519

ADL100-EY、ADL300-EY

Installation and operation instruction V1.0

ACREL Co,.Ltd
Declare
The copyright is the property of Acrel. Any information in any

paragraph or section cannot be extracted, copied or otherwise reproduced

or propagated. Otherwise offenders shall take all consequences.

All rights are reserved.

Acrel reserves the right to modify the product specifications herein

without notification. Please consult the local agent about the latest

specifications before placing a purchase order.


Contents
1 General...................................................................................................... 1

2 Model description..................................................................................... 1

3 Product specification................................................................................ 1

4 Main function............................................................................................1

5 Technical parameter.................................................................................. 2

6 Dimension drawings (Unit: mm)..............................................................3

7 Wiring and installing.................................................................................4

8 Display and operation............................................................................... 5

9 Communication description......................................................................5
1 General

ADL100-EY single phase pre-paid meters with intro-control, ADL300-EY three phase

pre-paid meters with intro-control are used for calculating the single and three phase active energy

respectively on the frequency of 50 Hz. The meter has functions of pre-paid, load controlling and

RS485 communication etc. meet the related technical requirements of electronic power meter in

the IEC62053-21, IEC62053-22 standards.

2 Model description

Moel Model Description


ADL100-EY/RF Single phase,RF card charging,external control
ADL100-EY/NK Single phase, remote recharge, with intro-control
ADL100-EY/Z Single phase, RF card charging, with intro-control
ADL300-EY/RF Three phase,RF card charging, external control
ADL300-EY/NK Three phase, remote recharge, with intro-control
ADL300-EY/Z Three phase, RF card charging, with intro-control

3 Product specification

Accuracy Reference Pulse constant


Type Current(A)
class voltage (imp/kWh)
3×1(6)A 6400
ADL300-EY 0.5s 3×220/380V
3×10(80)A 400
ADL100-EY 1 220V 10(60)A 1600

4 Main function

Function description Function


Function name
ADL300-EY ADL100-EY provide

1
Measurement of kWh Total active kWh (positive and negative in total) ■
Measurement of electrical U、I 、P、Q、S、PF、F ■
parameters
Pre-paid mode Through RS485 communication prepaid recharge, ■
data encryption

Control Built-in high-capacity sub-holding relay to achieve ■


load on-off control
LCD display 8 bits section LCD display ■
Communication Communication interface: RS485, Communication ■
protocol: MODBUS-RTU
Multi-tariff 4 tariff rates, 14 time interval by day □F
(■: means standard; □: means optional)
Note: Pre-paid mode function can only be achieved with the pre-paid system which designed
by Acrel Co,.Ltd.

5 Technical parameter

5.1 Electric performance


Technical parameter ADL300-EY ADL100-EY
Reference voltage 3×220/380V 220V
Reference 50Hz
Voltage
frequency
Consumption <4VA(Each phase)
Input current 1(6)A ,10(80)A 10(60)A
Current Starting current Connect directly: 0.004 Ib, connect via CT: 0.002In
Consumption <4VA (Maximum current)
Measurement Accuracy of 0.5s Class 1 Class
performance measuring
Clock accuracy Error ≤0.5s/d
Pulse width 80ms±20ms
Active pulse
Pulse constant 6400imp/kWh,400 imp/kWh 1600imp/kWh
Interface RS485(A+、B-)
Communicati
Connection mode Shielded twisted pair conductors
on
Protocol MODBUS-RTU

5.2 Mechanical performance


Mechanical performance ADL300-EY ADL100-EY
Outline (Length × Width × 144mm×88mm×70mm 72mm×88mm×70mm
Height)
Maximum wiring ability (flexible 25mm2
cable)

2
5. 3 Work environment
Work temperature -25℃~55℃
Temperature
Storage -40℃~70℃
range
Temperature
Relative humidity ≤95%)(No condensation)
Altitude <2000m

6 Dimension drawings (Unit: mm)

ADL100-EY

ADL300-EY

derect connect

3
connect via CT

Note: The torque of direct connect should not be greater than 4.0N·m ,and the torque of
connect via CT should not be greater than 2.0N·m.

7 Wiring and installing

load

ADL100-EY

load

ADL300-EY Three phase four lines direct connect

ADL300-EY Three phase four lines connect via CT

4
Auxiliary function

8 Display and operation

8.1 Display examples

dump energy Total Power

Voltage display Current Display

Table number(High six bit) Table number(Low six bit)

9 Communication description

9.1 Communication protocol


The meters adapt Modbus and DL/T645 protocol. Please refer to the relevant standards for more
information. The multi-tariff data mean nothing when multi-tariff function (F) is not applied.
9.2 MODBUS mailing address list
ADL100-EY mailing address list
Address Variable Length R/W Notes
0000H Current total electricity 4 R unit: 0.01kWh

5
0002H Current spike electric energy 4 R
0004H Current peak electric energy 4 R
0006H Current flat electric energy 4 R
0008H Current valley electric energy 4 R
000AH Code 2 R/W
000BH Voltage U 2 R
000CH Current I 2 R
000DH Active power P 2 R unit:0.001Kw
000EH Reactive power Q 2 R unit:0.001Kvar
000FH Apparent power S 2 R unit:0.001Kva
Calculation
factor:0.001
0010H power factor PF 2 R
effective range
(-1000~1000)
0011H Frequency 2 R unit:0.01Hz
0012H Year, month 2 R/W
0013H Day, hour 2 R/W
0014H Minute, second 2 R/W
0015H
… Reserved
003BH
003CH Current forward active total electric energy 4 R

Current reversing active total electric ener


003EH 4 R
gy

0040H-03
Reserved
5FH
Address:1~247
Baud rate:
0:1200
Main communication : Communication 1:2400
0360H 2 R/W
address and baud rate 2:4800
3:9600
4:19200
5:38400
Check bit:
0:No check
1:Odd
2:Parity check
0361H Main communication: Check bit stop bit 2 R/W
Stop bit:0:1
1:1.5
2:2

6
0362H-03
645Address[] 6 R/W BCD
64H
The second communicate:Communication
0365H 2 R/W
address and baud rate
The same as the
0366H The second communicate:Check bit stop bit 2 R/W
ADL100-EY
0367H-03
The second communicate:645Address[] 6 R/W
69H
036AH
… Reserved
1FFFH
2000H
… 4 time zones 3×4 R/W Time zone table
2005H
2006H
14-period of time Parameters setting
… 3×14 R/W The first time list
information
201AH
201BH
14-period of time Parameters setting The second time
… 3×14 R/W
information list
2029H

ADL300-EY mailing address list


Notes
Address Variable Length R/W

Current total
0000H 4 R
electricity
Current spike
0002H 4 R
electric energy
Current peak electric
0004H 4 R unit:0.01kWh
energy
Current flat electric
0006H 4 R
energy
Current valley
0008H 4 R
electric energy
second、minute、hour、day、
000AH-000CH Date, time 6 R/W
month、year

000DH-0027H Reserved

0028H 4 time zones 12 R/W Time zone table

002EH Voltage of A phase 2 R


unit:0.1V
002FH Voltage of B phase 2 R

7
0030H Voltage of C phase 2 R

Electricity of A
0031H 2 R
phase
Electricity of B
0032H 2 R unit:0.01A
phase
Electricity of C
0033H 2 R
phase
Voltage between
0034H 2 R
A-B
Voltage between
0035H 2 R unit:0.1V
C-B
Voltage between
0036H 2 R
A-C

0037H Voltage transfer 2 R/W Value range(0~9999)

0038H Current transfer 2 R/W Value range(0~9999)

0039H-003BH Reserved

003CH Level 1 password 2 R/W Value range(0~9999)


003DH Level 2 password 2 R/W Value range(0~9999)
003EH-0043H Reserved
0046H The alarm value 1 4 R/W
0048H The alarm value 2 4 R/W unit:0.01 Yuan
004AH Credit amount 4 R/W

004CH-0063H Reserved

0064H demand 2 R unit:0.001kW

0065H PA 4 R
0067H PB 4 R
unit:0.001kW
0069H PC 4 R
006BH PT 4 R
006DH QA 4 R
006FH QB 4 R
unit:0.001kvar
0071H QC 4 R
0073H QT 4 R
0075H SA 4 R
0077H SB 4 R
unit:0.001kVA
0079H SC 4 R
007BH ST 4 R

8
007DH PFA 2 R
007EH PFB 2 R Calculate the factor:0.001
007FH PFC 2 R effective range(-1000~1000)
0080H PFT 2 R
0081H Freq 2 R Calculate the factor:0.01
0082H-035FH Reserved
Main
communication:
0360H Communication 2 R/W
address and baud
The same as the ADL100-EY
rate
The main
0361H communication: 2 R/W
Check bit/ stop bit

0362H-1FFFH Reserved

14-period of time
2000H Parameters setting 42 R/W The first time list
information
14-period of time
2015H Parameters setting 42 R/W The first time list
information

There will not be control command because of the page limited, if there are any demand of
these command, contact us with no hesitate.