hbt-bms-VAV-DD7-E-datasheet
hbt-bms-VAV-DD7-E-datasheet
hbt-bms-VAV-DD7-E-datasheet
APPLICATIONS
Recommended for pressure-independent control of any
dual-duct variable air volume (VAV) box.
VAV-DD7-E-F
UI HBO GBO RO AO AF F
UNIVERSAL HOT SWITCHED TRIAC GROUND SWITCHED
INPUTS BINARY OUTPUTS BINARY OUTPUTS RELAY OUTPUT ANALOG OUTPUTS AIR-FLOW SENSOR FILTER
4 3 4 0 0 2 2
BINARY OUTPUTS – Triacs rated 24 VAC @ 50/60 Hz, 500 mA CERTIFICATION AND CONFORMANCE
continuous and 800 mA (AC rms) for 60 milliseconds. BACNET CONFORMANCE – An application specific controller (ASC)
MICROSET – Supports BACtalk® Microset, Microset II, or Microset level device; tested and approvedby BTL. See Protocol Implementation
4 on input 0 (IN-0). Conformance Statement (PICS).
INPUT/OUTPUT TERMINATIONS – Removable header-type UL – Listed Underwriters Laboratory for Open Energy Management
screw terminals accept 14-24 AWG wire Equipment (PAZX) under the UL Standard for Safety 916; listing includes
both U.S. and Canadian certification.
PRESSURE SENSORS –16-bit polarity insensitive pressure
sensor. 0-2 in.w.c. (500 Pa) range. 0.0004 in.w.c. (0.1 Pa) zero-point EMC – EMC Directive 89/336/EEC (European CE Mark).
accuracy. 0.5% span repeatability. 1/8-inch x 3/8-inch long barb- FCC – FCC Part 15, Subpart J, Class A.
fitting.
FILTERS – In-line filters for pressure sensor available to enhance
long-term stability.
MAX DIMENSIONS – 4.9" (125mm) H x 5" (127mm) W x
1.4" (36mm) D
MOUNTING – Screw mounting
ENVIRONMENTAL – 0 to 158°F (-17 to 70°C) / 5 to
95%RH, non-condensing
COMMUNICATIONS – EIA-485 (RS-485) over twisted shielded-
pair (TSP); auto-baud switching (9.6kbps, 19.2kbps, 38.4kbps,
76.8kbps, or 115.2kbps); communication status LED.
PROTOCOLS – BACnet MS/TP (master)
PROGRAMMING – Supports Alerton’s BD4 DDC file format using
Alerton’s VisualLogic® toolset.
MICROPROCESSOR – 32-bit ARM Cortex-M4F, 80 MHz
MEMORY – 512 MB non-volatile flash.
SECURITY – Integrated secure boot prevents loading of
tampered firmware.