Ats400 Brochure en
Ats400 Brochure en
Ats400 Brochure en
ATS4BC0400
MCCB Type Automatic Transfer Switch
Rated Voltage 100 to 600 Vac Rated Current 400 Amp
*Select ATS-245/ATS-385/ATS-465 based on the system voltage.
Features
Extraordinary modularized ATS design *1
Superior serviceability & simple maintenance
ATS-245/ATS-385/ATS-465 Intelligent Controller: Voltage monitoring &
protection with built-in 1 to 4 weeks exerciser timer
PTM-100/PTM-400 Voltage Transformer Module: Change voltage
easily by using pin terminal
BTS: Transfer switch built with high short circuit breaking capacity &
OCPD *2
All modules connected by harness with high voltage withstand plug-in
connectors sets
Complies with IEC 60947-6-1 requirements *3
ATS Rated Operating Current & AC Rated Breaking Capacity
AC Rated Breaking Capacity (KA)
Rated Current (A)
Type Poles IEC 60947-2 Icu / Ics Weight (Kg)
Ambient Temperature 40 °C
240V 380V 415V 440V 500V
ATS3BC0400 3P 400 50 / 25 30 / 15 30 / 15 25 / 13 20 / 10 49
ATS4BC0400 4P 400 50 / 25 30 / 15 30 / 15 25 / 13 20 / 10 57
*All dimensions and weights shown are approximate for reference only. For special high breaking capacity or other branded MCCB, please contact us.
Dimensions
W2 Enclosure P/N. CA-400 CA-4P400
W1 D
H1 800 mm 850 mm
H2 860 mm 910 mm
W1 550 mm 650 mm
W2 600 mm 700 mm
D 340 mm 340 mm
Thickness 1.6 mm 1.6 mm
Fixed Type Wall Mountable Wall Mountable
H1
H2
*1 KUTAI modularized ATS is combined with enclosure, ATS Intelligent Controller, PTM modules & BTS. For more details, please check the
brochure & manual of each item.
*2 OCPD: Over current protection device.
*3 IEC60947-6-1 Requirements:
(1) IEC60947-6-1 Class CB: ATS provided with over current releases and the main contacts of which are capable of making and are intended for
breaking short circuit currents.
(2) IEC60947-6-1 Utilization Category AC-33A:
Frequent operations.
Motor loads or mixed loads including motors, resistive loads and up to 30% incandescent lamp.