User's Manual
QX10 QY10
QX10-TS QY10-TS
QX28 QY18A
QX40 QY22
QX40-S1 QY40P
QX40-TS QY40P-TS
QX40H QY41H
QX41 QY41P
QX41-S1 QY42P
QX41-S2 QY50
QX42 QY68A
QX42-S1 QY70
QX50 QY71
QX70 QY80
QX70H QY80-TS
QX71 QY81P
QX72 QY82P
QX80 QH42P
QX80-TS QX41Y41P
QX80H QX48Y57
QX81 QI60
QX81-S2
QX82
QX82-S1
QX90H
SAFETY PRECAUTIONS
(Read these precautions before using this product.)
Before using this product, please read this manual and the relevant manuals carefully and pay full
attention to safety to handle the product correctly.
The precautions given in this manual are concerned with this product only. For the safety precautions of
the programmable controller system, refer to the user’s manual for the CPU module used.
In this manual, the safety precautions are classified into two levels: " ! WARNING" and " ! CAUTION".
Under some circumstances, failure to observe the precautions given under " ! CAUTION" may lead to
serious consequences.
Observe the precautions of both levels because they are important for personal and system safety.
Make sure that the end users read this manual and then keep the manual in a safe place for future
reference.
[Design Precautions]
! WARNING
• Configure safety circuits external to the programmable controller to ensure that the entire system
operates safely even when a fault occurs in the external power supply or the programmable
controller. Failure to do so may result in an accident due to an incorrect output or malfunction.
(1) Configure external safety circuits, such as an emergency stop circuit, protection circuit, and
protective interlock circuit for forward/reverse operation or upper/lower limit positioning.
(2) When the programmable controller detects an abnormal condition, it stops the operation and
all outputs are:
(a) Turned off if the overcurrent or overvoltage protection of the power supply module is
activated.
(b) Held or turned off according to the parameter setting if the self-diagnostic function of the
CPU module detects an error such as a watchdog timer error.
Note, however, that AnS series modules on the system turn off all outputs in both cases.
All outputs may turn on if an error occurs in a part, such as an I/O control part, where the
CPU module cannot detect any error. To ensure safety operation in such a case, provide a
safety mechanism or a fail-safe circuit external to the programmable controller. For a fail-
safe circuit example, refer to the user’s manual for the CPU module used.
(3) Outputs may remain on or off due to a failure of an output module relay or transistor.
Configure an external circuit for monitoring output signals that could cause a serious
accident.
A-1 A-1
[Design Precautions]
! WARNING
• In an output module, when a load current exceeding the rated current or an overcurrent caused
by a load short-circuit flows for a long time, it may cause smoke and fire. To prevent this,
configure an external safety circuit, such as a fuse.
• Configure a circuit so that the programmable controller is turned on first and then the external
power supply.
If the external power supply is turned on first, an accident may occur due to an incorrect output
or malfunction.
• For the operating status of each station after a communication failure, refer to relevant manuals
for each network.
Incorrect output or malfunction due to a communication failure may result in an accident.
• When changing data of the running programmable controller from a peripheral connected to the
CPU module or from a personal computer connected to an intelligent function module, configure
an interlock circuit in the sequence program to ensure that the entire system will always operate
safely.
For other controls to a running programmable controller (such as program modification or
operating status change), read relevant manuals carefully and ensure the safety before the
operation.
Especially, in the case of a control from an external device to a remote programmable controller,
immediate action cannot be taken for a problem on the programmable controller due to a
communication failure.
To prevent this, configure an interlock circuit in the sequence program, and determine corrective
actions to be taken between the external device and CPU module in case of a communication
failure.
[Design Precautions]
! CAUTION
• Do not install the control lines or communication cables together with the main circuit lines or
power cables.
Keep a distance of 100mm or more between them.
Failure to do so may result in malfunction due to noise.
• When a device such as a lamp, heater, or solenoid valve is controlled through an output module,
a large current (approximately ten times greater than normal) may flow when the output is
turned from off to on. Take measures such as replacing the module with one having a sufficient
current rating.
A-2 A-2
[Security Precautions]
! WARNING
• To maintain the security (confidentiality, integrity, and availability) of the programmable controller
and the system against unauthorized access, denial-of-service (DoS) attacks, computer viruses,
and other cyberattacks from external devices via the network, take appropriate measures such
as firewalls, virtual private networks (VPNs), and antivirus solutions.
[Installation Precautions]
! CAUTION
• Use the programmable controller in an environment that meets the general specifications in the
user’s manual for the CPU module used.
Failure to do so may result in electric shock, fire, malfunction, or damage to or deterioration of
the product.
• To mount the module, while pressing the module mounting lever located in the lower part of the
module, fully insert the module fixing projection(s) in the hole(s) in the base unit and press the
module until it snaps into place.
Incorrect interconnection may cause malfunction, failure, or drop of the module.
When using the programmable controller in an environment of frequent vibrations, fix the
module with a screw.
Tighten the screw within the specified torque range.
Undertightening can cause drop of the screw, short circuit or malfunction.
Overtightening can damage the screw and/or module, resulting in drop, short circuit, or
malfunction.
• When using an extension cable, connect it to the extension cable connector of the base unit
securely.
Check the connection for looseness.
Poor contact may cause incorrect input or output.
• When using a memory card, fully insert it into the memory card slot.
Check that it is inserted completely.
Poor contact may cause malfunction.
• Shut off the external power supply for the system in all phases before mounting or removing the
module.
Failure to do so may result in damage to the product.
• Do not touch the module during turning on electricity and immediately after power supply
interception. There is fear of a burn.
• Do not directly touch any conductive parts and electronic components of the module.
Doing so can cause malfunction or failure of the module.
A-3 A-3
[Wiring Precautions]
! WARNING
• Shut off the external power supply for the system in all phases before wiring.
Failure to do so may result in electric shock or damage to the product.
• After wiring, attach the included terminal cover to the module before turning it on for operation.
Failure to do so may result in electric shock.
[Wiring Precautions]
! CAUTION
• Individually ground the FG and LG terminals of the programmable controller with a ground
resistance of 100 Ω or less.
Failure to do so may result in electric shock or malfunction.
• Check the rated voltage and terminal layout before wiring to the module, and connect the cables
correctly.
Connecting a power supply with a different voltage rating or incorrect wiring may cause a fire or
failure.
• Connectors for external devices must be crimped or pressed with the tool specified by the
manufacturer, or must be correctly soldered.
Incomplete connections may cause short circuit, fire, or malfunction.
• When connecting or removing the connectors for external devices, insert or remove them
perpendicularly to the surface.
Pushing in or pulling out them at an angle may cause poor contact due to distorted connector
pins, resulting in malfunction.
• Tighten the terminal screw within the specified torque range.
Undertightening can cause short circuit, fire, or malfunction.
Overtightening can damage the screw and/or module, resulting in drop, short circuit, or
malfunction.
• Prevent foreign matter such as dust or wire chips from entering the module.
Such foreign matter can cause a fire, failure, or malfunction.
• A protective film is attached to the top of the module to prevent foreign matter, such as wire
chips, from entering the module during wiring.
Do not remove the film during wiring.
Remove it for heat dissipation before system operation.
• Mitsubishi Electric programmable controllers must be installed in control panels.
Connect the main power supply to the power supply module in the control panel through a relay
terminal block.
Wiring and replacement of a power supply module must be performed by qualified maintenance
personnel with knowledge of protection against electric shock.
(For wiring methods, refer to the QCPU User's Manual (Hardware Design, Maintenance and
Inspection).)
A-4 A-4
[Startup and Maintenance Precautions]
! WARNING
• Do not touch any terminal while power is on.
Doing so will cause electric shock.
• Correctly connect the battery connector.
Do not charge, disassemble, heat, short-circuit, or solder the battery, or throw it into the fire.
Doing so will cause the battery to produce heat, explode, or ignite, resulting in injury and fire.
• Shut off the external power supply for the system in all phases before cleaning the module or
retightening the terminal screws or module fixing screws.
Failure to do so may result in electric shock.
Undertightening the terminal screws can cause short circuit or malfunction.
Overtightening can damage the screw and/or module, resulting in drop, short circuit, or
malfunction.
[Disposal Precautions]
! CAUTION
• When disposing of this product, treat it as industrial waste.
A-5 A-5
• CONDITIONS OF USE FOR THE PRODUCT •
A-6 A-6
REVISIONS
The manual number is given on the bottom left of the back cover.
Print Date Manual Number Revision
Dec., 1999 SH(NA)-080042-A First edition
Feb., 2000 SH(NA)-080042-B Addition model
QH42P, QX48Y57, QX70, QX71, QX72, QY18A
Addition
Chapter 4
Partial correction
Section 1.2, Chapter 5, 8.1
Chapters 4 to 8 (changed into Chapters 5 to 9)
Apr., 2000 SH(NA)-080042-C Deletion
QY18A
Jul., 2000 SH(NA)-080042-D Addition model
QX28, QX40-S1, QY18A, QY22, QI60
Addition
Chapter 5
Partial correction
Section 1.2
Chapters 5 to 9 (changed into Chapters 6 to 10)
Nov., 2000 SH(NA)-080042-E Addition model
QY70, QY71
Addition
Section 1.3
Partial correction
CONTENTS, Section 3.3, 5.1
Jan., 2001 SH(NA)-080042-F Addition model
QY68A
Addition
Section 10.2
Partial correction
CONTENTS, Section 1.2, 3.3, 5.1, Chapters 7
Mar., 2001 SH(NA)-080042-G Partial correction
Section 2.4, 8.1
Jul., 2001 SH(NA)-080042-H Addition model
Q6TE-18S
Addition
Chapter 9, APP 1.3
Partial correction
CONTENTS, Section 2.1, 2.2, 2.4, 5.1
Chapters 9 to 10 (changed into Chapters 10 to 11)
Jul., 2002 SH(NA)-080042-I Addition model
QX41-S1, QX42-S1, A6CON4
A-7 A-7
Print Date Manual Number Revision
Mar., 2003 SH(NA)-080042-J Addition model
QX82
May, 2003 SH(NA)-080042-K Partial correction
Section 1.2, 2.2
May, 2003 SH(NA)-080042-L Addition model
QX82-S1
Partial correction
Section 1.2, 3.3
Addition
Section 2.15
Jul., 2004 SH(NA)-080042-M Partial correction
Section 1.2, 2.1 to 2.15, 3.1 to 3.12, 4.1, 4.2, 5.1, 8.1, 8.2.1, 8.2.2, 10
Jul., 2005 SH(NA)-080042-N Partial correction
SAFETY PRECAUTIONS, Section 3.3
Addition
Appendix 1.3
Apr., 2006 SH(NA)-080042-O Partial correction
SAFETY PRECAUTIONS, Section 4.1, Chapter 6
Sep., 2006 SH(NA)-080042-P Partial correction
Section 11.1, 11.2, Appendix 1.2, 1.3
Oct., 2006 SH(NA)-080042-Q Addition model
QX50
Partial correction
SAFETY PRECAUTIONS, Section 2.10 to 2.16, 3.4 to 3.12, 4.1, 4.2
Addition
Section 2.9
Sep., 2007 SH(NA)-080042-R Addition model
QX41Y41P
Partial correction
Section 1.2, 1.3.3, 2.1 to 2.16, 3.1 to 3.12, 4.1, 4.3, 5.1, 7.1, 8.1, Chapter
10, Section 11.1, 11.2, Appendix 1.2
Addition
Section 4.2
Jun., 2008 SH(NA)-080042-S Addition model
QX10-TS, QX40-TS, QX80-TS, QY10-TS, QY40P-TS, QY80-TS
Partial correction
Section 1.2, 2.3 to 2.19, 3.3 to 3.15, 9.2, Chapter 10
Addition
Section 2.2, 2.6, 2.16, 3.2, 3.6, 3.14, 9.1, 9.3
A-8 A-8
Print Date Manual Number Revision
Oct., 2008 SH(NA)-080042-T Addition model
QX40-H, QX70-H, QX80-H, QX90-H
Partial correction
Section 1.2.5, 1.3.1, 2.8 to 2.23, 9.2, Chapter 10
Addition
Section 2.7, 2.14, 2.19, 2.23
Apr., 2009 SH(NA)-080042-U Addition model
QX41-S2, QX81-S2
Partial correction
Section 2.7, 2.11 to 2.25, 5.1, 8.1
Addition
Section 2.10, 2.22
May, 2010 SH(NA)-080042-V External connections are reviewed according to IEC 60617.
Addition model
QY82P
Partial correction
SAFETY PRECAUTIONS, Section 1.1, 1.2, Chapter 2 to 4, Chapter 7,
Section 8.1, Chapter 10, Section 11.1, 11.2, Appendix 1.1
Addition
CONDITIONS OF USE FOR THE PRODUCT, Section 3.16
Jul., 2011 SH(NA)-080042-W Addition model
Q6TE-18SN
Partial correction
Section 1.2.1, 1.2.2, 1.2.3, 1.2.6, 3.11, Chapter 7, Section 9.1, 9.2,
Chapter 10, Section 11.2, Appendix 1.3
Mar., 2012 SH(NA)-080042-X Addition model
QY41H
Partial correction
Section 1.2.2, 2.3, 3.8 to 3.17, Chapter 7, Section 8.1
Addition
Section 3.7
Jun., 2013 SH(NA)-080042-Y Partial correction
Section 1.2.1, 1.3.1, 2.7, 2.15, 2.20, 2.25, 11.2
Dec., 2013 SH(NA)-080042-Z Partial correction
Section 2.8, 2.9, 2.10, 2.11, 2.12, 2.16, 2.17, 2.21, 2.22, 2.23, 2.24, 3.7,
3.8, 3.9, 3.13, 3.16, 3.17, 4.1, 4.2, Chapter 7, Appendix 1.2
Oct., 2014 SH(NA)-080042-AA Partial correction
SAFETY PRECAUTIONS, Section 1.2.2, 3.4, 9.2, 11.2
A-9 A-9
Print Date Manual Number Revision
Sep., 2015 SH(NA)-080042-AB Partial correction
Section 1.2.6, Chapter 2, Chapter 3, Section 5.1, Chapter 6, Section
8.1, Section 9.1, Appendix 1.1, Appendix 1.2, Appendix 1.3, Appendix
1.4
Mar., 2017 SH(NA)-080042-AC Partial correction
Section 1.2.2
Feb., 2018 SH(NA)-080042-AD Partial correction
Section 1.2.3, 2.3, 9.1, 9.2
Nov., 2019 SH(NA)-080042-AE Partial correction
Section 2.7, 2.20
Jun., 2021 SH(NA)-080042-AF Partial correction
SAFETY PRECAUTIONS
Mar., 2024 SH(NA)-080042-AG Partial correction
SAFETY PRECAUTIONS, CONDITIONS OF USE FOR THE
PRODUCT, Chapter 2, 3, 7
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses.
Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which
may occur as a result of using the contents noted in this manual.
1999 MITSUBISHI ELECTRIC CORPORATION
A - 10 A - 10
INTRODUCTION
Thank you for purchasing the Mitsubishi Electric MELSEC-Q series programmable controllers.
Before using this product, please read this manual carefully and develop familiarity with the functions and
performance of the MELSEC-Q series programmable controller to handle the product correctly.
CONTENTS
SAFETY PRECAUTIONS .............................................................................................................................A- 1
CONDITIONS OF USE FOR THE PRODUCT ............................................................................................A- 6
REVISIONS ...................................................................................................................................................A- 7
INTRODUCTION...........................................................................................................................................A- 11
CONTENTS ...................................................................................................................................................A- 11
ABOUT MANUALS .......................................................................................................................................A- 14
COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES ..............................................................A- 14
A - 11 A - 11
2.20 QX80H DC High-speed Input Module (Negative Common Type) ..................................................... 2-26
2.21 QX81 DC Input Module (Negative Common Type) ............................................................................. 2-28
2.22 QX81-S2 DC Input Module (Negative Common Type) ....................................................................... 2-29
2.23 QX82 DC Input Module (Negative Common Type) ............................................................................. 2-30
2.24 QX82-S1 DC Input Module (Negative Common Type) ....................................................................... 2-32
2.25 QX90H DC High-speed Input Module (Negative Common Type) ..................................................... 2-34
5. INTERRUPT MODULE 5- 1 to 5- 2
7. CONNECTORS 7- 1 to 7- 2
A - 13 A - 13
ABOUT MANUALS
Related Manuals
Manual Number
Manual Name
(Model Code)
QCPU User's Manual (Hardware Design/Maintenance and Inspection)
SH-080483ENG
This manual provides the specifications of the CPU modules, power supply modules, base units, extension
(13JR73)
cables, memory cards and others. (Sold separately)
A - 14 A - 14
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
This chapter describes the general specifications and precautions for use of the I/O
modules.
1
Refer to the following manual for the general specifications of the I/O modules.
• QCPU User's Manual (Hardware Design, Maintenance and Inspection)
1-1 1-1
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
(a) When switching to the high-speed input, the specifications of the high-speed
input modules and the input module QX40-S1 are identical. On the other
hand, when switching to the interrupt input, the specifications of the high-
speed input modules and the interrupt module QI60 are identical too.
Therefore, the specifications of the input module (QX40-S1) are construed as
the specifications of the high-speed input module switched to the high-speed
input. Similarly, the specifications of the interrupt module (QI60) indicated in
the manuals other than this manual are construed as the specifications of the
high-speed input module switched to the interrupt input.
(b) By using setting switches on the bottom of the module (refer to Chapter 10),
the high-speed input module switches module types (high-speed input or
interrupt input) for 16 input points all together and between valid and invalid
noise filters as shown below.
1-2 1-2
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
(c) If the small number of value of input response time is set, the modules tend to
have impact of noise. Ensure that the modules do not have impact of noise.
For details of the measure against noise, refer to the QCPU User’s Manual
(Hardware Design, Maintenance and Inspection).
(d) The high-speed input modules connected with electric appliance such as
relays may load a chattering as a signal.
(e) To use a high-speed input module as a CE marked product, keep the cable
length 3m or less.
(1) Maximum switching frequency when the module drives inductive load
The output must be on for one second or longer and off for one second or longer.
1-3 1-3
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
OUT OUT
Diode Diode
COM COM
1-4 1-4
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
1-5 1-5
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
200
100
70
50
Switching life (10,000 times)
30
20
10
5 30VDC =0ms
100VDC
=7ms
100VAC cos =0.7
3 200VAC cos =0.7
(L/R): Time constant 100VAC cos =0.35
cos : Power factor
2 200VAC cos =0.35
24VDC =7ms
120VAC cos =0.2
1-6 1-6
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
POINT
When using the module for the application in which the relay contact is
frequently switched, the relay life span should be considered. It is recommended
to use a triac output module.
1-7 1-7
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
The following table shows the relation between the load and the inrush current.
Select a load so that the inrush current (i) and the rated current (io) will be within
the rated switching current specified for the output module used.
The inrush current may flow for a longer time depending on the load.
Inrush Inrush
Load type Signal waveform diagram current(i)/rated Signal waveform diagram current(i)/rated
current (io) current (io)
Approx. 3 to Approx. 3
10 times times*1
Lamp load
Approx. 5 to
― ―
10 times
1-8 1-8
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
Inrush Inrush
Load type Signal waveform diagram current(i)/rated Signal waveform diagram current(i)/rated
current (io) current (io)
Capacitive Approx. 20 to
― ―
load 40 times
*2: When the wiring of the circuit is long, take care of the wire capacity.
1-9 1-9
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
*1: When using AC power, impedance of CR must be larger enough than that of
the load. (prevention of a malfunction due to leak current from the CR)
(To the next page)
1 - 10 1 - 10
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
Varistor method Select a cut voltage (Vc) for The recovery time delays
the varistor to meet the slightly.
following condition. Multiply
the value by root two for use
of AC power.
Vc Power supply voltage
1.5 (V)
Note that when selecting an
element whose Vc is too high,
its effect will weaken.
POINT
(1) Avoid providing contact protection circuits shown below.
These circuits are effective for preventing an arc at shut-off. However, the
contact welding may occur because the charge current flows to capacitor when
the contact turns on or off.
A DC inductive load is usually harder for switching than a resistor load, but if a
proper protection circuit is configured, the performance will be similar to the
resistor load.
1 - 11 1 - 11
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
A triac may not operate properly if the current forms rectangular waves
associated with sudden current changes. To avoid it, use a load with which the
load current does not form rectangular waves.
(c) Measures for connecting an inductive load
To connect an inductive load, take measures to reduce noise to the side where
the load is connected as shown below.
Varistor method Select a cut voltage (Vc) for The recovery time delays
the varistor to meet the slightly.
following condition.
• Vc > Power supply voltage
1.5(V) √2
This method is not effective
when the Vc is too high.
1 - 12 1 - 12
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
(d) Measures for connecting an inductive load (when installing a contact between
the load and the output terminal)
To install a contact (such as an interlock) between the load and the output
terminal, take measures to reduce noise as shown below.
Though measures (varistor method, capacitor + resistor method) are normally
taken to the load side, in some cases, it is more efficient to take the measures to
the module side considering the contact effect.
Varistor method • Measure taken to the load side Select a cut voltage (Vc) for The recovery time delays
the varistor to meet the slightly.
following condition.
• Vc > Power supply voltage
1.5(V) √2
This method is not effective
• Measure taken to the module side when the Vc is too high.
1 - 13 1 - 13
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
20 Y20
Vacant 32 points
3F Y3F
Module using same I/O numbers for input Module using sequential I/O numbers for input
and output (QH42P) and output (QX41Y41P)
1 - 14 1 - 14
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
The overload protection function and overheat protection function of the following
modules are explained below.
(1) QY40P, QY41P, QY42P, QX41Y41P, QH42P
Function Description
• If an overcurrent due to overload keeps flowing, heat is generated
and the overheat protection function is activated.
• The functions are provided for protecting only the circuits inside
Common
the module.
(Overload and overheat
A load error, which causes an increase in temperature within the
protection functions)
module, may deteriorate output elements or discolour the module
case or printed circuit board. If a load error occurs, turn off the
corresponding output immediately and eliminate the error cause.
• The overload protection function is activated in units of 1 point at
Overload protection 1A to 3A/point.
function • The overload protection function returns to normal operation when
the load becomes a rated load.
• The overheat protection function is activated in units of 1 point.
Overheat protection
• The overheat protection function automatically returns to normal
function
operation after heat reduces.
1 - 15 1 - 15
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
(1) If setting the response time during the interrupt input operation of QI60 or QX40H,
QX70H, QX80H, and QX90H, use the module whose contents are shown below.
The response time cannot be set with other contents (fixed at 0.2ms.).
Product Description
CPU module Product information "021120000000000-B" or later
GX Developer SW6D5C-GPPW or later
For how to check product information of the CPU module, refer to the QCPU User's
Manual (Hardware Design, Maintenance and Inspection).
1 - 16 1 - 16
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
Various settings for the I/O module can be made with GX Developer.
This section describes how to make the settings with GX Developer.
1.3.1 Setting of I/O response time
Set the I/O response time on the I/O assignment tab of PLC Parameter.
(1) For Input/I/O mix module
Select "Input" or "I/O mix" in "Type" combo box on the I/O assignment tab of PLC
parameter. Then, click the "Detailed setting" button, and then select the input
response time in "I/O response time" combo box.
Choose Input/I/O mix. Choose Detailed setting.
1 - 17 1 - 17
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
*1: When the actual response time differs from the setting value, refer to the specifications of
the relevant input modules.
1 - 18 1 - 18
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
*1: If a different module type from the one selected by the function selector switch (switch 2) of
the high-speed input module is selected, an error occurs.
*2: If the noise filter is disabled with the noise filter selector switch (switch 1) of the high-speed
input module, the setting value is ignored.
*3: When the actual response time differs from the setting value, refer to the specifications of
the relevant input modules.
1 - 19 1 - 19
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
Set the error-time output mode on the I/O assignment tab of PLC parameter in GX
Developer.
Select "Output" or "I/O mix" in the "Type" combo box on the I/O assignment tab of PLC
parameter. Then, click the "Detailed setting" button, and then select "Clear" or "Hold" in
the "Error time output mode" combo box.
Choose Output/I/O mix. Choose Detailed setting.
Choose Clear/Hold
(default: Clear).
1 - 20 1 - 20
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
Perform the switch setting on the I/O assignment tab of PLC parameter when
operating the interrupt input for QI60, QX40H, QX70H, QX80H, or QX90H.
Select "Interrupt" in the "Type" combo box on the I/O assignment tab of PLC
parameter. Then, click the "Switch setting" button, and then select "HEX" in the "Input
format" combo box. Lastly, set 0 (leading edge) or 1 (trailing edge) in the "Switch 1"
box for the interrupt processing.
Choose Interrupt. Choose Switch setting.
Choose HEX.
Set the interrupt processing condition with switch 1. The relationships between bits and inputs are as indicated
below.
b15 to b0
XF XE XD XC XB XA X9 X8 X7 X6 X5 X4 X3 X2 X1 X0
1 - 21 1 - 21
1 GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
MEMO
1 - 22 1 - 22
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
External connection
2-1 2-1
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
Rated input current Approx. 8mA (100VAC, 60Hz), approx. 7mA (100VAC, 50Hz)
Input derating Refer to the derating chart.
Inrush current Max. 200mA within 1ms (at 132VAC)
ON voltage/ON current 80VAC or higher/5mA or higher (50Hz, 60Hz)
1
OFF voltage/OFF current 30VAC or lower/1.7mA or lower (50Hz, 60Hz) 2
Input impedance Approx. 12kΩ (60Hz), approx. 15kΩ (50Hz) 3
Response OFF to ON 15ms or less (100VAC 50Hz, 60Hz) 4
time ON to OFF 20ms or less (100VAC 50Hz, 60Hz) 5
Dielectric withstand voltage 1780VAC rms/3 cycles (altitude 2000m) 6
Insulation resistance 10MΩ or more by insulation resistance tester 7
By noise simulator of 1500Vp-p noise voltage, 1 s noise width 8
Noise immunity and 25 to 60Hz noise frequency 9
First transient noise IEC61000-4-4: 1kV 10
11
Protection degree IP2X
12
Common terminal arrangement 16 points/common (common terminal: TB17)
13
Number of occupied I/O points 16 points (I/O assignment is set as a 16-point input module.) 14
Operation indicator ON indication (LED) 15
External connections Two-piece spring clamp terminal block 16
Applicable wire size 0.3 to 2.0mm2 core (22 to 15 AWG) 17
Applicable crimping terminal Refer to section 9.1 18
Internal current consumption
50mA (TYP. all points ON)
(5VDC)
Weight 0.17kg
External connection
2-2 2-2
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2-3 2-3
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2-4 2-4
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2-5 2-5
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
This module is a spring clamp terminal block type and an input module that has
indicators for checking the insertion state of wire.
Type DC input module (Positive common type)
Specifications QX40-TS Appearance
Number of input points 16 points
Isolation method Photocoupler
Rated input voltage 24VDC (+20/-15%, ripple ratio within 5%)
QX40-TS
Rated input current Approx. 4mA 012 34 567
8 9 A B CDE F
Input derating No
ON voltage/ON current 19V or higher/3mA or higher
OFF voltage/OFF current 11V or lower/1.7mA or lower
Input impedance Approx. 5.6kΩ
1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 1
OFF to ON 2
Response (Default: 10ms)
3
time 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1
ON to OFF 4
(Default: 10ms) 5
Dielectric withstand voltage 560VAC rms/3 cycles (altitude 2000m) 6
Insulation resistance 10MΩ or more by insulation resistance tester 7
By noise simulator of 500Vp-p noise voltage, 1 s noise width 8
9
Noise immunity and 25 to 60Hz noise frequency
10
First transient noise IEC61000-4-4: 1kV 11
Protection degree IP2X 12
Common terminal arrangement 16 points/common (common terminal: TB17) 13
Number of occupied I/O points 16 points (I/O assignment is set as a 16-point input module.) 14
15
Operation indicator ON indication (LED)
16
External connections Two-piece spring clamp terminal block
17
Applicable wire size 0.3 to 2.0mm2 core (22 to 15 AWG) 18
Applicable crimping terminal Refer to section 9.1
Internal current consumption
50mA (TYP. all points ON)
(5VDC)
Weight 0.16kg
2-6 2-6
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2-7 2-7
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
External connection
2-8 2-8
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2-9 2-9
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 10 2 - 10
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
Pin Signal Pin Signal
Derating chart Pin-Outs No. No. No. No.
B20 X00 A20 X10
(%)
B19 X01 A19 X11
100
90 B18 X02 A18 X12
80 B20 A20 B17 X03 A17 X13
ON 28.8VDC
ratio 70 B19 A19
B16 X04 A16 X14
B18 A18
60
B17 A17 B15 X05 A15 X15
50 B16 A16
40 B15 A15 B14 X06 A14 X16
0 10 20 30 40 50 55 ( C ) B14 A14
Ambient temperature B13 X07 A13 X17
B13 A13
B12 A12 B12 X08 A12 X18
B11 A11
External connection B10 A10
B11 X09 A11 X19
B9 A9 B10 X0A A10 X1A
B8 A8
B7 A7 B09 X0B A09 X1B
B6 A6 B08 X0C A08 X1C
B5 A5
B4 A4 B07 X0D A07 X1D
B3 A3
B2 A2
B06 X0E A06 X1E
B1 A1 B05 X0F A05 X1F
B04 Vacant A04 Vacant
Module front view B03 Vacant A03 Vacant
B02 COM A02 Vacant
B01 COM A01 Vacant
2 - 11 2 - 11
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 12 2 - 12
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 13 2 - 13
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
Pin Pin Pin Pin
Signal Signal Signal Signal
Derating chart Pin-Outs No.
No.
No.
No.
No.
No.
No.
No.
4 4 4 4
Module front 1B05 X0F 1A05 X1F 2B05 X2F 2A05 X3F
view 1B04 Vacant 1A04 Vacant 2B04 Vacant 2A04 Vacant
2 - 14 2 - 14
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 15 2 - 15
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
Pin Pin Pin Pin
No. Signal No. Signal No. Signal No. Signal
Derating chart Pin-Outs No. No. No. No.
4 4 4 4
1B20 X00 1A20 X10 2B20 X20 2A20 X30
(%)
100 1B19 X01 1A19 X11 2B19 X21 2A19 X31
90
1B18 X02 1A18 X12 2B18 X22 2A18 X32
80
ON ratio/ 70
1B17 X03 1A17 X13 2B17 X23 2A17 X33
24VDC
common 60
B20 A20
B19 A19 1B16 X04 1A16 X14 2B16 X24 2A16 X34
50 26.4VDC
B18 A18
40 28.8VDC B17 A17
1B15 X05 1A15 X15 2B15 X25 2A15 X35
30 B16 A16 1B14 X06 1A14 X16 2B14 X26 2A14 X36
20 B15 A15
0 10 20 30 40 50 55 ( C ) B14 A14 1B13 X07 1A13 X17 2B13 X27 2A13 X37
Ambient temperature B13 A13
B12 A12 1B12 X08 1A12 X18 2B12 X28 2A12 X38
B11 A11
External connection B10 A10 1B11 X09 1A11 X19 2B11 X29 2A11 X39
B9 A9
B8 A8 1B10 X0A 1A10 X1A 2B10 X2A 2A10 X3A
B7 A7
B6 A6 1B09 X0B 1A09 X1B 2B09 X2B 2A09 X3B
B5 A5
1B08 X0C 1A08 X1C 2B08 X2C 2A08 X3C
B4 A4
B3 A3 1B07 X0D 1A07 X1D 2B07 X2D 2A07 X3D
B2 A2
B1 A1 1B06 X0E 1A06 X1E 2B06 X2E 2A06 X3E
3: Selection of left-hand (F) side provides the first half (X00 to X1F) LED indications, and selection of right-hand (L) side provides the
latter half (X20 to X3F) LED indications.
4: Pin number of 1 indicates that of the left-hand side connector, and pin number of 2 indicates that of the right-hand
side connector.
2 - 16 2 - 16
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
(%)
100 48VDC/AC
90
80
ON 70
ratio
60 57.6VDC
50 52.8VAC
40
0 10 20 30 40 50 55 ( C)
Ambient temperature
External connection
1: Response time cannot be changed. Parameter setting of the CPU module will be invalid.
2 - 17 2 - 17
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 18 2 - 18
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 19 2 - 19
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 20 2 - 20
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 21 2 - 21
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 22 2 - 22
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 23 2 - 23
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 24 2 - 24
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
This module is a spring clamp terminal block type and an input module that has
indicators for checking the insertion state of wire.
Type DC input module (Negative common type)
Specifications QX80-TS Appearance
Number of input points 16 points
Isolation method Photocoupler
Rated input voltage 24VDC (+20/-15%, ripple ratio within 5%) QX80-TS
0123 4567
Rated input current Approx. 4mA 8 9 AB CDEF
Input derating No
ON voltage/ON current 19V or higher/3mA or higher
OFF voltage/OFF current 11V or lower/1.7mA or lower
Input impedance Approx. 5.6kΩ 1
1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 2
OFF to ON
Response (Default: 10ms) 3
time 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 4
ON to OFF 5
(Default: 10ms)
6
Dielectric withstand voltage 560VAC rms/3 cycles (altitude 2000m)
7
Insulation resistance 10MΩ or more by insulation resistance tester 8
By noise simulator of 500Vp-p noise voltage, 1 s noise width 9
Noise immunity and 25 to 60Hz noise frequency 10
First transient noise IEC61000-4-4: 1kV 11
12
Protection degree IP2X
13
Common terminal arrangement 16 points/common (common terminal: TB18) 14
Number of occupied I/O points 16 points (I/O assignment is set as a 16-point input module.) 15
Operation indicator ON indication (LED) 16
External connections Two-piece spring clamp terminal block 17
18
Applicable wire size 0.3 to 2.0mm2 core (22 to 15 AWG)
Applicable crimping terminal Refer to section 9.1
Internal current consumption (5VDC) 50mA (TYP. all points ON)
Weight 0.16kg
2 - 25 2 - 25
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 26 2 - 26
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
External connection
2 - 27 2 - 27
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 28 2 - 28
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 29 2 - 29
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 30 2 - 30
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
Pin Signal Pin Signal Pin Signal Pin Signal
Derating chart Pin-Outs No. No. No. No. No. No. No. No.
4 4 4 4
(%) 1B20 X00 1A20 X10 2B20 X20 2A20 X30
100 1B19 X01 1A19 X11 2B19 X21 2A19 X31
90
1B18 X02 1A18 X12 2B18 X22 2A18 X32
80
70 1B17 X03 1A17 X13 2B17 X23 2A17 X33
ON ratio/ 24VDC B20 A20
60 1B16 X04 1A16 X14 2B16 X24 2A16 X34
common B19 A19
50 26.4VDC B18 A18
40 B17 A17 1B15 X05 1A15 X15 2B15 X25 2A15 X35
28.8VDC
30 B16 A16
B15 A15
1B14 X06 1A14 X16 2B14 X26 2A14 X36
20 B14 A14
0 10 20 30 40 50 55 ( C ) 1B13 X07 1A13 X17 2B13 X27 2A13 X37
B13 A13
Ambient temperature B12 A12 1B12 X08 1A12 X18 2B12 X28 2A12 X38
B11 A11
External connection B10 A10 1B11 X09 1A11 X19 2B11 X29 2A11 X39
B9 A9
B8 A8 1B10 X0A 1A10 X1A 2B10 X2A 2A10 X3A
B7 A7
B6 A6 1B09 X0B 1A09 X1B 2B09 X2B 2A09 X3B
B5 A5 1B08 X0C 1A08 X1C 2B08 X2C 2A08 X3C
B4 A4
B3 A3 1B07 X0D 1A07 X1D 2B07 X2D 2A07 X3D
B2 A2
B1 A1 1B06 X0E 1A06 X1E 2B06 X2E 2A06 X3E
3: Selection of left-hand (F) side provides the first half (X00 to X1F) LED indications, and selection of right-hand (L) side provides the
latter half (X20 to X3F) LED indications.
4: Pin number of 1 indicates that of the left-hand side connector, and pin number of 2 indicates that of the right-hand
side connector.
2 - 31 2 - 31
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 32 2 - 32
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 33 2 - 33
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 34 2 - 34
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2 - 35 2 - 35
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
MEMO
2 - 36 2 - 36
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
Surge suppressor No 7
5
L
Fuse No 8 6
L
Dielectric withstand voltage 2830VAC rms/3 cycles (altitude 2000m) L
9 7
Insulation resistance 10MΩ or more by insulation resistance tester L
A 8
By noise simulator of 1500Vp-p noise voltage, 1 s noise width L
B
9
Noise immunity and 25 to 60Hz noise frequency L
C
A
D
First transient noise IEC61000-4-4: 1kV L
B
E
Protection degree IP1X L
F C
Common terminal L
16 points/common (common terminal: TB17) COM D
arrangement NC
Number of occupied I/O points 16 points (I/O assignment is set as a 16-point output module.) 24VDC E
Operation indicator ON indication (LED) 240VAC F
2A
External connections 18-point terminal block (M3 6 screws)
Applicable wire size 0.3 to 0.75mm2 core (2.8mm OD max.)
Applicable crimping terminal R1.25-3 (Sleeved crimping terminals cannot be used.)
Internal current consumption
430mA (TYP. all points ON)
(5VDC)
Weight 0.22kg
3-1 3-1
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3-2 3-2
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3-3 3-3
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3-4 3-4
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3-5 3-5
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
POINT
Do not touch the module during turning on electricity and immediately after power
supply interception. There is fear of a burn.
3-6 3-6
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3-7 3-7
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
This module is a spring clamp terminal block type and an output module that has
indicators for checking the insertion state of wire.
Type Transistor output module (Sink type)
Specifications QY40P-TS Appearance
Number of output points 16 points
Isolation method Photocoupler
Rated load voltage 12-24VDC (+20/-15%)
Maximum load current 0.1A/point, 1.6A/common
Maximum inrush current 0.7A, 10ms or less
QY40P-TS
Leakage current at OFF 0.1mA or less 0123 4567
8 9 AB CDEF
Maximum voltage drop at ON 0.1VDC (TYP.) 0.1A, 0.2VDC (MAX.) 0.1A
OFF to ON 1ms or less
Response time
ON to OFF 1ms or less (rated load, resistive load)
Surge suppressor Zener diode
Fuse No 1
2
External supply Voltage 12-24VDC (+20/-15%) (ripple ratio within 5%)
3
power Current MAX. 10mA (when 24VDC and all points are ON) 4
Dielectric withstand voltage 560VAC rms/3 cycles (altitude 2000m) 5
Insulation resistance 10MΩ or more by insulation resistance tester 6
By noise simulator of 500Vp-p noise voltage, 1 s noise width 7
and 25 to 60Hz noise frequency 8
Noise immunity
9
First transient noise IEC61000-4-4: 1kV
10
Protection degree IP2X 11
Common terminal arrangement 16 points/common (common terminal: TB18) 12
Number of occupied I/O points 16 points (I/O assignment is set as a 16-point output module.) 13
Yes (overload protection function, overheat protection function) 14
15
Protection function • Overheat protection function is activated in increments of 1 point.
16
• Overload protection function is activated in increments of 1 point. 17
Operation indicator ON indication (LED) 18
External connections Two-piece spring clamp terminal block
Applicable wire size 0.3 to 2.0mm2 core (22 to 15 AWG)
Applicable crimping terminal Refer to section 9.1
Internal current consumption 65mA (TYP. all points ON)
(5VDC) (0.07A is shown on the rating plate of the module.)
Weight 0.16kg
3-8 3-8
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3-9 3-9
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3 - 10 3 - 10
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3 - 11 3 - 11
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
1: Pin number of 1 indicates that of the left-hand side connector, and pin number of 2 indicates that of the right-hand
side connector.
2: Selection of left-hand (F) side provides the first half (Y00 to Y1F) LED indications, and selection of right-hand (L) side provides the
latter half (Y20 to Y3F) LED indications.
3: When using A6CON2 or A6CON3, refer to Chapter 7.
3 - 12 3 - 12
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
L
F C
Common terminal arrangement 16 points/common (common terminal: TB18)
D
Number of occupied I/O points 16 points (I/O assignment is set as a 16-point output module.) COM
E
12VDC
Operation indicator ON indication (LED) 24VDC F
0.5A
External connections 18-point terminal block (M3 6 screws)
Applicable wire size 0.3 to 0.75mm2 core (2.8mm OD max.)
Applicable crimping terminal R1.25-3 (Sleeved crimping terminals cannot be used.)
Internal current consumption
80mA (TYP. all points ON)
(5VDC)
Weight 0.17kg
1: Fuse blown is not detected when the external power supply is shut off.
3 - 13 3 - 13
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3 - 14 3 - 14
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3.11 QY68A Transistor Output Module (All Points Independent, Sink/Source Type)
3 - 15 3 - 15
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3 - 16 3 - 16
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3 - 17 3 - 17
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
1: Fuse blown is not detected when the external power supply is shut off.
2: When using A6CON2 or A6CON3, refer to Chapter 7.
3 - 18 3 - 18
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3 - 19 3 - 19
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3 - 20 3 - 20
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
This module is a spring clamp terminal block type and an output module that has
indicators for checking the insertion state of wire.
Type Transistor output module (Source Type)
Specifications QY80-TS Appearance
Number of output points 16 points
Isolation method Photocoupler
Rated load voltage 12-24VDC (+20/-15%)
Maximum load current 0.5A/point, 4A/common
Maximum inrush current 4A, 10ms or less
QY80-TS
Leakage current at OFF 0.1mA or less 0 123 4 567
8 9 AB CDEF
Maximum voltage drop at ON 0.2VDC (TYP.) 0.5A, 0.3VDC (MAX.) 0.5A FUSE
3 - 21 3 - 21
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3 - 22 3 - 22
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3 - 23 3 - 23
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3 - 24 3 - 24
4 I/O COMBINED MODULE
MELSEC-Q
4-1 4-1
4 I/O COMBINED MODULE
MELSEC-Q
(%)
100
90
ON Ratio
80
28.8VDC
70
60
50
40
0 10 20 30 40 50 55 (°C)
Ambient temperature
2: Selection of left-hand (F) side provides the first half (X00 to X1F) LED indications, and selection of right-hand (L) side provides the
latter half (Y00 to Y1F) LED indications.
4-2 4-2
4 I/O COMBINED MODULE
MELSEC-Q
4-3 4-3
4 I/O COMBINED MODULE
MELSEC-Q
4-4 4-4
4 I/O COMBINED MODULE
MELSEC-Q
(%)
100
90
ON Ratio
80
28.8VDC
70
60
50
40
0 10 20 30 40 50 55 (°C)
Ambient temperature
2: Selection of left-hand (F) side provides the first half (X00 to X1F) LED indications, and selection of right-hand (L) side provides the
latter half (Y20 to Y3F) LED indications.
4-5 4-5
4 I/O COMBINED MODULE
MELSEC-Q
4-6 4-6
4 I/O COMBINED MODULE
MELSEC-Q
4-7 4-7
4 I/O COMBINED MODULE
MELSEC-Q
TB18 COM2
4-8 4-8
4 I/O COMBINED MODULE
MELSEC-Q
4-9 4-9
5 INTERRUPT MODULE
MELSEC-Q
5. INTERRUPT MODULE
For usage of this module, refer to the User’s Manual (Function Explanation, Program
Fundamentals) for the CPU module used.
Type Interrupt module
Specifications QI60 Appearance
Number of input points 16 points
Isolation method Photocoupler
Rated input voltage 24VDC (+20/-15%, ripple ratio within 5%)
Rated input current Approx. 6mA QI60
Input derating No 0 1 2 3 4 5 6 7
8 9 A B CDE F
ON voltage/ON current 19V or higher/4.0mA or higher
OFF voltage/OFF current 11V or lower/1.7mA or lower
Input impedance Approx. 3.9kΩ
Set value 1 0.1 0.2 0.4 0.6 1 0
TYP. 0.05ms 0.15ms 0.30ms 0.55ms 1.05ms 1 0
Response OFF to ON
MAX. 0.10ms 0.20ms 0.40ms 0.60ms 1.20ms 2 1
time
TYP. 0.15ms 0.20ms 0.35ms 0.60ms 1.10ms 3 2
ON to OFF 4
MAX. 0.20ms 0.30ms 0.50ms 0.70ms 1.30ms 3
5
Dielectric withstand voltage 560VAC rms/3 cycles (altitude 2000m) 4
6
Insulation resistance 10MΩ or more by insulation resistance tester 7
5
By noise simulator of 500Vp-p noise voltage, 1 s noise width
5 Noise immunity and 25 to 60Hz noise frequency 9
8 6
7
First transient noise IEC61000-4-4: 1kV A 8
Protection degree IP2X B
9
Common terminal arrangement 16 points/common (common terminal: TB17) C
A
D
16 points (I/O assignment is set as a 16-point interrupt module.) B
Number of occupied I/O points E
3 C
F
Interrupt processing condition Set by Switch setting in GX Developer. 2 - +
COM D
Operation indicator ON indication (LED) NC
E
External connections 18-point terminal block (M3 6 screws) 24VDC F
Applicable wire size 0.3 to 0.75mm2 core (2.8mm OD max.) 6mA
5-1 5-1
5 INTERRUPT MODULE
MELSEC-Q
MEMO
5-2 5-2
6 BLANK COVER MODULE
MELSEC-Q
This chapter provides the specifications of the blank cover module used to protect the
vacant slot (between I/O modules) of the base unit from dust.
Load the blank cover module with the connector cover of the base unit fitted.
6-1 6-1
6 BLANK COVER MODULE
MELSEC-Q
MEMO
6-2 6-2
7 CONNECTORS
MELSEC-Q
7. CONNECTORS
The 40-pin connectors and 37-pin D-sub connectors used with the input and output
modules are to be user-prepared.
The following tables list the connector types and applicable models, and introduce
crimp-contact and pressure-displacement tools.
7-1 7-1
7 CONNECTORS
MELSEC-Q
7-2 7-2
8 SPECIFICATIONS OF CONNECTOR/TERMINAL BLOCK CONVERTER
MODULES
MELSEC-Q
8-1 8-1
8 SPECIFICATIONS OF CONNECTOR/TERMINAL BLOCK CONVERTER
MODULES
MELSEC-Q
POINT
(1) The number of connectable I/O points is 32 for all connector/terminal block
converter modules.
Two connector/terminal block converter modules and two cables for
connector/terminal block converter modules are required for 64-point I/O
modules.
(2) Though the A1SX81(S2) is used either as a sink or source type, use the
A6TBX36-E, A6TBX54-E or A6TBX70-E.
The A6TBXY36, A6TBXY54 or A6TBX70 cannot be used.
(3) Though the A1SX82-S1 is used either as a sink or source type, the
A6TBXY36/XY54/X70 may be used only when the A1SX82-S1 is used as a sink
type.
When it is used as a source type, the A6TBXY36/XY54/X70 cannot be used.
(4) Though the A1SY82 and QY82P are source type output modules, use the
A6TBXY36 or A6TBXY54. The A6TBY36-E or A6TBY54-E cannot be used.
(5) In the A series, the positive common input module is separately labeled as a
sink type input module, and the negative common input module is separately
labeled as a source type input module.
(6) When using the A6TBX70 as I/O combined module, use at the input side.
(7) Tighten the module terminal screws to the following torque.
Terminal screw (M3.5 screw): Tightening torque 0.78N•m
(2) Cable
Type Details Weight Applicable Models
AC05TB 0.5 m, for sink modules 0.17kg
AC10TB 1 m, for sink modules 0.23kg
AC20TB 2 m, for sink modules 0.37kg
AC30TB 3 m, for sink modules 0.51kg A6TBXY36
AC50TB 5 m, for sink modules 0.76kg A6TBXY54
8 m, for sink modules (common current not A6TBX70
AC80TB 1.2kg
exceeding 0.5 A)
10 m, for sink modules (common current
AC100TB 1.5kg
not exceeding 0.5 A)
AC05TB-E 0.5 m, for source modules 0.17kg A6TBX36-E
AC10TB-E 1 m, for source modules 0.23kg A6TBY36-E 8
AC20TB-E 2 m, for source modules 0.37kg A6TBX54-E
AC30TB-E 3 m, for source modules 0.51kg A6TBY54-E
AC50TB-E 5 m, for source modules 0.76kg A6TBX70-E
8-2 8-2
8 SPECIFICATIONS OF CONNECTOR/TERMINAL BLOCK CONVERTER
MODULES
MELSEC-Q
8-3 8-3
8 SPECIFICATIONS OF CONNECTOR/TERMINAL BLOCK CONVERTER
MODULES
MELSEC-Q
8.2.2 A6TBXY54
8-4 8-4
8 SPECIFICATIONS OF CONNECTOR/TERMINAL BLOCK CONVERTER
MODULES
MELSEC-Q
8.2.3 A6TBX70
8.2.4 A6TBX36-E
8-5 8-5
8 SPECIFICATIONS OF CONNECTOR/TERMINAL BLOCK CONVERTER
MODULES
MELSEC-Q
8.2.5 A6TBY36-E
8.2.6 A6TBX54-E
8-6 8-6
8 SPECIFICATIONS OF CONNECTOR/TERMINAL BLOCK CONVERTER
MODULES
MELSEC-Q
8.2.7 A6TBY54-E
8.2.8 A6TBX70-E
8-7 8-7
9 SPRING CLAMP TERMINAL BLOCK
MELSEC-Q
The spring clamp terminal block I/O module is an I/O module of spring clamp terminal
block type.
Since this module uses a spring clamp it does not require screw tightening, which
greatly reduces the number of wiring procedures.
POINT
• Use bar solderless terminals for wiring this module.
• For the signal names corresponding to the terminal numbers when connected to
an external device, refer to Chapter 2 and 3 in this manual.
9-1 9-1
9 SPRING CLAMP TERMINAL BLOCK
MELSEC-Q
Connection Check
Indicator
*1: If the connection check indicator does not come out, the bar solderless
terminal is not connected to the module properly.
Insert the bar solderless terminal until the connection check indicator comes
out.
9-2 9-2
9 SPRING CLAMP TERMINAL BLOCK
MELSEC-Q
Tool
*1: If the connection check indicator does not come out, the bar solderless terminal is
not connected to the module properly. Insert the terminal until the connection
check indicator comes out.
9-3 9-3
9 SPRING CLAMP TERMINAL BLOCK
MELSEC-Q
POINT
• If the stripped wire is inserted into the corresponding hole without installing the
bar solderless terminal, the connection check indicator does not come out. Do
not use the stripped wire without installing the bar solderless terminal.
• The wire strip length must follow the specification of the bar solderless
terminal. Also, use a crimp tool when installing the bar solderless terminal to
the wire.
• Before inserting the bar solderless terminal, check the corresponding circular
shaped hole and the bar solderless terminal. Before inserting, pay attention to
the angle of bar solderless terminal.
If a bar solderless terminal, which is bigger than the insertion slot, is inserted,
the terminal block may be damaged.
9-4 9-4
9 SPRING CLAMP TERMINAL BLOCK
MELSEC-Q
9-5 9-5
9 SPRING CLAMP TERMINAL BLOCK
MELSEC-Q
(2) Specifications
The Q6TE-18S(N) specification is explained.
Item Specifications
Applicable wire size 0.3 to 1.5 mm2 (22 to 16 AWG)
264VAC
Maximum rated voltage, maximum rated 125VDC
current 8A (terminal number: 17)
4A (terminal number: 1 to 16, 18)
Wire strip length 8 to 11 mm
Mounting screw tightening torque range 0.66 to 0.89 Nm
Weight 0.07kg
Unscrew the two terminal block mounting screws situated at the top and bottom
of the terminal block and take them off.
Module
Terminal
block mounting
screw
Terminal block
9-6 9-6
9 SPRING CLAMP TERMINAL BLOCK
MELSEC-Q
Module
Q6TE-18S(N)
Terminal block
mounting screw
9-7 9-7
9 SPRING CLAMP TERMINAL BLOCK
MELSEC-Q
9-8 9-8
9 SPRING CLAMP TERMINAL BLOCK
MELSEC-Q
9-9 9-9
10 PART NAMES
MELSEC-Q
18-point screw terminal block type (other than 40-pin connector type
high-speed input module)
1) 1) 1)
QX10 QX41 QX42
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
2) 8 9 A B CDE F 2) 8 9 A B C D E F 2) 8 9 A B C D E F
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
8 9 A B C D E F 8 9 A B C D E F
QX41 QX42
24VDC DISPLAY
3) 4mA 24VDC
0 4mA F L 6)
1
1
2
2
3
3
4
4
5 4)
5
6
6
7
7 5) 5)
8
8
9
9
10
A
11
B
12
C
13
D
14
E
15
F
16
COM
NC
17
100VAC 18
8mA60Hz
7mA50Hz
7) 7) 7)
10 - 1 10 - 1
10 PART NAMES
MELSEC-Q
8)
10)
7)
10
10 - 2 10 - 2
10 PART NAMES
MELSEC-Q
1)
6)
2)
3)
4)
7)
5)
A
8) 9)
10 - 3 10 - 3
10 PART NAMES
MELSEC-Q
3)
4)
5)
8)
6)
10 - 4 10 - 4
10 PART NAMES
MELSEC-Q
A6TB 36
A6TB 54
2)
1)
2) 1)
10 - 5 10 - 5
10 PART NAMES
MELSEC-Q
A6TBX70
1) 2)
+C -C +C -C +C -C +C -C +C -C +C -C +C -C +C -C +C 0V
0 1 2 3 4 5 6 7 8 9 A B C D E F 24V
3)
10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 24V
+C -C +C -C +C -C +C -C +C -C +C -C +C -C +C -C +C 0V
4)
2) 1)
Q6TE-18S(N)
1)
2)
3)
10 - 6 10 - 6
11 I/O MODULE TROUBLESHOOTING
MELSEC-Q
This chapter explains possible problems with I/O circuits and their corrective actions.
11
11.1 Input Circuit Troubleshooting
This section describes possible problems with input circuits and their corrective
actions.
11 - 1 11 - 1
11 I/O MODULE TROUBLESHOOTING
MELSEC-Q
DC input
Diode
Input Lamp E2 E1
module Input Lamp
E2 E1
module
E1>E2
An input Stepwise distortion as shown below appears to Improve input signal waveform by using the
signal does the zero cross voltage of input signal (AC). uninterruptible power system etc.
Example 6
not turn on
(AC input Zero cross
module). voltage
False input Noise has been taken as input data. Change the response time setting value.*1
due to Example
noise 1ms 5ms
If this action is not effective, take the following
Example 7
measures.
• To prevent excessive noise, avoid installing
power cables together with I/O cables.
• Take noise reduction measures. (Example:
Connect surge absorbers to noise-generating
devices such as relays and contactors using
the same power supply.)
*1: If excessive noise is periodically generated, setting a shorter response time value may be effective.
11 - 2 11 - 2
11 I/O MODULE TROUBLESHOOTING
MELSEC-Q
(1) In this case, the circuit does not satisfy the condition that the OFF current of the
QX40 is 1.7mA or less.
Connect a resistance as follows.
(2) In order to satisfy the condition that the OFF current of the QX40 is 1.7mA or less,
the resistance R, in which a 0.63mA or more current flows, shall be connected.
Calculating with the formula,
IR: IZ=Z (Input impedance): R
IZ 1.7
R Z (Input impedance) = 5.6=15.11[k ]
IR 0.63
(3) Since the resistance requires the electric power which is 3 to 5 times of the power
actually consumed, the resistance to be connected to the corresponding terminal
shall be 12.0kΩ and 1/4 to 1[W].
(4) The OFF voltage of the QX40 when the resistance R calculated above is connected
will be 8.90[V].
1
2.33[mA]=8.90[V]
1 1
12.0[k ] 5.6[k ]
This also satisfies the condition that the OFF voltage of the QX40 is 11V or less.
11 - 3 11 - 3
11 I/O MODULE TROUBLESHOOTING
MELSEC-Q
This section describes possible problems with output circuits and their corrective
actions.
[2]
• When the polarity of the power supply is as
shown in [1], C is charged. When the polarity is
as shown in [2], the voltage charged in C plus
the line voltage are applied across D1. Max.
voltage is approx. 2.2E.
(If a circuit is used in this way, it does not pose
a problem to the output element. But it may
cause the diode, which is built into the load, to
deteriorate, resulting in a fire, etc.)
The load • Leakage current due to built-in surge • Connect a resistor across the load.
does not suppressor. (When the wiring distance from the output
turn off. module to the load is long, there may be a
QY22
(triac leakage current due to the line capacity.)
Example 2
Output module
output) Load
Resistor
Leakage current
Load
11 - 4 11 - 4
11 I/O MODULE TROUBLESHOOTING
MELSEC-Q
Load
QY22 Surge suppressor
(Example)
Phototriac When using 100VAC (output voltage), for
instance, calculate the resistance value from
the formula below.
Control
circuit Load 100VAC / 100mA = 1kΩ
Resistance value = 1kΩ
Triac
11 - 5 11 - 5
11 I/O MODULE TROUBLESHOOTING
MELSEC-Q
10ms or less
Output Y0
* The measures are ineffective in the following
modules due to the characteristic of the external
Approx.100 s power supply circuit
QY81P
QY82P
R1: Several tens of ohms
Power capacity (external power supply current*1)2
resistance value
(3 to 5)*2
C1: several hundreds of microfarads 50V
*1 Refer to current consumption of the external power
supply for modules used in this manual.
*2 Select the power capacity of resistance to be 3 to 5
times larger than the actual power consumption.
(Example)
R1=40Ω, C1=300 F
Use the below expression to calculate a time
constant
C1 R1=300 10-6 40
=12 10-3s=12ms
11 - 6 11 - 6
11 I/O MODULE TROUBLESHOOTING
MELSEC-Q
11 - 7 11 - 7
11 I/O MODULE TROUBLESHOOTING
MELSEC-Q
supply. power
supply
(transistor
COM
output)
Output element
protection diode
11 - 8 11 - 8
APPENDICES
MELSEC-Q
APPENDICES
Appendix 1 External Dimensions
Appendix 1.1 I/O modules and blank cover module
(1) Terminal block connector type
(a) Other than QY22
A
2
QX10
0 1 2 3 4 5 6 7
89ABCDEF
0
1 0
2 1
3 2
4
3
5
4
6
98
105
7 5
8 6
9 7
A 8
B
9
C
D
A
E B
F C
COM D
NC
100VAC E
8mA60Hz
7mA50Hz
F
5
2 90 27.4
Unit: mm
Unit: mm
App - 1 App - 1
APPENDICES
MELSEC-Q
2
QX10-TS
01234567
8 9 A B CDEF
1
2
3
4 A
5
6
105
98
7
8
9
10
11
12
13
14
15
16
17
18
5
2 90 27.4
Unit: mm
App - 2 App - 2
APPENDICES
MELSEC-Q
2
QX41
0 1 2 3 4 5 6 7
89AB C D E F
0 1 2 3 4 5 6 7
89AB C D E F
QX41
24VDC
4mA
98
105
5
2 90 45 27.4
Unit: mm
QX42
0 1 2 3 4 5 6 7
89AB C D E F
0 1 2 3 4 5 6 7
89AB C D E F
QX42
24VDC DISPLAY
4mA F L
105
98
5
2 90 45 27.4
Unit: mm
App - 3 App - 3
APPENDICES
MELSEC-Q
2
QX81
0 1 2 3 4 5 6 7
89ABC D E F
0 1 2 3 4 5 6 7
89ABC D E F
QX81
24VDC
4mA
98
105
5
2 90 46 27.4
Unit: mm
Unit: mm
App - 4 App - 4
APPENDICES
MELSEC-Q
Unit: mm
8.25
Flat cable
arrangement is in the
following sequence.
A1 B1 A2…
22.5
10
Unit: mm
App - 5 App - 5
APPENDICES
MELSEC-Q
Unit: mm
If the cable diameter is thinner than the clamp portion, wind tape, etc. to
secure the cable so that it will not come off the cable clamp portion.
If the cable is made of slippery material, it is recommended to take anti-slip
measures by winding rubber-based tape, etc.
App - 6 App - 6
APPENDICES
MELSEC-Q
Unit: mm
12.6
3.4
5.9
Unit: mm
App - 7 App - 7
APPENDICES
MELSEC-Q
Unit: mm
Unit: mm
Unit: mm
App - 8 App - 8
APPENDICES
MELSEC-Q
(1) AC TB
Unit: mm
(2) AC TB-E
Unit: mm
App - 9 App - 9
APPENDICES
MELSEC-Q
Unit: mm
*1: The depth of the module installed with the Q6TE-18S(N) is equivalent with the factory default dimensions
for that module.
App - 10 App - 10
APPENDICES
MELSEC-Q
Note that the MELSEC-Q series I/O modules and MELSEC-AnS series I/O modules
are different in external terminal block configuration.
Differences in terminal block configuration are indicated below.
App - 11 App - 11
APPENDICES
MELSEC-Q
Terminal Terminal
Block QY50 A1SY50 Block QY80 A1SY80
Number Number
TB9 Y08 12/24VDC TB9 Y08 COM1
TB10 Y09 COM1 TB10 Y09 0V
TB11 Y0A Y08 TB11 Y0A Y08
• • • • • •
• • • • • •
• • • • • •
TB16 Y0F Y0D TB16 Y0F Y0D
TB17 12/24VDC Y0E TB17 COM Y0E
TB18 COM Y0F TB18 0V Y0F
TB19 — 12/24VDC TB19 — COM2
TB20 — COM2 TB20 — 0V
POINT
The 40-pin connector used with the MELSEC-AnS series I/O module can be used
intact with the MELSEC-Q series I/O module.
The 37-pin D-sub connector used with the MELSEC-AnS series I/O module is the
same in wiring as, but opposite in cable pulling direction to, the MELSEC-Q series
I/O module. (The conventional cable for A6TB cannot be used.)
App - 12 App - 12
APPENDICES
MELSEC-Q
MEMO
App - 13 App - 13
WARRANTY
The company names, system names and product names mentioned in this manual are either registered trademarks or
trademarks of their respective companies.
In some cases, trademark symbols such as '™' or '®' are not specified in this manual.
SH(NA)-080042-AG
SH(NA)-080042-AG(2403)MEE
MODEL: Q-IO-U-E
MODEL CODE: 13JL99
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
NAGOYA WORKS: 1-14, YADA-MINAMI 5-CHOME, HIGASHI-KU, NAGOYA 461-8670, JAPAN
When exported from Japan, this manual does not require application to the
Ministry of Economy, Trade and Industry for service transaction permission.