Sec 15261 - HVAC Piping Abd Equipment Insulation
Sec 15261 - HVAC Piping Abd Equipment Insulation
Sec 15261 - HVAC Piping Abd Equipment Insulation
PART 1 - GENERAL
A. Piping insulation.
B. Equipment insulation.
C. Jackets and accessories.
1.03.A. REFERENCES
1.05 SUBMITTALS
A. Deliver products to site, store and protect under provisions of Section 01600.
PART 2 - PRODUCTS
C. Type C: Aluminium foil backed, foamed plastic, self adhesive insulation tapes;
`ksi' value of 0.04 at 24 deg.C (`K' value of 0.28 at 75 deg.F) or Elastomeric
closed cell rubber insulation with K-valve < 0.04 @ 50oC (mean temperature).
F. Type F: Formed glass blocks, having conductivity less than 0.05 at 24 deg.C (0.4
at 75 deg.F) and permeability of 0.00 perms or Elastomeric closed cell with K-
valve < 0.04.
G. Type G: Pre-formed calcium silicate sections of 50 mm (2 inch) thickness applied
one over the other to make 100 mm (4 inch) overall thickness or Elastomeric
closed cell with K-valve < 0.04.
A. Polyester canvas with PVA Finish, with visual mesh 9x8 opening per square inch.
Ref: Foster Mast-A-FAB or approved equal.
B. Aluminium jackets: 0.9 mm (0.032 inch) thick with corrugated finish for indoor
and smooth finish for outdoor.
C. The aluminium cladding shall be with polycraft paper on one side as vapour
barrier.
D. For rubber closed cell insulation not required the protective jackets.
2.05 ACCESSORIES
B. Metal jacket bands: 10 mm (3/8 inch) wide; 0.38 mm (0.015 inch) thick
aluminium.
PART 3 - EXECUTION
3.01 PREPARATION
A. Install materials after piping has been tested and approved and painted with two
coats of approved primer paint, where applicable.
3.02 INSTALLATION
A. Install materials in accordance with manufacturer's instructions.
B. Continue insulation with vapor barrier polyester canvas through penetrations.
C. In exposed piping, locate insulation cover seams in least visible locations.
D. On insulated piping with vapor barrier, insulate fittings, valves, unions, flanges,
strainers, flexible connections, and expansion joints.
H. Where glass fiber rigid sectional insulation is specified, insulate fittings flanges
and valves by applying mineral wool cement, maintaining thickness of
insulation same as for adjoining pipe. Finish with asbestos free cement and
jacketing as specified.
--------------------------------------------------------------------------------------