EFS Chiller Training
EFS Chiller Training
EFS Chiller Training
Maintenance of Chiller
HVAC – Heating Ventilation Air Conditioning
HVAC is the removal of heat from indoor air for thermal comfort or conditioning
the air to human comfort. As per the ISHRAE standards air conditioning means
REFRIGERATION:
TONS OF REFRIGERATION:
1TR is also defined as 12,000 BTU (British Thermal Unit) per hour or 3517
Watts.
HVAC – Heating Ventilation Air Conditioning
CFM:
Short for cubic feet per minute, a measurement of the velocity at which air
BTU:
water to 1 degree F.
Humidity:
The moisture content in air is referred to as humidity.
RH = Percentage (%) at temperature (⁰C)
RH is the ratio between the moisture that can be held in a given volume of air
and the theoretical moisture that can be held in the same volume of air at
the same pressure and temperature
Moisture that can be held in a given volume of air
% RH= --------------------------------------------------------------------------- x 100
Theoretical moisture that can be held in given volume of air
Must be maintain Relative Humidity between 45% and 55%
Below 20% will cause the ESD and above 80% will cause the shorts in circuit
boards and will increase the speed of corrosion.
PRECISION AIR CONDITIONING
HVAC Refrigerant Cycle
Operation and Maintenance of Chiller
• Water Cooled Chiller cools the refrigerant by water cooled condensation and
• The Chill water circulated to air-handlers in order to transfer heat from air to water.
WATER COOLED CHILLER
WATER COOLED CHILLER
Operation Cycle,
• The cycle starts when refrigerant enters the compressor in a low pressure (suction
pressure), low temperature and gaseous form. The refrigerant is compressed by the
• The condenser precipitates the high pressure Refrigerant gas to a high temperature
• The high temperature liquid then enters the expansion valve allows liquid
• In evaporator the heat is transferred to the liquid refrigerant from the water. Thus
liquid refrigerant gets converted to low pressure gaseous state, further the cycle
repeats.
Air Cooled Chiller Circuit
Operation Cycle
Operation Cycle,
A Chiller unit consists of four major elements, a compressor, a condenser, an expansion
valve and an evaporator.
• The Low pressure Super heater vapor compressed in the Compressor and leaving as
• This mixer Refrigerant flow to the Oil Separator, due to centrifugal force oil settled
down in the oil separator tank bottom and refrigerant flows to the Condenser coil.
• In the Condenser coil the heat rejected from the refrigerant (Condenser cooling fan)
• This High pressure liquid expands in the Expansion Valve changed as Low pressure Wet
vapor.
• This Low pressure wet vapor flows to the Evaporator coil. The shell type Evaporator coil
has the inside tubes and water flows around the tubes. The chilled state wet vapor
flows through the tubes the outside water absorbs the chillness.
• Leaving from the Evaporator Refrigerant is in the state of Low pressure Super heated
Vapor and again it goes to the compressor for next cycle. This process is continuous till
the setting temperature is reached.
REFRIGERANT:
It is the vehicle that collects heat from the area to be cooled, moves it outside and
COMPRESSOR:
The purpose of the compressor is to draw the low-temperature, low-pressure vapour from
This compressor thus helps us to utilize the natural air or water which are available in plenty
at temperatures from 25°C to 45°C for condensing the refrigerant vapor into its liquid.
PRECISION AIR CONDITIONING
Types of Compressor - Scroll
Displacement mechanism.
The screw compressors comprise of the pair of meshing screws between which the
CRITICAL PARAMETERS
The critical parameters are Suction pressure & discharge pressure. Low Suction pressure
SUCTION PRESSURE
It is also said LOW SIDE PRESSURE. In air conditioning systems, the suction pressure is the
Shortage of Refrigerant
Leakage in Refrigerant
Compressor Critical Parameter
DISCHARGE PRESSURE:
It is also called as HIGH SIDE PRESSURE / HEAD PRESSURE. It is the pressure generated
• Step motors can run at 200 steps per second and can return to their exact position
very quickly. The controller remembers the number of step signals sent by the
controller. This makes it possible for the controller to return the valve to any previous
position at any time. This gives the valve very accurate control of refrigerant that
flows through it.
• EEVs have 1,596 steps of control and each step is 0.0000783 inches.
Sensors
• The electronic signals sent by the controller to the EEV are usually done by a
thermistor connected to discharge airflow in the refrigerated case.
• A thermistor is nothing but a resistor that changes its resistance as its temperature
changes.
• Pressure transducers can also be wired to the controller for pressure/temperature
and superheat control.
SUBCOOL ECONOMIZER
• Economizer operation mode improves both cooling capacity and efficiency by means
of a sub-cooling circuit.
• A plate type heat exchanger is utilized as a liquid sub cooler. A part of the refrigerant
mass flow from the condenser enters the sub cooler via an expansion device, and
evaporates upon absorbing heat from the main liquid refrigerant line.
• Liquid refrigerant gets sub cooled and the vapor refrigerant enters the compressor
Filter driers are usually installed in the liquid line of a dry-expansion refrigeration system,
First, they trap coarse particulate contamination and copper shavings, and second they
Sight Glass Moisture Indicator is usually fitted in the liquid line immediately after the filter
drier to measure the moisture content of the refrigerant.
If the indicator is yellow, there is a problem with the moisture content of the refrigerant.
Excessive moisture content can cause icing of the expansion valve. if the evaporating
temperature is 0 °C or lower. Frothing in the sight glass indicates either a shortage of
refrigerant or that the refrigerant in the liquid.
WATER COOLED CHILLER
In this, the tube carries water and the shell carries the refrigerant)
Condenser Approach
This is the difference between the liquid refrigerant temperature and the temperature of
water leaving the condenser. Normally when the condenser is clean, this difference must
be less than 1 deg C. if the condenser approach is more than 4 deg C this indicates the
COOLING TOWER:
The entire heat gained from the conditioned space is finally discharged into the
The cooling tower uses the water evaporation͛ principle to cool the condenser water.
WATER COOLED CHILLER
WATER COOLED CHILLER
RANGE:
Difference between the temperatures of inlet and outlet water of the cooling tower
Range (°C) = inlet water temp – outlet water temp
Higher the RANGE BETTER the PERFORMANCE
APPROACH:
Difference between cooling tower outlet water temperature from cooling tower and the
ambient wet bulb temperature:
Approach (°C) = outlet water temp from cooling tower – Wet bulb temp
Lower the APPROACH (in °C) BETTER the performance
Ideally a cooling tower can cool the condenser water to the wet bulb temperature. But this
will be very expensive. Any cooling tower will be designed to reduce the water temperature
5⁰C above the wet bulb temperature.
WATER COOLED CHILLER
BLOW DOWN:
The portion of the circulating water that is removed in order to maintain the amount of
dissolved solids and other impurities at an acceptable level is called cooling tower blow
down.
It may be noted that if we can, somehow, maintain higher TDS (total dissolved solids)
concentration in the circulating water, it will result in reduced blow down and hence water
conservation.
However, the higher the TDS concentration, the greater is the risk of scale, biological
• In cooling tower water the TDS should be less than 1000 PPM.
• Cooling tower fan and its motor should be maintained in good condition
• During chiller startup, condenser and chiller barrel water flow must first be established
WATER COOLED CHILLER
• An operation log should be kept for the chiller water-cooled require more maintenance
• Inspect complete power circuit for hot spots and discolored wires