Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

HIREF - MRAC - EN HF65000002C Web

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

MRAC

Mini Rack Cooler


for high density systems
L D

L D

H
H
Mini Rack Cooler for high density systems
MRAC
MRAC Indoor unit MTC Outdoor unit
Available also for 60 Hz power supply

MRAC INDOOR UNIT 0035 0035b 0070 0070i


@30Hz @70Hz @110Hz
Inlet air conditions 30°C - 35% r.h.; Condensing temperature 45°C
Cooling Capacity kW 3.6 4.1 6.8 3.0 6.0 7.9
SHR 1.0 1.0 0.9 1.0 0.9 0.8
Inlet air conditions 35°C - 30% r.h.; Condensing temperature 45°C
Cooling Capacity kW 3.9 4.4 7.4 3.2 6.4 8.6
SHR 1.0 1.0 1.0 1.0 0.9 0.8
Evaporator airflow m3/h 915 1330 1330 1330
Fans’ power input kW 0.15 0.33 0.33 0.33
Power Supply V/-/Hz 230/1/50 230/1/50-60
Dimensions (L x H x D) mm 485 x 300 x 600 485 x 300 x 600
Weight kg 26 26 29.5 29.5

MTC OUTDOOR UNIT 0035 2x0035 (*) 0070 i0070


@30Hz @70Hz @110Hz
Total power input kW 1.1 1.1 2.1 1.1 1.8 2.7
Total current absorption A 4.7 4.7 4.2 6.1 9.7 14.7
Lp @nominal rpm; Q = 2 (**) dB(A) 42 42 46 42
Power Supply V/-/Hz 230/1/50 400/3/50 230/1/50-60
Dimensions (L x H x D) mm 700 x 540 x 265 942 x 735 x 341 1305 x 648 x 420
Weight kg 34 34 71 91

(*) 1 running motocondensing unit (**) @2 m according to UNI EN 3744

HIREF S.p.A. HiRef S.p.A. reserves the right to change


the specifications and other information
3.6 - 7.9 kW
Viale Spagna, 31/33
contained herein without notice.
35020 Tribano (PD) Italy No part of this publication may be
Tel. +39 049 9588511 reproduced without the prior written
Fax +39 049 9588522 permission of HiRef S.p.A.
HF65000002 rev.C
e-mail: info@hiref.it © Copyright HiRef S.p.A. 2017
www.hiref.it
MRAC
MRAC is suitable for in-rack air conditioning
Mini Rack Cooler for high density systems

MRAC can be installed


in any 19-inch rack

19” RACK

Small dimensions: MRAC is MRAC is the right choice to cool 19” racks which need a close temperature
control and a 24h/24 operation. They come in split execution with an
as high as 7 rack units outdoor motocondensing R410A unit, from 3.6 up to 7.9 kW.
MRAC is controlled by a dedicated software, developed in the HiRef’s
N° 7
software Dept., and can be connected in a LAN (up to 8 units).
RACK The main controller can be linked to an automatic system for door opening
in case of alarm.

MRAC’s fans are exclusively


with EC motors
›› High efficiency cooling coil with hydrophilic treatment and structure made of aluminium
›› Brushless DC inverter driven compressor available for the 7 kW unit
electronically
commutated fans ›› Electrical and microprocessor quick connections
›› Low outdoor temperature version available
›› AISI 430 stainless steel drain pan
Highest redundancy with
›› Refrigerant connections on bottom
the 2 motocondensing
unit solution ›› Completely insulated panels
›› G3 air filter
›› Colour RAL 7016

HFC R410A EC FAN R INVERTER BLDC