ATV58 Wiring
ATV58 Wiring
ATV58 Wiring
Presentation : Altivar 58
pages 16 to 20
Characteristics :
pages 21 to 23 Schemes, compatibility
References :
pages 30 and 32
Functions : Basic schemes only : to be adapted to meet local standards and regulations
pages 86 to 109
Schemes without contactor, recommended for machines which are not dangerous
3-phase supply Single phase supply
5
1
– Q1 – Q1
6
2
(1) (1)
(2) (3) (4) (2) (3) (4)
A1 A1
L1
L2
R1A
R1C
R1B
LI1
LI2
LI3
LI4
L1
L2
L3
R1A
R1C
R1B
LI1
LI2
LI3
LI4
R2A
R2C
R2A
R2C
+ 24
+ 24
COM (0 V)
COM (0 V)
+ 10
+ 10
AI1
AI2
AI1
AI2
PA
PB
W
W
U
U
V
V
W1
W1
U1
V1
U1
V1
Optional
braking
M Reference M Reference
resistor X - Y mA X - Y mA
3 potentiometer 3 potentiometer
A1 A1
ATV- ATV-58
58iU09M2 and other ratings
58iU18M2
PA
PB
+
–
A2
–
+
(5)
PA
PB
Optional
braking
resistor
Note :
- All the terminals are located at the bottom of the controller.
- Fit suppressors to all the specific circuits close to the controller or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting,
etc.
Code Description
62 Te
Variable speed controllers for asynchronous motors
Presentation : Altivar 58
pages 16 to 20 Schemes, compatibility (continued)
Characteristics :
pages 21 to 23 Speed controllers ATV-58iU09M2 to iD12M2 and iU18N4 to iD23N4
References :
pages 30 and 32
Functions : Basic schemes only : to be adapted to meet local standards and regulations
pages 86 to 109
Schemes with downstream contactor, recommended for dangerous machines which are switched on and off frequ
ently
3-phase supply Single phase supply
1
5
– Q1 – Q1
2
6
(1) (1)
L1
L2
R1A
R1C
R1B
LI1
LI2
LI3
LI4
+ 24
L1
L2
L3
R1A
R1C
R1B
LI1
LI2
LI3
LI4
+ 24
R2A
R2C
R2A
R2C
COM (0 V)
COM (0 V)
+ 10
+ 10
AI1
AI2
AI1
AI2
PA
PB
W
W
U
U
V
V
Optional
braking Reference
Reference
1
resistor potentiometer
potentiometer
KM2 KM2
2
X - Y mA X - Y mA
A2
A2
– KM2 – KM2
W1
W1
U1
V1
U1
V1
A1
A1
M M
3 3
ATV- ATV-58
58iU09M2 other ratings
A1 and A1
58iU18M2
PA
PB
+
–
A2
–
+
(4) Optional
PA
PB
braking
resistor
Note :
- All the terminals are located at the bottom of the controller.
- Fit suppressors to all the specific circuits close to the controller or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting,
etc.
Code Description
64 Te
Variable speed controllers for asynchronous motors
Presentation : Altivar 58
pages 16 to 20
Characteristics : Schemes, compatibility
pages 21 to 23 Speed controllers ATV-58HD16M2X to HD46M2X and HD28N4 to HD79N4
References :
pages 30 to 32
Functions : Basic schemes only : to be adapted to meet local standards and regulations
pages 86 to 109
Schemes with downstream contactor, recommended for dangerous machines which are switched on and off frequently
3-phase supply
1
(3)
– Q1
A1
– KM2
2
1 – Q2 2 – T1 1 – Q3 2 R2A R2C A1 A2
3 4 5 – Q2 6
(1) (2)
A1
L1
L2
L3
R1A
R1C
R1B
LI1
LI2
LI3
LI4
+ 24
COM (0 V)
+ 10
AI1
AI2
PA
PB
W
U
V
1
Optional
KM2 braking X - Y mA
resistor Reference
2
potentiometer
W1
U1
V1
M
3
(1) Fault relay contacts; for remote signalling of speed controller status.
(2) Internal + 24 V. If an external + 24 V supply is used, connect the 0 V on the external supply to the COM terminal, do not use the + 24 of the speed controller,
and connect the common of the LI inputs to the + 24 V of the external supply.
(3) Use the "downstream contactor control" function with relay R2 or the logic output LO of one of the "I/O extension" cards, by relaying.
Note :
- All the terminals are located at the bottom of the controller.
- Fit suppressors to all the specific circuits close to the controller or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting,
etc.
Compatible components
Code Description
Q3 GB2-CB05
Te 65
Variable speed controllers for asynchronous motors
Altivar 58
Presentation :
page 38 Schemes (continued)
Characteristics :
page 38
References : Basic schemes only : to be adapted to meet local standards and regulations
page 39
24 V external supply for supplying logic inputs and/or the logic 2-wire control and step by step (JOG) operation
output
LO +
COM
+ 24
+ 24
LIi
LIi
LIi
LIi
LI1
LI2
LI3
LO
+
KA
–
Forward Reverse JOG
0V
+ 24
24 V supply
3-wire control and step by step (JOG) operation Motor protection via PTC probes, with optional analogue input extension
card
Optional card
COM
+ 24
AI3A
AI3B
+10
LI1
LI2
LI3
LI4
R = 10 kΩ ± 5 %
Forward
JOG
3 250 Ω probes in series
Reverse
JOG
Motor
I/O extension card with analogue input I/O extension card with inputs for encoder
VW3-A58201 VW3-A58202
LO +
LO +
+ 10
COM
COM
– 10
+ 24
+ 24
AI3A
AI3B
A–
B–
AO
AO
LI5
LI6
LI5
LI6
LO
LO
+ +
A
A–
B–
KA KA
± 10 V – –
+
–
Encoder
0v
24 v
24 V external supply
66 Te
Variable speed controllers for asynchronous motors
Altivar 58
Presentation :
page 38 Schemes (continued)
Characteristics :
page 38
References : Basic schemes only : to be adapted to meet local standards and regulations
page 39
+ 10
+ 10
COM
– 10
COM
– 10
AI3A
AI3B
AI3A
AI3B
R ± 10 V
+ 10
COM
COM
– 10
– 10
AI3A
AI3B
AI3A
AI3B
± 5 to 9 V
-R1 (1)
R B1
-R2 (1)
+ 24
A–
B–
AO
LI5
LI6
LO
A
+
NPN KA
sensor –
+
–
Te 67
Variable speed controllers for asynchronous motors
Presentation : Altivar 58
pages 48 and 50
Characteristics :
pages 48 and 51 Schemes (continued)
References :
pages 49 and 51
Dimensions : Basic schemes only : to be adapted to meet local standards and regulations
page 61
2c 2c
L1
L2
L3
L1
L2
VW3-A5840i VW3-A5840i
L'1
L'2
L'3
L'1
L'2
L1
L2
L3
L1
L2
ATV-58iiiiii ATV-58iiiiii
3-phase supply
3c
L1
L2
L3
VW3-A5840i
L'1
L'2
L'3
L1
L2
L3
ATV-58iiiiii
Output filters
VW3-A5845i i
LR cell
ATV-58iU09M2 à iD12M2
et ATV-58iU18N4 à iD23N4
W
U
V
L1
L2
L3
VW3-A5845i
G
3
W1
U1
V1
M
3c
68 Te
Variable speed controllers for asynchronous motors
Altivar 58
Electromagnetic compatibility
Principle
i The earths between the speed controller, motor and cable shielding must have "high frequency" equipotentiality.
i Use shielded cables with shielding connected to earth at 360° at both ends of the motor cable, braking resistor (if fitted)
and control-command cables. Tubes or metal ducting can be used for part of the shielding length provided that there
is no break in continuity.
i Ensure maximum separation between the power supply cable (mains supply) and the motor cable.
Installation diagram
1 5
4 7
3 6
8
1 Metal plate supplied with the speed controller, to be mounted as shown (machine earth).
2 Altivar 58.
3 Non-shielded power supply wires or cable, with link (if any) to line choke.
5 Fix and earth the shielding of cables 6, 7 and 8 as close as possible to the speed controller :
- strip the shielding
- use the correct size clamps on the stripped part of the shielding to fix to metal plate 1.
The shielding must be clamped tightly enough to the metal plate to ensure good contact.
- clamp types : stainless steel
6 Shielded cable for motor connection with shielding connected to earth at both ends.
The shielding must be continuous and intermediate terminal blocks must be in EMC shielded metal cases.
8 Shielded cable for connecting brake resistor (if fitted). The shielding must be connected to earth at both ends. The
shielding must be continuous and intermediate terminal blocks must be in EMC shielded metal cases.
Notes :
1 The HF equipotential earth connection between the speed controller, motor and cable shielding does not remove the
need to connect the PE protective conductors (green-yellow) to the appropriate terminals on each unit.
2 If using an additional input filter, it should be mounted under the speed controller (speed controller with heatsink) or to
one side (speed controller on a baseplate), and connected directly to the mains supply via an unshielded cable. Link 3
is via the filter cable.
Te 69
Variable speed controllers for asynchronous motors
Presentation : Altivar 58
pages 16 to 20
Characteristics :
pages 21 to 23 Schemes, compatibility (continued)
References :
pages 30 and 32
Functions : Basic schemes only : to be adapted to meet local standards and regulations
pages 86 to 109
Schemes with line contactor, recommended for dangerous machines which are switched on or off infrequently
3-phase supply Single phase supply
5
1
– Q1 – Q1
– KM1
6
– KM1
2
– S2 – S2
1 – Q2 2 – T1 1 – Q3 2 – S1 A1 A2 1 – Q2 2 – T1 1 – Q3 2 – S1 A1 A2
3 4 5 – Q2 6 3 4 5 – Q2 6
A1 A1
– KM1 – KM1
R1A R1C 13 14 R1A R1C 13 14
1
3
– KM1 – KM1
2
4
(1) (1)
(2) (3) (4) (2) (3) (4)
A1
L1
L2
L3
R1A
R1C
R1B
LI1
LI2
LI3
LI4
A1
R2A
R2C
L1
L2
R1A
R1C
R1B
LI1
LI2
LI3
LI4
+ 24
R2A
R2C
+ 24
COM (0 V)
COM (0 V)
+ 10
+ 10
AI1
AI2
PA
PB
AI1
AI2
W
W
U
V
W1
U1
V1
W1
U1
V1
Optional
braking Reference X - Y mA X - Y mA
M M Reference
3 resistor potentiometer 3 potentiometer
A1 A1
ATV- ATV-58
58iU09M2 other ratings
and
58iU18M2
PA
PB
+
–
A2
–
+
(5)
(1) Optional line choke
PA
PB
(2) Fault relay contacts; for remote signalling of speed controller status.
(3) Internal + 24 V. If an external + 24 V supply is used, connect the 0 V on the
external supply to the COM terminal, do not use the + 24 of the speed controller, Optional
braking
and connect the common of the LI inputs to the + 24 V of the external supply.
resistor
(4) R2 relay can be reassigned.
(5) VW3-A58701 braking module, if a braking resistor is used, for ratings ATV-
58iU09M2 and iU18M2 only.
Note :
- All the terminals are located at the bottom of the controller.
- Fit suppressors to all the specific circuits close to the controller or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting,
etc.
Code Description
Q3 GB2-CB05
Te 63