2023 NEC Code Changes
2023 NEC Code Changes
Code changes
based on the
2023 NEC
Save space
Stay safe
FC2 QSCP
Instantly calculate available fault current Selective Coordination just got a lot easier.
in the palm of your hand. The Eaton The Quik-Spec Coordination Panelboard
Bussmann SeriesTM FC2 mobile app is (QSCP) eliminates the need for expensive
easy to use, quick to operate, and FREE of studies and plotting time-current curves.
charge. Scan above to try it out. Scan above to learn more.
Bussmann SeriesTM products protect what With up to 69% space savings, the
matters most. Our PPE line includes arc Bussmann Series™ CCP with CUBEFuse™
flash suits, protective gloves, insulated tool simplifies selective coordination and allows
kits, and even lock out tag out devices. Scan for isolation of individual branch circuit
above to learn more. loads. Scan above to learn more.
Table of contents
Introduction Surge protection
National Electrical Code® (NEC®) style manual ............................ 4 215.18 Surge protection for feeders .................................... 22
Definitions ............................................................................................. 4 225.42 Surge protection for outside feeders ..................... 23
Medium voltage .................................................................................. 4 230.67 Surge protection for services ................................... 24
Short-circuit current & interrupting ratings ................................. 4 242.9 Surge protection indication ........................................ 25
Reconditioned equipment ................................................................ 5 409.70 Surge for ICP with safety circuits ............................. 26
Selective coordination ....................................................................... 6 670.6 Surge protection for industrial machinery with
safety circuits .............................................................................. 27
Definitions
Overcurrent protection ....................................................................... 8 Barriers in services and feeders
Safety circuit ........................................................................................... 9
215.15 Barriers for feeders ........................................................ 28
Short circuit ............................................................................................ 10
230.62(C) Revised wording for barriers .................................. 29
Interrupting rating ................................................................................ 11
240.16 Interrupting rating ................................................................. 12 110.3(B) Addition of QR code for instructions ...................... 30
110.16(B) Arc-flash hazard warning changes ................................ 17 440.11 A/C disconnecting means ............................................. 41
620.51(D)(1) Fault current marking moved to disconnecting 700.5(D) Redundant transfer switches ................................... 44
means instead of controller ............................................................... 20
670.3(A) Nameplate outside of the enclosure ............................... 21 2023 NEC Code Changes video series .............. Back cover
Definitions
locations.
and interrupting ratings. In past NEC editions, significant revisions Available fault current
have been made to improve terminology and add more prescriptive
requirements for establishing processes to verify overcurrent protective
Another significant change in the 2020 NEC was the addition of a
device interrupting ratings and equipment short-circuit current ratings
definition for “available fault current,” also prompted by a public input
are adequate at the point of installation.
by the Fault Current Working Group. The intent was for “available fault
current” to be used throughout the NEC rather than such terms as
For the 2020 edition, the Fault Current Working Group was formed to
“available short-circuit current”, “maximum available short-circuit current”,
support the Correlating Committee’s Usability Task Group and analyzed
and “maximum available fault current”. As a result, there are many 2020
the usage of “fault current”, “short-circuit current”, “available short-circuit
NEC changes incorporating this newly defined term.
current”, “available fault current”, “maximum available short-circuit
current”, “maximum available fault current” and other terms. During the
There are many requirements in the NEC in which the available fault
2020 NEC process, this Working Group submitted many public inputs
current must be determined to ensure circuit breakers and fuses have
(PIs) throughout the NEC to achieve consistency of terms as an objective.
sufficient interrupting ratings (110.9), devices and assemblies have
Individual Technical Committees considered these PIs.
sufficient short-circuit current ratings (110.10 plus many other sections),
overcurrent protective devices provide selective coordination (700.32
Though there were not as many significant changes in the 2023 NEC,
and many more sections). Now the terms available fault current, short-
there were still some key revisions that help to further clarify the
circuit current rating, interrupting rating and selective coordination are
differences between some terms and to use the newer nomenclature. In
all defined in the NEC. This should help in the proper interpretation and
the 2023 NEC there is now a definition for short circuit, which is a term
compliance of the many requirements for these items in the NEC.
used in several other related definitions. Also, Article 110.9 has been
revised to include the term “available fault current” to add clarity and
match the defined term that was added in the 2020 edition.
Interrupting rating
Fault Current The available fault current must be determined because each circuit
breaker or fuse is required to have an interrupting rating that is adequate
for the fault current at the point of application. The previous wording
Overcurrent and overload have been defined in the NEC for some time.
stated that the interrupting rating must be “at least equal to the current
However, the definition for “fault current” was only added in 2020. Prior
that is available at the line terminals of the equipment.” This has been
to the 2020 NEC, fault current and short-circuit current were used
revised for clarity to now state, “at least equal to the available fault
interchangeably but neither were defined. With the 2020 NEC changes
current at the line terminals of the equipment.” The requirement hasn’t
the proper term is fault current.
changed but adds clarity and better aligns with the defined terminology
that was updated in the 2020 NEC.
Fault current flows when a short-circuit condition occurs on an energized
circuit. A practical understanding when a short-circuit condition occurs is
Failure to install overcurrent protective devices having an interrupting
that fault current leaves the normal circuit conduction path. In contrast,
rating adequate for the available fault current can result in catastrophic,
during an overload condition, the current stays within the normal
violent explosions which are a serious fire and shock hazard. In addition,
conduction path.
if a person is near equipment in which an overcurrent protective device
fails while trying to interrupt a fault current beyond its interrupting rating,
the person may be subject to arc flash and arc blast hazards including
high speed projectiles from the exploding equipment.
Fault current can cause
tremendous damage in a
brief time
Reconditioned equipment
For many years the NEC had not directly addressed the reconditioning of
electrical equipment. The electrical equipment installed must perform
its duties safely, and to do that the quality of that equipment is critical.
In recent code cycles the NEC has made numerous revisions regarding
Time
reconditioned and refurbished equipment with the intent to increase
Normal Current safety.
NEC 2017 made the first significant revision by adding a new second
level sub-division (2) titled “Reconditioned Equipment” to Section
110.21(A), “Equipment Markings”. This new section provided specific
marking requirements for reconditioned equipment. It stated that
Short-circuit reconditioned equipment must be marked with the name, trademark,
or other descriptive marking by which the organization responsible for
occurs at this reconditioning the electrical equipment can be identified, along with
time the date of reconditioning. This 2017 NEC section also requires that
reconditioned equipment be identified as “reconditioned” and there is
a brief mention of the listing requirements for this equipment. These
marking requirements add transparency for all involved.
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 5
Introduction
NEC 2017 took the initial step forward on the topic of reconditioned 17. Snap switches of any type – 404.16(B)
equipment, but as usual changes of this magnitude generated industry 18. Molded-case switches – 404.16(D)
dialog that drove more public inputs and comments for the development
of NEC 2020. 19. Receptacles, attachment plugs, cord connectors, and flanged
surface devices – 406.2
The NEMA policy on refurbished equipment was a key reference for each 20. Panel boards – 408.2(A)
of the NEC code making panels as they deliberated on their changes for
21. Luminaires, lamp holders, ballasts, LED drivers, lamps, and
NEC 2020. A total of 18 sections of the NEC spanning 15 Articles were
retrofit kits – 410.2
added and/or modified to include new requirements. These sections can
be separated into three key areas: 22. Listed low-voltage lighting systems or a lighting system
assembled from listed parts - 411.2
1. General requirements 23. Resistors – 470.2(A)
2. That equipment which is NOT permitted to be reconditioned 24. Equipment over 1000 volts ac, 1500 volts dc within the scope of
3. That equipment which IS permitted to be reconditioned Article 495 (except as modified) – 495.2
25. Fire pump controllers and transfer switches - 695.2
The changes to reconditioned equipment requirements continued and
in the NEC 2023 there is a new section 110.20 addressing reconditioned 26. Transfer switches – 700.2, 701.2, 702.2, 708.2
equipment. The new section permits reconditioning of electrical
equipment except where specifically prohibited elsewhere in the Code
and has requirements addressing replacement parts and listing and Permitted to be reconditioned
labeling of reconditioned equipment. The marking requirements in
110.21(A)(2) were also revised and most of the requirements regarding When there is no code requirement that prohibits reconditioning,
reconditioning have been moved to section xxx.2 of the Article if reconditioning is permitted. In some areas equipment was identified
reconditioning is addressed in that Article. as being able to be reconditioned and a little more information was
provided. The following sections have language permitting reconditioning:
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
6 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Introduction
The 2023 NEC also has a significant addition in Article 240. The newly
created section 240.11 states:
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 7
Definitions
Overcurrent Protective Device, Branch-Circuit. (Branch-Circuit
Overcurrent Protective Device
Part I. General
Article 100 Definitions
Chapter 1 General
Revised text
Overcurrent Protective
Device, Branch-
Circuit. (Branch-Circuit
Overcurrent Protective
Device)
Significance of Change
The second sentence was removed because it contained a requirement. Per the NEC Style manual 2.2.2.2 definitions are not allowed to contain
requirements or recommendations. The requirement was moved to Article 240 in a newly created Section 240.16.
Change Summary
• Remove minimum interrupting rating from the definition
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
8 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Definitions
Safety Circuit
Part I. General
Article 100 Definitions
Chapter 1 General
Added text
Safety Circuit.
Informational Note: See NFPA 79-2021, Electrical Standard for Industrial Machinery. Safety-related control system and safety interlock circuit are
common terms that can be used to refer to the safety circuit in other standards. The safety circuit can include hard-wired, communication, and
software-related components.
Significance of Change
Added definition for safety circuits taken from NFPA 79 Electrical Standard for Industrial Machinery. Safety circuits are typically used in situations
where there is a risk of injury from electrical or mechanical energy. They are designed to detect and respond to hazardous conditions and to take
appropriate action to prevent harm such as stopping the mechanical motions of a machine if a worker gets too close to the moving parts. The term
safety circuits is used in section 409.70 and 670.6 for industrial control panels and industrial machinery which require surge protective devices be
installed when safety circuits are included.
Change Summary
• Added definition for safety circuits
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 9
Definitions
Short Circuit
Part I. General
Article 100 Definitions
Chapter 1 General
Short Circuit: Abnormal condition where current flows outside the normal path. The
resulting fault current could be many times the normal current due to decrease in resistance.
Significance of Change
The phrase short circuit is used throughout the NEC and is included in other definitions like fault current, available fault current and overload; however
it was not defined. The new definition was added to improve clarity and to recognize that a short circuit can occur between two points, such as a line-
to-line or line-to-ground short circuit, or more than two points, such as a three-phase, line-to-line-to-line short circuit.
Change Summary
• Add new definition for short circuit
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
10 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Definitions
110.9 Interrupting Rating
Part I. General
Article 110 General Requirements for Electrical
Installations
Chapter 1 General
Current
• Article 100 Definitions,
Available Fault Current
• Article 100 Definitions,
Interrupting Rating
• Article 240.16
Significance of Change
In the 2020 NEC a new definition of available fault current was added. The new language in 110.9 provides clarity that the interrupting rating needs to
be at least equal to the available fault current which is defined as the maximum amount of current that can be delivered to equipment during a short
circuit condition. The interrupting rating should not be confused with the equipment short-circuit current ratings which may be different.
Change Summary
• Wording was revised to clarify that the interrupting rating must be compared to the “available fault current” which is a defined term and used
consistently throughout the NEC.
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 11
Interrupting Rating
240.16 Interrupting Ratings
Part I. General
Article 240 Overcurrent Protection
Chapter 2 Wiring and Protection
Added text
240.16 Interrupting
Ratings.
Branch-circuit overcurrent
protective devices shall have an
interrupting rating no less than
5000 amperes.
Significance of Change
In previous editions of the Code the branch-circuit overcurrent protective device had a minimum interrupting rating of 5000 per the definition.
However, definitions are not allowed to have requirements per the NEC Style Manual, so the definition was revised in 2023 to remove the reference
to a minimum interrupting rating. Section 240.16 was added to include the 5000 A minimum interrupting rating.
Change Summary
• The requirement for a minimum interrupting rating of 5000 amperes was moved from the definition of branch-circuit overcurrent protective
device to a new section, 240.16
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
12 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Selective Coordination
240.11 Selective Coordination
Part I. General
Article 240 Overcurrent Protection
Chapter 2 Wiring and Protection
Added text
240.11 Selective
Coordination.
OCPD 5 is a feeder that is required to be selectively coordinated with the service OCPD 1
Related NEC Sections
• Article 100 Definitions,
Coordination, Selective
• 620.62
• 645.27
• 695.3(C)(3)
• 700.32
• 701.32
• 708.54
Because a feeder OCPD 5 is required to be selectively coordinated with the service OCPD 1, now all feeder
OCPDs 2, 3 & 4 are required to be selectively coordinated with the service OCPD 1.
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 13
Selective Coordination
240.11 Selective Coordination
Part I. General
Article 240 Overcurrent Protection
Chapter 2 Wiring and Protection
Significance of Change
There are selective coordination requirements in several Articles of the
Code typically involving systems that impact life safety. Those include:
Change Summary
• All feeder OCPDs fed directly from the service OCPD must now
selectively coordinate with the service OCPD if any feeder OCPD
in the system is required to selectively coordinate with the service
OCPD by other requirements in the Code, eg. emergency systems,
legally required standby systems and systems with multiple
elevators fed by the same source. It is part of the design features of
emergency systems and the reliability to be selectively coordinated
to avoid the inadvertent transfer to the emergency source simply
because an upstream overcurrent protective device tripped. The
requirement to have these selectively coordinated will prevent the
Informational Note: Figure 700.32 Emergency System selective coordination. unnecessary tripping of the OCPD on the normal side.
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
14 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Selective Coordination
700.32 Selective Coordination (Same as 701.32 and 708.54)
Part VI. Overcurrent Protection
Article 700 Emergency Systems
Chapter 7 Special Conditions
Revised text
700.32 Selective Coordination for services and
feeders
(A) General.
(B) Replacements.
(C) Modifications.
Revised text
701.10 Wiring Legally
Required Standby Systems.
(A) General.
(B) Wiring.
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
16 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Equipment Marking and Labeling
110.16(B) Service Equipment and Feeder Supplied Equipment
110.16 Arc-Flash Hazard Warning
Part I. General
Article 110 General Requirements for Electrical Installations
Chapter 1 General
Revised text
110.16 Arc-Flash Hazard Warning.
(A) General.
Electrical equipment, such as switchboards, switchgear,
enclosed panelboards, industrial control panels, meter socket
enclosures, and motor control centers, that is in other than
dwelling units, and is likely to require examination, adjustment,
servicing, or maintenance while energized, shall be field or
factory marked to warn qualified persons of potential electric
arc flash hazards. The marking shall meet the requirements
in 110.21(B) and shall be located so as to be clearly visible to
qualified persons before examination, adjustment, servicing, or
maintenance of the equipment.
NFPA 70®, National Electrical Code®, and NEC® are registered trademarks of the National Fire Protection
Association, Quincy, MA.
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 17
Equipment Marking and Labeling
110.21(A)(2) Reconditioned Equipment
110.21(A) Equipment Markings
Part I. General
Article 110 General Requirements for Electrical Installations
Chapter 1 General
Significance of Change
Revised text
The modifications clarify the marking requirements of reconditioned equipment. These changes
110.21(A)(2) Reconditioned involve specifying the organization responsible for performing the reconditioning, identifying
the equipment as reconditioned and clarifying the procedures for removing the original listing
Equipment. mark without removing the nameplate.
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
18 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Equipment Marking and Labeling
409.110 Marking
Part III. Construction Specifications
Article 409 Industrial Control Panels
Chapter 4 Equipment for General Use
Significance of Change
Revised text
Previous editions of the Code required markings to be “plainly visible after
409.110 Marking. installation,” but there was confusion as to whether markings located inside the
enclosure met this requirement, or if the markings had to be on the outside of
the enclosure. The revised wording clarifies that the voltage, number of phases,
An industrial control panel shall be marked with the frequency, and full load current, as well as markings required for multiple
following information have permanent markings disconnecting means must be located on the outside of the enclosure. All other
that is are visible after installation. The markings in markings can be either inside or outside of the enclosure. Users should strongly
409.110(2) and (3) shall be attached to the outside consider marking the short-circuit current rating (SCCR) on the outside of the panel
of the enclosure. The markings in 409.110(1), (4), (5), for ease of verification and inspection for compliance with 409.22 even though it is
(6), and (7) shall be attached to either the inside or allowable to mark the SCCR on the inside.
outside of the enclosure. The following markings shall
be included: It is important to note that this differs from the requirements in Article 670 for
Industrial Machinery which requires additional information like maximum ampere
1. Manufacturer’s name, trademark, or other rating of the short-circuit and ground-fault protective device, ampere rating of
descriptive marking by which the organization largest motor, from the motor nameplate, or load, SCCR and electrical diagram
responsible for the product can be identified. numbers or index to be marked “outside of the control equipment enclosure.”
2. Supply voltage, number of phases, frequency,
and full-load current for each incoming supply
circuit. Change Summary
3. Industrial Where the industrial control panels
panel is supplied by more than one electrical • The voltage and the marking to indicate more than one disconnecting means
source and where more than one disconnecting shall be visible on the outside of the industrial control panel
means is required to disconnect all circuits
• The manufacturers name, SCCR, suitability for use as service equipment,
50-volts or more within the control panel, shall
wiring diagram and enclosure type can be marked inside or outside of the
be marked to indicate that more than one
enclosure.
disconnecting means is required to de-energize
the equipment. The location of the means
necessary to disconnect all circuits 50-volts or
more shall be documented and available.
4. Short-circuit current rating of the industrial
control panel based on one of the following:
a. Short-circuit current rating of a listed and
labeled assembly
b. Short-circuit current rating established
utilizing an approved method
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 19
Equipment Marking and Labeling
620.51(D)(2) Available Fault Current Field Marking
620.51(D) Identification and Signs., 620.51 Disconnecting Means
Part VI. Disconnecting Means and Control
Article 620 Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and Stairway Chairlifts
Chapter 6 Special Equipment
Revised text
620.51(D)
(21) Available Fault Current
Field Marking.
More Resources
Calculating available fault current
FC2 Available Fault Current Calculator (no cost): available from the Apple App Store, Google Play Store, or
on-line at https://faultcurrentcalculator.bussmann.com/web/index.html
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
20 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Equipment Marking and Labeling
670.3(A) Permanent Nameplate
670.3 Machine Nameplate Data
Article 670 Industrial Machinery
Chapter 6 Special Equipment
Significance of Change
Revised text
The requirements in 670.3(A) were revised to clarify the location of the machine
670.3(A) Permanent Nameplate. nameplate and align with the requirement for nameplate marking per NFPA 79 16.4.1.
The term “plainly visible” introduced confusion as to whether the nameplate was
permitted to be inside the enclosure, or if it had to be outside of the enclosure. This
change removes ambiguity by stating that the nameplate must be on the outside of the
A permanent nameplate shall be attached enclosure. The information required to be included on the nameplate has not changed.
to the outside of the control equipment
enclosure or machine and shall be plainly on
the machine immediately adjacent to the main
control equipment enclosure that is visible after Change Summary
installation. The nameplate shall include the
following information: • A permanent nameplate must be attached to the outside of the control equipment
enclosure or on the machine immediately adjacent to the main control equipment
1. Supply voltage, number of phases, enclosure and it must be visible after installation.
frequency, and full-load current
2. Maximum ampere rating of the short-circuit
and ground-fault protective device
3. Ampere rating of largest motor, from the
motor nameplate, or load
4. Short-circuit current rating of the machine
industrial control panel based on one of the
following:
a. Short-circuit current rating of a listed and
labeled machine control enclosure or
assembly
b. Short-circuit current rating established
utilizing using an approved method
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 21
Surge Protection
215.18 Surge Protection
Article 215 Feeders
Chapter 2 Wiring and Protection
Added Text
215.18 Surge Protection.
215.18(A) Surge-Protective
Device.
Where a feeder supplies any of the
following, a surge-protective device
(SPD) shall be installed:
1. Dwelling units
2. Dormitory units
3. Guest rooms and guest
suites of hotels and motels
4. Areas of nursing homes Significance of Change
and limited-care facilities
used exclusively as patient Electronics in appliances and electronic equipment such as GFCI’s and AFCI’s could be damaged when
sleeping rooms surges occur due to lightning, internal local switching as well as external utility switching. In many cases,
electronic devices and equipment can be damaged and rendered inoperable by a surge.
215.18(B) Location.
The SPD shall be installed in or The 2020 NEC introduced the need for surge protection on services of dwelling units. This new section
adjacent to distribution equipment, adds surge protection to feeders for the following occupancies: dwelling units, dormitory units, guest
connected to the load side of the rooms and guest suites of hotels and motels, and areas in nursing homes and limited-care facilities used
feeder, that contains branch circuit exclusively as patient sleeping rooms. These occupancies are very similar to dwelling units and have
overcurrent protective device(s) equipment and appliances with sensitive electronics that may be susceptible to damage from surges.
that supply the locations specified The SPD must be installed in or adjacent to the distribution equipment on the load side of the feeder
in 215.18(A). OCPD. The SPD must be a Type 1 or Type 2 SPD and have a nominal discharge current rating (In) of 10kA.
If the distribution equipment is replaced, the replacement equipment needs to comply with all of the
Informational Note: Surge requirements of this section.
protection is most effective when
closest to the branch circuit. Surges
can be generated from multiple Change Summary
sources including, but not limited
to, lightning, the electric utility, or
• Surge protection is required for feeders supplying dwelling units, dormitory units, guest rooms and
utilization equipment.
suites of hotels and motels, and areas of nursing homes and limited-care facilities used as patient
sleeping rooms
215.18(C) Type.
The SPD shall be a Type 1 or Type • The SPD must be installed in or adjacent to the distribution equipment on the load side of the
2 SPD. feeder OCPD
• The SPD must be a Type 1 or Type 2 SPD and have a nominal discharge current rating (In) of 10kA
215.18(D) Replacement.
Where the distribution equipment
supplied by the feeder is replaced,
all of the requirements of this
section shall apply.
215.18(E) Ratings.
SPDs shall have a nominal
discharge current rating (In) of not
less than 10kA.
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
22 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Surge Protection
225.42 Surge Protection
Part II. Buildings or Other Structures Supplied by a Feeder(s) or Branch Circuit(s)
Article 225 Outside Branch Circuits and Feeders
Chapter 2 Wiring and Protection
1. Dwelling units
2. Dormitory units
3. Guest rooms and guest suites of
hotels and motels
4. Areas of nursing homes and Significance of Change
limited-care facilities used
exclusively as patient sleeping
Electronics in appliances and electronic equipment such as GFCI’s and AFCI’s could be damaged
rooms
when surges occur due to lightning, internal local switching as well as external utility switching. In
many cases, electronic devices and equipment can be damaged and rendered inoperable by a surge.
225.42(B) Location.
The 2020 NEC introduced the need for surge protection on services of dwelling units. This new
The SPD shall be installed in or adjacent section adds surge protection to feeders for the following occupancies: dwelling units, dormitory
to the distribution equipment that is units, guest rooms and guest suites of hotels and motels, and areas in nursing homes and limited-
connected to the load side of the feeder care facilities used exclusively as patient sleeping rooms. These occupancies are very similar to
and contains branch circuit overcurrent dwelling units and have equipment and appliances with sensitive electronics that may be susceptible
protective device(s) that supply the to damage from surges.
location specified in 225.42(A). The SPD must be installed in or adjacent to the distribution equipment on the load side of the feeder
OCPD. The SPD must be a Type 1 or Type 2 SPD and have a nominal discharge current rating (In) of
Informational Note: Surge protection 10kA. If the distribution equipment is replaced, the replacement equipment needs to comply with
is most effective when closest to all of the requirements of this section. As noted in the informational note, to optimize protection of
the branch circuit. Surges can be the SPD, the lead length should be kept as short and also as straight as possible to provide the best
generated from multiple sources performance.
including, but not limited to, lightning,
the electric utility, or utilization
equipment.
Change Summary
225.42(C) Type.
• Surge protection is required for feeders supplying dwelling units, dormitory units, guest
The SPD shall be a Type 1 or Type 2 SPD. rooms and suites of hotels and motels, and areas of nursing homes and limited-care facilities
used as patient sleeping rooms
• The SPD must be installed in or adjacent to the distribution equipment on the load side of the
225.42(D) Replacement. feeder OCPD
• The SPD must be a Type 1 or Type 2 SPD and have a nominal discharge current rating (In) of
Where the distribution equipment
10kA
supplied by the feeder is replaced, all
of the requirements of this section shall
apply.
225.42(E) Ratings.
• 215.18
• 230.67
• Article 242
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 23
Surge Protection
230.67 Surge Protection
Part V. Service Equipment - General
Article 230 Services
Chapter 2 Wiring and Protection
Added text
230.67 Surge Protection.
(A) Surge-Protective Device.
(B) Location. The SPD must be installed in or adjacent to the distribution equipment on the load side of the feeder OCPD. The
The SPD shall be an integral part SPD must be a Type 1 or Type 2 SPD and a new requirement to have a nominal discharge rating (In) of not less
of the service equipment or shall than 10kA nominal current discharge rating, In, requirement was added in 2023. The nominal discharge rating of
be located immediately adjacent an SPD has a current impulse with a virtual front time (rise time) of 8 µs and a time to half-value (decay time) of 20
thereto. µs as defined by UL 1449 4th Edition. It is the peak value of the current through the SPD having a current wave
shape of 8/20 µs where the SPD remains functional after 15 surges. For Type 2 SPDs, In ratings can be 3kA, 5kA,
Exception: The SPD shall not 10kA or 20kA. The 10kA In rating requirement was put in place to help ensure that the SPD would be active since
it is a passive device and doesn’t interrupt the circuit like an OCPD. If the distribution equipment is replaced, the
be required to be located in
replacement equipment needs to comply with all of the requirements of this section.
at the service equipment as
required in 230.67
230.67(B) if located
at each next level distribution
equipment downstream toward Change Summary
the load.
• Surge protection is required for services supplying dwelling units, dormitory units, guest rooms and suites of
hotels and motels, and areas of nursing homes and limited-care facilities used as patient sleeping rooms
(C) Type.
The SPD shall be a Type 1 or Type • The SPD must be installed in or adjacent to the distribution equipment on the load side of the feeder OCPD
2 SPD. • The SPD must be a Type 1 or Type 2 SPD and have a nominal discharge current rating (In) of 10kA
(D) Replacement.
Where service equipment is
replaced, all of the requirements of
this section shall apply.
(E) Ratings.
SPDs shall have a nominal discharge
current rating (In) of not less than
10kA.
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
24 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Surge Protection
242.9 Indicating
Part II. Surge-Protective Devices (SPDs), 1000 Volts or Less
Article 242 Overvoltage Protection
Chapter 2 Wiring and Protection
Added text
242.9 Indicating.
Change Summary
• Surge-Protective Devices rated 1000V or less that are permanently installed on premises wiring
systems now must indicate if they are functioning properly
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 25
Surge Protection
409.70 Surge Protection
Part II. Installation
Article 409 Industrial Control Panels
Chapter 4 Equipment for General Use
Added text
409.70 Surge Protection.
Significance of Change
Recent studies revealed that numerous facilities reported that safety circuits installed on machinery had sustained damage from transient overvoltage
or surge events. These safety circuits are in place to safeguard workers from potential harm and damage to the safety circuit could result in unsafe
working conditions or prevent the machinery from operating.
The addition of surge protection devices (SPDs) will help protect safety circuits from damage due to surge events. Some examples of safety circuits
that may be susceptible to surges include, but are not limited to, light curtains, proximity switches, optic actuators and microprocessor controls. This
new section requires the SPD to installed within or immediately adjacent to an industrial control panel if it has a safety circuit.
Change Summary
• Industrial control panels that include safety circuits subject to damage from surges must have surge protection
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
26 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Surge Protection
670.6 Surge Protection
Article 670 Industrial Machinery
Chapter 6 Special Equipment
Revised text
670.6 Surge Overvoltage
Protection.
Significance of Change
Recent studies revealed that numerous facilities reported that safety circuits installed on machinery had sustained damage from transient overvoltage
or surge events. These safety circuits are in place to safeguard workers from potential harm and damage to the safety circuit could result in unsafe
working conditions or prevent the machinery from operating.
The requirement for overvoltage protection has been substantially simplified and now simply states that when an industrial machine has any type
of safety circuit, it must have overvoltage protection. The surge protection devices (SPDs) will help protect safety circuits from damage due to surge
events.
Some examples of safety circuits that may be susceptible to surges include, but are not limited to, light curtains, proximity switches, optic actuators and
microprocessor controls.
Change Summary
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 27
Barriers in Services and Feeders
215.15 Barriers
Article 215 Feeders
Chapter 2 Wiring and Protection
Added text
215.15 Barriers.
Significance of Change
This change improves safety when work is required to be done on the load side of the feeder disconnecting means. Barriers must be placed to
prevent contact with terminals on the line side of the disconnecting means in switchboards, switchgear, motor control centers or transformer
secondaries. When the feeder disconnecting means is in the open position an electrical worker performing work on the load side of the disconnecting
means will have a reduced risk of contacting energized parts on the line side of the disconnecting means.
Change Summary
Barriers are required to prevent inadvertent contact to any energized parts when the feeder disconnecting means is open.
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
28 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Barriers in Services and Feeders
230.62(C) Barriers
230.62 Service Equipment — Enclosed or Guarded
Part V. Service Equipment — General
Article 230 Services
Chapter 2 Wiring and Protection
Revised text
230.62(C) Barriers.
Significance of Change
The additional wording makes it clear that any terminals that are de-energized by opening the service disconnect are not required to be insulated
or protected by barriers. Only exposed, energized components on the line side of the service disconnect need to be protected from inadvertent
contact.
The incident energy available at the line terminals of the service disconnect may be considerably higher than the incident energy on the load side
of the service disconnect. It may also be difficult to de-energize the line side of the service disconnect to do work inside the equipment. For these
reasons, it is important prevent any inadvertent contact and provide protection against shock hazard and reduce the likelihood of initiating an arcing
fault.
Change Summary
Additional language “with the service disconnect in the open position” was added to clarify that the intent of this section is to provide protection for
exposed service conductors and circuit parts on the line side of the service OCPD or disconnect, not those that are downstream from the service
disconnect.
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 29
Other Significant Changes
110.3(B) Installation and Use
110.3 Examination, Identification, Installation, Use, and Listing (Product Certification) of Equipment
Part I. General
Article 110 General Requirements for Electrical Installations
Chapter 1 General
Added text
110.3(B) Installation and
Use.
Informational Note:
Significance of Change
Text has been added to include equipment or components that have been identified for a use in addition to those that are listed and labeled. An
informational note has been added to give users guidance that the installation and use instructions may be printed and included in the packaging or it
can be referenced by a QR code or internet address. This can be beneficial if printed instructions are lost or otherwise unavailable.
Change Summary
• Added identified along with listed and labeled
• Addition of informational note to describe how installation and use instructions for the equipment can be accessed
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
30 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Other Significant Changes
110.20 Reconditioned Equipment
Part I. General
Article 110 General Requirements for Electrical Installations
Chapter 1 General
Added Text
110.20 Reconditioned
Equipment.
110.20(C) Approved Equipment. The first sentence of the new Section clarifies that reconditioned equipment is allowed under the
If the options specified in 110.20(A) Code when the Code does not explicitly prohibit or otherwise address the equipment in question. The
or (B) are not available, the equipment must be reconditioned using identified replacement parts either provided by the original
authority having jurisdiction shall be manufacturer or that are designed by an engineer with experience for the type of equipment being
permitted to approve reconditioned reconditioned.
equipment, and the reconditioner
shall provide the authority having Additionally, if the equipment is required by the Code to be listed, it then must be listed or field labeled
jurisdiction with documentation of as reconditioned. If the equipment is not required to be listed, it can be listed or field labeled as
the changes to the product. reconditioned, or the reconditioning must be in accordance with the original manufacturer’s instructions.
If those options are not available, the AHJ is permitted to approve the equipment.
Change Summary
Related NEC Sections
• New language was added to provide clarity on the specific types of equipment allowed to be
• Article 100 Definitions, reconditioned as well as providing requirements for listing or labeling, replacement parts and the
Reconditioned approval process by an AHJ.
• 110.21(A)(2)
• See section 2 of each article
for additional reconditioned
equipment requirements
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 31
Other Significant Changes
230. 71(B) Two to Six Service Disconnecting Means
230.71 Maximum Number of Disconnects
Part VI. Service Equipment — Disconnecting Means
Article 230 Services
Chapter 2 Wiring and Protection
Significance of Change
Revised text
In 2020 there were significant revisions made to the “six disconnect
rule” for service equipment. The Code still permits two to six
230.71(B) Two to Six Service Disconnecting Means. disconnects, but the 2020 revision required separation by having
the disconnecting means in their own enclosure, vertical section or
Two to six service disconnects shall be permitted for each service compartment. These requirements were added to provide additional
permitted by 230.2 or for each set of service-entrance conductors safety for electrical workers to reduce any chance of contact with live
permitted by 230.40, Exception No. 1, 3, 4, or 5. The two to six service parts.
disconnecting means shall be permitted to consist of a combination of
any of the following: The revisions made for the 2023 NEC add transfer switches, metering
centers and motor control centers increasing the number of options
1. Separate enclosures with a main service disconnecting means for the types of equipment that can have service disconnecting
in each enclosure means. The service disconnects still need to be in either their own
2. Panelboards with a main service disconnecting means in each enclosure, compartment, or have barriers that provide protection from
panelboard enclosure inadvertent contact with live parts required in 230.62.
3. Switchboard(s) where there is only one service disconnect The flexibility to be able to use two to six service disconnects may be
in each separate vertical section where there are barriers advantageous for several reasons. For further discussion of design
separating each vertical section.
section. with barriers provided between considerations see the following page.
each vertical section to maintain the inadvertent contact
protection required in 230.62 based on access from the
adjacent section(s)
4. Service disconnects in switchgear, transfer switches,
switches, or Change Summary
metering centers where each disconnect is located in a
separate compartment • Added references for inadvertent contact protection required in
5. Metering centers with a main service disconnecting means in 230.62
each metering center • Added transfer switches, metering centers and motor control
6. Motor control center(s) where there is only one service centers as equipment that can contain service disconnecting
disconnect in a motor control center unit and a maximum of means if they meet specific requirements
two service disconnects provided in a single motor control
center with barriers provided between each motor control
center unit or compartment containing a service disconnect to
maintain the inadvertent contact protection required in 230.62
based on access from adjacent motor control center unit(s) or
compartment(s)
Exception to (2), (3), (4), (5), and (6): Existing service equipment,
installed in compliance with previous editions of this Code that
permitted multiple service disconnecting means in a single
enclosure, section, or compartment, shall be permitted to contain a
maximum of six service disconnecting means.
• 230.62(C)
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
32 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Other Significant Changes
230.71(B) Two to Six Service Disconnecting Means
230.71 Maximum Number of Disconnects
Part VI Service Equipment - Disconnecting Means
Article 230 Services
Chapter 2 Wiring and Protection
Alternate
3 2 1
rated service disconnect. 3 Op�onal Standby System Transfer Switch
Figure 2 If the normal source disconnects to the emergency system and legally required standby system
normal supply path for
are less than 1000 A, the 230.71(B) two to six service disconnect rule permits this configuration with
emergency systems, legally
GFPE. (480/277 V system)
required standby systems,
or other portions of the
Alternate
system. 700.31 and 701.31 Normal Source
allow not using GFPE, if Source G
otherwise required in the
NEC, for the alternate source Five Service
Disconnects
of emergency systems and
legally required standby
Disconnect & Overcurrent Protec�ve Device
systems, respectively. For
larger normal systems, the
Emergency System
two to six service disconnect 1
Transfer Switch
rule may be used for normal Legally Required Standby System Transfer
2
source supply to emergency N E N E N E Switch
systems and legally required 3 2 1
3 Op�onal Standby System Transfer Switch
standby systems, if the
service disconnect can be Op�onal Legally Emergency
kept less than 1000A. See Standby Required Loads
Loads
Figure 1, 2 and 3. Standby
Loads
3
Figure 3 If the normal source disconnects to the emergency system and legally required standby system
are less than 1000 A, as well as the other normal source disconnects, the 230.71(B) two to six service
disconnect rule permits this configuration without GFPE (480/277 V system).
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 33
Other Significant Changes
240.4(D)(1) & (2) Small Conductors
240.4 Protection of Conductors
Part I. General
Article 240 Overcurrent Protection
Chapter 2 Wiring and Protection
Added text
240.4(D) Small Conductors.
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
34 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Other Significant Changes
240.6(A) Fuses and Fixed-Trip Circuit Breakers
240.6 Standard Ampere Ratings
Part I. General
Article 240 Overcurrent Protection
Chapter 2 Wiring and Protection
Table 240.6(A) standard ampere ratings for fuses and inverse time circuit
Revised text breakers
Standard Ampere Ratings
240.6(A) Fuses and Fixed-Trip 10 15 20 25 30
Circuit Breakers. 35 40 45 50 60
70 80 90 100 110
The standard ampere ratings for
fuses and inverse time circuit 125 150 175 200 225
breakers shall be considered as 250 300 350 400 450
shown in Table 240.6(A). Additional
500 600 700 800 1000
standard ampere ratings for fuses
shall be 1, 3, 6, 10
10, and 601. The 1200 1600 2000 2500 3000
use of fuses and inverse time circuit 4000 5000 6000 — —
breakers with nonstandard ampere
ratings shall be permitted.
Significance of Change
Prior to the 2023 NEC the smallest standard rating for a circuit breaker was 15 amps. A new standard
rating of 10 amps was added to table 240.6(A) for inverse time circuit breakers. Now both fuses and
Related NEC Sections circuit breakers have a standard ampere rating of 10A. Fuses have additional standard ampere ratings of
1, 3, 6 and 601 that are not standard rating for circuit breakers.
• 210.23(A)
• 210.24 Change Summary
• Added 10 amp rating as a standard ampere rating for inverse time circuit breakers
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 35
Other Significant Changes
240.7 Listing Requirements
Part I. General
Article 240 Overcurrent Protection
Chapter 2 Wiring and Protection
Added text
240.7 Listing
Requirements.
1. Branch-circuit overcurrent
protective devices
2. Relays and circuit breakers
providing ground-fault
protection of equipment
3. Ground-fault circuit
interrupter devices
Significance of Change
Branch-circuit overcurrent protective devices provide protection of service, feeder, and branch circuits and equipment over the full range of
overcurrents between its rated current and its interrupting rating. This change requires these devices, such as circuit breakers and fuses, to be listed.
This revision assures that circuit breakers, such as supplemental protectors, which are UL recognized, are not suitable as a branch circuit overcurrent
protective device. For fuses, this revision reinforces that listed plug fuses and Class fuses are suitable as a branch circuit protective device.
Change Summary
• Branch-circuit overcurrent protective devices (typically fuses or circuit-breakers), relays and circuit breakers providing GFPE, and GFCI devices
are now required to be listed
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
36 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Other Significant Changes
240.60(E) Fuse Reducers
240.60 General
Part VI. Cartridge Fuses and Fuse holders
Article 240 Overcurrent Protection
Chapter 2 Wiring and Protection
Added text
240.60(E) Fuse Reducers.
Significance of Change
Fuse reducers are commonly used in temporary and permanent applications. Fuse reducers are used to increase the length of the fuse in order to
allow insertion of a lower ampere rated fuse into a higher ampere rated fuse holder or fuse switch. Class fuses and fuse holders come in case sizes
such as 30, 60, 100, 200, 400 and 600 amperes. For example, a 30 ampere Class R fuse can be installed in a 60A or higher ampere rated Class R fuse
holder by using the proper fuse reducer. By requiring the fuse reducers to be listed, this assures that this application is suitable and will not result in
an unsafe installation.
Change Summary
• Fuse reducers are now required to be listed
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 37
Other Significant Changes
430.6(A) General Motor Applications
430.6 Ampacity and Motor Rating Determination
Part I. General
Article 430 Motors, Motor Circuits, and Controllers
Chapter 4 Equipment for General Use
AC Induction Motor Nameplate- marked nameplate current ratings used to determine values for
separate overload protection. It is also used in place of the tables for motors built for low speeds, high
torques, canned pumps or multi-speed motors, and large motors exceeding the table values.
Table values used to determine ampacity of conductors, current rating of switches, and current ratings of
branch-circuit short-circuit and ground-fault protection.
* Note the difference between the ampere rating listed in fuse sizing and what is listed on the label.
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 39
Other Significant Changes
430.52 Rating or Setting for Individual Motor Circuit
Part IV. Motor Branch-Circuit Short-Circuit and Ground-Fault Protection
Article 430 Motors, Motor Circuits, and Controllers
Chapter 4 Equipment for General Use
Revised text
Table 430.52(C)(1) Maximum Rating or Setting of Motor Branch-Circuit Short-Circuit and Ground-Fault Protective Devices
The values in the Nontime Delay Fuse column apply to time-delay Class CC fuses.
1
2
The values given in the last column also cover the ratings of nonadjustable inverse time types of circuit breakers that may can be modified as in
430.52(C)(1), Exceptions No. 1 and No. 2 430.52(C)(1)(a) and (C)(1)(b).
3
Synchronous motors of the low-torque, low-speed type (usually 450 rpm or lower), such as are those used to drive reciprocating compressors,
pumps, and so forth, that start unloaded, do not require a fuse rating or circuit-breaker setting in excess of 200 percent of full-load current.
Significance of Change
The requirements in 430.52(C) have not significantly changed, but they have undergone an extensive reorganization in an effort to improve clarity and
usability. In 430.52(C)(1) Exceptions No. 1 and No. 2 have been re-written as rules rather than exceptions in compliance with the NEC Style Manual.
Section 430.52(C)(3) has been re-organized to part (a) covering application requirement and part (b) covering settings and the two exceptions have
been re-written as rules.
Design B premium efficiency motors have largely replaced Design B energy-efficient motors so they have been added to the requirements in Table
430.52(C)(1) and throughout 430.52(C).
Change Summary
• Design B premium efficiency motors were added and treated the same as Design B energy-efficient motors
• Several requirements were re-written as rules rather than exceptions
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
40 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Other Significant Changes
440.11 General
Part II. Disconnecting Means
Article 440 Air-Conditioning and Refrigerating
Equipment
Chapter 4 Equipment for General Use
Revised text
440.11 General.
Non-fused disconnect
Significance of Change
Disconnecting means for residential and some commercial air-conditioning units are often located where they are accessible by unqualified persons.
The language was added to ensure that if there are any exposed energized parts when the door or cover is opened, then a tool is required to open the
enclosure or the enclosure is capable of being locked.
Change Summary
• Added requirement to require a tool to open the disconnecting means or that the disconnecting means is capable of being locked if there are
exposed energized parts when open.
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 41
Other Significant Changes
440.22(A) Rating or Setting
440.22(A) Rating or Setting for Individual Motor-Compressor
Revised text
440.22 (A) Rating or Setting for
Individual Motor-Compressor.
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
42 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
Other Significant Changes
700.3(F) Temporary Source of Power for Maintenance or Repair of the Alternate Source of Power
700.3 Test and Maintenance
Part I. General
Article 700 Emergency Systems
Chapter 7 Special Conditions
Revised text
700.3(F) Temporary Source of Power for Maintenance or Repair of the
Alternate Source of Power.
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org. 43
Other Significant Changes
700.5(D) Redundant Transfer Switches
700.5 Transfer Equipment
Part I. General
Article 700 Emergency Systems
Chapter 7 Special Conditions
Reproduced with permission of NFPA from NFPA 70®, National Electrical Code®, 2023 edition. Copyright©
44 2022, National Fire Protection Association. For a full copy of the NFPA 70®, please go to www.nfpa.org.
NEC Code Changes video series
Eaton’s Bussmann Series brand is creating a growing library of video content discussing the recent NEC code changes to supplement this written guide.
This is great for listening while you drive or watching during your down time. Scan the QR code below and get FREE access now.
Watch
Here
Notice:
This publication has not been processed in accordance with NFPA® Regulations Governing Committee Projects. As such, it is not to be construed as an official posting of the NFPA or any
of its committees, nor relied upon as a formal interpretation of the meaning or intent of any section of the 2023 edition of the NFPA 70® National Electrical Code (NEC).
The reader is expressly warned to consider and adopt all safety precautions that might be indicated by the activities described herein and to avoid all potential hazards. By following
directions in this publication, the reader willingly assumes all risks in connection with such directions. Bussmann Division makes no representation of any kind, including but not limited to,
the representation of fitness for particular purpose or merchantability, nor are any such representations implied with respect to the presented material. Eaton’s Bussmann Division shall
not be liable for any special, consequential, or exemplary damages resulting, in whole or in part, from the reader’s use of, or reliance upon, this material.
Please refer to the NFPA 70 2023 NEC for complete information on the sections referenced in this publication.
Some photographs used in this publication were shot . Use of these photographs does not imply endorsement by Eaton’s Bussmann Division of the depicted manufacturers’ products.
This publication conveys information related to each of the Code changes it contains as of August, 2019, but does not reflect any subsequent appeal or action taken by the NFPA
Standards Council.
©2023
Eaton’s Bussmann Division
All rights reserved. No part of this work may be reproduced in whole or in part, in any graphic, electronic, or mechanical, including photocopying, audio or video
recording form, or information storage and retrieval systems without the expressed written permission of the Bussmann Division.
Eaton
1000 Eaton Boulevard Eaton and Bussmann are valuable trademarks
Cleveland, OH 44122 of Eaton in the US and other countries.
For Eaton’s Bussmann series
Eaton.com You are not permitted to use the Eaton product information,
trademarks without prior written consent of
Bussmann Division Eaton. call 1-855-287-7626 or visit:
114 Old State Road Eaton.com/bussmannseries
Ellisville, MO 63021 NFPA 70®, National Electrical Code®, and NEC®
United States are registered trademarks of the National Fire
Eaton.com/bussmannseries Protection Association.
© 2024 Eaton NEMA is a registered trademark of the Follow us on social media to get the
All Rights Reserved National Electrical Manufacturers Association. latest product and support information.
Printed in USA
Publication No. 11318 — BU-MC20287 UL is a registered trademark of the
January 2024 Underwriters Laboratories, Inc.