FACTS Unit-5
FACTS Unit-5
FACTS Unit-5
independently
with directionprovided"Converteras Figure
erchanged
an urced
8.3 in from onlythe the andmachine 2r),
Figure phasor wisource
th V Basic 8.2.1
V, controllable
Converter ideal Lo transmission it, angle in From
Conceptual
igure8.3 transformer. the by
between converters, by reactive 8.3. series (SVS),
system
ac-to-ac presently is regulation,
a the
Vag ger.eraie
a 1" provided suitable In with
2 dc and thisrepresented'at Operating
provides
magnitude estorage
h"Converter
tpower power system. controllable
(or conceptual
Veett as functionally for the
This illustrated used power
by the
= (or ac exchanged, transmission two
rcprcscntation Vs terminals capacitor.
converter practical one Since, SVS Principles
injected absorb) the supply independeDt viewpoint,
t V
main of mnagnitude the
Vpg 2" in the unrestricted generally as
and in
Figure established fundamentai
voltage reactive implementation,
function of As
in the end or the line,
of X Vx pbase sink. the
the the
which
indicated buses real
opeiated
figure,are 8.4. exchanges systems as V
UPFC acts two In
power UPFC
V power operation, illustrated (0s
of
esseatiallyangleconverters, the These the
(e.g.,previously,
in the (power is
a real
bcfore, UPFC must both with V a
two-machine UPFCp at back-to-back the the generalized
in its powerUPFCconsists serding-end a forsystem) s
series
as own this arTangement reactive be whi
transmission ch V)
Vet Vpa supplied an th e
a by and can froma
powe synchronousinjecting arangement ac SVS clearly
usual
with output cachfreely and and
frequency
synchronous
converters, is
V bus), to
able elementary anglep
the converter common of the it, real
includes lin k
Vxo terminal. a Aow two
ac iFe
voltage asreal orpower to ictertie)
functions in indicated absorbed generate (0 by
voltage via either labeled dc voltage power voltage voltagevoltage
V sps
an V can link with two
in
Transmission line V
Series transformer
SuppBy transfomer
Converter 1 Converter 2
V
ac
8C
Measured o Vpot
variables
Control
Parameter
settings
source. The iransmission line current flows through this voltage source resulting in
reactive and real power exchange between it and the ac system. The reactive power
exchanged at the ac tefminal (i.e., at the terminal of the series insertion transformer)
is generated internally by the converter. The real power exchanged at the ac terminal
is converted into dc puwer which appears at the dc link as a positive or negative real
power demand.
The basic function of Converter 1isto supply or absorb the real power demanded
byConverter 2 at the commcn de link to support the real power exchange resulting
from the series voltage injection. This dc link power demand of Converter 2is converted
back to ac by Converter 1and coupled to the transmission linc bus via a shunt
connected transtormer. In addition to the real power need of Converter 2, Converter
1can also generate or absorb controllable reactive power, if it is desired, and thereby
provide independent shunt reactive compensation for the line. It is important to note
that whereas there is aclosed dizect path for the real power negotiated by the action of
series voltage injection through Converters 1and 2back to the line, the corresponding
reactive power exchanged issupplied or absorbed locally by Converter 2and therefore
does not have to be transmitted by the line. Thus,Converter1 can be operated at a
unity power factor or be controlled to have a reactive power exchange with the line
independent of the reactive power exchanged by Converter 2. Obviously, there can
be no reactive power flow through the UPFC dc link.
8.2.2 Conventional Transmission Control Capablities
standpoint
Viewing the operation of the Uniñed Power Flow Controller from the
compensation, series com
of traditional power transmission based on reactive shunt functions and
pensation, and phase angle regulation, the UPFC can fulill all these
thereby meet multiple control objectives by adding the injected voltage V with
appropriate amplitude and phase angle, to the (sending-end) terminal voltage V,. Using
phasor representation, the basic UPFC power low control
Figure 8.5. functions are ilustrated in
Voltage
tion, is shown regulation
with
in Figure 8.5(a)continuously variable
for voltage incrementsin-phase/anti-phase
V tAV (p voltage injec
in Chapter 7, this is functionally similar to 0). As shown
that obtainable With atransformer tap
changer having infinitely small steps.
Series reactive compensation is shown in Figure 8.5(b) where V= V,is
in quadrature with the line current I. Functionally this is similar to series injected
and inductive line compensation attained by the SSSC in capacitive
Chapter 6: the injected series
compensating voltage can be kept constant, if desired, independent of line curent
variation, or can be varied in proportion with the line current to imitate the compensa
tion obtained with a series capacitor or reactor.
Phase angle regulation (phase shift) is shown in Figure 8.5(c) where V V,
isinjected with an angular relationship with respect to V, that achieves the desired a
phase shift (advance or retard) without any change in magnitude. Thus the UPFC can
function as a perfect Phase Angle Regulator which, as discussed in Chapter 7, can
also supply the reactive power involved with the transmission angle control by internal
var generation.
Multifunction power flow control, executed by simultancous terminal voltage
regulation, series.capacitive line compensation, and phase shifting, is showu in Figure
8.5(d) where V= AV+ V,+ V,. This functional capaoility is unique to the UPFC.
No single conventional equipment has similar multifunctional capability.
The general power flow controB capability of the UPFC, from the viewpoint of
conventional transmission control, can be illustrated best by the teal and reactive
power transmission versus transmission angle characteristics of the simple two-machine
system shown in Figure 8.3. With reference to this figure, the transmitted power P
and the reactive power -j2, suppied by the receiving end, can be expressed as follows:
(8.1)
(a) (b) (C ()
Vt4V Vpq
vV+Ve V+Vpa
(8.4)
(8.5)
and
(8.6)
where
and
Qo(5) VV,qmax
at any
X (8.12)
transmission angle 6, as
the transmitted power that is illustratcd inofFigure 8.6. The wide range of control for
the figure, indicates not only indeperndent the transmission angle &, observable in
superior capability of the UPFCin power flow apolica
tions, but it also suggests powerful
power oscillation damping. capacity for transient stability improvement and
To illustrate further the
which is, for copvenience, also meaning of (8.7) and (8.8), consider again
shown in a simplified manner in Figure 8.7(a).Figure 8.3
A phasor diagram, defning the
phasor across X) and the inserted voltage relationship between V,, V, V, (the voltage
{0s VsVm) and angie (0 s P s 360), phasor V with controllable magnitude
ilhustrations, &=30° and V,= V,=1, X= 0.5, Vmis shown in Yigure 8.7(a). (For the
0.25 p.u. values were assumed.)
As illustated, the inserted voltage
phasor.V is added to the fixedsending-end
phasor V, toproduce the effective sending-end voltage Vg V,+ voltage
V- V. provides the compensated voltage phasor, Vx, V. The difference,
varied over its full 360 degree range,
across X. As
the end of phasor V moves along aangle P is
its center located at the end of phasor V,. The circle with
arca within this circle, obtained with
Vpmar, defines the operating range of phasor V and thereby the
tion of the line. achievable compensa
The rotation of phasor V With angle p modulates both the
angle of phasor Vr and, therefore, both the transmitted real power, P, and magnitude and
thà reactive
-Q
2.0
3.5 X (=0.5)
-1.5
VWea (= -0.5)
1.0 -1.0
WsX (= 0.5)
0.5 -0.5
WE (=0.5)
X
0.0 0.0 2
2
-0.5 1.0
Figure &6 Range of transmittable real power P and receiving-end reactive power
demand 0 vs. transmission ande &of a UPFC controlled transnis
sion line.
Pa, P
Vx (Vpg =0)
V 0.5
P.Q,
0.5
1800 380
0.5
(a) (b)
Figure &7 Phasor diagram representation of the UPFC (1) and variation of the
receiving-end real and reactive powe, and the real and reactive power
supplied by the UPFC,with the angular rotation of the injected voltage
phasor (b).
P 15 relpnControlable
P, -15 -1.5
-10 1.0
cos8)
(8)-(1- \a,
-10 C.5
0.5
P
raglCont
on rqlable
13
.0
regiControlaible
on
system at the other end. Similar control characteristics for real power P and the reactive
power Q, can be observed at angles =3°, 60,and 90° in Figures 8.9(b), (c), and (d),
In general, at any given transmission angle 6, the transmitted real power P. as
well as the reactive power demand at the receiving end r, can be controlled freely
by the UPFCwithin the boundary circle obtained in the (, P} plane by rotating the
injected voltage phasor V with its maximum magnitude a full revolution. Further
more, it should be noted that, although the above presentation focuses on the receiving
end reactive power, Q, the reactive component of the line current, and the correspond
ing reactive power can actually be controlled with respect to the voltage selected at
any point of the line.
Figures 8.9(a) through (d) clearly demonstrate that the UPFC, with its unique
capability to control independently the real and reactive power flow at aiy transmission
angle, provides a powerful, bitherto unattainable, new tool for transmission system
control
In order to put the capabilities of the UPFC into proper perspective in relation
to other related power flow controllers, such as the
Thyristor-Switched, Thyristor
Controlled and GTO-Controlled Series Capacitor (TSSC TCSCand GCSC), the
Static Synchronous Series Compensator (SSSC), and the Thyristor-Controlled Phase
Angle Regulator (TCPAR),a basic comparison between the respective power low
control characteristics are presented in the next section. The basis chosen for this
comparison is the capability of each type of power flow controller to vary the transmit
ted real power and the reactive power demand at the receiving end. The
end var demand is usually an important factor because it receiving
significantly infuences the
variation of the line voltage with load demand, the overvoltage at
the steady-state system losses. Similar comparison, of course, couldload rejcction, and
the sending end or at other points of the transmission line, but the easily be made at
quite similar for all practical transmission angles. results would he
for pot
Principles and Characteristlcs
Operating
8.3.1 Besic Power Flow Controller
form the Interline employs number of
a
general providing series compensation for a different line. In other
In its each
do-to-ac Converterscormprises a number of Statte Synchrenous Series ompengators
words, thc PFC of the IPFC, the compensating converters are
within the general concept as ilustrated in Figure 8.29. With this scheme,
However, their dc terminals,
linked together at series reactive compensation, any converter canbebecontroled
providing
in addition to power to the cOmmondclinnk from its own transmission line. Thås, sn
tosupply real the under utilized lines which then
power can be made available from
overall surplus lines for real power compensation. In this way, some of the
an be used by cther overloaded lines Or lines with a heavy burden of reactive
coTverter, compensating with full two-dimensional, reactive and real power control
equipped
power dow, can be offered by the UPFG Evidently, this arrangerment mandates
capability, similar to that terminal
maintenance of the overall power balance at the common de
the igorous
the general principle that the underloaded ines are
using
by appropriate control action, appropriatereal power transfer,for thÃoverloaded lines.
to-provide belp, înthe form of
HV2
HVn
Lo00
do bus
Optical links
Control