Manual Crusair
Manual Crusair
Manual Crusair
English
OWNER/OPERATOR
For Direct Expansion SMX II Control Systems using SMXIIAB, SMXir or the new SMXht keypad/displays.
Table of Contents
SMX II Control Systems Introduction
Introduction ......................................................................... 4
14
The SMXIIAB & SMXir Keypad/Display .............................. 5 The SMXir Remote Control ................................................ 6
Basic Operation ................................................................ 14 Programming .................................................................... 14 Factory Memory Reset ..................................................... 15 Fault Code Displays .......................................................... 15 SMXht Keypad/Display Programming Summary Table ..... 15
Basic Operation
Power On ............................................................................ 7 System Off .......................................................................... 7 Selecting Setpoint .............................................................. 7 Displaying Temperature ...................................................... 7 Cool Mode .......................................................................... 7 Heat Mode .......................................................................... 7 Automatic Switchover Mode ............................................... 7 Manual Fan Speed Control ................................................. 7 Automatic Fan Speed Control ............................................. 7 Adjusting Brightness ........................................................... 7 Using The Humidity Control Program ............................... 7 Anti-Ice Routine .................................................................. 8 Seawater Temperature ....................................................... 8
Owners Warranty Periods Limited Warranty Periods Cruisair Worldwide Service Dealer Locator
18 20 21
To Enter, Use and Exit the Programming Mode .................. 8 Compressor Time Delay ..................................................... 8 Fahrenheit/Celsius Display ................................................. 8 Compressor Restart Differential ......................................... 9 Fan Response Differential .................................................. 9 Low Fan Speed Adjustment ............................................... 9 High Fan Speed Adjustment ............................................... 9 Fan Mode ......................................................................... 10 AC Line Voltage Calibration .............................................. 10 Temperature Calibration ................................................... 10 Factory Memory Reset ..................................................... 10
10
11 11 11 12
12
Fault Codes ...................................................................... 12 High-Pressure Shutdown ................................................. 12 Low-Pressure Shutdown .................................................. 12 Low-Voltage Shutdown ..................................................... 13 Software Error .................................................................. 13 Determining Your Software Version and Revision Level ............................................ 13
Initial Start Up
13
Copyright 2004 Dometic Corporation, All Rights Reserved - Every precaution has been taken in the preparation of this manual to insure its accuracy. However, Dometic Corporation assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of this product and information contained herein.
L-2362
English
Introduction
The term SMX II refers to the overall product family of keypad/display controls and to the power/logic circuit board located in the a/c units electrical box. There are three different keypad/displays that can operate an SMX II control system. The three different keypad/displays are: SMXIIAB (previously known as SMX II) - rectangular in shape and larger than the other two, this was the standard for many years. (See The SMXIIAB & SMXir Keypad/ Display section.) SMXir - newer and smaller than the SMXIIAB, this contol has a hinged cover and an optional remote control. (See The SMXIIAB & SMXir Keypad/Display section.) SMXht - the newest High Technology keypad/display, this European style control fits into a decorative bezel and has many new features. (See SMXht Keypad/Display Basic Operation & Programmers Guide section) If you have the new SMXht, familiarize yourself in general with the operation and programming sections of this manual, but go to the SMXht Keypad/Display Basic Operation & Programmer's Guide section for specific information on that control. If you have an SMX Net control system, refer to the SMX Net Control Systems (DX) Installation and Operation manual.
L-2362
English
Hint
Press both Heat and Cool at the same time, and the system will automatically switch between Cooling and Heat Mode. When in this Automatic Switchover Mode, both the Cool and Heat indicators are lit.
13. Manual Fan Mode Indicator Lights when fan is running in Manual Fan Mode. 14. Slow and Fast Keys Control fan speed when the fan is in the Manual Fan Mode. Pressing Slow or Fast key when in Automatic Fan Mode will change the system into Manual Fan Mode. 15. Fan Key Selects Manual or Automatic Fan Mode. Press once for manual control. Press Fan again to select automatic fan speed control. In this mode, the fan speed is controlled by the microprocessor as a function of the difference between setpoint and inside temperature. See the Fan Response Differential programming section. 16. Fan Speed Indicators Row of five small LEDs below Fan key that indicate the current fan speed. 17. Inside Temperature Indicator (SMXir Display Only) When illuminated, inside temperature is displayed. When light is off, setpoint is displayed. 18. IR Receiver (SMXir Display Only) Infrared remote receiver. 19. Dehumid Key (Remote Control Only) Changes system into the Humidity Control Program. 20. Auto Switchover Key (Remote Control Only) Places the system into Automatic Switchover Mode, so it will change from cooling to heating as needed.
Hint
You can display temperature in degrees Fahrenheit or Celsius.
8. Off Key Turns system off. Note that the Data Display remains on. You can continue to adjust setpoint, display temperature readings and activate the manual fan to circulate air while the system is in the Off Mode. 9. Cool Mode Indicator Lights when you press the Cool key to select the Cool Mode. 10. Heat Mode Indicator Lights when you press the Heat key to select the Heat Mode. 11. Cool Key Turns the system on in the Cool Mode.
L-2362 Operation
Definitions
LED - Light Emitting Diode. An indicator light used to denote mode or operating status. Setpoint - The desired room temperture that is set by programming the SMX control. IR - Infrared
English
SMXir Keypad/Display
SMXIIAB Keypad/Display
L-2362 Operation
English
Basic Operation
Power On
When AC power is applied to the system at the circuit breaker, the SMX II microprocessor performs a self-check and retrieves the last operating configuration from permanent memory. This process takes about four seconds, after which the system will begin operating just as it had been when power was last turned off.
System Off
Press the Off key to turn the system off. Note that the Data Display remains energized even when the system is off. The fan can be turned on manually when the system is in the Off Mode.
Note
The SMX II has built-in protection against sudden power interruptions. The system automatically stores the current operating configuration in permanent memory every time any changes are made. (The new operation mode must be in affect for 30 seconds before it is saved into permanent memory.) When AC power is lost, the SMX II system retains these settings, and when AC power is restored it resumes operation using the same settings as before.
Selecting Setpoint
Press the Set key and the current setpoint will be displayed. Press the Up or Down key to change the setpoint.
Displaying Temperature
To display cabin temperature, press the Temp key. Press Temp twice for an alternating display of inside temperature and setpoint. Press again to return to inside temperature only.
Adjusting Brightness
Pressing the Set key repetitively will dim the LED display. Keep pressing Set to return to full brightness.
Cool Mode
Press the Cool key to select Cool Mode. The Cooling Indicator will light to show that you have selected the Cool Mode. The Cooling Indicator will be lit whenever the system is in the Cool Mode and the compressor is running. When the compressor cycles off, the Cooling Indicator turns off, but the Cool Mode Indicator remains on.
Heat Mode
Press the Heat key to select Heat Mode. The Heating Indicator will light to show that you have selected the Heat Mode. The Heating Indicator will be lit whenever the system is in the Heat Mode and the compressor is running. When the compressor cycles off, the Heating Indicator turns off, but the Heat Mode Indicator remains on.
L-2362 Operation
Press Off. Press Cool, Heat and Fan keys simultaneously. For the SMXir Remote Control only - Press the Dehumid key to enter Humidity Control Program. The Data Display will flash HU, indicating that the program is active. To halt the program, press any key. The HU message will stop flashing.
English
Safety Note
Whenever the system is in the Humidity Control Program, all of the system safeguard controls remain active. For example, if the seawater flow fails or if line voltage falls below preset limits, the system will automatically shut down. Or, if AC power is interrupted, the system will automatically resume operation in the Humidity Control Program when power is restored.
Anti-Ice Routine
The SMX II control will occasionally shut down the compressor in the Cool Mode to allow any ice that may have formed on the evaporator coil to melt. The Anti-Ice Routine shutdown will occur only when the inside cabin temperature falls below 70F (21C). During the ten minute cycle period, the compressor will shut off for 15 seconds for each degree below 70F. For example, if the inside temperature is 67F, the compressor will shut off for 45 seconds, and then run for nine minutes and 15 seconds, repeating on ten minute intervals.
To enter the Programming Mode: Press Off, then press Set. Successful entry into the Programming Mode is indicated by the presence of a decimal point to the right of the two displayed characters. See the following table and each individual program for specific instructions on using each programmable function. Press the keys indicated to select that particular function. Once a programmable function has been selected, then use the Up and Down keys to raise, lower or change its setting. Press Off to exit the Programming Mode.
Fahrenheit/Celsius Display
(Factory Default: Fahrenheit) Temperature can be displayed in degrees Fahrenheit or Celsius. Upon entering the Programming Mode, press the Down, Temp and Up keys simultaneously.
Warning
Do not operate your air conditioning unit in water that is colder than 38F (3.3C). Doing so could lead to water freezing in the condenser coil which can cause damage to the unit.
Note
If you switch from Fahrenheit to Celsius for temperature displays, the Compressor Restart Differential will also operate on degrees Celsius. Thus, the factory set Compressor Restart Differential will be 1.5 Celsius, which is too much. To correct this, reset the differential value from 12 to 6. This will provide a differential of 0.75 C, or about 1.4 F.
8
L-2362 Operation
English
This will also affect the Fan Response Differential, which is factory set at a value of 4, or 0.5 Fahrenheit. When changing from Fahrenheit to Celsius, you should reset the Fan Response Differential from 4 to 2. This will provide a fan differential of 0.25 C, or about 0.5 F.
Note
If the Compressor Restart and the Fan Response Differentials are both set to the factroy default, or a comparable range, and the Automatic Fan Mode is on, then the fan will not run at high speed unless the cabin temperature rises 2.5 Fahrenheit above setpoint.
Note
On SMX II systems built before 8/98, press Slow, Fan and Fast simultaneously to adjust Fan Response Differential.
Hint
Be careful not to set your compressor restart differential too low, since it will cause the compressor to start and stop quite often. This will place an undue load on your electrical system and may shorten the life of the compressor.
Hint
You should normally keep the low fan speed at the highest possible setting, consistent with a comfortable noise level, for most efficient operation of your system. Running the fan speed too slow may have an adverse affect on the system and may cause the evaporator coil to freeze.
L-2362 Operation
English
Fan Mode
(Factory Default: Continuous) You can select continuous or intermittent fan operation. Select C and the fan will run continuously while the system is on. Select I for intermittent operation and the fan will cycle on and off with the compressor. Upon entering the Programming Mode, press the Down, Fan and Up keys simultaneously.
Hint
If you select intermittent fan operation, you should relocate the thermistor from the return air grill to a cabin wall where it can best sense the average room temperature. Check with your dealer or call the Cruisair Applications Department for more information.
Temperature Calibration
The temperature sensor should be within one or two degrees of actual room temperature. To check or re-calibrate the sensor: Upon entering the Programming Mode, press the Set and Up keys simultaneously. The sensed temperature will be displayed. Place an accurate thermometer beside the sensor and compare the temperatures.
L-2362 Operation
10
English
L-2362 Operation
11
English
Keystroke Combination
Down & Set & Up Down & Temp & Up Slow & Fan Cool & Slow
(Slow & Fan & Fast Before 8/98)
Factory Setting
0 F 12 4 38 60 C -
Range
0 to 70 sec. F or C 4 to 24 2 to 8 2 to 57 41 to 99 C or I 1% 1%
Down & Set Set & Slow Down & Fan & Up Down & Up Set & Up Off & Set & Fan, then Set Temp & Down Temp & Set Temp & Up
High-Pressure Shutdown
In the Cool Mode, if head pressure rises above 400-425 PSI (28-30 kg/cm2) (usually caused by loss of cooling water flow, refrigerant gas overcharge or a fouled condenser) the SMX II will attempt three restarts, then shut down the entire system. The display will alternately flash HI/PS. This is a sustained shutdown, and even when the pressure lowers after shutdown, the system will remain off until reset by pressing the Off key. In the Heat Mode, a rise in head pressure above the set limit (usually caused by poor airflow or incorrect charge) will cause the compressor to cycle off for two minutes, allowing the heat in the coil to dissipate. This prepares the system for recycling in the Heat Mode. The compressor will then continue to cycle, based on input from the high-pressure switch, until the cabin temperature reaches setpoint, after which compressor cycling is automatically restored to normal operation.
Hint
Your system must be equipped with a high-pressure switch and low-pressure switch for the high- and low-pressure shutdown to operate. You should check with your dealer to make sure these important protective devices are installed properly.
Fault Codes
If an operational failure occurs, the display will flash one of the following fault code messages. Fault code displays are cancelled by pressing the Off key.
Meaning Operating voltage remained below 100V for three minutes for 230V system) Head pressure above 425 PSI
Result Shutdown
Low-Pressure Shutdown
When installed, the optional low-pressure switch is monitored by the SMX II control. The low-pressure switch opens when the suction pressure drops below 30 PSI (2.11 kg/ cm2), and resets at 45 PSI (3.16 kg/cm2). The low-pressure fault routine operates differently in the Cool and Heat Modes.
Shutdown
Cool Mode:
When the low-pressure switch first opens, the unit will run for two minutes, then shut down for 50 seconds. It will do this four times. If the switch has not closed, the unit will shut 12
* Note: The PS in the high-pressure and low-pressure fault warning should not be confused as P5 on the SMX II LED Data Display.
L-2362 Operation
English
down for 15 minutes, and alternately flash LO/PS on the display. After 15 minutes of shut down, the cycle stats again in which the unit runs for two minutes and then shuts down for 50 seconds. If, after 18 attempted compressor starts, the low-pressure switch does not stay closed, the unit will go into a sustained shutdown and flash LO/PS. If the low-pressure switch closes at any time before the sustained shutdown, the unit will then operate normally.
Likewise, the self-diagnostic routine runs continuously whenever the SMX II system is on. If a system fault is detected, the system shuts down, and the PE error message appears. If this message occurs, contact your nearest Cruisair dealer, or call the Factory Service Department for assistance. Please read the next paragraph before calling.
Heat Mode:
If the low-pressure switch opens, the fan will automatically change to low speed to try and raise system pressure. It will run for 11 minutes in this mode. Note that the fan speed can not be adjusted at this time. Any attempt to raise fan speed will result in LO/PS being flashed, while the unit continues to run. After 11 minutes, the unit will run for two minutes, then shut down for 50 seconds. It will do this four times. If the switch has not closed, the unit will shut down for 15 minutes, and flash LO/PS on the display. After 15 minutes of shut down, the cycle stats again in which the unit runs for two minutes and then shuts down for 50 seconds. If, after 18 attempted compressor starts, the low-pressure switch does not stay closed, the unit will go into a sustained shutdown and flash LO/PS. If the low-pressure switch closes at any time before the sustained shutdown, the unit will then operate normally.
Initial Start Up
The following instructions apply to both self-contained and remote condensing systems. 1. Open the seacock (seawater inlet valve). 2. Turn on the circuit breaker for the air conditioner. If a pump relay is installed, the breaker for the pump must also be turned on. 3. Set the system for cooling or heating at the SMX II keypad, and adjust temperature setting so the unit will turn on. 4. Verify that water is flowing from the overboard discharge. If more than one unit is installed, then check all such discharges. 5. Allow unit to run for ten minutes at high fan speed. Check the temperature differential between discharge and return air by placing an accurate thermometer in front of the discharge grill and then in front of the return air grill. In the Cool Mode, the difference between the discharge and return should be 15 - 20F (8.3 - 11.1C), with normal ambient air and water temperatures. In the Heat Mode the differential can be as high as 25F (13.9C).
Low-Voltage Shutdown
The low-voltage protection feature is always active. If AC line voltage drops and remains below the limit, 100 volts for a 115V system or 200 volts for a 230V system, for more than three minutes, the SMX II shuts down the entire system. The display will flash LO/AC. This is a sustained shutdown, and the system will not resume operation even if the line voltage rises to normal levels. To reset, press the Off key.
Hint
For the low-voltage shutdown function to work properly, the SMX internal voltmeter should be calibrated. This should be done when the system is installed. To check or recalibrate line voltage, see the AC Line Voltage Calibration section.
Software Error
Whenever power is applied to the SMX II, the microprocessor goes through an automatic self-check and software loading process. If all is well, the SMX II loads the most recent operating configuration from its internal memory, and turns on normally. If a program fault is found during the selfcheck, the error message PE (Program Error) will be displayed.
L-2362 Operation
13
English
Backlight Mode:
While in the Sleep Mode (backlight is off, see function #20) press any button to light the display, and then operate as usual.
Programming
SMXht must be in the Off Mode prior to entering Programming Mode; pressing the POWER key turns the display off or on. Once in the Off Mode, then: 1. Simultaneously press and hold the MODE and Down Arrow keys for three seconds. The word PROG will flash in the display while the buttons are being held. Successful entry into the Programming Mode is indicated when the word PROG stops flashing, and a flashing 1 appears in the display. 2. Use the Up or Down Arrow keys to scroll until the desired program Function Number is displayed. (See SMXht Keypad/Display Programming Summary Table.) 3. Press the MODE key to enter the desired function. The current value and the word PROG will be displayed. 4. Use the Up or Down Arrow keys to change the value of that program. 5. Press the POWER key to save the new settings, exit the Programming Mode, and return to the Off Mode. Note: If SMXht is programmed for displaying C (rather than the factory setting F), then functions 3 & 4 should be adjusted. For function 3, the factory setting of 12 (or 1.5F) should be changed to 7 (7/8 = 0.8C). For function 4, the factory setting of 4 (or 0.5F) should be changed to 2 (2/8 = 0.3C). For these functions, 1F (or 8) = 0.6C (or 5). 14
Basic Operation
Turning the System On:
Press the POWER or MODE keys to turn the system on. In three seconds, the system will start operating in whatever mode it was running prior to the last shut down. Press the MODE key prior to three seconds (while the display is flashing) to change mode before system starts, or any time to change the mode while the system is on. The modes available are: Cool, Heat Auto Switchover (automatically switches from Cool to Heat Mode), or Dehumidification Mode. A solid dot will light up next to the words COOL or HEAT when the compressor is on and running in that mode.
L-2362 Operation
English
L-2362 Operation
15
English
Situation
Air from the unit does not feel cool in the Cool Mode or warm in the Heat Mode.
Problem/Solution
1. The selector switch is set for Fan only. Switch the system into the Cool or Heating Mode. 2. The thermostat is set incorrectly. Set the thermostat for a cooler or warmer setting. 3. Water flow is restricted. Clear restriction. Clean strainer.
Situation
The unit operates but the cabin fails to cool normally.
Problem/Solution
1. Dirty air filter. Clean lint screen or air filter. 2. The thermostat is set too high. Reset the thermostat to a cooler setting. 3. The evaporator coil has iced. Turn the system to Fan only for five minutes, then restart.
Situation
Compressor cycles on and off.
Problem/Solution
1. Dirty air filter. Clean lint screen or air filter. 2. Water flow restriction. Clear restriction. Clean strainer.
Warning
The Power/Logic board operates at 115VAC or 230VAC. Make sure the power is off before removing the cover of the Power/Logic box.
Contact an authorized Cruisair servicing dealer if the problem continues, or for replacement parts.
Situation
Water dripping inside cabin.
Problem/Solution
1. Condensate drain is clogged. Clean out drain holes. 2. Blockage in hose. Clear hose. Check downhill routing of hose.
System Troubleshooting
Before you call for service, review this list. It may save you time and expense. This list contains common occurrences that are not a result of defective workmanship or materials. If you need service after trying these procedures, call your nearest Cruisair dealer.
Situation
The unit will not operate at all.
Problem/Solution
1. Blown fuse or tripped circuit breaker. Replace fuse with time delay type or reset breaker. Check for correct sizing. 2. Low voltage to unit. Check shore power supply and rating of electrical power cord to boat.
L-2362 Troubleshooting
16
English
Air Filters
At least once a month, check the lint screen or filter behind the return air grill or on the face of the cooling/heating unit and clean if necessary.
Seawater Connections
Verify that all seawater connections are tight, and check for water flow from each units overboard discharge.
Seawater Pump
If the seawater pump has a plastic pump head, then the impeller is made of either plastic or rubber, and should be inspected after 300 hours of operation. Replace the impeller if it is worn. Whereas, if the pumps head is made of bronze, then the impeller is too, and regular maintenance is not needed as often.
Seawater Strainer
Check the seawater strainer daily. Remove any debris.
Refrigerant Gas
The refrigerant gas used in the air conditioning system is adequate for the life of the system. Routine seasonal charging of the system is not typically necessary.
L-2362 Maintenance
17
English
Section I
What does the Limited Warranty cover?
Products manufactured by Dometic Corporation (Dometic) are under limited warranty to be free from defects in workmanship or materials under normal use and service with the obligation of Dometic under this limited warranty being limited to replacing or repairing any component(s) which shall disclose defects within the time limits defined in Section III and which, upon examination by Dometic, shall appear to the satisfaction of Dometic to be defective or not up to specifications.
goods are used. The duration of any implied warranty rights is limited to the duration of the express warranty as found in Section III. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
Section II
What does this Limited Warranty not cover? This Warranty Shall Not Apply to:
1. Failures resulting from improper installation or use contrary to instructions. 2. Failures resulting from abuse, misuse, accident, fire, or submergence. 3. Any part manufactured by Dometic which shall have been altered so as to impair its original characteristics. 4. Any parts which fail as a result of misuse, improper application or improper installation. 5. Items not manufactured by Dometic, i.e., items which are purchased from another manufacturer and supplied as received by Dometic without alteration or modification except as any part of an Dometic-manufactured unit or component. 6. Components or parts used by or applied by the purchaser as an integral part of products not manufactured by Dometic. 7. Warranty does not cover damage to components that comprise a Custom Wrapped Box Evaporator refrigeration system (aka: catch boxes, fish boxes, etc.) when the box is installed in such a way that the customer can move it. These damages may include, but are not limited to: crimped refrigerant linesets (copper tubing or flexible linesets), refrigerant leaks, moisture ingression into the refrigeration system, subsequent damage to condensing unit from being operated with low refrigerant charge or moisture in the system, broken refrigerant connections, broken thermostat sensors, and/or broken constant pressure valves. Installation and application of Dometic components is not warranted by Dometic because Dometic has no control or authority over the selection, location, application, or installation of these components.
This Limited Warranty is made in lieu of all other express warranties, obligations, or liabilities on the part of Dometic. In addition, Dometic shall not be responsible for any incidental or consequential damages. In those instances in which a cash refund is made, such refund shall effect the cancellation of the contract of sale without reservation of rights on the part of the purchaser. Such refund shall constitute full and final satisfaction of all claims which purchaser has or may have against Dometic due to any actual or alleged breach of warranty, either express or implied, including, without limitation, any implied warranty of merchantability or fitness for a particular purpose. Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation may not apply to you. The terms and conditions of this warranty shall be governed by the laws of the Commonwealth of Virginia.
The Dealer is not an agent for Dometic except for the purpose of administering the above warranty to the extent herein provided, and Dometic does not authorize the dealer or any other person to assume for Dometic any liability in connection with such warranty, or any liability or expense incurred in the replacement or repair of its products other than those expressly authorized herein. Dometic shall not be responsible for any liability or expense except as is specifically authorized and provided in this section. Dometic reserves the right to improve its products through changes in design or material without being obligated to incorporate such changes in products of prior manufacture, and to make changes at any time in design, materials, or part of units of any one year's model, without obligation or liability to owners of units of the same year's model of prior manufacture. This warranty gives you, the purchaser, specific legal rights, and you may also have other rights which vary from state to state. You also have implied warranty rights, including an implied warranty of merchantability, which means that your product must be fit for the ordinary purposes for which such
L-2362
Section III
What is the period of coverage?
See the Limited Warranty Periods, document # L-0694, for the period of coverage. 18
English
All Dometic components bear a data plate on which there are model and serial numbers. The serial number is date coded. To determine whether or not any Dometic component is in warranty, proceed as follows: 1. Determine the manufacture date of the component from the serial number on the data plate. If you are not familiar with the date code, write or call the Dometic Customer Service Department at (804)746-1313, to obtain the manufacture date. The hours of the Customer Service Department are 8:00 am - 5:00 pm (USA, Eastern Time Zone) Monday through Friday excluding holidays. 2. It is possible that there might exist a considerable time lag between the date a component is manufactured and the date it is put in service. In such instances, the date of manufacture could indicate that the item is out of warranty. However, based on the date the equipment is first put in service, the item may still be covered by the Dometic warranty described in Section I. For proof of date put in service, Dometic will require a copy of the bill of sale of the Dometic equipment from the installer or new boat dealer to the original owner.
WARNING
Dometic Corporation (Dometic) manufacturers of Cruisair, Grunert, Marine Air, Sentry and Tundra Products, makes the following safety warnings concerning the application, installation, use and care of its products. Although these warnings are extensive, there may be specific hazards which may arise out of circumstances which we have not outlined herein. Use this as a guide for developing an awareness of potential hazards of all kinds. Such an awareness will be a key factor in assuring your SAFETY and comfort. ELECTRICITY - Many Dometic products operate on 115, 230 or 440 volt AC power. Such voltages can be LETHAL; therefore, the chassis, cabinets, bases, etc., on all components must be grounded together and connected to the vessel's grounding system. Sparks can occur as switches, thermostats and relays open and close in the normal operation of the equipment. Since this is the case, ventilating blowers for the removal of hazardous fumes or vapors should be operated at least 5 minutes before and during operation of any Dometic product or group of Dometic products. All electrical connections must be covered and protected so accidental contact cannot be made by persons using the equipment, as such contact could be LETHAL. ELECTROLYSIS - Electrical leakage of any component can cause electrolytic deterioration (electrolysis) of thru-hull components which could result in leakage serious enough to sink a vessel which could result in loss of life. All Dometic components must be kept clean and dry and checked periodically for electrical leakage. If any electrical leakage is detected, the component should be replaced or the fault causing the leakage corrected before the component is put back into service. GAS - CRUISAIR, MARINE AIR, GRUNERT and TUNDRA components utilize R-22 (Chlorodifluoromethane), R134a refrigerant (Tetrafluoroethane), R-407C (which contains Diflouromethane (HFC-32), Pentafluoroethane (HFC125), and 1.1.1.2 Tetrafluoroethane (HFC134a)), R404A (R125/R143a/R134 (44%/52%/4%)), or R417a, which are non-toxic, non-flammable gases; however, these gases contain no oxygen and will not support life. Refrigerant gas tends to settle in the lowest areas of the compartment. If you experience a leak, evacuate all personnel, and ventilate area. Do not allow open flames in the area of leaks because refrigerant gas, when burned, decomposes into other potentially LETHAL gases. Refrigerant components operate at high pressure and no servicing should be attempted without gloves, long-sleeved clothing and eye protection. Liquid refrigerant gas can cause severe frost burns to the skin and eyes. VENTILATION - To cool or heat air, CRUISAIR, MARINE AIR and GRUNERT components are designed to move air through a heat exchanger by a blower or propeller fan. This design necessarily produces a suction on one side of the air handling component and a pressure on the other side. Air handling components must be installed so that the suction-pressure action does not: (1) pressurize an area to the extent that structural failure occurs which could cause harm to occupants or bystanders, or (2) cause a suction or low pressure in an area where hydrogen gas from batteries, raw fuel vapor from fuel tanks, carbon monoxide from operating propulsion engines, power generators or heaters, methane gas from sewage holding tanks, or any other dangerous gas or vapor could exist. If an air handling unit is installed in such a manner that allows potentially lethal gases or vapors to be discharged by the air handling unit into the living space, this could result in loss of life. Maximum protection against the introduction of dangerous gases or vapors into living spaces can be obtained by providing living spaces which are sealed from all other spaces by use of airtight bulkheads and decks, etc., and through the introduction of clean air into the living space. Bear in mind that the advent of air conditioning, whether it be for cooling or for heating, naturally leads to the practice of closing a living space tightly. Never close all windows and doors unless auxiliary ventilating systems, which introduce clean outside air into the living space, are used. Always leave enough window and door openings to provide adequate ventilation in the event potentially lethal gases or fumes should escape from any source. CONDENSATE - All cooling units produce water condensate when operating on the cooling cycle. This water must be drained from the cooling unit overboard. If condensate is allowed to drip on a wooden structure, rotting or decay and structural failure may occur which could result in loss of life. If condensate is allowed to drip on electrical components, deterioration of the electrical components could result in hazardous conditions. When an air conditioning system is in operation, condensate drains may be subjected to negative pressure. Always locate condensate drains as far as possible from points where engine waste and other dangerous gases are exhausted so no such dangerous gases can be drawn into the condensate drains.
Section IV
How do you get service? Please Read the following Warranty Procedure.
WARRANTY PROCEDURE
If the failure of a Dometic component is determined to be covered under the Dometic warranty and the time in service is determined to be within the warranty time limit, the owner has the following three options: 1. Preferred option: Have a Dometic authorized Servicing Dealer perform the work needed. The customer should call Dometic's Service Department for a recommendation as to the closest dealer. If the customer already knows an authorized servicing dealer, the dealer should be contacted directly. 2. If the customer contacts Dometic's Service Department for a Servicing Dealer and Dometic has no one in that particular area, Dometic will authorize the use of a local service company and Dometic will work with the local company to assist in any way possible. 3. The customer may send his equipment back to the factory to have the repair work done. Dometic will make every effort to return the equipment to the customer within a three week time period. If the claim represents a legitimate warranty problem, Dometic will pay the freight both ways. Dometic prefers option one and two, if at all possible. The customer may contact the Dometic Service Department at (804) 746-1313.
Warning
Never sleep in a closed area on a boat when any equipment, which functions as a result of the combustion of a volatile fuel, is in operation (such as engines, generators, power plants, or oil-fired heaters, etc.). At any time, the exhaust system of such devices could fail, resulting in a build-up of LETHAL gases within the closed area.
L-0123
L-2362
Revised: 10-16-03
19
English
Refrigerators/Freezers/Fish Boxes
The below warranty periods do not apply to systems that are installed as described in Section II, item #7, of the Owners Limited Warranty, document # L-0123. New installation of entire system including condensing unit, line sets, evaporator, etc. 1 year warranty including Parts and Labor New complete model sold as a partial system retrofit to an existing Cruisair system. 1 year warranty including Parts and Labor New installation of condensing unit only, with line sets, evaporators, etc. done by others i.e. not Cruisair precharged line sets and evaporators. 1 year warranty including parts and labor on mechanical and electrical parts of condensing unit only.
Replacement Parts
Replacement parts and components - example: A-509, 40401-30. 90 day warranty, Parts only Replacement Compressors for other than Tempered Water Systems - example: R3101-16T, DX equipment installed in an existing Cruisair system or a competitors system. 1 year warranty including Parts and Labor Replacement compressors for Tempered Water - example: 30130-36 installed in an existing Cruisair system. 1 year warranty including Parts and Labor A Tempered Water compressor - example: 30130-36 installed with competitors equipment. 90 day warranty, Parts only
* The box denotes the part of the warranty that pertains to this particular product.
L-2362
20
English
Connecticut
USA
AAP Inc.
Location: Milford, VA, USA Territory: National Coach & Mobile Products Only Phone: Fax: Web: 804-633-9454 804-633-5499 www.aap.com
Martin's Marine
Location: Wilmington, NC, USA Territory: North Carolina and Myrtle Beach, SC Phone: Fax: 910-799-9362 910-793-4267
Angola
Southern Power Products
Location: Cape Town, South Africa Phone: Fax: E-mail: 27-21-511-0653 27-21-510-3049 sales@southernpower.co.za
Bangladesh
Tritex Equipment Pte. Ltd.
Location: , Singapore Phone: Fax: E-mail: Web: (65) 6861 1188 (65) 6861 4263, (65) 6861 8797 sales@tritex.com.sg www.tritex.com.sg
Antigua
Aboard Refrigeration
Location: English Harbour, Antigua Phone: Fax: E-mail: 268-460-1690 419-858-0544 aboardrf@candw.ag
Belgium
Eberca
Location: , Netherlands Phone: Fax: E-mail: 31 186621955 31 186621818 info@eberca.nl
Bermuda
Flatt's Marine
Location: St. Georges, Bermuda Phone: Fax: E-mail: 441-293-5740 441-293-5740 bermudabanger@ibl.bm
Argentina
Trimer S.A.
Location: Buenos Aires, Argentina Phone: Fax: E-mail: Web: 5411-4580-0444 5411-4580-0440 trimer@trimer.com.ar www.trimer.ar
Botswana
Southern Power Products
Location: Cape Town, South Africa Phone: Fax: E-mail: 27-21-511-0653 27-21-510-3049 sales@southernpower.co.za
Australia
Seabreeze Industries
Location: Coomera, Queensland, Australia Phone: Fax: E-mail: Web: 61-7-55806371 61-7-55806372 seabreez@bigpond.net.au www.seabreeze-industries.com.au
Brazil
Sailing Products
Location: Rio de Janeiro, Brazil Phone: Fax: E-mail: 55 (0) 21 3154-9990 55 (0) 21 2494-7223 sailing@sailing.com.br
Austria
Dometic Marine Italy, Sales Company
Location: Milano, Italy Phone: Fax: E-mail: 390 26172583 390 266010223 marine.info@dometic.it
Sailing Products
Location: Sao Paulo, Brazil Phone: Fax: 55 (0) 11 81 1985 55 (0) 11 81 1936
Bahamas
Freezing Point, Ltd.
Location: Nassau, Bahamas Phone: Fax: E-mail: 242-325-3589 242-356-5271 freezingpoint@bahamas.net.bs
Nixon's Refrigeration
Location: Abaco, Bahamas Territory: Abaco Island only Phone: Fax: E-mail: 242-367-5219 242-367-5219 seannixon@email.com
Marine Power
Location: Grand Cayman Island, British West Indies Phone: Fax: E-mail: 345-947-1945 345-947-1909 mpower@candw.ky
Bahrain
Mantech
Location: Dubai, United Arab Emirates Phone: Fax: E-mail: 971 4 333 25 42 971 4 333 06 49 mge@emirates.net.ae
Canada
British Columbia Accutemp Refrigeration and Air Conditioning
Location: Victoria, BC, Canada Territory: Western Canada Phone: Fax: E-mail: Web: 250-475-2665 250-475-1957 info@accutemp.ca www.accutemp.ca
Dr. Ice
Location: St. Thomas, US Virgin Islands Territory: St. Thomas Phone: Fax: E-mail: 340-775-4540 340-775-6575 lastlaugh44@pennswoods.net
Enertech N.V.
Location: Simpson Bay, St. Maarten/St. Martin, Netherland Antilles Phone: Fax: E-mail: Web: 599-551-2145 305-675-5857 (USA) service@enertechnv.com www.enertechnv.com
China
Chi-Mo Inc.
Location: Shanghai, China Phone: Fax: E-mail: Web: 8621-5917-1111 8621-5917-1166 sales@springfieldmarine.com.cn www.springfieldmarine.com.cn
Iceberg Refrigeration
Location: Guadeloupe, French West Indies Phone: Fax: E-mail: 590-24 35 35 590-24 35 35 iceberg.refrigeration@wanadoo.fr
Caribbean Islands
Aboard Refrigeration
Location: English Harbour, Antigua Phone: Fax: E-mail: 268-460-1690 419-858-0544 aboardrf@candw.ag
Marine Power
Location: Grand Cayman Island, British West Indies Phone: Fax: E-mail: 345-947-1945 345-947-1909 mpower@candw.ky
C.S. Services
Location: Martinique, French West Indies Phone: Fax: 596-749113 596-749174
Costa Rica
Costa Rica Yacht Sales
Location: Marina Los Sueos, Playa Herradura, Costa Rica Territory: Costa Rica, Panama Phone: Fax: E-mail: 506-637-7181 506-637-7180 airwick@costarica.net
Nixon's Refrigeration
Location: Abaco, Bahamas Territory: Abaco Island only Phone: Fax: E-mail: 242-367-5219 242-367-5219 seannixon@email.com
Metro Marine
Location: Herradura, Costa Rica Phone: Fax: 506-643-3942 506-643-2426
Outfitters International
Location: St. Georges, Grenada Phone: Fax: E-mail: 473-440-7949 473-440-6680 footloos@caribsurf.com
Croatia
Dometic Marine Italy, Sales Company
Location: Milano, Italy Phone: Fax: E-mail: 390 26172583 390 266010223 marine.info@dometic.it
Reefco
Location: St. Thomas, U.S. Virgin Islands Phone: Fax: E-mail: 340-776-0038 340-776-0038 dennyedy@viaccess.net
Cyprus
Dometic Marine - United Kingdom, Sales Company
Location: Poole, Dorset, United Kingdom Phone: Fax: E-mail: Web: 44 (0) 870 3306101 44 (0) 870 3306102 sales@dometicmarine.com www.dometic.com
Germany
GEMO GmbH
Location: Travemunde, Germany Phone: Fax: E-mail: Web: 49-4502-2466 49-4502-2425 gemo_gmbh@t-online.de www.gemo_online.de
Italy
Cummins Diesel Italia S.P.A
Location: Milan, Italy Territory: Central & Southern Italy Phone: Fax: E-mail: 39 02 51 655 856 39 02 51 65 58 55 luigi.casaburi@cummins.com
Greece
Dometic Marine - United Kingdom, Sales Company
Location: Poole, Dorset, United Kingdom Phone: Fax: E-mail: Web: 44 (0) 870 3306101 44 (0) 870 3306102 sales@dometicmarine.com www.dometic.com
Dominican Republic
Agencias Navieras B&R S.A.
Location: Santo Domingo, Dominican Republic Territory: Dominican Republic Phone: Fax: E-mail: 809-562-3353 809-562-3383 hsosa@navierasbr.com
E.T.N. S.A.S.
Location: Milan, Italy Territory: Northwest Italy Phone: Fax: E-mail: 390-2-253-6115 390-2-253-6115 geolino@tiscalinet.it
Grenada
Outfitters International
Location: St. Georges, Grenada Phone: Fax: E-mail: 473-440-7949 473-440-6680 footloos@caribsurf.com
Egypt
Climate Company
Location: Cairo, Egypt Phone: Fax: E-mail: 20-2-2598092 20-2-4523028 climate@tedata.net.eg
Japan
Gunji Corporation
Location: Osaka, Japan Phone: Fax: E-mail: Web: 81-6-6451-5615 81-6-6454-0056 gunji@gunji.com www.gunji.com
Guam
Fentress Refrigeration Service Co.
Location: Tamuning, Guam Phone: Fax: 671-565-4038 671-565-3315
Equador
Navas-Bustos Representaciones
Location: Guayaquil, Equador Phone: Fax: 593-2-252542 593-2-251-421
Guatemala
Automotores y Marina, S.A.
Location: Villa Nueva, Guatemala Phone: Fax: E-mail: 502-6631-2033 502-6631-2034 info@automotoresymarina.com
Kuwait
Mantech
Location: Dubai, United Arab Emirates Phone: Fax: E-mail: 971 4 333 25 42 971 4 333 06 49 mge@emirates.net.ae
Eritrea
DM Electrical Engineering
Location: Asmara, Eritrea Phone: Fax: 291-1-126737 291-1-127650
Hong Kong
Astral Marine, Ltd.
Location: Sai Kung, NT, Hong Kong Phone: Fax: E-mail: Web: 852-2719-5982 852-2335-0580 funcle@pacific.net.hk www.astral.com.hk
Luxembourg
Eberca
Location: , Netherlands Phone: Fax: E-mail: 31 186621955 31 186621818 info@eberca.nl
France
Dometic Marine - France, Sales Company
Location: 60 128 Plailly, France Phone: Fax: E-mail: Cell: 0033 (0)680 415 543 0033 (0)344 633 518 marine.sales@dometic.fr
Malaysia
Tritex Equipment Pte. Ltd.
Location: , Singapore Phone: Fax: E-mail: Web: (65) 6861 1188 (65) 6861 4263, (65) 6861 8797 sales@tritex.com.sg www.tritex.com.sg
Polymarine Distribution
Location: Cannet, Rocheville, France Phone: Fax: E-mail: 0033 493463634 0033 493463634 polymarine.bayle@free.fr
Indonesia
Tritex Equipment Pte. Ltd.
Location: , Singapore Phone: Fax: E-mail: Web: (65) 6861 1188 (65) 6861 4263, (65) 6861 8797 sales@tritex.com.sg www.tritex.com.sg
Maldives
Tritex Equipment Pte. Ltd.
Location: , Singapore Phone: Fax: E-mail: Web: (65) 6861 1188 (65) 6861 4263, (65) 6861 8797 sales@tritex.com.sg www.tritex.com.sg
Israel
Yamit Mil Ltd.
Location: Tel-Aviv, Israel Phone: Fax: E-mail: 972-3-5271778 972-3-5271772 mil@yamitysb.co.il
Iceberg Refrigeration
Location: Guadeloupe, French West Indies Phone: Fax: E-mail: 590-24 35 35 590-24 35 35 iceberg.refrigeration@wanadoo.fr
Malta
Dometic Marine - United Kingdom, Sales Company
Location: Poole, Dorset, United Kingdom Phone: Fax: E-mail: Web: 44 (0) 870 3306101 44 (0) 870 3306102 sales@dometicmarine.com www.dometic.com
Philippines
Tritex Equipment Pte. Ltd.
Location: , Singapore Phone: Fax: E-mail: Web: (65) 6861 1188 (65) 6861 4263, (65) 6861 8797 sales@tritex.com.sg www.tritex.com.sg
New Caledonia
Altomarine
Location: Noumea, New Caledonia Phone: Fax: E-mail: 687 25 96 12 687 25 43 30 altomar@altomarine.com
Portugal
Powercool Lda
Location: Portimao, Portugal Phone: Fax: E-mail: Web: 351 91 786 63 73 351 282 461 818 info@powercool.org www.powercool.org
Inmartech Ltd
Location: Swieqi, STJ 04, Malta Territory: Malta Phone: Fax: E-mail: 00356 21376476 00356 21376476 inmartech@waldonet.net.mt
New Zealand
Whiting Power Systems
Location: Auckland, New Zealand Phone: Fax: E-mail: Web: 64-9-358-2050 64-9-358-0285 sales@whiting.co.nz www.whitingpower.com
Mexico
Southern California Marine Enterprises
Location: San Diego, CA, USA Phone: Fax: E-mail: Web: 619-224-2869 619-226-0496 sales@southerncalmarine.com www.southerncalmarine.com
Puerto Rico
Centro Cruisair de Puerto Rico
Location: Santurce, Puerto Rico Phone: Fax: E-mail: 787-727-3637 787-727-3637 fernan_moreno@hotmail.com
Norway
Refnor A.S.
Location: sters, Norway Phone: Fax: E-mail: 47-67 14 07 50 47-67 14 70 88 refnor.as@c2i.net
Monaco
Polymarine Distribution
Location: Cannet, Rocheville, France Phone: Fax: E-mail: 0033 493463634 0033 493463634 polymarine.bayle@free.fr
Oman
Hi-Tech Projects LLC
Location: Muscat, Oman Phone: Fax: E-mail: 968-595056/57/58 968-595054 hitech1@omantel.net.om
Mozambique
Southern Power Products
Location: Cape Town, South Africa Phone: Fax: E-mail: 27-21-511-0653 27-21-510-3049 sales@southernpower.co.za
Mantech
Location: Dubai, United Arab Emirates Phone: Fax: E-mail: 971 4 333 25 42 971 4 333 06 49 mge@emirates.net.ae
Myanmar
Tritex Equipment Pte. Ltd.
Location: , Singapore Phone: Fax: E-mail: Web: (65) 6861 1188 (65) 6861 4263, (65) 6861 8797 sales@tritex.com.sg www.tritex.com.sg
Pakistan
Communications & Machinery Corp.
Location: Karachi, Pakistan Phone: Fax: E-mail: 92-21-5678252 92-21-5683283 cmcorp@cyber.net.pk
Nambia
Southern Power Products
Location: Cape Town, South Africa Phone: Fax: E-mail: 27-21-511-0653 27-21-510-3049 sales@southernpower.co.za
Qatar
Laffan Marine
Location: Doha, Qatar Phone: Fax: E-mail: 974-4326893/4328021 974-4327452 laffanmarine@qatar.net.qa
Panama
Costa Rica Yacht Sales
Location: Marina Los Sueos, Playa Herradura, Costa Rica Territory: Costa Rica, Panama Phone: Fax: E-mail: 506-637-7181 506-637-7180 airwick@costarica.net
Netherlands
Eberca
Location: , Netherlands Phone: Fax: E-mail: 31 186621955 31 186621818 info@eberca.nl
Mantech
Location: Dubai, United Arab Emirates Phone: Fax: E-mail: 971 4 333 25 42 971 4 333 06 49 mge@emirates.net.ae
Russia
Standarte
Location: Starbeevo, Moscow region, Russia Phone: Fax: E-mail: Web: 7 095 575 67 23 7 095 575 39 77 info@standarte.ru www.standarte.ru
Netherlands Antilles
Enertech N.V.
Location: Simpson Bay, St. Maarten/St. Martin, Netherland Antilles Phone: Fax: E-mail: Web: 599-551-2145 305-675-5857 (USA) service@enertechnv.com www.enertechnv.com
Saudi Arabia
Mantech
Location: Dubai, United Arab Emirates Phone: Fax: E-mail: 971 4 333 25 42 971 4 333 06 49 mge@emirates.net.ae
Samaco Marine
Location: Jeddah, Saudi Arabia Phone: Fax: 966-2-6990064 966-2-6991024
Switzerland
Marine Parts Heimgartner
Location: Volketswil, Switzerland Phone: Fax: E-mail: Web: 41-1-997 40 90 41-1-997 40 94 info@marineparts.ch www.marineparts.ch
Ukraine
Standarte
Location: Starbeevo, Moscow region, Russia Phone: Fax: E-mail: Web: 7 095 575 67 23 7 095 575 39 77 info@standarte.ru www.standarte.ru
Scandinavia
Dometic Marine Nordic Sales, Sales Company
Location: Halmstad, Sweden Phone: Fax: E-mail: Web: +46 35 16 57 00 +46 35 16 57 10 marine.info@dometic.se www.dometic.com
Taiwan
Ing Hai Company, Ltd.
Location: Kaohsiung, Taiwan Phone: Fax: 886-7-802-1809 886-7-802-1809
Refnor A.S.
Location: sters, Norway Phone: Fax: E-mail: 47-67 14 07 50 47-67 14 70 88 refnor.as@c2i.net
United Kingdom
Dometic Marine - United Kingdom, Sales Company
Location: Poole, Dorset, United Kingdom Phone: Fax: E-mail: Web: 44 (0) 870 3306101 44 (0) 870 3306102 sales@dometicmarine.com www.dometic.com
Singapore
Tritex Equipment Pte. Ltd.
Location: , Singapore Phone: Fax: E-mail: Web: (65) 6861 1188 (65) 6861 4263, (65) 6861 8797 sales@tritex.com.sg www.tritex.com.sg
Thailand
Thai Kolon Co. Ltd.
Location: Bangkok, Thailand Phone: Fax: E-mail: 66-2-745-6468-77 (10 lines) 66-2-745-6152 thkolon@ji-net.com
Uruguay
Trimer S.A.
Location: Buenos Aires, Argentina Phone: Fax: E-mail: Web: 5411-4580-0444 5411-4580-0440 trimer@trimer.com.ar www.trimer.ar
Slovenia
Dometic Marine Italy, Sales Company
Location: Milano, Italy Phone: Fax: E-mail: 390 26172583 390 266010223 marine.info@dometic.it
Venezuela
Rich Marine Center, C.A.
Location: Puerto La Cruz,, Estado Anzoategui, Venezuela Phone: Fax: E-mail: Web: 58 281 2181630 58 281 2811630 richmarine@telcel.net.ve www.tuyate.net
Turkey
Dometic Marine - United Kingdom, Sales Company
Location: Poole, Dorset, United Kingdom Phone: Fax: E-mail: Web: 44 (0) 870 3306101 44 (0) 870 3306102 sales@dometicmarine.com www.dometic.com
South Africa
Southern Power Products
Location: Cape Town, South Africa Phone: Fax: E-mail: 27-21-511-0653 27-21-510-3049 sales@southernpower.co.za
West Indies
Regis Electronics (St Lucia) LTD.
Location: St. Lucia, West Indies Phone: Fax: E-mail: 758-452-0205 758-452-0206 stlucia@regiselectronics.com
Spain
Acastimar
Location: Tarragona, Spain Phone: Fax: E-mail: 349-77-362118 349-77-362687 acastimar@acastimar.com
Zambia
Southern Power Products
Location: Cape Town, South Africa Phone: Fax: E-mail: 27-21-511-0653 27-21-510-3049 sales@southernpower.co.za
Sri Lanka
G&M Enterprises
Location: Borella-Colombo 8, Sri Lanka Phone: Fax: E-mail: 94-11-2691966 94-11-2691751 gandm@sltnet.lk
Zimbabwe
Southern Power Products
Location: Cape Town, South Africa Phone: Fax: E-mail: 27-21-511-0653 27-21-510-3049 sales@southernpower.co.za
Dr. Ice
Location: St. Thomas, US Virgin Islands Territory: St. Thomas Phone: Fax: E-mail: 340-775-4540 340-775-6575 lastlaugh44@pennswoods.net
Sweden
Dometic Marine Nordic Sales, Sales Company
Location: Halmstad, Sweden Phone: Fax: E-mail: Web: +46 35 16 57 00 +46 35 16 57 10 marine.info@dometic.se www.dometic.com
Reefco
Location: St. Thomas, U.S. Virgin Islands Phone: Fax: E-mail: 340-776-0038 340-776-0038 dennyedy@viaccess.net
Dometic Corporation
Environmental Systems
P.O. Box 15299 Richmond, VA 23227-0699 USA Phone: 804-746-1313 Facsimile: 804-746-7248 For Sales and Service Calls within Europe and the Middle East, please contact +44 (0) 870 330 6101 Email: sales@cruisair.com Website: www.cruisair.com
L-2362