and the corresponding plates;
y lower the two guides and withdraw filter;
y clean the filter gently with soapy water or with a vacuum cleaner;
y reinsert and position the filter in the guides, keeping the photo catalytic filter tabs upwards as
illustrated;
y return the filter guides to their original position;
y tighten the screws and associated plates.
It is advisable to clean and if necessary replace the air filter before the winter season.
Condensate draining
During the summer season check that the condensate drain is free from dust and lint that could
8
Installation Instruction