AIR-CONDITIONING SYSEM FOR LAB AND OFFICE AREA
CHILLER:
Evaporator Condenser Electrical Data
Tag Location Qty. Type Unit Capacity Water Water Temp. Pressure Water Flow Ambt. Power Supply Max. Operating Weight Remarks
Temp. In Out Temp. KW/TR
Floor Nos. TR 0
F 0
F psi US GPM 0
F V/ Ph / Hz Kg
CH-01, CH-02 Roof Top 2 Air-Cooled Scroll 50 54 44 150 120 100.4 415 / 3 / 50 1.15 1980 02 Nos.: Duty
CH-03, CH-04 Roof Top 2 Air-Cooled Scroll 17 54 44 150 40 100.4 415 / 3 / 50 1.13 660 02 Nos.: Duty
CHWP-01 & CHWP-02 Roof Top 2 End Suction Centrifugal Chilled Water 120 80 1500 150 415 / 3 / 50 4.0 102 02 Nos.: Duty
CHWP-03 & CHWP-04 Roof Top 2 End Suction Centrifugal Chilled Water 40 80 1500 150 415 / 3 / 50 3.0 90 02 Nos.: Duty