1 PDF
1 PDF
1 PDF
CONDENSERS
Table 4-1. Reduction in system efficiency when condensers and evaporators are
not maintained.
————————————————————————————————
Operating Evaporating Condensing Tons Brake BHP Increased
Condition Temperature Temperature Ref. HP per ton BHP per ton
————————————————————————————————
Normal Operation 45°F 105°F 17.0 15.9 0.93
————————————————————————————————
Dirty Condenser 45°F 115°F 15.6 17.5 1.12 20%
————————————————————————————————
Dirty Evaporator 35°F 105°F 13.8 15.3 1.10 18%
————————————————————————————————
Dirty Cond. & Evap. 35°F 115°F 12.7 16.4 1.29 39%
————————————————————————————————
68 HVAC Fundamentals
COMPRESSORS
METERING DEVICES