VAV-DD7-E

The Alerton® VisualLogic® VAV-DD7-E is a versatile, BACnet-compliant


field controller that provides pressure-independent control of any
dual-duct variable air volume (VAV) box. It is particularly suited for
controlling dual-duct fan-powered variable volume or constant volume
terminal units. As a native BACnet controller, the VAV-DD7-E integrates
seamlessly with your BACnet system, communicating at up to 115.2
Kbps on a BACnet MS/TP LAN.
The VAV-DD7-E-F includes two filters to reduce dust contamination.
The VAV-DD7-E eliminates the need for expensive products and
external pressure sensors to control fan-powered dual-duct VAV boxes.
The VAV-DD7-E supports the Alerton Microtouch™, as well as the
BACtalk® Microset, Microset II, and Microset 4 intelligent wall sensors,
which offer convenient data display, setpoint adjustment, and technician
access to equipment setup parameters.
All VAV-DD7-E control logic is programmed using Alerton's easy-to-
learn graphical programming language, VisualLogic®. Programming and
setup data are stored in non-volatile flash memory, ensuring stable and
reliable operation.
DUAL-DUCT VARIABLE AIR The VAV-DD7-E contains two integral airflow sensors to provide
VOLUME UNITARY FIELD pressure independent operation of a dual-duct VAV box.The airflow
sensors are factory calibrated at multiple velocity points and are
CONTROLLER field-adjustable during balancing. Minimum, maximum, and reheat
airflows can be entered using a Microset wall unit or compatible
FEATURES AND HIGHLIGHTS operator workstation software.
• Fully BACnet-compliant on MS/TP LAN at up to 115.2 Kbps.
• Programmable control logic can be field-modified.
• Download-able operating code to allow for future
software improvements
• 32-bit processor architecture with all program data backed up in
nonvolatile flash memory.
• High-speed processing of DDC program, with an internal
logical loop time of 100 msec.
• Backwards compatible with older VAV-DD7 and
VAV-DD7C3 models.

APPLICATIONS
Recommended for pressure-independent control of any
dual-duct variable air volume (VAV) box.

VAV-DD7-E-F

UI HBO GBO RO AO AF F
UNIVERSAL HOT SWITCHED TRIAC GROUND SWITCHED
INPUTS BINARY OUTPUTS BINARY OUTPUTS RELAY OUTPUT ANALOG OUTPUTS AIR-FLOW SENSOR FILTER

4 3 4 0 0 2 2

© 2020 Honeywell International Inc. All Rights Reserved. LTDATA-VAV-DD7-E 0620 1


VAV-DD7-E

TECHNICAL DATA ORDERING INFORMATION


POWER – 24 VAC @ 50-60 Hz. 5 VA minimum (maximum 89 VA ITEM NUMBER
with loads). Half-wave rectified. VAV-DD7-E ALERTON VAV DUAL-DUCT
INPUTS – 16-bit universal inputs accept 3k (Ibex) or 10k thermistor BACNET CONTROLLER
(type II), dry contact, 0-20 mA, 0-10 V, 0-5V, or dry-contact pulse. VAV-DD7-E-F ALERTON VAV DUAL-DUCT
External 250-ohm resistor required for 0-20 mA inputs. Pulse input BACNET CONTROLLER WITH FILTER
maximum frequency of 100 Hz. Pulse input minimum duty cycle 5mS VAV-FILTER ALERTON VAV FILTER SINGLE
ON / 5mS OFF (pulse input not supported on IN-0). VAV-FILTER-50 ALERTON VAV FILTER BULK PACK (50)

BINARY OUTPUTS – Triacs rated 24 VAC @ 50/60 Hz, 500 mA CERTIFICATION AND CONFORMANCE
continuous and 800 mA (AC rms) for 60 milliseconds. BACNET CONFORMANCE – An application specific controller (ASC)
MICROSET – Supports BACtalk® Microset, Microset II, or Microset level device; tested and approvedby BTL. See Protocol Implementation
4 on input 0 (IN-0). Conformance Statement (PICS).
INPUT/OUTPUT TERMINATIONS – Removable header-type UL – Listed Underwriters Laboratory for Open Energy Management
screw terminals accept 14-24 AWG wire Equipment (PAZX) under the UL Standard for Safety 916; listing includes
both U.S. and Canadian certification.
PRESSURE SENSORS –16-bit polarity insensitive pressure
sensor. 0-2 in.w.c. (500 Pa) range. 0.0004 in.w.c. (0.1 Pa) zero-point EMC – EMC Directive 89/336/EEC (European CE Mark).
accuracy. 0.5% span repeatability. 1/8-inch x 3/8-inch long barb- FCC – FCC Part 15, Subpart J, Class A.
fitting.
FILTERS – In-line filters for pressure sensor available to enhance
long-term stability.
MAX DIMENSIONS – 4.9" (125mm) H x 5" (127mm) W x
1.4" (36mm) D
MOUNTING – Screw mounting
ENVIRONMENTAL – 0 to 158°F (-17 to 70°C) / 5 to
95%RH, non-condensing
COMMUNICATIONS – EIA-485 (RS-485) over twisted shielded-
pair (TSP); auto-baud switching (9.6kbps, 19.2kbps, 38.4kbps,
76.8kbps, or 115.2kbps); communication status LED.
PROTOCOLS – BACnet MS/TP (master)
PROGRAMMING – Supports Alerton’s BD4 DDC file format using
Alerton’s VisualLogic® toolset.
MICROPROCESSOR – 32-bit ARM Cortex-M4F, 80 MHz
MEMORY – 512 MB non-volatile flash.
SECURITY – Integrated secure boot prevents loading of
tampered firmware.

16201 25th Avenue W., Lynnwood, WA 98087


Telephone: (425) 921-4900 / Fax: (425) 921-4872
alerton.com / sales@alerton.com

© 2020 Honeywell International Inc. All Rights Reserved. LTDATA-VAV-DD7-E 0620 2