Wind Tracker
Wind Tracker
Wind Tracker
INSTRUCTIONS
MODEL 06206
2801 AERO PARK DRIVE, TRAVERSE CITY, MICHIGAN 49686, USA TEL: (231) 946-3980 FAX: (231) 946-4772 WEB: www.youngusa.com
PN: 06206-90
REV: D062309
MODEL 06206
INTRODUCTION
The YOUNG Model 06206 Marine Wind Tracker is a compact wind speed and wind direction display. This model has features such as relative wind angle and NMEA compatibility that make it suitable for shipboard use.
FEATURES
3 digit wind speed display 3 digit maximum wind speed or wind direction display Multi-color wind direction display with variability display Wind speed and direction alarms with delay RS-485/NMEA serial connections Calibrated 0-5 VDC outputs Display brightness control 4-20 mA Sensor Inputs Luminous front panel markings
PRECAUTIONS
INDOOR USE ONLY unless placed in approved enclosure. Operating temperature range 0-50C (32-122F), 0-95% RH. Use only recommended power sources; 12-30 VDC, 4.5 W. Disconnect power when making connections or servicing sensors. MAXIMUM 24 VAC/30 VDC on alarm relay contacts.
SPECIFICATIONS
Size: 144 mm (5.65 in) x 144 mm (5.65 in) x 36 mm (1.4 in) Panel Cutout: 138 mm (5.43 in) x 138 mm (5.43 in) Compatible Sensors: Wind Monitor Wind Monitor-SE Wind Sentry Wind Monitor-MA Wind Monitor-JR
Other Inputs: 4-20 mA NMEA Serial Input/Output $WIMWV,ddd,R,sss,u,A[CR][LF] where: ddd wind direction in degrees sss wind speed (ss.s for m/s) u units (N = knots, K = kilometers/hour, M = meters/second, S = miles/hour) Accuracy: 0.6% F.S. 10 circular pattern (36 points) 1 w/ dSP dIr selected 1 Knot, 1 MPH, 1 KM/H, 0.1 M/S
3. 4.
Voltage Outputs: Wind Direction Range: 0-5 VDC 0-360 Wind Speed Range: (dependent on units selected) 0-5 VDC 0-100 Knots 0-100 MPH 0-200 KM/H 0-50 M/S Alarm Relays: Non-latching Normally Open contacts for WS and WD. Contact rating 5A resistive, 2A inductive @ 24 VAC, 30 VDC. Input Power: 12-30 VDC, 4.5 W
6.
Observe the unit for a few minutes to verify that it is operating properly. If you wish to change settings (ie: wind speed units). See the following section. 06206-90
Page 1
FRONT PANEL
CHANGING SETTINGS
The Wind Tracker has a setup mode that allows you to easily change sensor type, wind speed units, alarm settings, and other functions. Press and hold ENTER and SELECT keys (about 5 seconds). The display will briefly flash SET UP, then begin the SETUP sequence. Change settings with the SELECT key. Press the ENTER key to save a setting and move to the next step. Abbreviations in the left and right display windows identify each function and the available selections. DISPLAY
LEFT RIGHT
SETUP FUNCTION Input/Sensor Type Line Driver 4-20 mA input Wind Sentry Wind Monitor-Jr Wind Monitor, Wind Monitor-MA Serial input from Wind Monitor-SE or main display If SEr is selected, wind speed units and NMEA output rate selections do not appear. Wind Speed Units Press SELECT to change units, ENTER to proceed.
InP
LDi 03 04 05 SEr
SPd 1. 2. 3. 4. 5. 6. 7. Wind Speed Display Wind Speed Units Indicator Alarm Status Indicators Maximum Wind Speed or Relative Wind Direction Display Relative Wind Direction and Variability Display Brightness (operate mode), ENTER (setup mode) MAX RESET (operate mode), SELECT (setup mode)
unt
OUT
NMEA Output Rate FST 16 sentences sent per second SLO 1 sentence sent per second SPd dir Display Displays MAXIMUM wind speed in right display. Displays WIND DIRECTION degrees (1 resolution) in right display.
dSP
BACK PANEL
ALr
Wind Direction Alarm no WD alarm not used. YES WD alarm activated. If no is selected, the following 2 steps do not appear. dir SPn Press SELECT to position alarm sector. Press ENTER. Press SELECT to set size (span) of alarm sector.
Wind Speed Alarm no WS alarm not used. YES WS alarm activated. If no is selected, the following 3 steps do not appear. 000 WS alarm set point. Press SELECT to change digits. ENTER to save. Alarm Delay Time Set alarm delay time in seconds (0-999).
ALr
dLY Snd 1. 2. 3. 4. 5. 6. 7. Power input (12-30 VDC) AC adapter supplied Sensor or 4-20 mA inputs Earth ground connection RS-485/NMEA serial connections 0-5 VDC calibrated outputs Alarm relay connections (normally open) Input selector switch
030
Sound no No sound with alarm. YES Audible beeper will sound with alarm. Test Functions no Skip test functions. YES For troubleshooting only. YES will initiate the following tests. If no is selected, the unit will return to normal operation. Snd dSP Press SELECT to sound beeper. Press SELECT to illuminate all display segments.
tSt
tSt tSt
06206-90 Page 2
tSt CAL
ALr 0.00
Press SELECT to close alarm relays. Press SELECT to alternate between 0.00 Vout and 5.00 Vout at terminals. Use to calibrate external
SEr
Err
Unit is set to receive RS-485 NMEA serial signal, but no serial data is coming in. Verify that NMEA source is operating. Check cables for proper connection.
ADDITIONAL INFORMATION
ALARMS
Wind speed and wind direction alarm functions are accessed in the SETUP sequence. Either or both alarms may be used. When activated, alarms are indicated on the front panel. When an alarm condition exists, the indicator will blink and the associated relay contact will close and the beeper will sound if selected in SETUP. When a delay time is set, the indicator will not report an alarm condition until it has existed for one complete delay period. Alarm activity will cease when conditions are outside the alarm range for one complete delay period. For a "latching" alarm effect, use the Wind Tracker alarm contacts to activate an external latching-type relay.
WARRANTY
The Wind Tracker is warranted to be free of defects in materials and construction for a period of 12 months from date of purchase. Coverage is limited to repair or replacement of defective unit.
CE COMPLIANCE
This product has been tested and shown to comply with European CE requirements for the EMC Directive. Please note that shielded cable must be used.
BRIGHTNESS
Declaration of Conformity R. M. Young Company 2801 Aero Park Drive Traverse City, MI 49686 USA Model 06206 Marine Wind Tracker The undersigned hereby declares on behalf of R. M. Young Company that the above-referenced product, to which this declaration relates, is in conformity with the provisions of: Council Directive 2004/108/EC (December 15, 2004) on Electromagnetic Compatibility
The right display window can show either MAXIMUM WIND SPEED or Numerical WIND DIRECTION. This selection is made in the setup mode under Display (dSP).
NMEA OUTPUT
The Wind Tracker features NMEA serial output from the RS-485 terminals. These terminals can be used to operate remote displays or connect to other NMEA compatible devices. The NMEA output sentence is sent 16 times per second (Fast) or once per second (Slow) depending on the NMEA Output (OUT) setting in SETUP. For best remote display, use the Fast setting.
REMOTE DISPLAYS
The Wind Tracker can be used as a remote display by selecting "InP SEr" during SETUP. Remote displays are connected to the main display using the RS-485 terminals. NMEA Serial Protocol is used to operate remote displays. Up to 16 remote displays can be connected to one main display. Use the serial input when connecting to a Model 09101 Wind Monitor-SE sensor. See wiring diagram.
VOLTAGE OUTPUTS
The Wind Tracker offers calibrated voltage outputs for both wind speed and wind direction. This feature allows the use of recorders and other devices. Full scale voltage for each channel is 5.00 VDC. 4-20mA INPUTS The Wind Tracker accepts 4-20 mA (Line Driver) inputs. Line Driver circuit must provide 0-50 M/S Wind Speed scaling ("M" suffix). Connect cable as indicated on page 4. Slide switch on back must be UP at power up for correct 4-20 mA operation. Select LDI as input in SETUP. 24 VDC power is required for line driver applications.
ERROR MESSAGES
The Wind Tracker detects and indicates two errors. Once corrected, the error indication disappears. DISPLAY LDi Err 4-20 mA (line driver) signal. Signal is missing or outside of acceptable range. Verify proper switch position or signal.
06206-90 Page 3
06206-90 Page 4
06206-90 Page 5