Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

VRF Indoor Unit Four Way Cassette (2 Generation DC Series, 50/60Hz)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

VRF Indoor unit

Four Way Cassette (2nd Generation DC Series,50/60Hz)

Submittal Data
Job Data Location
Buyer Buyer PO# ComfortStar #
Unit number Model number
Performance data certified by Date

Four Way Cassette Features


10 models from 2.8~14kW
High efficiency DC fan motor
distribution of
cooling and heating
5-step swing louver
7-speed fan control
Specifications Quiet operation
Accessories (optional) Fresh air intake
Wireless remote controller: CWL-05B, CWL-012D Built-in EXV
Wired remote controller: CWR-86E, CWR-120G High-lift drain pump with 750mm pump head
Centralized controller: CVC-30, CVC-180A, CVC-270A Optional brand-new, elegant panel with round air
Grille panel: CSTPA-048PN discharge and four independently controlled louvers

Model CSTPA-ASD009-1S CSTPA-ASD012-1S CSTPA-ASD016-1S CSTPA-ASD020-1S CSTPA-ASD024-1S


Power supply 1 phase,220-240V, 50/60Hz
Cooling1 Capacity kBtu/h 9.6 12.3 15.4 19.1 24.2

Power input kW 0.040 0.045 0.050 0.060 0.070


Heating2 Capacity kBtu/h 10.9 13.6 17.1 21.5 27.3
Power input kW 0.040 0.045 0.050 0.060 0.070
Fan Type DC

motor Quantity 1
Minimum Circuit Amps(MCA) A 0.41 0.41 0.56 0.56 0.56
Maximum Overcurrent Protection(MOP) A 15 15 15 15 15
Indoor air flow rate CFM 471/442/418/387/375/360/319 526/510/473/438/ 526/510/473/438/ 575/552/509/471/

420/411/374 420/411/374 458/434/395

Fan speed RPM 390/370/350/330/ 450/440/410/380/ 490/470/440/410/

320/310/280 370/360/330 400/380/350

Sound pressure level3 dB(A) 32/31/30/28/28/26/23 35/34/31/31/30/28/26 35/35/34/31/30/28/27


Main Net dimension(W×H×D) mm 840×230×840

body Ship dimension(W×H×D) mm 955×260×955


Net weight kg 21.3 23.2
Ship weight kg 25.8 27.6
Panel Net dimension(W×H×D) mm 950×54.5×950

Ship dimension(W×H×D) mm 1035×90×1035


Net/Ship weight kg 5/8
Pipe Liquid pipe o.d.(flare) mm 6.35 9.53

connectio Gas pipe o.d.(flare) mm 12.7 15.9


Drain pipe o.d. mm OD 32
n
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m, level difference 0.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m, level difference 0.
3. Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs and without incurring obligations
Page 1
Specifications
Model CSTPA-ASD028-1S CSTPA-ASD030-1S CSTPA-ASD034-1S CSTPA-ASD036-1S CSTPA-ASD048-1S
Power supply 1 phase,220-240V, 50/60Hz
Cooling1 Capacity kBtu/h 27.3 30.7 34.1 38.2 47.8

Power input kW 0.096 0.100 0.150 0.160 0.170


Heating2 Capacity kBtu/h 30.7 34.1 37.5 42.7 54.6
Power input kW 0.096 0.100 0.150 0.160 0.170
Fan motor Type DC
Quantity 1
Minimum Circuit Amps(MCA) A 0.76 0.88 1 1 1.2
Maximum Overcurrent Protection(MOP) A 15 15 15 15 15
Indoor air flow rate CFM 708/666/626/575/ 794/762/724/706/ 966/909/842/770/ 978/926/852/793/

536/494/456 654/606/571 721/705/673 738/718/689

Fan speed RPM 590/560/530/490/ 490/470/450/440/ 590/560/520/480/ 620/590/550/510/

460/430/400 410/380/360 450/435/420 480/465/450

Sound pressure level3 dB(A) 36/35/34/31/ 37/35/34/31/ 38/36/35/34/ 38/36/35/34/ 39/37/36/35/

31/29/28 31/30/28 31/31/30 31/31/30 34/31/31

Main body Net dimension(W×H×D) mm 840×230×840 840×300×840


Ship dimension(W×H×D) mm 955×260×955 955×330×955

Net weight kg 23.2 28.4 30.7


Ship weight kg 27.6 33.8 35.8
Panel Net dimension(W×H×D) mm 950×54.5×950
Ship dimension(W×H×D) mm 1035×90×1035
Net/Ship weight kg 5/8
Pipe Liquid pipe o.d.(flare) mm 9.53

connectio Gas pipe o.d.(flare) mm 15.9


Drain pipe o.d. mm OD 32
n
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m, level difference 0.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m, level difference 0.
3. Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.

Dimensional Drawing

Model A(mm) B(mm) C(mm) D(mm)

2.8-4.5kW 230 126 6.35 12.7

5.6-8.0kW 230 126 9.53 15.9

9.0-14.0kW 300 197 9.53 15.9

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs and without incurring obligations