Manual For C&S Relay Settings
Manual For C&S Relay Settings
ZEN C- Series
PMD Division
CSEZEN-F 450-C2-H
Feeder Protection Relay
1.0 Introduction
CSEZEN series offers a multi functional comprehensive smart protection solution for Feeder, Generator,
Motor & Transformer segment.
CSEZEN family of protective relays are advance numerical relays that provide multi protection and
monitoring with reliable and fast protection solution in a single unit.
In this family of CSEZEN series, the CSEZEN-F is an advanced Feeder protection relay designed for
controlling, protecting and monitoring industrial installations, public distribution networks and substations.
CSEZEN-F also provides an automation solution of power control. It complies with IEC 60870-5-103, IEC
61850, Modbus protocol for high integration of protection & control. CSEZEN-F offers following features in a
compact & smart flush mounting enclosure.
3
CSEZEN-F 450-C2-H
Feeder Protection Relay
2.0 Application
CSEZEN-F relay will cover wide range of protection functions required for feeder segment. It can be used as
part of protection scheme for transformers and generator transformers. CSEZEN-F relays can also provide
back-up protection for HV and EHV transmission systems.
3.0 Hardware
4
* Model dependent
CSEZEN-F 450-C2-H
Feeder Protection Relay
5
CSEZEN-F 450-C2-H
Feeder Protection Relay
RECORDING FEATURES
27 59 79 86
PSL
50N/
67P 67N 50/51 59N 46BC 49 50BF 47
51N
Figure-1
6
CSEZEN-F 450-C2-H
Feeder Protection Relay
t_I>>
t_I>>>
0 I
I> I>> I>>>
Figure-2
Over current Element
13.5
Very Inverse t= ti [s]
(I / IS) - 1
80
Extremely Inverse t= ti [s]
(I / IS) 2 - 1
120
Long time Inverse t= ti [s]
(I / IS) - 1
0.14/0.061/0.028
Normal Inverse 3.0/1.3/0.6 t= ti [s]
(I / IS) 0.02 - 1
7
CSEZEN-F 450-C2-H
Feeder Protection Relay
Its main function is to apply a blocking signal to the over current elements to prevent their operation when the
current is flowing in a certain direction. In order to determine the direction of the current, the element uses
phase current values as operation magnitude and phase-to-phase voltage values as polarization
magnitude. This means that in order to polarize a phase, we use the phase-to-phase voltage of the other two
phases known as crossed polarization.
Feature : This setting allows enabling or disabling the corresponding directional element.
MTA : The MTA setting corresponds to the Torque angle, which is the rotation applied
To phase-to-phase crossed voltage.
Direction : This setting allows selecting the area for the directional element to operate either
forward or reverse.
Polarization Voltage Threshold : This is the minimum voltage considered for the direction calculation. Under
this setting, the element will be blocked or behave as non-directional depends on the below settings.
Behaviour below minimum polarization : This setting allows selecting either non directional or block
depending on the selection, when applied voltage is less than polarization voltage threshold.
In order to give directionality to an over current relay, it is necessary to provide it with a suitable reference or
polarizing signal. The reference generally used is the system voltage, as its angle remains relatively
constant under fault conditions. The phase fault elements of the directional relay are internally polarized by
the quadrature phase-phase voltages, as listed in the table below:-
A Phase IA VBC
B Phase IB VCA
C Phase IC VAB
8
CSEZEN-F 450-C2-H
Feeder Protection Relay
UAB
IA
UBC
IC IB
Figure-3
UCA
M TA
Iph
Uph-ph
Forward
tripping zone
Backward
tripping zone
The directional element analyze the relation between operating current and reference voltage to determine
the fault direction. This is related to the relay characteristics angle (range -900 to +900C) as selected by the
0 0
user. Typically a relay characteristics angle of 45 is chosen for transformer feeders and 30 for plain feeders.
0
The operate zone is effectively bounded +90 about the system characteristics angle for current levels
exceeding the set level.
9
CSEZEN-F 450-C2-H
Feeder Protection Relay
The derived earth over current element protection is used to cover application such as HTB/HTA
transformers. The derived earth current (Ie_d>) is the vector summation:
Ie_d = ( I L1 + I L2 + I L3)
The derived earth over current has two independent thresholds: Ie_d> and Ie_d>>.
Earth directional is a directional protection element used for monitoring the earth over current element.
The operation magnitude is the earth current measured directly from the corresponding input B13-B15/B14-
B16, while the polarization magnitude is the residual voltage U0. Polarization voltage is calculated from the
three phase voltages using algorithm U0=1/3[UL1+UL2+UL3].
The direction is evaluated using the earth current with the U0 as polarization voltage for the earth fault
directional protection. The angle determines the range in which the fault is considered forward and reverse.
M TA
Ie
U0
Forward
tripping zone
Backward
tripping zone
Figure-5
10
CSEZEN-F 450-C2-H
Feeder Protection Relay
CSEZEN relays incorporate a current based thermal replica, using load current to reproduce the heating
and cooling of the equipment to be protected. The element thermal overload protection can be set with both
alarm and trip stages.
The heating within any plant equipment, such as cables or transformers, is of resistive type
2 2
(I R x t), thus the quantity of heat generated is directly proportional to current squared (I ). The thermal time
characteristics used in the relay is based on current squared, integrated over time.
The CSEZEN relays automatically use the highest phase current as input information for the thermal model.
Thermal protection can be inhibited on start-up. The thermal time characteristic is given by following
formula:-
I2
- p2
Ib2 I2
Trip time (taus)=τIn
2
for p < ∩ p2 ≤ k2
I2 (Ib2)
Ib2 - k2
11
CSEZEN-F 450-C2-H
Feeder Protection Relay
In CSEZEN relay three modes are available for saving of thermal memory during power reset. These modes
are programmable.
M1: On Power Reset thermal memory becomes 0.
M2: On Power Reset thermal memory starts from the same value as at the time of Power Off.
M3: On Power Reset thermal memory subtracts for the time it is in Off state & starts from the
remaining value.
Figure-6
12
CSEZEN-F 450-C2-H
Feeder Protection Relay
Series faults will not induce an increase in phase current on the system and hence are not easily detectable.
However on a lightly loaded line, the negative sequence current resulting from a series fault condition may be
very close to or less than the full load steady state unbalance arising from CT errors, load unbalance etc. a
negative sequence protection element therefore would not operate at low load levels.
CSEZEN relays incorporate a protection element, which measures the ratio of negative to positive phase
sequence current (I2/I1). This protection element will be affected to a lesser extent than the measurement of
negative sequence current alone, since the ratio is approximately constant with variations in load current.
Hence a more sensitive setting may be achieved.
Typically this auto reclose (AR) sequence of Instantaneous Trip(s) and Reclose Delays (Dead times)
followed by Delayed Trip(s) provide the automatic optimum method of clearing all types of faults i.e. both
Transient and Permanent, as quickly as possible and helps in improving the up time of the network in service.
DI Inputs
AR Blocking - To block the auto re-closer through remote DI
CB Close DI - To get the circuit breaker status
CB Ready - To get the CB ready or to give the closing command
Configurable Outputs:
79 AR Close
79 Lockout
13
CSEZEN-F 450-C2-H
Feeder Protection Relay
AR - Blocked
Unit changes immediately to "AR-blocked" status when an external AR Blocking DI is applied or internal
EXIT is chosen for AR cycle in HMI. No Auto reclosing is possible in "AR-blocked" status.
Activating of AR
Prior to every AR it is possible to select which kind of tripping (I> or I>>, Ie>, I>>> etc.) will lead to automatic
reclosing. This can be separately fixed for each protection.
User programmable dead times are available for each protection trip operation.
The dead time is initiated when the trip output contact resets, the pickup is reset and the CB is open.
The CB close output relay is energized after the dead time has elapsed If CB ready input is present.
The dead time (dead time td1, dead time td2 dead time td3 dead time td4) starts when the feedback on 'CB
CLOSE DI' is not available.
If the number of the set shots is reached, the relay is locked for this time after the last reclosing attempt.
If the circuit breaker dose not trip again, the auto re-close cycle resets to original STATE-1 at the end of the
reclaim time.
After Successful re-closure the relays goes to the lock out state.
C either advances to the next AR cycle that is expected in next auto re-close state or if all the
programmed re-closer attempts have been accomplished, it locks out.
14
CSEZEN-F 450-C2-H
Feeder Protection Relay
Once a CB has reclosed and remained closed for a specified time period (the reclaim time), the AR
sequence is reinitialized and a successful close output issued. A single common reclaim time is used
(Reclaim Timer). when an auto reclose sequence does not result in a Starting Condition for Auto recloser
In any of these cases, Manual reset will be required to reinitiate the AR.
2 3 4 5 6 7 8
Pickup
Trip Command
End of
Starting of reclaim time reclaim time
CB Close Status
Reclaim Time
Dead Time
Reclaim Time
CB Ready
AR Cycle AR Cycle
Reclose Command
Figure-7
15
CSEZEN-F 450-C2-H
Feeder Protection Relay
Voltage Protection
CSEZEN relay are equipped with under voltage, over voltage, Positive phase sequence voltage, negative
phase sequence over voltage and zero phase sequence over voltage protections.
U0=1/3| (UL1+UL2+UL3)|
2
U1=1/3|(UL1+aUL2+a UL3)|
When positive phase sequence voltage goes below the programmed positive phase sequence threshold for
a programmed definite time the trip signal is given.
2
U2=1/3| (UL1+a UL2+aUL3)|
16
CSEZEN-F 450-C2-H
Feeder Protection Relay
17
CSEZEN-F 450-C2-H
Feeder Protection Relay
The CT supervision feature operates on detection of derived zero sequence current, in the absence of
corresponding derived zero sequence voltage that would normally accompany it.
A CTS alarm will occur when a CT fault (zero sequence current is above set value of I0> and below set value
of zero sequence voltage U0<) occur during more than set value of t_CTS time delay.
Some faults may be caused by conditions not removed from the feeder after a reclosing cycle or a manual
trip or due to earthed clamps left on after maintenance works. In these cases, it may be desirable to clear the
fault condition in fast time, rather than waiting for the Trip time delay associated with the I>> & I>>>
protection. t_SOTF time delay is used for I>> & I>>> protections in such conditions.
With the switch on to fault (SOTF) submenu, it is possible to shorten the time to trip For I>> & I>>> protection
if selected, when for example the relay has detected a fault that is still present on a feeder after energizing.
To avoid any undesirable tripping, the setting group change is only executed when none of the protection
functions are running (deactivated or inhibited).
18
CSEZEN-F 450-C2-H
Feeder Protection Relay
Time Synchronization
Inside CSEZen there is an internal time clock. Relay supports SNTP Protocol (ordering based). SNTP
(Simple network Time Protocol) have mechanisms within the protocol to synchronize the clock and keep it
accurate to certain accuracy. The protocol itself has the ability to send commands and re-synchronize the
clock so that each attached IED using its synchronization capability on the network is accurate within
resolution.. The relay makes the synchronization automatically using SNTP protocol. The internal clock of
the relay is synchronized to the UTC time of the NTP server.
Measurement
u 3 Phase Current, 3 Phase Star Voltage, 3Phase Delta Voltage, Bus Voltage, Bus
Frequency, 3 Phase Active Power,3 Phase Reactive Power, 3 Phase Apparent Energy,
Individual Power Factor, 3 Phase Power Factor, Forward Active Energy, Reverse Active
Energy, Forward reactive Energy, Reverse Reactive Energy, Energy Counters (1 Energy
Counter is equivalent to 6553.5 Gwh/GVarh) Total Energy Calculation (6553.5 x energy
counter + displayed energy) & Line Frequency.
u Earth current measurement
u Derived earth current measurement
u Positive phase sequence
u Trip counter
u Thermal memory
u AR cycles
u I1/I2 (Positive Phase Sequence current)
19
CSEZEN-F 450-C2-H
Feeder Protection Relay
CSEZEN-F records last 20 faults in its non volatile memory with its time stamp.
Each record has the following information:
Fault Format
IL1 : XX.XXA UL31 : XX.XXV
IL2 : XX.XXA U0 : XX.XXV
IL3 : XX.XXA U1 : XX.XXV
Ie : XX.XXA U2 : XX.XXV
Ie_d : XX.XXA Them_mem : XXXX%
Ul1 : XX.XXV Dir_Status : XXXX
UL2 : XX.XXV HR MIN : HH:MIN
UL3 : XX.XXV SEC Ms : Sec: mSec
UL12 : XX.XXV DATE : DD:MM:YY
F-TYPE : Type of fault
UL23 : XX.XXV
Figure-8
20
CSEZEN-F 450-C2-H
Feeder Protection Relay
The unit stores in non volatile memory the last 500 events with its time stamp. When the
available memory space is exhausted, the new event automatically overwrites the oldest
event, which can be retrieved from a PC.
The user can view event records via the front USB interface software.
Figure-9
21
CSEZEN-F 450-C2-H
Feeder Protection Relay
The CSEZEN-F relay has an oscillograph data recorder with the following characteristics:
u Oscilloscopic recording can trigger on Pickup or on trip or via DI i.e. change from
pre-fault to post-fault stage. It is programmable.
u Each record comprises the samples from max. 8 analog signals (depends upon the
different models) and the status of maximum 16 digital inputs and maximum 16
digital outputs. There will be 30 samples per cycle.
u Relay saves maximum 1200 cycles, and the number of cycles per record is
programmable which limits the maximum no. of records possible to store in the
relay (for example: if 40 cycles are selected, then there will be maximum
30 records of 40 cycles each).
u The pre-fault and post-fault cycles are programmable.
u Records are in the non volatile memory.
u The records are transferred to PC using USB interface. The data is graphically
displayed and can be taken on printer.
u Record 1 is always latest record. 2nd record is older than 1st...... and so on.
u Disturbance record is available in comtrade format as per IEC60255-24.
Figure-10
22
CSEZEN-F 450-C2-H
Feeder Protection Relay
Output Contacts
Max. No. of digital outputs : 16 (DO1, DO2 ......DO16)
Type of outputs : Relay
Programmable (DO Assignment) : Yes (Max. 15 DO are programmable and 1 is fixed for self
supervision function
Relay reset type : Programmable (Auto/Manual)
Input Contacts
Max. No of digital inputs : 16 (DI1, DI2...... DI 16)
Type of inputs : AC/DC Voltage
Programmable (DI Assignment) : Yes
Figure-11
23
CSEZEN-F 450-C2-H
Feeder Protection Relay
In order to change any setting first press enter then only (t / u) key will act as
decrement/increment else these key will function as scroll in backward/forward direction.
CSEZEN- F450
ZEN C- Series
F1 FUNCTION
ENTER
F2 CB OPEN
F3 CB CLOSE
COMM
Figure-12
24
CSEZEN-F 450-C2-H
Feeder Protection Relay
Key Description
is used as intelligent key to see the details of the fault pickup / digital input
/ output status & last fault details / LED Status.
25
CSEZEN-F 450-C2-H
Feeder Protection Relay
LED Description
In CSEZEN Relay Ten LEDs are given for pickup or tripping on faults & events in any phase.
3 LEDs are fix
1) PICKUP/TRIP Relay is in Pickup / Trip mode
2) BLOCK Some protection function is blocked
3) OUT OF SERVICE Relay is in out of service mode (Protection on hold)
10 LEDs are programmable via front end software CSE Designer Suite - M12. For these 10
LEDs protection function naming sticker is needed to be inserted.
USB Description
CSE Designer Suite - M12
USB port is available as HOST. PC/Laptop can be interfaced via USB port for connecting with
CSE Designer Suite - M12 Front End Software.
Programmable scheme logic is configured using the front end interface CSE Designer suite-
M12. This interface uses Boolean equations. Flexible logic allows user to create logic diagram to
be assigned digital output.
The designed logic is event driven to ensure that protection is not delayed.
The following figure describes the use of protection schemes using the over current pickup &
under voltage pickup from downstream relays to block operation of upstream relays using a
digital output.
Figure-13
26
CSEZEN-F 450-C2-H
Feeder Protection Relay
(Table-1)
Trip circuit supervision TCS Deft time 0.03sec 2.00sec 0.01sec Disable
(Table-2)
Earth Fault Protection Setting (These setting will not be applicable if sensitive earth fault protection is available)
Parameters Display Setting Range Step Default
Min Max Size Setting
(Table-3)
27
CSEZEN-F 450-C2-H
Feeder Protection Relay
(Table-4)
(Table-5)
Earth Directional Setting (67N) (These setting will not be applicable if sensitive earth fault protection is available)
Parameters Display Setting Range Step Default
Min Max Size Setting
(Table-6)
28
CSEZEN-F 450-C2-H
Feeder Protection Relay
Neutral voltage pickup setting U0> Pickup 2 %Un 100 %Un 1%Un Disable
Neutral voltage characteristic U0> Characteristics DEFT IDMT - DEFT
Neutral voltage TMS setting U0> TD Multiplier 0.05 2.00 0.01 0.05
Neutral voltage definite time U0> Deft Time 00.03sec 20.00sec 00.01sec 00.05sec
Positive sequence voltage pickup setting U1< Pickup 10 %Un 100 %Un 1 %Un Disable
Positive sequence voltage definite time U1< Deft Time 00.03sec 10.00sec 00.01sec 00.10sec
Negative sequence voltage pickup setting U2> Pickup 10 %Un 100 %Un 1 %Un Disable
Negative sequence voltage definite time U2> Deft Time 00.03sec 10.00sec 00.01sec 00.10sec
(Table-8)
Circuit Breaker Failure Protection Setting (50BF)
Parameters Display Setting Range Step Default
Min Max Size Setting
Circuit breaker failure protection CBFP Deft time 0.03sec 2.00sec 0.01sec Disable
time delay
(Table-9)
(Table-10)
Cold Load Protection Setting (62 CLD)
(Table-12)
(Table-13)
(Table-14)
30
CSEZEN-F 450-C2-H
Feeder Protection Relay
DO Assignment Setting
31
CSEZEN-F 450-C2-H
Feeder Protection Relay
DI Assignment Setting
(Table-16)
32
CSEZEN-F 450-C2-H
Feeder Protection Relay
33
CSEZEN-F 450-C2-H
Feeder Protection Relay
(Table-18)
34
CSEZEN-F 450-C2-H
Feeder Protection Relay
(Table-19)
Common Setting
These are the settings common for all the protections:
(Table-20)
(Table-21)
35
CSEZEN-F 450-C2-H
Feeder Protection Relay
(Table-22)
Communication
Default
RS-485 Communication Setting
Baud rate selection (programmable) 9600 / 19200 / 38400 / 57600 bps 9600 bps
Parity selection (programmable) EVEN / ODD / NONE NONE
Stop bit 1 Bit 1 Bit
Data bit 8 Bit data 8 Bit data
Remote address (programmable) 247/254 1
Cable required for Interface Two wire twisted shielded cable ------
*
For MODBUS : Remote Address Setting Range is 1 - 247 (Table-24)
& For IEC 103 : Remote Address Setting Range is 1 - 254
USB Communication
(Table-25)
36
CSEZEN-F 450-C2-H
Feeder Protection Relay
Measuring Input
(Table-26)
Trip time accuracy for protections except NPS +30mSec OR +5% (whichever is higher)
Trip time accuracy for NPS +60mSec OR +7.5% (whichever is higher)
(Table-27)
Trip time accuracy for voltage protections Inaccuracy in Trip Timing in reference to +2%
error in measured voltage OR +30mSec
(Table-28)
Measurement Accuracy
Parameters Range Frequency Range Accuracy
(Table-29)
37
CSEZEN-F 450-C2-H
Feeder Protection Relay
(Table-30)
Auxiliary Supply
(Table-31)
Common Data
Dropout ratio > 96%
Relay reset time 30 ms
Minimum operating time 30 ms
Transient overreach at
instantaneous operation <5 %
(Table-32)
Date & Time Setting
(Table-33)
38
CSEZEN-F 450-C2-H
Feeder Protection Relay
16) Standards
Type Test
F1 Functional Tests Internal Design Performance in line with Specification & Standards
Pickup / Drop down / Power consumption in Current /
Specifications & Voltage / Aux. Supply / Trip timing accuracy: OC /
IEC60255-151:2009 NPS / Thermal / Zero Sequence
Climatic Test
Enclosure
Mechanical Test
Relay Operational
39
CSEZEN-F 450-C2-H
Feeder Protection Relay
Electrical Test
E1 Insulation Resistance IEC 60255-27:2013 500V DC, 5 sec between all terminals & case
>100MΩ earth, between terminals of independent circuits
including contact circuits and across open contacts
E2 DC & AC Supply Voltage IEC 60255-26 Voltage range, upper & lower limit continuous
(Relay operational) withstand, ramp up & down over 1 minute
E3 Voltage Dips, Short IEC 60255-26 3 Dips & 3 Interruptions at 10 sec intervals
Interruptions & Voltage of duration between 10mS and 500mS at zero
variations immunity crossings & at other points on wave
(Relay operational) Variation: 100% to 40% over 2s, hold for 1s,
return to 100% over 2s
E5 Dielectric Test
(Relay de-energised) IEC 60255-27:2013 2.0 KV @ 1min All circuit to Earth / Between IP & OP
No breakdown or
flash over
Test voltage 45~65 Hz
sinusoidal
or with DC voltage
at 1.4x the stated
AC values
E6 High Voltage Impulse IEC 60255-27:2013 5 kV peak 1.2/50uS, 0.5 J-3 positive,
(Relay de-energised) 3 negative between all terminals to case
earth between independent circuits
40
CSEZEN-F 450-C2-H
Feeder Protection Relay
Electro-magnetic Compatibility
R1 Electrical fast Transient/Burst IEC 60255-26 : 2013 Class IV- +4.0 kV All Circuits.
(Relay operational) IEC 61000-4-4 Pulse 5 / 50nsec / Duration 15msec /
Period:300msec/Pulse Freq: 5KHz / 2KV at I/O
R6 Surge Immunity capacitively Latest: IEC 60255-26:2013 Short circuit combination wave generator
coupled 1.2 uS/50 uS open circuit
(Relay operational) repetition rate 1 per minute
Power supply, CT & VT circuits –
4kV common mode 2 Ohm source
2kV differential mode 12 Ohm source
41
CSEZEN-F 450-C2-H
Feeder Protection Relay
Rear Comm. Port Pin Type lug / 1.5 mm2 / 2.5 mm2 control cable
Figure-14
Figure-15
42
CSEZEN-F 450-C2-H
Feeder Protection Relay
(10 DI + 2 DO)
Earth
B27 B28
A1 A2
A27 A28
+ - + -
B17 RJ 45 *
RS-485
VL1
B18
LINE VT ANALOG INPUT
Power Supply
B19 NO
A3
VL2 D0 1
B20
DIGITAL OUTPUT
COM
A4
NC
A5
B21
VL3 NO
A6
B22
COM
D0 2 A7
NC
A8
B1
1A IL1
B2
B5
CT-1A ANALOG INPUT
1A
IL2
B6 A9
DI 1
A10
B9
A11
1A DI 2
IL3 A12
B10
A13
DI 3
A14
B13
1A
A15
IN DI 4
B14 A16
A17
DIGITAL INPUT
DI 5 A18
B3
5A A19
IL1 DI 6
B4 A20
A21
B7 DI 7
A22
CT-5A ANALOG INPUT
5A
IL2
B8 A23
DI 8
B11 A24
DI 9
5A
IL3
B12 A25
DI 10
43
CSEZEN-F 450-C2-H
Feeder Protection Relay
(10 DI + 5 DO)
Earth
B27 B28
A1 A2
A27 A28
+ - + -
B17 RJ 45 *
RS-485
VL1
B18
LINE VT ANALOG INPUT
Power Supply NO
A3
D0 1
B19 COM
A4
NC
VL2 A5
B20
NO
A6
B21 D0 2
DIGITAL OUTPUT
COM
A7
VL3
B22
NO
A8
D0 3 COM
A9
NO
B1 A10
1A IL1
D0 4 COM
A11
B2
B5 NO
A12
CT-1A ANALOG INPUT
1A D0 5 COM
IL2 A13
B6
B9 C1
1A DI 1
IL3 C2
B10
C3
DI 2
C4
B13
1A C5
IN DI 3
B14 C6
C7
DI 4
C8
B3
DIGITAL INPUT
5A C9
IL1 DI 5 C10
B4
C11
B7 DI 6
C12
CT-5A ANALOG INPUT
5A
IL2
B8 C13
DI 7
C14
B11 C15
5A DI 8
IL3
B12 C16
DI 9
B15 C17
5A DI 10
IN
B16 C18 Common
44
CSEZEN-F 450-C2-H
Feeder Protection Relay
(10 DI + 10 DO)
Earth
19.0 Connection Diagram B27 B28
A1 A2
A27 A28
+ - + - D0 1
NO
A3
B17 RJ 45 * COM
A4
RS-485
VL1 NC
A5
B18
LINE VT ANALOG INPUT
NO
Power Supply A6
D0 2 COM
B19 A7
NO
VL2 A8
B20 D0 3 COM
A9
NO
A10
B21 D0 4 COM
DIGITAL OUTPUT
A11
VL3
B22 NO
A12
D0 5 COM
A13
NO
A14
D0 6 COM
B1 A15
1A IL1
NO
A16
B2 D0 7 COM
A17
B5 NO
CT-1A ANALOG INPUT
A18
1A
IL2 D0 8 COM
B6 A19
NO
A20
B9 D0 9 COM
A21
1A
IL3 NO
A22
B10 D0 10 COM
A23
B13
1A C1
IN DI 1
B14 C2
C3
DI 2
C4
C5
DI 3
C6
C7
B3 DI 4
C8
5A IL1
DIGITAL INPUT
B4 C9
DI 5 C10
B7
CT-5A ANALOG INPUT
5A C11
IL2 DI 6
B8 C12
C13
DI 7
B11 C14
5A
IL3 C15
B12 DI 8
C16
DI 9
B15
5A
IN C17
B16 DI 10
C18 Common
45
* Model dependent
CSEZEN-F 450-C2-H
Feeder Protection Relay
(16 DI + 16 DO)
Earth
20.0 Connection Diagram B27 B28
A1 A2
A27 A28
+ - + -
A15 (Watch NO during
B17 RJ 45 * D0 1 healthy
RS-485 A16 Dog) condition
VL1
B18
Power Supply A14
B19 D0 2 A12
VL2
B20 LINE VT
ANALOG A11
INPUT D0 3
(DIGITAL OUTPUT)
A9
B21
VL3
B22 A8
D0 4
B1 D0 5 A7
1A IL1
B2
D0 6 A6
B5 A5 Common
1A
IL2 A4
B6
CT-1A- D0 7 A13
B9 ANALOG
INPUT A3
1A
IL3 D0 8
B10 A10
B13
C3
1A
IN C5
B14 D0 9
C4
C6
B3 D0 10 C8
*based on Ordering Information)
( A d d i t i o n a l 8 D O s
5A IL1 C7
B4
D0 11 C9
B7
5A
IL2
B8 D0 12 C10
CT-5A-
B11 ANALOG
INPUT D0 13 C12
5A
IL3
B12
D0 14 C13
B15 C11 Common
5A
IN
B16 C15
D0 15
C16
D0 16
(Additional 8 DIs *based on Ordering Information) DIGITAL INPUT C14 Common
DI 16 DI 15 DI 14 DI 13 DI 12 DI 11 DI 10 DI 9 DI 1 DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8
C22 Common
C17 Common
A26 Common
A17 Common
C26
C25
C24
C23
C21
C20
C19
C18
A25
A24
A23
A22
A21
A20
A19
A18
46
* Model dependent
CSEZEN-F 450-C2-H
Feeder Protection Relay
STAR CONNECTION
L1 L2 L3
52
B17
VL1
B18
B19
LINE VT
VL2 ANALOG
B20 INPUT
B21
VL3
B22
CSEZEN
L1 L2 L3
DELTA CONNECTION
52
B17
VL1
B18
B19
VT
VL2 ANALOG
B20 INPUT
B21
VL3
B22
CSEZEN
47
CSEZEN-F 450-C2-H
Feeder Protection Relay
CT Schemes
Holmgreen Residual CT’s Connection for 1A
L1
L2
L3
P1 S1 B1
1A IL1
B2
P2 S2
P1 S1 B5
1A IL2
B6
P2 S2
P1 S1 B9
1A IL3
B10
P2 S2
B13
1A IN
B14
48
CSEZEN-F 450-C2-H
Feeder Protection Relay
CT Schemes
Holmgreen Residual CT’s Connection for 5A
L1
L2
L3
P1 S1 B3
5A IL1
B4
P2 S2
P1 S1 B7
5A IL2
B8
P2 S2
P1 S1 B11
5A IL3
B12
P2 S2
B15
5A IN
B16
49
CSEZEN-F 450-C2-H
Feeder Protection Relay
Trip Circuit
(+) Target Indicator
(Hand Reset Type)
DI-1
A26
A25
D
DI-2 >1 1 t 0 0 t
A26
A24 0.4s 0.4s
52a 52b
CB Coil
(-)
50
CSEZEN-F 450-C2-H
Feeder Protection Relay
25.0 Dimensional Details All the dim are in mm (Gen. Tol + 1.0mm)
250.5
218
179.5
190
190.5
23.5
Side View
158
51
CSEZEN-F 450-C2-H
Feeder Protection Relay
C S E Z E N R e l a y
Panel cut out dimensions
220.0 (W) x 162.0 (H) mm
Hole dia = 6.0 mm
52
CSEZEN-F 450-C2-H
Feeder Protection Relay
53
CSEZEN-F 450-C2-H
Feeder Protection Relay
CT inputs 4
VT inputs 3
Opto inputs (Max) 16
Output contacts (Max) 16
Function keys / Hot keys l
Programming logic l
Protection
Three phase over current 50P/51P ü
Earth over current 50N/51N ü
3 Phase directional over current 67P ü
Earth fault directional over current 67N ü
Derived earth Fault 50N/51N ü
Phase under / over voltage (AND & OR mode) 27/59 ü
Thermal over load 49 ü
Output relay latching 86 ü
Auto-reclose 79 ü
Circuit breaker failure detection 50BF ü
Broken conductor detection I2/I1 46BC ü
Blocking logic ü
Test of output relays (Maintenance) ü
CB control local / remote ü
Circuit breaker maintenance and trip circuit supervision 74TC ü
Cold load pick up 62CLD ü
Selective relay scheme logic ü
Harmonic blocking 50H ü
Switch on to fault (SOTF) ü
VT supervision (VTS) ü
CT supervision (CTS) ü
Phase Selection (ABC, ACB) ü
Communication
Front (USB) ü
RS-485 Modbus ü
RS-485 IEC 60870-5-103 l
RJ-45 IEC 61850 l
SNTP-Time Synch RJ-45 l
54
CSEZEN-F 450-C2-H
Feeder Protection Relay
CSEZEN - F - 450 - x - x - N - 0 - x - x - x - E - H - C2
Model 450
VOLTAGE INPUT
110V 1
400V 4
EARTH FAULT
Sensitive S
Non Sensitive N
DIGITAL I O CARD
8 DI / DO 0
16 DI / DO 1
10 DI / 2 DO 2
10 DI / 10 DO 3
10 DI / 5 DO 4
AUXILIARY SUPPLY
18V-150V DC L
80V-280V AC / 90V-300V DC H
COMMUNICATION
MODBUS on RS-485 A
IEC 60870-5-103 on RS-485 B
IEC 61850 on RJ-45 C
TIME SYNCHRONIZATION
None 0
SNTP on RJ-45 S
55
CSEZEN-F 450-C2-H
Feeder Protection Relay
NOTE
The content in this document are not binding and is for general information.
C&S reserves the right to change the design, content or specification contained
in this catalog without prior notice.
CSEZ EN- E Ca t a l o g u e
56
CSEZEN-F 450-C2-H
Feeder Protection Relay
Revision History
57