Collins Avenue Preliminary Review Plans for 40 Year Re-certification

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 84

SOUTH CONDOMINIUM

CHAMPLAIN TOWERS
89th ST

COLLINS AVE

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
O 1
40 YEAR BUILDING REPAIR AND RESTORATION

TI 02
88th ST

PHASE IIC: OVERALL BUILDING REPAIR AND RESTORATION


CHAMPLAIN TOWERS SOUTH CONDOMINIUM

C /2
N
87th ST
8777 COLLINS AVENUE
SURFSIDE, FLORIDA 33154

U 7
100% BID DOCUMENTS SET - 4/26/21
COLLINS AVE

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


86th ST

R /2

PHASE IIC: OVERALL BUILDING


LOCATION MAP STREET VIEW

REPAIR AND RESTORATION


REPAIR & RESTORATION
4
DRAWING LIST - PHASE IIC STRUCTURAL DRAWING LIST - PHASE IIC ARCHITECTURAL DRAWING LIST - PHASE IIC LANDSCAPE

N ET
.C2C-1.0 COVERSHEET A-1 OVERALL FIRST FLOOR RAMP, WINDOW, & DOOR PLAN LD-1 TREE DISPOSITION PLAN
.C2C-1.1 GENERAL NOTES & DESIGN DATA A-2 OVERALL 2ND THRU 8TH FLOOR WINDOW & DOOR PLAN LH-1 HARDSCAPE PLAN
A2C-0.5 BASEMENT PARKING PLAN A-3 OVERALL 8TH THRU 11TH FLOOR WINDOW & DOOR PLAN LP-1 LANDSCAPE PLAN
A2C-1.0 LEVEL 1 FLOOR PLAN A-4 OVERALL 12TH FLOOR WINDOW & DOOR PLAN LR-1 IRRIGATION PLAN AND LEGEND
A2C-1.1 LEVEL 2-8 FLOOR PLAN A-5 OVERALL ROOF & PENTHOUSE FLOOR WINDOW & DOOR PLAN LR-2 IRRIGATION NOTES AND DETAILS

O S
A2C-1.2 LEVEL 9-11 FLOOR PLAN A-6 DOOR & WINDOW ELEVATION PROFILES LT-1 LANDSCAPE LIGHTING PLAN

ST
A2C-1.3 LEVEL 12 FLOOR PLAN A-7 DOOR & WINDOW SCHEDULE, DOOR & WINDOW NOTES, DOOR
A2C-1.4 LOW ROOF & PENTHOUSE FLOOR PLAN HARDWARE SCHEDULE
A2C-1.5 PENTHOUSE AND HIGH ROOF PLAN A-8 WEST & NORTH BUILDING ELEVATIONS SPECIFICATIONS

S
D2C-1.0 LEVEL 1 DEMO PLAN A-9 EAST 7 SOUTH BUILDING ELEVATIONS
S2C-1.0 LEVEL 1 SLAB REINFORCEMENT AND FRAMING PLAN A-10 PRELIMINARY COLOR CHART & NEW BUILDING ELEVATIONS SECTION 00 2113 INSTRUCTION TO BIDDERS
SEAL License: 89035
SECTION 00 4100 BID FORM Expires: 02/28/23

R S
S2C-1.1 LEVEL 1 BONDED OVERLAY AND TOPPING ELEVATIONS
S2C-1.2 LEVEL 2 FRAMING PLAN DRAWING LIST - PHASE IIC MEP SECTION 00 5213
SECTION 00 7212
CONTRACT AGREEMENT FORM
ADDITIONS TO THE CONTRACT AGREEMENT
S2C-2.0 TYPICAL REINFORCEMENT & REPAIR NOTES SECTION 00 7300 SUPPLEMENTAL CONTRACT CONDITIONS
S2C-2.1
S2C-2.2
S2C-2.3
CONCRETE REPAIR DETAILS
CONCRETE/MASONRY REPAIR DETAILS
PLAZA DETAILS
EE-0
E-1
E-2
ELECTRICAL SYMBOL LEGEND AND NOTES
BASEMENT PARKING PLAN - LIGHTING
FIRST FLOOR PARKING PLAN - LIGHTING
SECTION 01 1100
SECTION 01 2100
SECTION 01 2200
SUMMARY OF WORK
ALLOWANCES
UNIT PRICES
FO R
This item has been digitally signed and sealed by Robert J. Miller on the
SECTION 01 2300 ALTERNATES date adjacent to the seal. Printed copies of this document are not

C
E-3 BASEMENT PARKING PLAN - POWER considered signed and sealed and the signature must be verified on
any electronic copies.

S2C-2.4 PLAZA DETAILS SECTION 01 3100 PROJECT MANAGEMENT AND COORDINATION


E-4 PENTHOUSE FLOOR PLAN / LOWER ROOF SECTION 01 3300 SUBMITTAL PROCEDURES
S2C-2.5 PLAZA DETAILS
E-5 GENERATOR ROOM PLAN SECTION 01 4000 QUALITY REQUIREMENTS
T G

S2C-2.6 PLAZA DETAILS


E-6 ELECTRICAL NOTES SECTION 01 5000 TEMPORARY FACILITIES & CONTROL
S2C-2.7 PLAZA DETAILS SECTION 01 6000 PRODUCT REQUIREMENTS
Structural Engineers | Remediation & Parking Consultants

E-7 ELECTRICAL GEAR SPECIFICATIONS 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
S2C-2.8 PLAZA DETAILS SECTION 01 7300 EXECUTION © Copyright Morabito Consultants, Inc.

E-8 ELECTRICAL PANELS


S2C-2.9 PLAZA & FOUNDATION DETAILS SECTION 01 7400 CLEANING & WASTE MANAGEMENT
O O

E-9 ELECTRICAL DETAILS SECTION 02 4119 SELECTIVE DEMOLITION No. Date Revisions
S2C-3.0 POOL REPAIR DETAILS
FP-1 FIRE PROTECTION NOTES, SCHEDULES AND DETAILS SECTION 03 0100 MAINTENANCE OF CONCRETE
S2C-3.1 STUCCO REPAIR DETAILS
FP-2 FIRST FLOOR PLAN - FIRE PROTECTION SECTION 04 0120 MAINTENANCE OF MASONRY
S2C-3.2 SOFFIT AND RAIL REPAIR DETAILS
N R

M-0 MECHANICAL NOTES AND SCHEDULES SECTION 04 1100 PREPARATION OF LIME OR PORTLAND BASED STUCCO
S2C-3.3 BALCONY DOOR WATERPROOFING SECTION 04 1101 REPAIR OF STUCCO
M-1 MECHANICAL - HVAC GARAGE PLAN SECTION 05 0519 POST-INSTALLED ANCHORS IN CONCRETE & MASONRY
S2C-3.4 SHORING DETAILS
M-2 MECHANICAL GROUND FLOOR PLAN SECTION 05 4000 COLD FORMED METAL FRAMING
-P

S2C-3.5 FIRE DOOR REPLACEMENT DETAILS


M-3 LOW ROOF HVAC REPLACEMENT PLAN SECTION 05 5000 METAL FABRICATIONS
S2C-3.6 SOUTH WALL REPAIR SECTION 07 1413 HOT FLUID APPLIED RUBBERIZED ASPHALT WATERPROOFING
P-0 PLUMBING GENERAL NOTES AND DETAILS
TBM-1 TRAFFIC BEARING WATERPROOFING MEMBRANE & FINISH SECTION 07 1610 CEMENTITIOUS AND REACTIVE WATERPROOFING
P-0A NATURAL GAS BASEMENT PARKING PLAN DESIGNED DRAWN
WP-1 CCW-500 WALL DETAILS SECTION 07 1810 PEDESTRIAN BEARING WATERPROOFING MEMBRANE HR/JB/RM HR/JB/RM
P-1 PLUMBING GAS GARAGE PLAN SECTION 07 9200 SEALANT CHECKED APPROVED
IN

WP-2 CCW-500 SLAB-WALL DETAILS RM FPM


P-1A NATURAL GAS BASEMENT PLAN SECTION 09 2400 PORTLAND CEMENT PLASTERING STUCCO
WP-4 CCW-500 TIE-IN TO OTHER MEMBRANES Project No.: 18217
P-2 PLUMBING - FIRST FLOOR PARKING PLAN SECTION 09 9120 PAINTING
WP-5 CCW-500 DRAINS SECTION 31 4100 SHORING Date: 04/26/21
P-2A NATURAL GAS - FIRST FLOOR PARKING PLAN
WP-6 CCW-500 PAVERS SECTION 32 1400 CLAY AND CONCRETE UNIT PAVING Scale: As indicated
WP-7 CCW-500 PENETRATIONS SECTION 32 9218 TOPSOIL FINISH GRADING SHRUBS & SOD Sheet Title:
COVERSHEET
WP-8 MIRACOTE POOL MEMBRANE

Sheet No.:

.C2C-1.0
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS
GENERAL NOTES CONCRETE: EXISTING CONDITIONS:
1. ALL CONCRETE WORK SHALL CONFORM TO ALL THE PROVISIONS OF THE "SPECIFICATIONS FOR STRUCTURAL 1. ALL DIMENSIONS AND ELEVATIONS OF EXISTING STRUCTURES SHOWN ON THE DRAWINGS ARE OBTAINED
CONTRACTORS RESPONSIBILITIES: CONCRETE FOR BUILDINGS" (ACI 301) AND TO THE "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" FROM AVAILABLE SOURCES, AND ARE NOT GUARANTEED TO BE TRUE AND EXACT. THE GENERAL

SURFSIDE, FLORIDA 33154


1. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER THE BUILDING IS FULLY (ACI 318). CONTRACTOR SHALL VERIFY THESE DIMENSIONS AND ELEVATIONS BY ACTUAL FIELD MEASUREMENTS

8777 COLLINS AVENUE


COMPLETED. IT IS SOLELY THE CONTRACTOR’S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND 2. CONCRETE PROPERTIES FOR EACH STRUCTURAL ELEMENT IS DEFINED IN THE DESIGN DATA SECTION ON THIS PRIOR TO FABRICATION OF ANY MATERIALS AND START OF ANY WORK, AND REPORT ANY DISCREPANCIES
SEQUENCE, AND TO ENSURE THE STABILITY OF THE BUILDING AND ITS COMPONENT PARTS, AND THE ADEQUACY SHEET. TO THE ARCHITECT/ENGINEER.
OF TEMPORARY OR INCOMPLETE CONNECTIONS, DURING ERECTING. THIS INCLUDES THE ADDITION OF ANY 3. CONCRETE SHALL CONFORM TO ALL THE PROVISIONS OF "RECOMMENDED PRACTICE FOR HOT WEATHER 2. FOR ADDITIONAL INFORMATION ON THE EXISTING CONSTRUCTION, THE CONTRACTOR SHALL REFER TO
SHORING, SHEETING, TEMPORARY GUYS, BRACING OR TIEDOWNS THAT MIGHT BE NECESSARY. SUCH MATERIAL CONCRETING" (ACI 305) AND "RECOMMENDED PRACTICE FOR COLD WEATHER CONCRETING" (ACI 306). DRAWINGS OF THE EXISTING STRUCTURE.
IS NOT SHOWN ON THE DRAWINGS. IF APPLIED, THEY SHALL BE REMOVED AS CONDITIONS PERMIT AND SHALL 4. ALL FORMWORK SHALL BE IN ACCORDANCE WITH THE AMERICAN CONCRETE INSTITUTE "FORMWORK FOR 3. IN AS MUCH AS THE REMODELING AND/OR REHABILITATION OF AN EXISTING BUILDING REQUIRES THAT
REMAIN THE CONTRACTOR’S PROPERTY. CONCRETE" SPECIAL PUBLICATION NO. 4 AND ACI'S "STANDARD RECOMMENDED PRACTICE FOR CONCRETE CERTAIN ASSUMPTIONS BE MADE REGARDING EXISTING CONDITIONS, AND BECAUSE SOME OF THESE
2. CONTRACTOR SHALL VERIFY CONDITION IN THE FIELD AND IMMEDIATELY NOTIFY THE ARCHITECT/ENGINEER OF FORMWORK" (ACI 347). ASSUMPTIONS CANNOT BE VERIFIED WITHOUT EXPENDING GREAT SUMS OF ADDITIONAL MONEY, OR
ANY CONDITIONS NOT AS ASSUMED; HE SHALL TAKE FIELD MEASUREMENTS AS REQUIRED AND BE RESPONSIBLE 5. CONCRETE MIX DESIGN SHALL BE BASED ON LABORATORY TRIAL BATCH METHOD DESCRIBED IN ACI-318. DESTROYING OTHERWISE ADEQUATE OR SERVICEABLE PORTIONS OF THE BUILDING, THE OWNER AGREES
FOR THE SAME. CONCRETE SHALL ALSO CONFORM TO THE FOLLOWING REQUIREMENTS. THAT, EXCEPT FOR NEGLIGENCE ON THE PART OF MORABITO CONSULTANTS, THE OWNER WILL HOLD
3. CONTRACTOR SHALL COORDINATE WITH ALL RELATED TRADES FOR DETAILING, FABRICATION AND ERECTION 6. THE MAXIMUM WATER CEMENT RATIO W/C SHALL NOT EXCEED 0.56 FOR ALL CONCRETE EXCEPT CONCRETE HARMLESS AND INDEMNIFY MORABITO CONSULTANTS FOR AND AGAINST ANY AND ALL CLAIMS, DAMAGES,
PRIOR TO SUBMITTING SHOP DRAWINGS FOR APPROVAL. EXPOSED TO WEATHER WHICH SHALL NOT EXCEED 0.42. AWARDS, AND COSTS OF DEFENSE ARISING OUT OF DEFICIENCIES IN THE ORIGINAL BUILDING STRUCTURE.
4. ALL STRUCTURAL WORK SHALL BE COORDINATED WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, 7. NO ADMIXTURES CONTAINING CALCIUM CHLORIDE SHALL BE PERMITTED.
ETC. REQUIREMENTS. DISCREPANCIES AND/OR INTERFERENCES SHALL BE REPORTED TO THE 8. THE MAXIMUM SLUMP OF ALL CONCRETE SHALL BE 4". LOAD LIMITATIONS:
ARCHITECT/ENGINEER IMMEDIATELY. 9. ALL CONCRETE SHALL BE CURED WITH LIQUID SEALING COMPOUND CONFORMING TO ASTM C-309, TYPE I AND 1. CONSTRUCTION ACTIVITIES SHALL NOT EXCEED THE FOLLOWING LOAD LIMITATIONS:
5. THE ENGINEER HAS NO EXPERTISE IN, AND TAKES NO RESPONSIBILITY FOR, CONSTRUCTION MEANS AND FEDERAL SPECIFICATION TT-C-00800 OR OTHER APPROVED METHOD WHICH IS COMPATIBLE WITH FLOORING ROOFS: 20 PSF
METHODS OR JOBSITE SAFETY DURING CONSTRUCTION. ADHESIVES AND OTHER SURFACE TREATMENTS. TYPICAL FLOORS: 50 PSF
6. PROCESSING AND/OR APPROVED SUBMITTALS MADE BY THE CONTRACTOR WHICH MAY CONTAIN INFORMATION 10. ALL CONCRETE LEFT EXPOSED AT THE COMPLETION OF THE PROJECT SHALL BE TREATED WITH A CLEAR, PLAZA LEVEL: 100 PSF
RELATED TO CONSTRUCTION METHODS OF SAFETY ISSUES, OR PARTICIPATION IN MEETINGS WHERE SUCH PENETRATING ACRYLIC BASE POLYMER CAPABLE OF PREVENTING INFILTRATION OF WATER BORNE CHLORIDES 2. CONSTRUCTION LOADS IMPOSED BY HEAVY EQUIPMENT OR OTHER CONSTRUCTION ACTIVITY THOUGHT TO
ISSUES MIGHT BE DISCUSSED, SHALL NOT BE CONSTRUED AS VOLUNTARY ASSUMPTION BY THE ENGINEER OF SUCH AS "US CURE & SEAL” BY US CONCRETE PRODUCTS OR APPROVED EQUAL EXCEED THIS LIMIT SHALL BE EVALUATED BY AN INDEPENDENT ENGINEER TO BE HIRED BY THE
ANY RESPONSIBILITY OF EACH CONTRACTOR TO FOLLOW ALL APPLICABLE SAFETY CODES AND REGULATIONS 11. CONTRACTOR SHALL SUPPORT ADJACENT STRUCTURES, UTILITIES, AND EXCAVATIONS AS REQUIRED FOR CONTRACTOR AND SUBMITTED TO THE ARCHITECT/ENGINEER-OF-RECORD FOR APPROVAL
DURING ALL PHASES OF CONSTRUCTION. COMPLETION OF WORK.
7. THE ENGINEER IS NOT ENGAGED IN AND DOES NOT SUPERVISE CONSTRUCTION. 12. ONE SET OF COMPRESSIVE TEST CYLINDERS FOR EACH 100 CUBIC YARDS POURED, BUT NOT LESS THAN ONE SET OWNERSHIP OF DOCUMENTS:
FOR EACH DAY’S POUR AND EACH CLASS OF CONCRETE, ALONG WITH SLUMP TESTS SHALL BE PERFORMED BY A 1. THE CONTRACTOR ACKNOWLEDGES THESE PLANS AND SPECIFICATIONS PREPARED BY MORABITO
DEMOLITION: TESTING LABORATORY APPROVED BY THE STRUCTURAL ENGINEER. CONSULTANTS, INC., AS INSTRUMENTS OF PROFESSIONAL SERVICE.
1. REMOVE EXISTING CONSTRUCTION AS SHOWN ON PLANS. SEE SECTIONS AND DETAILS FOR EXTENT OF 13. NO CONCRETE SHALL BE PLACED UNTIL CONCRETE DESIGN MIXES HAVE BEEN SUBMITTED FOR EACH CLASS OF 2. NEVERTHELESS, THE PLANS AND SPECIFICATIONS PREPARED UNDER THIS AGREEMENT SHALL REMAIN THE
STRUCTURE TO BE REMOVED. CONCRETE AND HAVE BEEN APPROVED BY THE ENGINEER. PROPERTY OF MORABITO CONSULTANTS, INC. UPON COMPLETION OF THE WORK.
2. EXISTING STRUCTURAL ELEMENTS SHALL REMAIN UNLESS SPECIFICALLY NOTED ON PLAN TO BE REMOVED. 14. CONCRETE ON METAL DECK: THE CONTRACTOR SHALL CALCULATE AND INCLUDE ALL ADDITIONAL CONCRETE 3. THE CONTRACTOR AGREES TO HOLD HARMLESS AND INDEMNIFY MORABITO CONSULTANTS, INC., AGAINST

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


3. IF FIELD CONDITIONS DIFFER FROM THOSE SHOWN ON DRAWINGS, NOTIFY ARCHITECT/ENGINEER BEFORE THAT MAY BE REQUIRED DURING PLACING DUE TO DEFLECTION OF STRUCTURE. ALL DAMAGES, CLAIMS, AND LOSSES, INCLUDING DEFENSE COSTS, ARISING OUT OF ANY REUSE OF THE
PROCEEDING WITH DEMOLITION. 15. POLISHED CONCRETE SHALL BE NORMAL WEIGHT CONCRETE A MINIMUM COMPRESSIVE STRENGTH OF f’c = 4500 PLANS AND SPECIFICATIONS WITHOUT THE WRITTEN AUTHORIZATION OF MORABITO CONSULTANTS, INC.
PSI. POLISHED CONCRETE SHALL NOT CONTAIN ANY AIR ENTRAINING ADD MIXTURES OR FLY ASH.

EXCAVATION SUPPORT SYSTEMS: CONCRETE SUPERSTRUCTURE CONSTRUCTION: DESIGN DATA:


1. PROTECT THE SITE FROM CAVING AND UNACCEPTABLE SOIL MOVEMENT. 1. FLOOR SLABS SHALL BE FINISHED TO A MINIMUM FLATNESS F-NUMBER Ff = 30 AND A MINIMUM LEVELNESS F-
NUMBER F1 = 25 IN ANY DIRECTION.

PHASE IIC: OVERALL BUILDING


2. LOCATE THE SHORING SYSTEM TO CLEAR PERMANENT CONSTRUCTION AND TO PERMIT FORMING AND BUILDING CODE: FLORIDA BUILDING CODE 7TH ED - FBC 2020, EXISTING FBC 2020
FINISHING OF CONCRETE SURFACES. 2. LOADS GREATER THAN THE DESIGN LIVE LOADS SHALL NOT BE PLACED ON THE STRUCTURE.

REPAIR AND RESTORATION


3. PROVIDE SHORING SYSTEM ADEQUATELY ANCHORED AND BRACED TO RESIST EARTH AND HYDROSTATIC 3. A CONCRETE STRUCTURE MAY NOT SUPPORT ITS DESIGN LIVE LOAD FOR 28 DAYS. CONCRETE:
PRESSURES. 4. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR ALL TEMPORARY FORMWORK INCLUDING STRIPPING NORMAL WEIGHT CONCRETE HAVING A MINIMUM 28 DAY COMPRESSIVE STRENGTH (f’c) AS FOLLOWS:

REPAIR & RESTORATION


4. THE CONTRACTOR SHALL EMPLOY AN INSPECTION AGENCY APPROVED BY THE A/E TO INSPECT THE SHEETING PROCEDURES FOR CONCRETE FLAT SLABS, SHEETING, SHORING, UNDERPINNING, ETC. SEALED BY A REGISTERED ALL CONCRETE, UNO 4000 PSI
AND SHORING OPERATION TO ASSURE COMPLIANCE IN ALL REQUIREMENTS. PROFESSIONAL ENGINEER AS PART OF THE CONTRACTOR’S WORK.
5. RESPONSIBILITY FOR ALL WORK SHALL BE ASSUMED BY THE CONTRACTOR. HE SHALL TAKE ALL PRACTICAL 5. DO NOT PLACE CONDUITS AND/OR PIPES IN THE PLANE OF SLABS OR WALLS WITHOUT PRIOR APPROVAL OF THE REINFORCING STEEL: Fy = 60,000 PSI
PRECAUTIONS TO ASSURE COMPLETE SAFETY AND SUFFICIENCY OF WORK PROVIDED UNDER THIS SECTION ARCHITECT/ENGINEER.
AND SHALL BE RESPONSIBLE FOR ANY AND ALL DAMAGE. 6. SUBMIT FLOOR PENETRATION LAYOUT COORDINATION DRAWINGS / ELECTRONIC FILES: STRUCTURAL STEEL:
6. SUBMIT SHEETING AND SHORING DESIGN DRAWINGS AND CALCULATIONS WITH THE CONSTRUCTION A. FLOOR PENETRATIONS AFFECT THE STRUCTURAL CAPACITY OF THE FLOOR SYSTEM. THEREFORE, TO VERIFY W & WT SHAPES ASTM A-992 Fy = 50,000 PSI, UNO
ENGINEER'S SEALS SHOWING METHODS, MATERIALS, LOADS, SEQUENCING, AND COORDINATION FOR THAT THE FLOOR PENETRATIONS LAID OUT BY THE CONTRACTOR DO NOT ADVERSELY AFFECT THIS CAPACITY, M & MT SHAPES ASTM A-36 Fy = 36,000 PSI, UNO
APPROVAL PRIOR TO COMMENCEMENT OF WORK. COORDINATION DRAWINGS OF THE FLOOR PENETRATIONS ARE TO BE SUBMITTED FOR APPROVAL. S & ST SHAPES ASTM A-36 Fy = 36,000 PSI, UNO
B. SOLE PURPOSE OF MORABITO CONSULTANTS REVIEW IS TO APPROVE THE LAYOUT RELATIVE TO THE IMPACT IT HP SHAPES ASTM A-36 Fy = 36,000 PSI, UNO
CONTROLLED FILL AND BACKFILL: HAS ON THE STRUCTURE. WHETHER OR NOT THE LAYOUT COMPLIES WITH THE CONTRACT DOCUMENTS CHANNELS ASTM A-36 Fy = 36,000 PSI, UNO
1. SAMPLES OF ALL MATERIALS THAT THE CONTRACTOR PROPOSES TO USE FOR COMPACTED FILL SHALL BE RELATIVE TO ANY ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION OR ANGLES ASTM A-36 Fy = 36,000 PSI, UNO
APPROVED BY THE GEOTECHNICAL ENGINEER. COMMUNICATION CRITERIA WILL NOT BE REVIEWED AND APPROVAL IN NO WAY AUTHORIZES THE CONTRACTOR RECTANGULAR & SQUARE HSS ASTM A-500 GR. B Fy = 46,000 PSI, UNO
2. COMPACTED FILL SHALL CONSIST OF LOCAL MATERIAL FREE OF DELETERIOUS MATTER AND CLASSIFIED SP, TO DEVIATE FROM THE CONTRACT DOCUMENTS. ROUND HSS ASTM A-500 GR. B Fy = 42,000 PSI, UNO
SW, SM, SC, GP, GW, GM, OR GC PER ASTM D 2487. C. OBTAIN FROM ARCHITECT ELECTRONIC BASE FILES OF THE ARCHITECTURAL AND STRUCTURAL FLOOR PLANS STEEL PIPE ASTM A-53 GR. B Fy = 35,000 PSI, UNO
3. THE CONTROL OF THE MOISTURE FOR PLACING THE FILL WILL BE BASED ON THE RESULTS OF COMPACTION FOR USE IN CREATING THE FLOOR PENETRATION LAYOUT COORDINATION DRAWINGS. STEEL PLATES & BARS ASTM A-36 Fy = 36,000 PSI, UNO
TESTS PER ASTM D 1557. D. SUBMIT ELECTRONIC CAD FILES IN AUTOCAD OF FLOOR PENETRATION LAYOUT COORDINATION DRAWINGS ANCHOR BOLTS ASTM F-1554 Fy = 36,000 PSI, UNO
4. ALL COMPACTED FILL SHALL HAVE A DENSITY OF AT LEAST 95% OF THE MODIFIED PROCTOR MAXIMUM DRY SHOWING:
DENSITY AS DETERMINED BY ASTM D 1557. a. ARCHITECTURAL AND STRUCTURAL BACKGROUND.
5. PRIOR TO PLACEMENT OF ANY FILLS, THE SITE SHALL BE STRIPPED OF ALL TOPSOIL, VEGETATION, ROCKS, AND b. OPENING SIZE STRUCTURAL ALUMINUM (UNO):
ORGANIC MATERIALS AND THE EXPOSED SUBGRADE SHALL BE COMPACTED IN PLACE TO A CONFIRMED c. OPENING LOCATION DIMENSIONED RELATIVE TO GRID LINES. SHEET & PLATE UP TO 4” THICK 6061-T6 (Ftu = 42 KSI, Fty = 35 KSI)*
DENSITY OF 95% OF THE MODIFIED PROCTOR MAXIMUM DRY DENSITY. d. ALL OPENINGS FOR MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION, AND COMMUNICATION SHALL BARS, WIRE, AND ROD 6061-T6 (Ftu = 42 KSI, Fty = 35 KSI)*
6. FILL MATERIAL SHALL BE PLACED IN LOOSE LIFTS NOT EXCEEDING 8" IN THICKNESS AND SHALL BE MIXED, BE SHOWN ON THE SAME DRAWINGS EXTRUSIONS, TUBE, PIPES, & FORGINGS 6061-T6 (Ftu = 38 KSI, Fty = 35 KSI)*
SPREAD AND PLACED IN SUCH A WAY AS TO PRODUCE A UNIFORM THICKNESS OF MATERIAL AFTER PLACING. *NOMINAL STRESSES. WELD-AFFECTED STRESSES ACCOUNTED FOR WHERE REQUIRED
7. EACH LAYER OF FILL SHALL BE COMPACTED WITH A MINIMUM OF 6 COMPLETE PASSES ON ALL PORTIONS OF CORE DRILLING:
THE SURFACE OF EACH LIFT OF FILL BY RUBBER TIRED ROLLERS, SHEEPS FOOT ROLLERS OR OTHER 1. THE CONTRACTOR SHALL REVIEW THE EXISTING STRUCTURAL DRAWINGS AND SHALL UNDERTAKE TESTING TO WELD FILLER (AWS D1.2) 5356 (Ftuw = 35 KSI, Ftyw = 14 KSI)
MECHANICAL EQUIPMENT APPROVED BY THE GEOTECHNICAL ENGINEER. LOCATE THE POSITION AND DEPTH OF THE REINFORCING BARS OR PRESTRESSING AT THE LOCATIONS OF THE BOLTS (ASTM F468 / B316) 2024-T4 (Fsu = 37 KSI, Ftu = 62 KSI)
8. COMPACTED FILL PLACED WITHIN 4 FEET OF STRUCTURES AND PIPES SHOULD BE PLACED IN HORIZONTAL PROPOSED CORE, BY HILTI FERROSCAN, GPR, X-RAY, CHIPPING OR OTHER MEANS.
LIFTS NOT TO EXCEED 4 INCHES THICKNESS AND COMPACTED WITH HAND TAMPERS OR LIGHT COMPACTION 2. CORE DRILLED HOLES SHALL ONLY BE ALLOWED THRU THE CONVENTIONALLY REINFORCED ONE-WAY SLABS LIVE LOADS:
EQUIPMENT TO THE SAME STANDARD. UNLESS SPECIFICALLY NOTED ON THE STRUCTURAL DRAWINGS. RESIDENTIAL = 40 PSF
9. HEAVY COMPACTION EQUIPMENT SHOULD NOT BE ALLOWED WITHIN 4 FEET OF STRUCTURES UNLESS A 3. ALL NEW HOLES SHALL BE LOCATED SUCH THAT THEY AVOID EXISTING PRIMARY SLAB REINFORCING. PARKING = 40 PSF
MINIMUM 2 FEET DEPTH OF FILL COVERS THE STRUCTURES. 4. SLAB TEMPERATURE REINFORCING MAY BE CUT WITH APPROVAL FROM DESIGN TEAM. PUBLIC SPACES = 100 PSF
10. WHENEVER IN PLACE DENSITIES ARE FOUND BELOW ACCEPTABLE LIMITS, ADDITIONAL ROLLING TO PRODUCE 5. IF THE OPENINGS CAN NOT BE RELOCATED AWAY FROM PRIMARY REBAR, SUBMIT RFI TO MORABITO GREEN ROOF w/ ACCESS = 100 PSF
THE SPECIFIED DENSITIES SHALL BE REQUIRED. CONSULTANTS REQUESTING APPROVAL PRIOR TO CUTTING ANY BARS. GREEN ROOF w/o ACCESS = 20 PSF
11. THE CONTRACTOR SHALL TAKE ALL MEASURES REQUIRED TO PROVIDE FOR FREE DRAINAGE OF THE SITE AND STAIRS = 100 PSF SEAL License: 89035
TO PREVENT PONDING OF WATER. SEDIMENT CONTROL MEASURES SHALL BE MAINTAINED AT ALL TIMES. REINFORCING STEEL: ROOF = 20 PSF Expires: 02/28/23
12. PLACING OF FILL CONTAINING ORGANIC MATTER; PLACING OF FILL WITH MOISTURE CONTENT TOO HIGH OR 1. REINFORCING STEEL SHALL BE DEFORMED BARS IN ACCORDANCE WITH ASTM A 615, GRADE 60. PARTITIONS = 15 PSF
TOO LOW FOR PROPER COMPACTION; PLACING OF FILL WHEN FREE WATER IS STANDING ON THE EXISTING FILL 2. BENDS AND HOOKS ARE TO BE FABRICATED IN ACCORDANCE WITH ACI SP-66 ACI DETAILING MANUAL AND AS PER
SURFACE; PLACING OF FILL IN A FROZEN CONDITION OR ON TOP OF FROZEN MATTER WILL NOT BE PERMITTED. DETAILS. SUPERIMPOSED DEAD LOADS:
13. THE SOILS ENGINEER SHALL SUPERVISE THE PLACING OF THE COMPACTED FILL AND ALL THE MATERIAL AND 3. PLACE MAIN REINFORCING STEEL SO AS TO PROVIDE 3" MINIMUM COVER FOR FOUNDATIONS POURED ON EARTH, RESIDENTIAL = 6 PSF
EQUIPMENT USED FOR THIS PURPOSE AND SHALL MAKE SUCH SOILS TESTS AS MAY BE REQUIRED FOR THE 2" MINIMUM COVER FOR BEAMS AND COLUMNS, 3/4" MINIMUM COVER FOR SLABS AND 1 1/2" FOR ALL REBAR IN ROOF = 11 PSF
COMPLETION OF THE WORK PERFORMING AT LEAST 6 IN PLACE DENSITY TESTS DURING EACH EIGHT HOUR EXPOSED CONCRETE (EXCEPT AS OTHERWISE IN DETAILS). PAVER TERRACE WITH TOPPING = 85 PSF
SHIFT. 4. LAP DEFORMED BARS IN ACCORDANCE WITH LAP SPLICE SCHEDULE ON THESE DRAWINGS, UNO. GREEN ROOF = 120 PSF + TREES
5. HOOKS SHALL BE STANDARD HOOKS, UNO.
6. PROVIDE ACCESSORIES AND BAR SUPPORTS IN ACCORDANCE WITH THE MANUAL OF STANDARD PRACTICE FOR WIND LOAD ASCE 7-16 /FBC-2020
POST-INSTALLED ANCHORS: DETAILING REINFORCED CONCRETE STRUCTURES (ACI 315).
1. POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE CONSTRUCTION DOCUMENTS. 1. ULTIMATE WIND SPEED: V = 175 MPH
7. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A 1064, UNO. 2. RISK CATEGORY II
2. SUBSTITUTION REQUESTS FOR ALTERNATE PRODUCTS MUST BE APPROVED IN WRITING BY THE STRUCTURAL 8. END LAPS OF ALL WWF REINFORCING SHALL BE LAPPED (1) SQUARE
ENGINEER OF RECORD PRIOR TO USE. CONTRACTOR SHALL PROVIDE CALCULATIONS DEMONSTRATING THAT 3. EXPOSURE CATEGORY D
9. CONCRETE ENGINEERED REINFORCING FIBERS SHALL BE POLYPROPYLENE, COLLATED, FIBRILLATED FIBERS FROM 4. INTERNAL PRESSURE COEFFICIENT = ±0.18 This item has been digitally signed and sealed by Robert J. Miller on the
THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE PERFORMANCE VALUES OF THE SPECIFIED FIBERMESH, INC. INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER’S RECOMMENDATIONS. date adjacent to the seal. Printed copies of this document are not

PRODUCT. SUBSTITUTIONS WILL BE EVALUATED BY THEIR HAVING AN ICC ESR SHOWING COMPLIANCE WITH THE 5. DIRECTIONALITY: Kd = 0.85 considered signed and sealed and the signature must be verified on
any electronic copies.
RELEVANT BUILDING CODE FOR SEISMIC USES, LOAD RESISTANCE, INSTALLATION CATEGORY, AND AVAILABILITY
OF COMPREHENSIVE INSTALLATION INSTRUCTIONS. ADHESIVE ANCHOR EVALUATION WILL ALSO CONSIDER STRUCTURAL COLD FORMED METAL FRAMING: COMPONENTS & CLADDING PRESSURE - WALLS (LRFD)
CREEP, FATIGUE, IN-SERVICE TEMPERATURE AND INSTALLATION TEMPERATURE. 1. ALL STUDS AND RUNNERS SHALL BE FORMED FROM CORROSION-RESISTANT STEEL, CORRESPONDING TO THE WINWARD LEEWARD
3. ANCHOR CAPACITY IS HIGHLY DEPENDENT UPON SPACING BETWEEN ADJACENT ANCHORS AND PROXIMITY OF REQUIREMENTS OF ASTM A-653, CQ, WITH A MINIMUM YIELD STRENGTH OF 33 KSI FOR 18 AND 20 GAUGE STEEL, TRIB. AREA ZONES 4 & 5* ZONE 4 ZONE 5*
ANCHORS TO EDGE OF CONCRETE/MASONRY. INSTALL ANCHORS IN ACCORDANCE WITH SPACING AND EDGE ASTM A-653, SQ, WITH A MINIMUM YIELD STRENGTH OF 50 KSI FOR 16 GAUGE OR HEAVIER, AND SHALL BE DESIGNED <20 SF 107.8 PSF -107.8 PSF -197.6 PSF
CLEARANCES INDICATED ON THE DRAWINGS. IF EDGE DISTANCES OR ANCHOR SPACING IS NOT SPECIFIED ON IN ACCORDANCE WITH AMERICAN IRON & STEEL INSTITUTE (AISI) "SPECIFICATION FOR THE DESIGN OF COLD 50 SF 99.2 PSF -102.1 PSF -174.8 PSF
THE DRAWINGS, PROVIDE THE FOLLOWING MINIMUM DISTANCES. FORMED STEEL MEMBERS." 200 SF 86.4 PSF -93.5 PSF -140.5 PSF
A. EDGE DISTANCES 2. ALL STUDS AND RUNNERS SHALL BE GALVANIZED PER ASTM A-955, G60 AND HAVE THE MINIMUM PHYSICAL >500 SF 77.8 PSF -87.8 PSF -117.7 PSF
Structural Engineers | Remediation & Parking Consultants
a. ADHESIVE ANCHORS: 2 TIMES THE ANCHOR EMBEDMENT LENGTH PROPERTIES BASED ON THE "MARINO/WARE LIGHTWEIGHT STEEL FRAMING MEMBERS AS REQUIRED BY THE *ZONE 5 WIDTH = 8.4 FT 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
b. UNDERCUT ANCHORS: 2.5 TIMES THE ANCHOR EMBEDMENT LENGTH DETAILS ON THESE DRAWINGS. © Copyright Morabito Consultants, Inc.
c. EXPANSION ANCHORS (SLEEVE OR WEDGE): 4 TIMES THE ANCHOR EMBEDMENT LENGTH 3. THE MAXIMUM ALLOWABLE WEB PUNCHING FOR ALL "C" SHAPED STRUCTURAL STUDS SHALL BE ONE (1) INCH FLOOD LOADING – ASCE 24-14 & 7-16
B. ANCHOR SPACING DIAMETER HOLES AT 30” o/c. 1. STRUCTURE FLOOD DESIGN CLASS 2
a. ALL ANCHORS: 3 TIMES THE ANCHOR EMBEDMENT 4. HORIZONTAL STIFFENERS SHALL BE INSTALLED IN THE STUD SYSTEM AT NOT MORE THAN 4'-0" o/c VERTICALLY. 2. FEMA FIRM MAP PANEL 0326L (MAIMI-DADE COUNTY)
3. FLOOD ZONE X
4. ANCHORS SHALL BE INSTALLED BY QUALIFIED PERSONNEL IN ACCORDANCE WITH THE CONSTRUCTION 5. THE FASTENING OF COMPONENTS SHALL BE OF WELDS OF SUFFICIENT SIZE TO INSURE THE STRENGTH OF THE
4. LOMR 15-04-3498P EFFECTIVE 2/5/16
No. Date Revisions
DOCUMENTS, BUILDING CODE, AND MANUFACTURER’S PRINTED INSTALLATION INSTRUCTIONS (MPII). CONNECTION.
5. THE STRUCTURAL ENGINEER OF RECORD MUST RECEIVE DOCUMENTED CONFIRMATION THAT ALL OF THE 6. ALL WELDS AND ANY PROTECTIVE COATINGS DAMAGED DURING HANDLING AND INSTALLATION SHALL BE TOUCHED
CONTRACTOR’S PERSONNEL WHO INSTALL POST-INSTALLED ANCHORS HAVE BEEN PROPERLY TRAINED PRIOR TO UP WITH A ZINC RICH PAINT.
THE COMMENCEMENT OF INSTALLING FOR EACH SPECIFIC PRODUCT. 7. ENGINEERING CALCULATIONS SHALL BE PREPARED, SEALED, AND SUBMITTED FOR ALL MEMBERS NOT
6. INSTALLATION OF ADHESIVE ANCHORS HORIZONTALLY OR UPWARDLY INCLINED TO SUPPORT SUSTAINED SPECIFICALLY SPECIFIED INCLUDING SIZE AND CONNECTIONS OF ALL COMPONENTS.
TENSION LOADS (AS DETERMINED BY THE ENGINEER) SHALL BE PERFORMED BY PERSONNEL CERTIFIED BY THE 8. CONTRACTOR SHALL PROVIDE ADDITIONAL JOISTS, TRUSSES, RAFTERS, STUDS, TRACKS, ETC. BEYOND THAT
ACI-CRSI “ADHESIVE ANCHOR INSTALLER CERTIFICATION PROGRAM”. PRESENTLY SHOWN ON THESE DOCUMENTS TO ASSURE THE ROOF AND EXTERIOR WALL SYSTEM IS COMPLETE
7. ADHESIVE ANCHORS INSTALLED IN HORIZONTAL OR UPWARDLY INCLINED ORIENTATIONS TO RESIST SUSTAINED AND SUFFICIENT TO MEET ALL OF THE REQUIREMENTS OF THE CODE.
TENSION LOADS SHALL BE CONTINUOUSLY INSPECTED DURING INSTALLATION BY AN INSPECTOR SPECIALLY
APPROVED FOR THAT PURPOSE BY THE BUILDING OFFICIAL. THE SPECIAL INSPECTOR SHALL FURNISH A REPORT
EXISTING CONDITIONS:
TO THE STRUCTURAL ENGINEER OF RECORD AND BUILDING OFFICIAL THAT THE WORK COVERED BY THE REPORT
1. ALL DIMENSIONS AND ELEVATIONS OF EXISTING STRUCTURES SHOWN ON THE DRAWINGS ARE OBTAINED FROM
HAS BEEN PROPERLY PERFORMED AND THAT THE MATERIALS USED AND THE INSTALLATION PROCEDURES USED
AVAILABLE SOURCES, AND ARE NOT GUARANTEED TO BE TRUE AND EXACT. THE GENERAL CONTRACTOR SHALL
CONFORM WITH THE APPROVED CONSTRUCTION DOCUMENTS AND THE MANUFACTURER’S PRINTED
VERIFY THESE DIMENSIONS AND ELEVATIONS BY ACTUAL FIELD MEASUREMENTS PRIOR TO FABRICATION OF ANY
INSTALLATION INSTRUCTIONS (MPII).
MATERIALS AND START OF ANY WORK, AND REPORT ANY DISCREPANCIES TO THE ARCHITECT/ENGINEER.
8. ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS AT TIME OF ANCHOR
2. FOR ADDITIONAL INFORMATION ON THE EXISTING CONSTRUCTION, THE CONTRACTOR SHALL REFER TO DRAWINGS OF
INSTALLATION. IF HIGH-EARLY STRENGTH CONCRETE MIXES ARE SPECIFIED, CONTACT THE STRUCTURAL
THE EXISTING STRUCTURE.
ENGINEER OF RECORD FOR APPROVAL OF MINIMUM INSTALLATION AGE.
3. IN AS MUCH AS THE REMODELING AND/OR REHABILITATION OF AN EXISTING BUILDING REQUIRES THAT CERTAIN
9. EXISTING REINFORCING BARS OR PRESTRESSING STEEL IN THE CONCRETE STRUCTURE MAY CONFLICT WITH
ASSUMPTIONS BE MADE REGARDING EXISTING CONDITIONS, AND BECAUSE SOME OF THESE ASSUMPTIONS CANNOT
SPECIFIC ANCHOR LOCATIONS. UNLESS NOTED ON THE DRAWINGS THAT THE BARS CAN BE CUT, THE DESIGNED DRAWN
BE VERIFIED WITHOUT EXPENDING GREAT SUMS OF ADDITIONAL MONEY, OR DESTROYING OTHERWISE ADEQUATE OR
CONTRACTOR SHALL REVIEW THE EXISTING STRUCTURAL DRAWINGS AND SHALL UNDERTAKE TESTING TO HR/JB/RM HR/JB/RM
SERVICEABLE PORTIONS OF THE BUILDING, THE OWNER AGREES THAT, EXCEPT FOR NEGLIGENCE ON THE PART OF
LOCATE THE POSITION AND DEPTH OF THE REINFORCING BARS OR PRESTRESSING AT THE LOCATIONS OF THE
MORABITO CONSULTANTS, THE OWNER WILL HOLD HARMLESS AND INDEMNIFY MORABITO CONSULTANTS FOR AND CHECKED APPROVED
CONCRETE ANCHORS, BY HILTI FERROSCAN, GPR, X-RAY, CHIPPING OR OTHER MEANS.
AGAINST ANY AND ALL CLAIMS, DAMAGES, AWARDS, AND COSTS OF DEFENSE ARISING OUT OF DEFICIENCIES IN THE
10. EXCEPT WHERE INDICATED ON THE DRAWINGS, POST-INSTALLED ANCHORS SHALL CONSIST OF THE FOLLOWING
ORIGINAL BUILDING STRUCTURE.
RM FPM
ANCHOR TYPES. ANCHORS EXPOSED TO WEATHER AND AT SILL PLATES SHALL BE STAINLESS STEEL.
A. MECHANICAL ANCHORS IN CRACKED OR UNCRACKED CONCRETE USE:
LOAD LIMITATIONS: Project No.: 18217
a. HILTI KWIK BOLT-TZ2 EXPANSION ANCHORS
1. CONSTRUCTION ACTIVITIES SHALL NOT EXCEED THE FOLLOWING LOAD LIMITATIONS:
b. HILTI KWIK HUS-EZ AND KH-EZ I SCREW ANCHORS
B. ADHESIVE ANCHORS IN CRACKED AND UNCRACKED CONCRETE USE:
TYPICAL FLOOR 50 PSF Date: 04/26/21
TYPICAL ROOF 20 PSF
a. HILTI HIT-HY 200 SAFE SET SYSTEM WITH HILTI HIT-Z ROD
1. CONSTRUCTION LOADS IMPOSED BY HEAVY EQUIPMENT OR OTHER CONSTRUCTION ACTIVITY THOUGHT TO EXCEED
b. HILTI HIT-HY 200 SAFE SET SYSTEM WITH HILTI HOLLOW DRILL BIT SYSTEM WITH HAS-E THREADED ROD
THIS LIMIT SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER FOR APPROVAL Scale:
C. REBAR DOWELING INTO CONCRETE:
a. HILTI HIT-HY 200 SAFE SET SYSTEM WITH HILTI HOLLOW DRILL BIT SYSTEM
OWNERSHIP OF DOCUMENTS: Sheet Title:
D. ADHESIVE ANCHORS IN HOLLOW / GROUTED / MULTI-WYTHE MASONRY USE:
1. THE CONTRACTOR ACKNOWLEDGES THESE PLANS AND SPECIFICATIONS PREPARED BY MORABITO CONSULTANTS, GENERAL NOTES &
a. HILTI HIT-HY 270 MASONRY ADHESIVE ANCHORING SYSTEM
INC., AS INSTRUMENTS OF PROFESSIONAL SERVICE.
E. MECHANICAL ANCHORS IN GROUTED MASONRY USE:
2. NEVERTHELESS, THE PLANS AND SPECIFICATIONS PREPARED UNDER THIS AGREEMENT SHALL REMAIN THE DESIGN DATA
a. HILTI KWIK BOLT-1 EXPANSION ANCHORS
PROPERTY OF MORABITO CONSULTANTS, INC. UPON COMPLETION OF THE WORK.
b. HILTI KWIK BOLT- EXPANSION ANCHORS
3. THE CONTRACTOR AGREES TO HOLD HARMLESS AND INDEMNIFY MORABITO CONSULTANTS, INC., AGAINST ALL
c. HILTI KWIK HUS-EZ AND KH-EZ I SCREW ANCHORS
DAMAGES, CLAIMS, AND LOSSES, INCLUDING DEFENSE COSTS, ARISING OUT OF ANY REUSE OF THE PLANS AND Sheet No.:
SPECIFICATIONS WITHOUT THE WRITTEN AUTHORIZATION OF MORABITO CONSULTANTS, INC.

.C2C-1.1
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
MAINTENANCE MAINT.
ROOM ROOM

1 2 3 4 5 6 7
114 114 114 114 114 114 122 122 122 36 61

113

112

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


95 94 93 92 91 90 89 13 12 11 10 9
96 STAIRS
111

PHASE IIC: OVERALL BUILDING


RAMP UP

REPAIR AND RESTORATION


REPAIR & RESTORATION
110 97

109 98

83 84 85 86 87 88 14 15 16 17 18 19
MAINTENANCE
ROOM
108 99

107 100
ELEV.

VESTIBULE
STORAGE ROOM 106 101 ELEV.

105 102 82 81 80 79 78 77 27 26 25 24 23 22 21 20
STAIRS SEAL License: 89035
Expires: 02/28/23

104 103

73 74 75 76 This item has been digitally signed and sealed by Robert J. Miller on the
28 29 30 31 32 33 34 35 date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.

67 68 69 70 71 72
142 62 63 64 65 66

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.
15'-5 1/4" (VIF)

20'-0"

NEW COLUMN - SEE No. Date Revisions


STRUCTURAL PLANS

POOL
60 59 58 57 56 55 54 53 52 51 50 49 48 47 46 45 44 43 42 41 40 39 38 37

JACUZZI

DESIGNED DRAWN
POOL EQUIPMENT HR/JB/RM HR/JB/RM
CHECKED APPROVED
RM FPM
PLAN NOTES Project No.: 18217
1. EXISTING BUILDING FRAMING AND CONDITIONS INDICATED ON PLAN ARE BASED ON 5. ALL STRIPING SHALL BE 4" IN WIDTH.
EXISTING DRAWINGS PREPARED BY WILLIAM M. FRIEDMAN & ASSOCIATES EXISTING STANDARD PARKING THIS LEVEL = 120 SPACES Date: 04/26/21
ARCHITECTS, INC AND BREITERMAN JUARDO & ASSOCIATES, DATED 08-22-1979 AND A 6. ALL NON-PARKING AREAS SHALL HAVE 4" WIDE PAINTED STRIPING AT 1'-6" o/c.
LIMITED FIELD INVESTIGATION CONDUCTED BY MORABITO CONSULTANTS.
CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND CONTACT MORABITO 7. ALL STRIPING FOR THE STANDARD STALLS AND ASSOCIATED NON-PARKING AREAS SHOULD BE EXISTING PARKING THIS LEVEL = 120 SPACES Scale: 3/32" = 1'-0"
CONSULTANTS PRIOR TO CONSTRUCTION IF CONDITIONS VARY FROM WHAT IS YELLOW.
SHOWN ON PLAN. Sheet Title:
8. ALL STRIPING FOR THE HANDICAP STALLS AND ASSOCIATED NON-PARKING AREAS SHOULD BE BASEMENT PARKING
2. EXISTING STRUCTURE CONSISTS OF CAST-IN-PLACE CONCRETE TWO-WAY FLAT SKY BLUE. THE HANDICAP FIGURE SHOULD BE WHITE WITH A SKY-BLUE BACKGROUND.
PLATE ELEVATED FLOOR SLABS BEARING ON CAST-IN-PLACE CONCRETE COLUMNS PLAN
OVER A FRAMED CONCRETE SLAB ON GRADE SUPPORTED BY PILE CAPS. 9. PARKING SPACE NUMBERING IN 6" LETTERING TO END OF PARKING SPACE AND ON COLUMN
ADJACENT TO SPACE PER PAINT SPECIFICATION SECTION 09 9120. PARKING SPACE NUMBERING
3. EXISTING ELEVATION TOP OF STRUCTURAL SLAB VARIES. AS NOTED ON THIS SHEET. Sheet No.:
4. EXISTING CONDITIONS ARE SHOWN HALF-TONE. 10. APPLY SILANE SEALER TO ALL CONCRETE SLAB ON GRADE AREAS. SEE SPECIFICATION 03 0100.
A2C-0.5
6
A.1 B.1 S2C-2.5 D E 5 1 H I K L M 8.130
N O O.1 Q
S2C-2.9

SOUTH CONDOMINIUM
S2C-2.8

CHAMPLAIN TOWERS
8'-4" ± 19'-8" ± 14'-6" ± 32'-6" ± 5'-0" ± 23'-0" ± 21'-6" ± 22'-6" ± 19'-8" ± 20'-4" ± 10'-4" ± 10'-4" ±
4
EX. SIDEWALK
S2C-2.5 T/SLAB= 8.71±

SURFSIDE, FLORIDA 33154


EX. SHAFT

3'-6"

8777 COLLINS AVENUE


NOTE 7
EX. CONC.

NOTE 2

ACCESS RAMP DOWN


SERVICE AREA

EX. CONC. GARAGE


EX. CONC. SERVICE
ACCESS RAMP UP
EX. SHAFT
1 TRANSITION 6 NOTE 7
S2C-2.8 NEW PAVING TO NOTE 7 S2C-2.8
4 EX. GRADE NOTE 7

S2C-2.5 CONTROL NON-VEHICULAR


4 JOINT (TYP) NEW PRECAST 4 PAVEMENT AREA - NOTE 3
4
WHEEL STOP S2C-2.4
S2C-2.4 S2C-2.4

2'-0"
1.1 1.1
NOTE 6 (TYP.)
3 NOTE 5 (TYP.)
S2C-2.3
NOTE 7
EMERGENCY
20'-8" ±

NOTE 7
GENERATOR ROOM

23'-8" ±
6
S2C-2.4 2
S2C-2.3

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


NEW CLOSURE
2.1 WALL EX. STEPS
ELECTRICAL 3
NEW PRECAST
WHEEL STOP ROOM
4'-0"

13'-8" ±
PROPERTY LINE VEHICULAR PAVEMENT
22'-0" ±

PHASE IIC: OVERALL BUILDING


EX. PLANTER AREA - NOTE 1 STAIR
REPAIR STEPS
TOWER

REPAIR AND RESTORATION


8'-0"
WALLS NOTE 15 SIMILAR TO
3 7 / S2C-2.4

REPAIR & RESTORATION


S2C-2.3 4
7'-0"
NEW ACCESSIBLE

NOTE 7
EX. SIDEWALK TRASH
RAMP (NOTE 3) NOTE 7
5 ROOM

14'-6" ±
T/SLAB= 7.71±

1'-0"
5 4'-0"

3 S2C-2.7
• ADA RAMP SHALL HAVE ALL 2
S2C-2.8 PAVERS MORTAR SET AND JOINTS S2C-2.3 HANDRAILS
UP
20'-0" ±

(1:1 GROUTED 1'-0"


2) 6

UP (1:12)
1'-0
"
"

15'-11"

7'-6" ±
7'-9

4'-6"
UP (1:20 MAX.) NEW ACCESSIBLE
4 RAMP
8
S2C-2.8 EX. STEPS
8.1 LANDING (1:50 CONT. HANDRAIL
NOTE 7 MAX SLOPE) REPAIR STEPS
2 1'-10"

5'-0"
SIMILAR TO
S2C-2.3 7 / S2C-2.4
1A

21'-4" ±
ELEVATORS
1 NOTE 7
S2C-2.3
20'-0" ±

S2C-2.7 EX. STEPS NEW HAND RAIL


1'-0" FIRE DOOR TO NON-VEHICULAR
EX. SIDEWALK EX. FFE = 10.89±
T/SLAB= 7.26± BE REPLACED PAVEMENT AREA - NOTE 3
EX. RAILINGS NOTE 5 (TYP.)
7
NOTE 3 TO REMAIN
EX. STEPS S2C-2.4 9.1
NOTE 6 (TYP.) REPAIR STEPS
10.1 EX. STAIR FINISHES SIMILAR TO
TO REMAIN
NOTE 3 7 / S2C-2.4
1A
(TYP)
S2C-2.3

19'-10" ±
1A
STAIR NOTE 7
1 EX. STEPS EX. STEPS S2C-2.3 SEAL License: 89035
20'-0" ±

TOWER Expires: 02/28/23


S2C-2.8 EX. STEP EX. SHAFT
2
S2C-2.3 EX. RAILING EX. STEPS
TO REMAIN NOTE 7
EX. SHAFT EX. PLANTER WALLS
EX. PLANTER
WALLS 11.1
12.1 4
NOTE 7
S2C-2.6 EX. STEPS
REMOVE STONE FROM PLANTER 1A

19'-10" ±
NOTE 7 1A REPAIR STEPS

2'-6"
BOX, RE-WATERPROOF AND
EX. SIDEWALK S2C-2.3 S2C-2.3 SIMILAR TO
REINSTALL STONE 1A 7 / S2C-2.4
23'-0" ±

T/SLAB= 6.99± This item has been digitally signed and sealed by Robert J. Miller on the
date adjacent to the seal. Printed copies of this document are not
S2C-2.3
AY

considered signed and sealed and the signature must be verified on


1 any electronic copies.
VEW

S2C-2.6 1 4
DRI
IDEN 3/4"

5 9'-3" MIN 13.1


ED
22'-3

NOT NOTE 5 (TYP.) VARIES


E2 S2C-2.4
2
14 S2C-2.8 3
NOTE 8 (TYP)
W

S2C-2.6 5
NEW

Structural Engineers | Remediation & Parking Consultants


S2C-2.6 1A 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
REPLACE 561.316.7660 | www.morabitoconsultants.com
S2C-2.3 © Copyright Morabito Consultants, Inc.
BOLLARD 5
S2C-2.4
23'-0" ±

3 NON-VEHICULAR
NOTE 6 S2C-2.3 PAVEMENT AREA - NOTE 3 No. Date Revisions
(TYP.)
VEHICULAR PAVEMENT
4 AREA - NOTE 1
NOTE 7
S2C-2.5
NOTE 9
14.1 NEW SUN SHADE
NOTE 7 STRUCTURE. SUBMIT SIGNED EX. POOL
EX. HYDRANT AND SEALED SHOP
9'-0" MIN
DRAWINGS FOR APPROVAL
VARIES
1A
16'-4"

4" CLEAR OF EX. SHAFT NOTE 8 (TYP) S2C-2.3

EX. JACUZZI
HYDRANT 1
1 14
S2C-2.8
RAISED WALL FOR
SIGNAGE
PROPERTY LINE EX. FOUNDATION
WALL BELOW DESIGNED DRAWN
14'-8"± HR/JB/RM HR/JB/RM
OUTSIDE
RADIUS 7 NOTE 7 CHECKED APPROVED
S2C-2.9
RM FPM
START CURVE
NOTE 14 17'-0"± 19'-0" ± 19'-0" ± 19'-6" ± 20'-0" ± 20'-0" ± 8'-0" ± 12'-0" ± 20'-0" ± Project No.: 18217
7. NEW SOIL AND PLANTING MATERIAL SHALL BE LIGHTWEIGHT (80 PCF MAX.) AND SHALL NOT EXCEED 1
EXPANDED PLANTER / 1'-6" DEEP, EXCEPT AT TREE LOCATIONS. CONTRACTOR SHALL PROVIDE GEOFOAM INFILL AS REQUIRED
GAS METER ACCESS TO ACHIEVE TOP OF SOIL ELEVATIONS IN PLANTERS. SUBMIT SOIL DATA FOR APPROVAL. NEW PLANTER S2C-3.6 Date: 04/26/21
R S T A.1 B.2 D.1 F.1 G.1 I SOIL INDICATED AS THUS:
PLAN NOTES
12. APPLY SILANE SEALER TO ALL CONCRETE SLAB ON GRADE AREAS. SEE Scale: 3/32" = 1'-0"
1. TYPICAL VEHICULAR PAVEMENT SYSTEM SHALL BE 2-3/8" CONCRETE INTERLOCKING PAVERS OVER 1" SETTING BED CONSISTING OF A BLEND OF 3 PARTS 8. NEW AND REPLACEMENT PLANTER AND HARDSCAPE DRAIN LOCATIONS ARE SHOWN ON THE PLAN. SEE SPECIFICATION 03 0100.
ASTM C33 SAND AND 1 PART DRY TYPE IV (LOW HEAT HYDRYATION) PORTLAND CEMENT. SEE LANDSCAPE ARCHITECT PLANS FOR PAVER STYLES AND 4. ALL STEP RISER AND TREAD PAVERS SHALL BE MORTAR SET ON DRAINAGE BOARD AND JOINT GROUTED. SEE S2C-1.1 FOR CONCRETE TOPPING SLOPES. SEE PLUMBING FOR DRAIN TYPES. Sheet Title:
PATTERNS. TYPICAL PAVER JOINTS SHALL HAVE POLYMERIC AGGREGATE. SEE SPECIFICATION SECTION 32 14 00 FOR ADDITIONAL REQUIREMENTS. PAVER SPECIFICATION SECTION 32 14 00 FOR MORTAR AND GROUT REQUIREMENTS. SEE SHEET WP-6 FOR MORTAR SET
13. EXISTING POOL FINISH TO BE REMOVED, STRUCTURE REPAIRED AS NECESSARY,
SYSTEM TO BE PLACED OVER SLOPED CONCRETE TOPPINGS PER STRUCTURAL PLANS. DETAILS. 9. RESTORE PARKING SPACES WITH THE QUANTITY OF SPACES AS SHOWN. ALL PARKING STRIPING SHALL AND WATERPROOFING APPLIED. REFERENCE SHEETS S2C-3.0 AND WP-8. LEVEL 1 FLOOR PLAN
BE YELLOW AND 4" IN WIDTH. SEE PROJECT SPECIFICATIONS FOR PAINTING REQUIREMENTS.
2. VEHICULAR PAVEMENT AREAS AT TRANSITIONS TO SIDEWALK / ROADWAY SHALL BE MORTAR SET ON DRAINAGE BOARD FOR MINIMUM 2'-0" WIDTH, UNO. 5. REPLACE GLASS WINDOWS AND DOORS AT FIRST FLOOR COMMON AREAS AS NOTED ON PLAN. REPLACEMENT
14. CREATE SOLID REINFORCED CONCRETE WALL FOR 5 FOOT WIDTH CENTERED IN
MORTAR SET PAVERS SHALL HAVE GROUTED JOINTS. SEE SPECIFICATION SECTION 32 14 00 FOR MORTAR AND GROUT REQUIREMENTS. SEE SHEET WP-6 WINDOWS AND DOORS SHALL HAVE AN APPROVED NOA MEETING THE REQUIREMENTS OF THE 2020 FBC. REPLACEMENT 10. CONTRACTOR'S MISC METALS FABRICATOR SHALL RETAIN A LICENSED PROFESSIONAL ENGINEER TO
FRONT OF PROPOSED GAS METER. SEE DETAIL 7/S2C-2.9.
FOR MORTAR SET DETAILS. INCLUDES NEW WOOD BUCKS, WATERPROOFING OF MASONRY OPENING AND WOOD BUCKS, AND PLACEMENT OF DESIGN NEW RAILINGS TO MEET LOAD AND DIMENSIONAL REQUIREMENTS OF THE 2020 FBC. SUBMIT
TEMPORARY WEATHER WALLS TO PROTECT THE INTERIOR DURING DOOR REPLACEMENT STRUCTURAL SIGNED AND SEALED SHOP DRAWINGS FOR APPROVAL. 15. CREATE PARTITIONS FOR EXPANDED ELECTRICAL ROOM. USE 8" ASTM C-90
Sheet No.:
3. TYPICAL NON-VEHICULAR PAVEMENT SYSTEM SHALL BE 2-3/8" CONCRETE INTERLOCKING PAVERS OVER 1" SETTING BED CONSISTING OF ASTM C33 SAND. REINFORCEMENTS.
BLOCKS. EPOXY DOWEL #5 VERTICAL BARS AT ENDS AND WALL MID SPAN AND FILL
SEE LANDSCAPE ARCHITECT PLANS FOR PAVER STYLES AND PATTERNS. TYPICAL PAVER JOINTS SHALL HAVE POLYMERIC AGGREGATE. SEE SPECIFICATION
SECTION 32 14 00 FOR ADDITIONAL REQUIREMENTS. PAVER SYSTEM TO BE PLACED OVER SLOPED CONCRETE TOPPINGS PER STRUCTURAL PLANS. 6. NEW PLANTER WALLS ARE INDICATED ON PLAN THUS: AND BE TOOTHED INTO EXISTING CMU TO REMAIN.
11. SEE BID FORM FOR ALL OTHER ITEMS NOTE SHOWN ON PLAN. WITH TYPE S MORTAR. USE HORIZONTAL JOINT REINFORCING EVERY OTHER
COURSE. JOINTS TO BE TUCK POINTED. PAINT TO MATCH EXISTING.
A2C-1.0
A B D E I K L M 8.130
N O O.1 P

SOUTH CONDOMINIUM
8" ±

CHAMPLAIN TOWERS
9'-0" ± 21'-0" ± 14'-6" ± 32'-6" ± 5'-0" ± 23'-0" ± 21'-6" ± 22'-6" ± 19'-8" ± 20'-4" ± 10'-4" ±

SURFSIDE, FLORIDA 33154


NOTE 6 (TYP.)

8777 COLLINS AVENUE


1 1

NOTE 5 (TYP.) 1.1


21'-0" ±

24'-4" ±
NOTE 6 (TYP.)
2
STAIR #2
3

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


13'-8" ±
22'-4" ±

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
4

REPAIR & RESTORATION


5

14'-6" ±
NOTE 5 (TYP.)
11'-0" ±

6
7

7'-6" ±
8
17'-6" ±

NOTE 5 (TYP.)

22'-0" ±
ELEV.
9
12'-6" ±

ELEV. 9.1
NOTE 5 (TYP.)
SEAL License: 89035
Expires: 02/28/23
10
11 STAIR #1

NOTE 6 (TYP.)
17'-6" ±

NOTE 6 (TYP.)

This item has been digitally signed and sealed by Robert J. Miller on the
PLAN NOTES date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.
FIRE DOOR TO FIRE DOOR TO 1. EXISTING BUILDING FRAMING AND CONDITIONS INDICATED ON PLAN ARE BASED ON
BE REPLACED BE REPLACED EXISTING DRAWINGS PREPARED BY WILLIAM M. FRIEDMAN & ASSOCIATES
12 ARCHITECTS, INC AND BREITERMAN JUARDO & ASSOCIATES (CONSULTING
ENGINEERS), DATED 08-22-1979 AND A LIMITED FIELD INVESTIGATION CONDUCTED BY
7'-2" ±

MORABITO CONSULTANTS. THE CONTRACTOR SHALL VERIFY ALL EXISTING


CONDITIONS AND CONTACT MORABITO CONSULTANTS PRIOR TO CONSTRUCTION IF
CONDITIONS VARY FROM WHAT IS SHOWN ON PLAN.
13 2. EXISTING STRUCTURE CONSISTS OF CAST-IN-PLACE CONCRETE TWO-WAY FLAT
Structural Engineers | Remediation & Parking Consultants
206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
PLATE ELEVATED FLOOR SLAB BEARING ON CAST-IN-PLACE CONCRETE COLUMNS. 561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

3. EXISTING ELEVATION TOP OF STRUCTURAL SLAB VARIES, REFER TO EXISTING


ARCHITECTURAL ELEVATIONS FOR TOP OF SLAB ELEVATION AT EACH FLOOR. ALL
ELEVATIONS AND DIMENSIONS SHALL BE VERIFIED BY THE CONTRACTOR. No. Date Revisions
17'-4" ±

4. EXISTING CONDITIONS ARE SHOWN HALF-TONE.

5. UNIT OWNERS MAY ELECT TO REPLACE THEIR EXISTING WINDOWS/DOORS.


REPLACEMENT HARDWARE SHALL BE PER THE SCHEDULES AND GUIDELINES ON
THE ARCHITECTURAL DRAWINGS BY SCOTT DYER ARCHITECTS. AS A COMPONENT
OF WINDOW/DOOR REPLACEMENT, STORM SHUTTERS SHALL BE REMOVED.
WINDOW/DOOR REPLACEMENT MASONRY OPENINGS WILL BE WATERPROOFED IN
14 ACCORDANCE WITH S2C-3.3.

6. AFTER ALL CONCRETE REPAIRS AT UNIT BALCONIES HAVE BEEN COMPLETED THE
CONTRACTOR SHALL CONDUCT A WATER TEST AND PROVIDE AN EPOXY/SAND
LEVELING COAT AS REQUIRED TO ELIMINATE PONDING. FINISH ALL BALCONIES WITH
A TRAFFIC BEARING MEMBRANE PER SHEET TBM-1.

7. SEE BID FORM FOR ALL OTHER ITEMS NOTE SHOWN ON PLAN.
23'-8" ±

DESIGNED DRAWN
HR/JB/RM HR/JB/RM
CHECKED APPROVED
RM FPM
Project No.: 18217
NOTE 5 (TYP.)
Date: 04/26/21
15
Scale: 1/8" = 1'-0"
Sheet Title:
NOTE 6 (TYP.)
LEVEL 2-8 FLOOR PLAN
G
24'-4" ± 23'-8" ± 10'-0" ± 26'-0" ±
Sheet No.:
A C F J
A2C-1.1
A B D E I K L M 8.130
N O O.1 P

SOUTH CONDOMINIUM
8" ±

CHAMPLAIN TOWERS
9'-0" ± 21'-0" ± 14'-6" ± 32'-6" ± 5'-0" ± 23'-0" ± 21'-6" ± 22'-6" ± 19'-8" ± 20'-4" ± 10'-4" ±

SURFSIDE, FLORIDA 33154


NOTE 6 (TYP.)

8777 COLLINS AVENUE


1 1

NOTE 5 (TYP.) 1.1


21'-0" ±

24'-4" ±
NOTE 6 (TYP.)
2
STAIR #2
3

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


13'-8" ±
22'-4" ±

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
4

REPAIR & RESTORATION


5

14'-6" ±
NOTE 5 (TYP.)
11'-0" ±

6
7

7'-6" ±
8
17'-6" ±

NOTE 5 (TYP.)

22'-0" ±
ELEV.
9
12'-6" ±

ELEV. 9.1
NOTE 5 (TYP.)
SEAL License: 89035
Expires: 02/28/23
10
11 STAIR #1

NOTE 6 (TYP.)
17'-6" ±

NOTE 6 (TYP.)

This item has been digitally signed and sealed by Robert J. Miller on the
PLAN NOTES date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.
FIRE DOOR TO FIRE DOOR TO 1. EXISTING BUILDING FRAMING AND CONDITIONS INDICATED ON PLAN ARE BASED ON
BE REPLACED BE REPLACED EXISTING DRAWINGS PREPARED BY WILLIAM M. FRIEDMAN & ASSOCIATES
12 ARCHITECTS, INC AND BREITERMAN JUARDO & ASSOCIATES (CONSULTING
ENGINEERS), DATED 08-22-1979 AND A LIMITED FIELD INVESTIGATION CONDUCTED BY
7'-2" ±

MORABITO CONSULTANTS. THE CONTRACTOR SHALL VERIFY ALL EXISTING


CONDITIONS AND CONTACT MORABITO CONSULTANTS PRIOR TO CONSTRUCTION IF
CONDITIONS VARY FROM WHAT IS SHOWN ON PLAN.
13 2. EXISTING STRUCTURE CONSISTS OF CAST-IN-PLACE CONCRETE TWO-WAY FLAT
Structural Engineers | Remediation & Parking Consultants
206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
PLATE ELEVATED FLOOR SLAB BEARING ON CAST-IN-PLACE CONCRETE COLUMNS. 561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

3. EXISTING ELEVATION TOP OF STRUCTURAL SLAB VARIES, REFER TO EXISTING


ARCHITECTURAL ELEVATIONS FOR TOP OF SLAB ELEVATION AT EACH FLOOR. ALL
ELEVATIONS AND DIMENSIONS SHALL BE VERIFIED BY THE CONTRACTOR. No. Date Revisions
17'-4" ±

4. EXISTING CONDITIONS ARE SHOWN HALF-TONE.

5. UNIT OWNERS MAY ELECT TO REPLACE THEIR EXISTING WINDOWS/DOORS.


REPLACEMENT HARDWARE SHALL BE PER THE SCHEDULES AND GUIDELINES ON
THE ARCHITECTURAL DRAWINGS BY SCOTT DYER ARCHITECTS. AS A COMPONENT
OF WINDOW/DOOR REPLACEMENT, STORM SHUTTERS SHALL BE REMOVED.
WINDOW/DOOR REPLACEMENT MASONRY OPENINGS WILL BE WATERPROOFED IN
14 ACCORDANCE WITH S2C-3.3.

6. AFTER ALL CONCRETE REPAIRS AT UNIT BALCONIES HAVE BEEN COMPLETED THE
CONTRACTOR SHALL CONDUCT A WATER TEST AND PROVIDE AN EPOXY/SAND
LEVELING COAT AS REQUIRED TO ELIMINATE PONDING. FINISH ALL BALCONIES WITH
A TRAFFIC BEARING MEMBRANE PER SHEET TBM-1.

7. SEE BID FORM FOR ALL OTHER ITEMS NOTE SHOWN ON PLAN.
23'-8" ±

DESIGNED DRAWN
HR/JB/RM HR/JB/RM
CHECKED APPROVED
RM FPM
Project No.: 18217
NOTE 5 (TYP.)
Date: 04/26/21
15
Scale: 1/8" = 1'-0"
Sheet Title:
NOTE 6 (TYP.)
LEVEL 9-11 FLOOR PLAN
G
24'-4" ± 23'-8" ± 10'-0" ± 26'-0" ±
Sheet No.:
A C F J
A2C-1.2
A B D E I K L M 8.130
N O O.1 P

SOUTH CONDOMINIUM
8" ±

CHAMPLAIN TOWERS
9'-0" ± 21'-0" ± 14'-6" ± 32'-6" ± 5'-0" ± 23'-0" ± 21'-6" ± 22'-6" ± 19'-8" ± 20'-4" ± 10'-4" ±

H NOTE 6

SURFSIDE, FLORIDA 33154


(TYP.)

8777 COLLINS AVENUE


1 1

NOTE 5 (TYP.) 1.1


21'-0" ±

24'-4" ±
NOTE 6 (TYP.)
2
STAIR #2
3

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


13'-8" ±
22'-4" ±

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
4

REPAIR & RESTORATION


5

14'-6" ±
NOTE 5 (TYP.)
11'-0" ±

6
7

7'-6" ±
8
17'-6" ±

NOTE 5 (TYP.)

22'-0" ±
ELEV.
9
12'-6" ±

ELEV. 9.1
NOTE 5 (TYP.)
SEAL License: 89035
Expires: 02/28/23
10
11 STAIR #1

NOTE 6 (TYP.)
17'-6" ±

NOTE 6 (TYP.)

This item has been digitally signed and sealed by Robert J. Miller on the
PLAN NOTES date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.
FIRE DOOR TO FIRE DOOR TO 1. EXISTING BUILDING FRAMING AND CONDITIONS INDICATED ON PLAN ARE BASED ON
BE REPLACED BE REPLACED EXISTING DRAWINGS PREPARED BY WILLIAM M. FRIEDMAN & ASSOCIATES
12 ARCHITECTS, INC AND BREITERMAN JUARDO & ASSOCIATES (CONSULTING
ENGINEERS), DATED 08-22-1979 AND A LIMITED FIELD INVESTIGATION CONDUCTED BY
7'-2" ±

MORABITO CONSULTANTS. THE CONTRACTOR SHALL VERIFY ALL EXISTING


CONDITIONS AND CONTACT MORABITO CONSULTANTS PRIOR TO CONSTRUCTION IF
CONDITIONS VARY FROM WHAT IS SHOWN ON PLAN.
13 2. EXISTING STRUCTURE CONSISTS OF CAST-IN-PLACE CONCRETE TWO-WAY FLAT
Structural Engineers | Remediation & Parking Consultants
206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
PLATE ELEVATED FLOOR SLAB BEARING ON CAST-IN-PLACE CONCRETE COLUMNS. 561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

3. EXISTING ELEVATION TOP OF STRUCTURAL SLAB VARIES, REFER TO EXISTING


ARCHITECTURAL ELEVATIONS FOR TOP OF SLAB ELEVATION AT EACH FLOOR. ALL
ELEVATIONS AND DIMENSIONS SHALL BE VERIFIED BY THE CONTRACTOR. No. Date Revisions
17'-4" ±

4. EXISTING CONDITIONS ARE SHOWN HALF-TONE.

5. UNIT OWNERS MAY ELECT TO REPLACE THEIR EXISTING WINDOWS/DOORS.


REPLACEMENT HARDWARE SHALL BE PER THE SCHEDULES AND GUIDELINES ON
THE ARCHITECTURAL DRAWINGS BY SCOTT DYER ARCHITECTS. AS A COMPONENT
OF WINDOW/DOOR REPLACEMENT, STORM SHUTTERS SHALL BE REMOVED.
WINDOW/DOOR REPLACEMENT MASONRY OPENINGS WILL BE WATERPROOFED IN
14 ACCORDANCE WITH S2C-3.3.

6. AFTER ALL CONCRETE REPAIRS AT UNIT BALCONIES HAVE BEEN COMPLETED THE
CONTRACTOR SHALL CONDUCT A WATER TEST AND PROVIDE AN EPOXY/SAND
LEVELING COAT AS REQUIRED TO ELIMINATE PONDING. FINISH ALL BALCONIES WITH
A TRAFFIC BEARING MEMBRANE PER SHEET TBM-1.

7. SEE BID FORM FOR ALL OTHER ITEMS NOTE SHOWN ON PLAN.
23'-8" ±

DESIGNED DRAWN
HR/JB/RM HR/JB/RM
CHECKED APPROVED
RM FPM
Project No.: 18217
NOTE 5 (TYP.)
Date: 04/26/21
15
Scale: 1/8" = 1'-0"
Sheet Title:
NOTE 6 (TYP.) LEVEL 12 FLOOR PLAN
G
24'-4" ± 23'-8" ± 10'-0" ± 26'-0" ±
Sheet No.:
A C F J
A2C-1.3
A B D E I K L M 8.130
N O O.1 P

SOUTH CONDOMINIUM
8" ±

CHAMPLAIN TOWERS
9'-0" ± 21'-0" ± 14'-6" ± 32'-6" ± 5'-0" ± 23'-0" ± 21'-6" ± 22'-6" ± 19'-8" ± 20'-4" ± 10'-4" ±

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
P27 S1 EX. WALL BELOW
P26
1 1

8"
P28 P29 P30 P31 P32 P33 P34
EL.124'-2"± 1.1
P35
EX. SOFFIT NOTE 6 (TYP.)
ANCHOR
21'-0" ±

EX. COLUMN

24'-4"
ANCHOR

EX. POSTED ROOF ANCHOR,


(TYP, 1 OF 42)

2
P36
P37 P38 P39 STAIR #2
3

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


FIRE DOOR TO

13'-8"
BE REPLACED
22'-4" ±

NOTE 8 NOTE 8
NOTE 8

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
4

REPAIR & RESTORATION


P40 FIRE DOOR TO
5 BE REPLACED

14'-6"
NOTE 5 (TYP.)
11'-0" ±

P41 6
7

7'-6"
P42
P43
C6
8
EL.124'-2"±
17'-6" ±

EX. WALL BELOW

C7

ELEV. NOTE 5 (TYP.)

22'-0"
EX. COLUMN
9 FIRE DOOR TO ANCHOR
BE REPLACED
P44
12'-6" ±

ELEV. 9.1

8"
P45 SEAL License: 89035
Expires: 02/28/23
C8 C9 10
P46
11 STAIR #1

P47

FIRE DOOR TO NOTE 6 (TYP.)


17'-6" ±

BE REPLACED

This item has been digitally signed and sealed by Robert J. Miller on the
PLAN NOTES date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.

1. EXISTING BUILDING FRAMING AND CONDITIONS INDICATED ON PLAN ARE BASED ON


12 EXISTING DRAWINGS PREPARED BY WILLIAM M. FRIEDMAN & ASSOCIATES
ARCHITECTS, INC AND BREITERMAN JUARDO & ASSOCIATES (CONSULTING
ENGINEERS), DATED 08-22-1979 AND A LIMITED FIELD INVESTIGATION CONDUCTED BY
7'-2" ±

P48 FIRE DOOR TO P50 MORABITO CONSULTANTS. THE CONTRACTOR SHALL VERIFY ALL EXISTING
BE REPLACED P49 CONDITIONS AND CONTACT MORABITO CONSULTANTS PRIOR TO CONSTRUCTION IF
EL.124'-2"± CONDITIONS VARY FROM WHAT IS SHOWN ON PLAN.
13 Structural Engineers | Remediation & Parking Consultants
206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
2. EXISTING STRUCTURE CONSISTS OF CAST-IN-PLACE CONCRETE TWO-WAY FLAT 561.316.7660 | www.morabitoconsultants.com
PLATE ELEVATED FLOOR SLAB BEARING ON CAST-IN-PLACE CONCRETE COLUMNS. © Copyright Morabito Consultants, Inc.
P51
3. EXISTING ELEVATION TOP OF STRUCTURAL SLAB IS 124'-2"±. ALL ELEVATIONS AND
DIMENSIONS SHALL BE VERIFIED BY THE CONTRACTOR.
P52 No. Date Revisions
17'-4" ±

P53
4. EXISTING CONDITIONS ARE SHOWN HALF-TONE.

5. UNIT OWNERS MAY ELECT TO REPLACE THEIR EXISTING WINDOWS/DOORS.


REPLACEMENT HARDWARE SHALL BE PER THE SCHEDULES AND GUIDELINES ON
THE ARCHITECTURAL DRAWINGS BY SCOTT DYER ARCHITECTS. AS A COMPONENT
OF WINDOW/DOOR REPLACEMENT, STORM SHUTTERS SHALL BE REMOVED.
WINDOW/DOOR REPLACEMENT MASONRY OPENINGS WILL BE WATERPROOFED IN
ACCORDANCE WITH S2C-3.3.
14 P56
P54 P55 6. AFTER ALL CONCRETE REPAIRS AT UNIT BALCONIES HAVE BEEN COMPLETED THE
CONTRACTOR SHALL CONDUCT A WATER TEST AND PROVIDE AN EPOXY/SAND
LEVELING COAT AS REQUIRED TO ELIMINATE PONDING. FINISH ALL BALCONIES WITH
A TRAFFIC BEARING MEMBRANE PER SHEET TBM-1.

7. SEE BID FORM FOR ALL OTHER ITEMS NOTE SHOWN ON PLAN.

8. REPLACE COMMON AREA WINDOWS WITH NEW UNIT COMPLYING WITH FBC 2020.
23'-8" ±

REPLACEMENT TO INCLUDE NEW WOOD BUCKS, WATERPROOFING OF THE


P57 MASONRY OPENING AND BUCKS, TEMPORARY PROTECTION, AND STRENGTHENING DESIGNED DRAWN
OF THE ADJACENT MASONRY CELL AT EACHSIDE OF WINDOW TO BE REPLACED. HR/JB/RM HR/JB/RM
CHECKED APPROVED
P58 RM FPM

P59
Project No.: 18217

P60 Date: 04/26/21


15
Scale: 1/8" = 1'-0"
EX. WALL BELOW
P61 P62 P63 P64 P65 P66 P67 Sheet Title:
LOW ROOF & PENTHOUSE
FLOOR PLAN
G
24'-4" ± 23'-8" ± 10'-0" ± 26'-0" ±
Sheet No.:
A C F J
A2C-1.4
A B D E I K L M 8.130
N O P
9'-0" ± 21'-0" ± 14'-6" ± 32'-6" ± 5'-0" ± 23'-0" ± 21'-6" ± 22'-6" ± 19'-8" ± 20'-4" ± 11'-0" ±

SOUTH CONDOMINIUM
CHAMPLAIN TOWERS
H

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
EX. WALL BELOW

1 1
P1 P2 P3
21'-0" ±

24'-4" ±
EX. COLUMN
ANCHOR

2 C1
P4
3
P5 P6 P7

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


13'-8" ±
22'-4" ±

PHASE IIC: OVERALL BUILDING


4

REPAIR AND RESTORATION


P8 P9

EX. WALL BELOW

REPAIR & RESTORATION


5

14'-6" ±
11'-0" ±

EL.133'-0"±
6
7

7'-6" ±
EX. POSTED
ROOF ANCHOR
(TYP, 1 OF 25)
C2
8
P10 P11 P12 P13
17'-6" ±

NEW FIXED LADDER WITH ACCESS FROM EL.133'-0"±


PENTHOUSE ROOF LEVEL TO ELEVATOR SHAFT
ROOF LEVEL. LADDER TO BE IN ACCORDANCE
WITH THE 2020 FBC - MECHANICAL, 7TH EDITION
EX. COLUMN
ANCHOR
P20 P21

22'-0" ±
EL.139'-6"±
9
P14
EX. WALL BELOW
12'-6" ±

P22 P23 DN

C3 10 SEAL License: 89035


P15 P16 P17 P18 P19 Expires: 02/28/23
11
P24

EL.132'-6"±
17'-6" ±

P25

PLAN NOTES
This item has been digitally signed and sealed by Robert J. Miller on the
date adjacent to the seal. Printed copies of this document are not
1. EXISTING BUILDING FRAMING AND CONDITIONS INDICATED ON PLAN ARE BASED ON considered signed and sealed and the signature must be verified on
any electronic copies.
EXISTING DRAWINGS PREPARED BY WILLIAM M. FRIEDMAN & ASSOCIATES
12 ARCHITECTS, INC AND BREITERMAN JUARDO & ASSOCIATES (CONSULTING
ENGINEERS), DATED 08-22-1979 AND A LIMITED FIELD INVESTIGATION CONDUCTED BY
7'-2" ±

MORABITO CONSULTANTS. THE CONTRACTOR SHALL VERIFY ALL EXISTING


CONDITIONS AND CONTACT MORABITO CONSULTANTS PRIOR TO CONSTRUCTION IF
CONDITIONS VARY FROM WHAT IS SHOWN ON PLAN.
13 2. EXISTING STRUCTURE CONSISTS OF CAST-IN-PLACE CONCRETE TWO-WAY FLAT
Structural Engineers | Remediation & Parking Consultants
PLATE ELEVATED FLOOR SLAB BEARING ON CAST-IN-PLACE CONCRETE COLUMNS. 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
3. EXISTING ELEVATION TOP OF STRUCTURAL SLAB IS 124'-2"±. ALL ELEVATIONS AND © Copyright Morabito Consultants, Inc.
DIMENSIONS SHALL BE VERIFIED BY THE CONTRACTOR.
17'-4" ±

4. EXISTING CONDITIONS ARE SHOWN HALF-TONE.


No. Date Revisions
5. UNIT OWNERS MAY ELECT TO REPLACE THEIR EXISTING WINDOWS/DOORS.
REPLACEMENT HARDWARE SHALL BE PER THE SCHEDULES AND GUIDELINES ON
THE ARCHITECTURAL DRAWINGS BY SCOTT DYER ARCHITECTS. AS A COMPONENT
OF WINDOW/DOOR REPLACEMENT, STORM SHUTTERS SHALL BE REMOVED.
WINDOW/DOOR REPLACEMENT MASONRY OPENINGS WILL BE WATERPROOFED IN
ACCORDANCE WITH S2C-3.3.
14
6. SEE BID FORM FOR ALL OTHER ITEMS NOTE SHOWN ON PLAN.
23'-8" ±

DESIGNED DRAWN
HR/JB/RM HR/JB/RM
CHECKED APPROVED
RM FPM
Project No.: 18217
15
Date: 04/26/21

Scale: 1/8" = 1'-0"


Sheet Title:
G PENTHOUSE AND HIGH
24'-4" ± 23'-8" ± 10'-0" ± 26'-0" ± ROOF PLAN

A C F J Sheet No.:

A2C-1.5
A.1 B.1 D E H I K L M 8.130
N O O.1 Q

SOUTH CONDOMINIUM
8'-4" ± 19'-8" ± 14'-6" ± 32'-6" ± 5'-0" ± 23'-0" ± 21'-6" ± 22'-6" ± 19'-8" ± 20'-4" ± 10'-4" ± 10'-4" ±

CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


EX. SHAFT

8777 COLLINS AVENUE


EX. SHAFT
NOTE 11 TEST PROBE 'E'
18"± SOIL FILL
9"± CONC. TOPPING
9-1/2" STRUCTURAL SLAB
NOTE 10 REMOVE EXISTING
FUEL TANK

1.1 1.1
TEST PROBE 'F'
NOTE 5 (TYP.) 5-7/8"± CONC. TOPPING NOTE 6 (TYP.)
9-1/2" STRUCTURAL SLAB
20'-8" ±

23'-8" ±

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


2.1
3
PROPERTY LINE REMOVE WALL SECTION
NOTE 11

13'-8" ±
22'-0" ±

TEST PROBE 'D'

PHASE IIC: OVERALL BUILDING


2-3/8" CONC. TOPPING 4'-0"

REPAIR AND RESTORATION


NO WATERPROOFING
10-1/2" STRUCTURAL SLAB

REPAIR & RESTORATION


4

5 REMOVE BOLLARD

14'-6" ±
TEST PROBE 'C'
NOTE 5 18"± SOIL FILL
(TYP.) WATERPROOFING
10-1/2" STRUCTURAL SLAB
20'-0" ±

NOTE 5 6

7'-6" ±
NOTE 5 (TYP.)
8
AREA OF SLAB
8.1 REMOVAL FOR NEW
RAMP SELECTIVELY
REMOVE STEPS

21'-4" ±
20'-0" ±

EX. RAILINGS NOTE 6 (TYP.)


TO REMAIN
NOTE 5
9.1
10.1 (TYP.)

19'-10" ±
20'-0" ±

SEAL License: 89035


Expires: 02/28/23
EX. SHAFT

EX. SHAFT
11.1
12.1
UPSET BEAM TO
REMAIN THIS SIDE
TEST PROBE 'A'

19'-10" ±
1-1/4" PAVERS ON SAND
NOTE 5
WATERPROOFING
23'-0" ±

TEST PROBE 'B' 1-3/8" TILE AND MORTAR This item has been digitally signed and sealed by Robert J. Miller on the
3-5/8" CONC. TOPPING 2-1/8" CONC. TOPPING date adjacent to the seal. Printed copies of this document are not
"
25'-0

considered signed and sealed and the signature must be verified on


NO WATERPROOFING 9-1/2" STRUCTURAL SLAB any electronic copies.
10-1/4" STRUCTURAL SLAB

EX. COLUMN 6'-0" SHORING 13.1


(ENGINEERING BY NOTE 6 (TYP.)
OTHERS)
14 REMOVE BOLLARD

Structural Engineers | Remediation & Parking Consultants


AREA OF SLAB AND UPSET 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
BEAM REMOVAL FOR REVISED © Copyright Morabito Consultants, Inc.
ENTRANCE CONFIGURATION
23'-0" ±

No. Date Revisions


UPSET BEAM TO
REMAIN OUTSIDE OF
`

NOTE 11
SLAB REMOVAL
17
'-1

NOTE 5 (TYP.)
0"

14.1 EX. COLUMN


±

EX. SHAFT
5"
• CONTRACTOR SHALL SHORE THE REMAINING
SLAB, FOUNDATION WALL, AND BEAM AS
REQUIRED DURING CONSTRUCTION. SIGNED
AND SEALED SHORING DRAWINGS SHALL BE
SUBMITTED FOR REVIEW AND APPROVAL
PRIOR TO BEGINNING WORK
DESIGNED DRAWN
HR/JB/RM HR/JB/RM
CHECKED APPROVED
RM FPM
PROPERTY LINE 8. ALL AREAS TO BE REPAIRED MUST BE REVIEWED AND APPROVED BY MORABITO CONSULTANTS, INC. PRIOR TO
19'-0" ± 19'-0" ± 19'-6" ± 20'-0" ± 20'-0" ± 8'-0" ± 12'-0" ± 20'-0" ±
COMMENCEMENT OF WORK. DEMOLITION NOTES: Project No.: 18217

9. THE REPAIR CONTRACTOR SHALL SUBMIT A CONSTRUCTION SCHEDULE WITH PHASING AND TRAFFIC CONTROL PLANTER: REMOVE ALL EXISTING VEGETATION/SOIL AND REMOVE THE EXISTING Date: 04/26/21
R S T A.1 B.2 D.1 F.1 G.1 I PLANS TO THE OWNER AND ENGINEER FOR REVIEW AND APPROVAL PRIOR TO COMMENCEMENT OF WORK. WATERPROOFING MEMBRANE TO EXPOSE THE EXISTING STRUCTURAL SLAB.
PLAN NOTES
10. PRIOR TO FINAL ACCEPTANCE OF WORK THE CONTRACTOR SHALL PREPARE AND SUBMIT DIGITAL AS BUILTS WITH STAMPED CONCRETE: REMOVE STAMPED CONCRETE TOPPING TO EXPOSE THE
Scale: 3/32" = 1'-0"
1. EXISTING BUILDING FRAMING AND CONDITIONS INDICATED ON PLAN ARE BASED ON EXISTING DRAWINGS
PREPARED BY WILLIAM M. FRIEDMAN & ASSOCIATES ARCHITECTS, INC AND BREITERMAN JUARDO & ASSOCIATES, 4. EXISTING CONDITIONS ARE SHOWN HALF-TONE. "PATCH LOGS" OF ALL WORK COMPLETED. EXISTING STRUCTURAL SLAB.
DATED 08-22-1979 AND A LIMITED FIELD INVESTIGATION CONDUCTED BY MORABITO CONSULTANTS. CONTRACTOR
Sheet Title:
5. EXISTING PLANTER/MASONRY WALLS TO BE REMOVED ARE NOTED ON PLAN THUS: 11. THE PLANTER AREA ALONG 88TH STREET INDICATED ON PLAN (IN ADDITION TO REMOVAL OF THE VEGETATION, POOL DECK/PRIVATE BALCONIES: REMOVE ALL EXISTING PAVERS AND SAND
SHALL VERIFY ALL EXISTING CONDITIONS AND CONTACT MORABITO CONSULTANTS PRIOR TO CONSTRUCTION IF LEVEL 1 DEMO PLAN
CONDITIONS VARY FROM WHAT IS SHOWN ON PLAN. SOIL, AND WATERPROOFING) REQUIRES REMOVAL OF THE EXISTING CONCRETE TOPPING SLAB TO EXPOSE THE SETTING BED, WATERPROOFING MEMBRANE, ABANDONED TILE AND MORTAR
6. INSTALL TEMPORARY WEATHER WALLS AND REMOVE GLASS WINDOWS AND DOORS AT FIRST FLOOR COMMON AREAS EXISTING STRUCTURAL SLAB. LAYER, AND CONCRETE TOPPING SLAB TO EXPOSE THE EXISTING STRUCTURAL SLAB.
2. EXISTING STRUCTURE CONSISTS OF CAST-IN-PLACE CONCRETE TWO-WAY FLAT PLATE ELEVATED FLOOR SLAB AS NOTED ON PLAN.
BEARING ON CAST-IN-PLACE CONCRETE COLUMNS. 12. AFTER STAMPED CONCRETE REMOVAL, REMOVE EXISTING FILL TO EXPOSE THE EXISTING STRUCTURAL SLAB AT EXPOSED CONCRETE SURFACE: REMOVE EXISTING CONCRETE TOPPING SLAB TO
7. ONCE ALL DEMOLITION IS COMPLETE AND THE EXISTING STRUCTURAL SLAB IS EXPOSED, THE ENTIRE CONCRETE THE LOCATIONS NOTED ON PLAN. EXPOSE THE EXISTING STRUCTURAL SLAB. Sheet No.:
3. EXISTING ELEVATION TOP OF STRUCTURAL SLAB VARIES. SEE STRUCTURAL PLAN S2C- 1.0 FOR ELEVATIONS OF STRUCTURE SHALL BE SURVEYED AND ALL DETERIORATED CONCRETE SHALL BE NOTED BY THE CONTRACTOR AS PART
OF THEIR WORK. 13. SEE BID FORM FOR ALL OTHER ITEMS NOTE SHOWN ON PLAN.
THE FIRST FLOOR SLAB. **SEE TEST PROBES NOTED ON PLAN FOR EXISTING CONDITIONS**
D2C-1.0
R S
A.1 B.1 6
D E 5 1 H I K L M 8.130
N O O.1 Q
S2C-2.8 S2C-2.9

SOUTH CONDOMINIUM
8'-4" ± 19'-8" ± S2C-2.5 14'-6" ± 32'-6" ± 5'-0" ± 23'-0" ± 21'-6" ± 22'-6" ± 19'-8" ± 20'-4" ± 10'-4" ± 10'-4" ±

CHAMPLAIN TOWERS
14 4
NEW 16x12 S2C-2.5

6'-11"

1'-11"±
COLUMN

SURFSIDE, FLORIDA 33154


EX. SHAFT

8777 COLLINS AVENUE


GRADE BEAM
14a 4
S2C-2.9
EX. SHAFT
1

16'-9"
S2C-2.8
4 EL.8.25'±

8 #5 B
S2C-2.5 3 1'-11"± EL.10.17'±
14.1 4 6 4 4

8 #5 T

5 #5 T
S2C-2.4 S2C-2.4 S2C-2.4
S2C-2.4 S2C-2.8
15

2'-6"±
1'-0"±
SIM.

7"±
ASSUMED (1) EX.
5 150 TON P.I.F.
1.1 FRANKI PILE (TYP) 1.1

3'-0"
S2C-2.9

8'-0"
FOUNDATION FRAMING PART PLAN AT NEW COLUMN
3

8 #5 B
4'-1"± 4'-1"±
1. EXISTING BASEMENT FRAMING IS A 9" THICK CAST-IN- S2C-2.3
20'-8" ±

PLACE CONCRETE TWO-WAY FLAT PLATE FLOOR

23'-8" ±
5'-0" 8'-0"
SLAB REINFORCED WITH A BOTTOM MAT OF #4 AT SEE BID ITEM "SEGS" FOR SLAB

8 #5 T
12"o/c AND TOP BARS AS INDICATED ON 'S4' OF THE 6 CL COL 2 REINFORCEMENT FOR NEW 1'-11"±
EXISTING DRAWINGS. S2C-2.4 EMERGENCY GENERATOR 7"±
S2C-2.3 EL.14.83'±
2. ELEVATION TOP OF EX. STRUCTURAL SLAB = EL. -0.42± SIM.

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


2.1 3. ELEVATION TOP OF EX. PILE CAPS = EL. -1.17±

3'-0"

1'-9"±
4. EXISTING CONDITIONS ARE SHOWN HALF-TONE. 3

8'-0"
1
3'-0" 3'-0" EL.13.08'±
EL.7.92'± S2C-2.4

13'-8" ±
1'-0"±
22'-0" ±

PHASE IIC: OVERALL BUILDING


5'-0" 5'-0" REPAIR STEPS
3 SIMILAR TO

REPAIR AND RESTORATION


CL COL S2C-2.3 7 / S2C-2.4

REPAIR & RESTORATION


EL.8.25'± 4

2'-6"±
5

14'-6" ±
5 EL.10.75'±
3 S2C-2.7
2
S2C-2.8 S2C-2.3
20'-0" ±

7'-6" ±
4

2'-2"±
S2C-2.8

8
8.1
2 REPAIR STEPS
SIMILAR TO
S2C-2.3 7 / S2C-2.4
TYP.

21'-4" ±
1A 4"±
S2C-2.3
20'-0" ±

1
S2C-2.7 1'-0"±
EL.10.42'±
7
8'-0"

S2C-2.4
10 #5 T x 17'

10 #5 T x 17'
3'-0"

9.1
6 #5 T x 17'

REPAIR STEPS

1'-6"±
10.1

7"±

4"±
1'-6"±
SIMILAR TO
EL.10.17'±
2 7 / S2C-2.4
1A
S2C-2.4

1'-6"±

19'-10" ±
S2C-2.3

11"±

1'-2"±
1 TYP.
20'-0" ±

SEAL License: PE89035


S2C-2.8 1A Expires: 02/28/21
2 EX. SHAFT

11"±
S2C-2.3
9 #5 B

9 #5 B

1'-6"±
S2C-2.3

EX. SHAFT
EL.8.25'± 3
11.1
S2C-2.4
12.1 4
10 #5 T x 17'

10 #5 T x 17'
5'-8" ±

6#5 T x 17'

S2C-2.6
NOTE 11 EL.10.75'±
13 1A

19'-10" ±
EX. 1A REPAIR STEPS
UP T
6" (TYP.)

URN S2C-2.3 S2C-2.3 SIMILAR TO


CO N
8'-0"

1 C. B 1A 7 / S2C-2.4
EAM
T)

CL COL
B)

S2C-2.6 CL COL S2C-2.3


o /c (

EL.9.25'±
o /c (

1'-6"±
17'-4" ±

.79'±

T 9"

#5 A
T 9"

T 9"
o /c (
5
6

3'-0" 3'-0" 3'-0" 3'-0"


#5 A

#4 A T)
#4 A

T 9"
EL.

S2C-2.4
o /c (
B) 13.1
5'-0" 5'-0" 9'-0" 5'-0" 5'-0"
2
3
14 S2C-2.8 2
S2C-2.6 1A
S2C-2.6
6'-11"

Structural Engineers | Remediation & Parking Consultants


NEW 16x12 S2C-2.3 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
5 561.316.7660 | www.morabitoconsultants.com
COLUMN
14a S2C-2.6 1'-0"± 5 © Copyright Morabito Consultants, Inc.
EL. 8.25'±

5'-0" 5'-0" S2C-2.4 EL.9.25'± 1 2 5 6


23'-0" ±

2 3
S2C-2.7 3'-0" 3'-0" S2C-3.0 S2C-3.0 S2C-3.0 S2C-3.0
4'-0" S2C-2.3 No. Date Revisions
CL COL
9 #5 T

3
S2C-2.4
3'-0"
11 #5 T
11 #5 T

4 #5 T
6 #5 T

14.1
11 #5 T
8" ±

10 #5 B

1 5 POOL
15
6#5 T

S2C-2.4 S2C-2.3
EX. SHAFT
1A
4
10 #5 B

1 S2C-2.3
9 #5 B

S2C-2.5 CL COL
S2C-2.8
SIM. EL.8.25'±
4'-0" 4'-0"

10'-0" 9'-0" 10'-0"


DESIGNED DRAWN
HR/JB/RM HR/JB/RM
CHECKED APPROVED
RM FPM
19'-0" ± 19'-0" ± 19'-6" ± 20'-0" ± 20'-0" ± 8'-0" ± 12'-0" ± 20'-0" ± Project No.: 18217
1
S2C-3.6 Date: 04/26/21
PLAN NOTES
R S T A.1 B.2 D.1 F.1 G.1 I
Scale: 3/32" = 1'-0"
1. EXISTING BUILDING FRAMING AND CONDITIONS INDICATED ON PLAN ARE BASED ON EXISTING DRAWINGS 4. EXISTING ELEVATION TOP OF STRUCTURAL SLAB VARIES. REFER TO PLAN FOR TOP OF SLAB 8. FULLY BONDED CONCRETE OVERLAY AREAS ARE NOTED ON PLAN THUS: . BONDED OVERLAYS SHALL BE 11. NEW ENTRANCE DRIVE RAMP SLAB SHALL BE 9-1/2" MINMUM THICK REINFORCED CONCRETE SLAB (f'c
PREPARED BY WILLIAM M. FRIEDMAN & ASSOCIATES ARCHITECTS, INC AND BREITERMAN JUARDO & ASSOCIATES ELEVATIONS. ALL ELEVATIONS AND DIMENSIONS SHALL BE VERIFIED BY THE CONTRACTOR. A MINIMUM OF 2" THICK AND REINFORCED AS INDICATED ON PLAN. REINFORCEMENT SHALL BE EVENLY SPACED = 4,000 PSI) WITH MAXIMUM W/C RATIO OF 0.42, REINFORCED AS SHOWN ON PLAN. TIE EXISTING SLAB
(CONSULTING ENGINEERS), DATED 08-22-1979 AND A LIMITED FIELD INVESTIGATION CONDUCTED BY MORABITO ACROSS THE WIDTH OF THE BONDED OVERLAY. REFER TO ELEVATIONS PROVIDED ON S2C-1.1 FOR ELEVATION REINFORCEMENT INTO NEW CONCRETE PER DETAILS.
Sheet Title:
CONSULTANTS. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND CONTACT MORABITO 5. SEE SHEET A2C-1.0 FOR NEW CMU WALL LOCATIONS TOP OF BONDED CONCRETE OVERLAYS. LEVEL 1 SLAB
CONSULTANTS PRIOR TO CONSTRUCTION IF CONDITIONS VARY FROM WHAT IS SHOWN ON PLAN. 12. ONCE CONCRETE REPAIRS AND PLACEMENT OF BONDED OVERLAYS AND TOPPINGS HAVE BEEN
6. CONCRETE WALLS THAT ARE SUPPORTING EARTH MUST BE ALLOWED TO CURE FOR 7 DAYS PRIOR TO 9. ALL REMAINING EXPOSED CONCRETE AREAS NOT SPECIFICALLY NOTED AS FULLY BONDED SHALL RECIEVE COMPLETED, THE HOT APPLIED WATERPROOFING SYSTEM SHALL BE APPLIED OVER THE ENTIRE REINFORCEMENT AND
2. EXISTING FIRST FLOOR (LOBBY LEVEL) FRAMING IS A 9 1/2" THICK CAST-IN-PLACE CONCRETE TWO-WAY FLAT PLACING ANY RETAINED EARTH. CONCRETE TOPPING TO ACHIEVE REQUIRED ELEVATIONS AND SLOPE FOR DRAINAGE. REFER TO SPOT DECK PER APPROVED DETAILS. IMMEDIATELY PROTECT WATERPROOFING WITH PROTECTION FRAMING PLAN
PLATE FLOOR SLAB REINFORCED WITH A BOTTOM MAT OF #4 AT 12"o/c AND TOP BARS AS INDICATED ON 'S5' OF ELEVATIONS PROVIDED ON S2C-1.1 FOR ELEVATION TOP OF CONCRETE TOPPINGS. BOARD, INSTALLED PER MANUFACTURERS REQUIREMENTS.
THE EXISTING DRAWINGS. 7. FOR ELEVATION TOP OF EXISTING FINISHED SURFACES, REFER TO 'BOUNDARY SURVEY' BY J. BONFILL & Sheet No.:
ASSOCIATES, INC. DATED AUGUST 7, 2020. 10. DROP PANEL LOCATIONS ARE INDICATED ON PLAN THUS: . DROPS PANEL DEPTH SHALL BE A 4" 13. SEE BID FORM FOR ALL OTHER ITEMS NOTE SHOWN ON PLAN.
3. EXISTING CONDITIONS ARE SHOWN HALF-TONE. PROJECTION BELOW THE BOTTOM OF THE SLAB. DROPS SHALL BE REINFORCED AS INDICATED ON PLAN,
REINFORCEMENT SHALL BE EVENLY SPACED ACROSS THE WIDTH OF THE DROP PANEL. S2C-1.0
A.1 B.1 D E H I K L M N O O.1 Q
8'-4" ± 19'-8" ± 14'-6" ± 32'-6" ± 5'-0" ± 23'-0" ± 21'-6" ± 22'-6" ± 19'-8" ± 20'-4" ± 10'-4" ± 10'-4" ±

SOUTH CONDOMINIUM
CHAMPLAIN TOWERS
8.46± 8.50± 8.50± 8.63±

1'-11"±
8.50± 8.50± 8.63±
8.35± TOS 8.63± 8.68± TOS EX. SHAFT 8.35± TOS
8.35± TOS

SURFSIDE, FLORIDA 33154


8.35± TOS
8.63± 8.68± TOS

8777 COLLINS AVENUE


8.68± TOS
8.64±TOS 8.49± TOS
EX. SHAFT 8.38± 8.38± 8.35± TOS 8.49± TOS 10.41± TOS
BELOW TOPPING
SLAB DRAIN ONLY
EL.8.25'± 3 NO TOPPING ON
8.35± TOS 10.41± TOS 10.41± TOS
8.50±TOS GARAGE RAMP
8.35± TOS S2C-2.5 EX. DR 10.27± TOS
8.35± TOS
EX. DR 10.27± TOS
1'-11"±
8.58±TOS 8.51± 8.35± TOS
EL.8.25'±
EL.10.17'±
3

2'-6"±
1'-0"±
8.48±
9.54± 8.63± 8.50± 8.63± 8.63± 8.49± TOS 10.40± TOS

7"±
S2C-2.5 9.54± 8.48± 8.63± 8.50± 8.63± 8.49± TOS 10.40± TOS

1.1 8.42± TOS 1.1


8.35± TOS
8.45±TOS EX. DR
ABANDON
8.58±TOS
4'-1"± 4'-1"±
20'-8" ±

8.45±TOS 10.40± TOS 10.33± TOS

23'-8" ±
8.35± TOS
EL.8.25'± 9.25± TOS
10.27± TOS 10.27± TOS

8.43±
7"±
EL.14.83'±
8.54±TOS 8.56±
8.64±
1'-11"±
2.1 10.40± TOS

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


8.35± TOS

1'-9"±
3
9.31± EL.13.08'±
EXTENT OF GEOFOAM
BELOW CONCRETE TOPPING 9.54± 8.68± TOS

13'-8" ±
1/8" / FT

1/8" / FT
8.43±
1'-0"±
22'-0"

10.34± TOS 8.68± TOS 8.68± TOS

PHASE IIC: OVERALL BUILDING


8.35± TOS EX. DR 10.40± TOS

REPAIR AND RESTORATION


9.25± TOS
EXTENT OF NEW
10.52± TOS EL.8.25'± 4
STRUCTURAL SLAB TO BE

REPAIR & RESTORATION


2'-6"±
8.47± 2 10.63± TOS
SLOPED TO MEET TOPPINGS
8.47±TOS
S2C-2.5
8.35± TOS
5

14'-6" ±
EX. DR
8.35± TOS 8.53±
EL.10.75'± 3
2 S2C-2.5
8.47±TOS S2C-2.3 TYP

1/8" / FT

1/8" / FT
7.71± 9.35± TOS
20'-0" ±

7.71± 8.47± 10.53± TOS


8.68± TOS 8.68± TOS
6
1:1

7'-6" ±
2
8.73±

2'-2"±
1:66±

3"±
8.89± 9.30± 9.31±
8.47±TOS 1:48

8.40±TOS 8.62±
8
8.53±TOS 8.62±
8.1 8.40±TOS 8.59± 10.63± TOS 10.63± TOS 10.63± TOS

8.35± TOS 9.35± TOS 10.63± TOS


8.45± 10.90 10.63± TOS
8.40±TOS 8.65±TOS

21'-4" ±
EX. DR ABANDON 4"±
8.47±TOS
8.51± 9.51 10.52± TOS 10.52± TOS
20'-0" ±

8.35± TOS EX. DR 9.31(VIF) EX. DR


8.53±TOS 9.25± TOS ABANDON
8.35± TOS EX. DR
1'-0"±
1/8
"/F
ABANDON EL.10.42'±
T 5 5
8.51± S2C-2.5 S2C-2.5 10.63± TOS
8.48±TOS 8.42± TOS 10.63± TOS
8.57±
8.5
6± T 8.45± 9.31(VIF)
9.1
OS

1'-6"±
10.1

7"±

4"±
1'-6"±
10.32± TOS 10.32± TOS 10.52± TOS 10.52± TOS
1/8" / FT 10.27± TOS 10.27± TOS 10.44± TOS
1/8" / FT

EL.10.17'± 10.27± TOS 10.27± TOS


8.57± 8.57± 10.39± TOS
10.32± TOS

1'-6"±

19'-10" ±
8.56±TOS 8.56±TOS 9.35± TOS 9.48± TOS

11"±

1'-2"±
9.54± TOS 9.35± TOS 10.42± TOS
20'-0" ±

9.82± TOS EX. DR


3 8.56±TOS 9.35± TOS RELOCATE TO
9.35± TOS EX. SHAFT SEAL License: 89035

11"±
EX. DR 9.35± TOS 9.51± TOS
S2C-2.5 9.50± TOS 9.50± TOS 9.35± TOS 9.52± TOS LOW SPOT Expires: 02/28/23
EL.8.25'± 9.35± TOS
1/8" / FT

9.35± TOS 9.35± TOS


8.42± TOS 9.31± 9.35± TOS
1'-6"± 9.82± TOS
EX. SHAFT 1:20 MAX
EL.9.25'± EX. DR
9.35± TOS 11.1
12.1 8.35± TOS 8.56±TOS 9.52± TOS
8.42± TOS 1/8" / FT 9.35± TOS 1/8" / FT
5'-8" ±

9.35± TOS 9.35± TOS 9.35± TOS IN 9.35± TOS


1/8" / FT 8.55±TOS 9.50± TOS 9.35± TOS 9.35± TOS 9.35± TOS
8.56±TOS PLANTERS
9.50± TOS 9.53± TOS
1/8" / FT

EL.10.75'± (TYP)
13

19'-10" ±
9.54± TOS 9.54± TOS
6.79± TOS 9.25± TOS

9.35± TOS
.79'±

2 1'-6"±
17'-4" ±

This item has been digitally signed and sealed by Robert J. Miller on the
9.35± TOS date adjacent to the seal. Printed copies of this document are not
S2C-2.3 SIM
6

1/8" / FT
2 EX. DR considered signed and sealed and the signature must be verified on
EL.

EX. DR
1/8" / FT

any electronic copies.


2'-5" ± S2C-2.5 ABANDON
ABANDON
9.35± TOS 13.1
9.50± TOS
8.57±TOS 9.35± TOS 9.35± TOS
9.10± TOS 9.35± TOS
9.54± TOS 9.52± TOS 9.51± TOS
6.79± TOS 1
14 9.35± TOS
S2C-2.5
6'-11" ±

9.48± TOS 9.54± TOS


EX. STRUCTURE
1/8" / FT 3
RIDGE %V
EL. 8.25'±

S2C-2.5 Structural Engineers | Remediation & Parking Consultants


ARIE 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
14a S EX. DR
9.00± TOS 1'-0"± ABANDON EX. DR 561.316.7660 | www.morabitoconsultants.com
9.54± TOS ABANDON
© Copyright Morabito Consultants, Inc.
23'-0" ±

9.54± TOS
8.35± TOS
8.62± TOS 4'-0" EL.8.25'± 2 9.35± TOS EX. DR
9.35± TOS 9.53± TOS
9.10± TOS 9.35± TOS EL.9.25'±
S2C-2.5 ABANDON
9.54± TOS 9.54± TOS No. Date Revisions
12

8.60± TOS
'-1

EL.9.25'±
0
3/

8.62± TOS
4"

9.56± TOS 9.56± TOS


8.52± TOS
14.1 9.35± TOS
4'-0"
8" ±

9.3± TOS 9.54± TOS 9.54± TOS 9.54± TOS


POOL
15 8.42± TOS
9.31± TOS
EL.8.25'± 9.35± TOS

1/8" / FT
EX. DR
EX. SHAFT 8.63± TOS EX. DR
3 ABANDON
S2C-2.5 TYP. DRAIN 9.35± TOS 9.35± TOS
9.35± TOS 9.54± TOS
9.54± TOS 9.35± TOS
IN PLANTER EX. FOUNDATION
9.54± TOS 9.54± TOS JACUZZI
WALL BELOW 9.54± TOS
8.60± TOS 9.35± TOS
8.60± TOS 9.61± TOS
9.80± TOS 9.54± TOS 9.54± TOS 9.54± TOS 9.54± TOS 9.54± TOS 9.54± TOS
8.69± TOS
1 /8 " 9.35± TOS 9.35± TOS 9.35± TOS DESIGNED DRAWN
/ FT 9.53± TOS 9.35± TOS 9.53± TOS
1/8" / FT 8.35± TOS 1/8" / FT 1/8" / FT 1/8" / FT 1/8" / FT 1/8" / FT 1/8" / FT HR/JB/RM HR/JB/RM
EX. DR
9.35± TOS
ABANDON CHECKED APPROVED
9.54± TOS RM FPM
19'-0" ± 19'-0" ± 19'-6" ± 20'-0" ± 20'-0" ± 8'-0" ± 12'-0" ± 20'-0" ±
Project No.: 18217
R S T A.1 B.2 D.1 F.1 G.1 I Date: 04/26/21
PLAN NOTES
1. EXISTING BUILDING FRAMING AND CONDITIONS INDICATED ON PLAN ARE BASED ON EXISTING DRAWINGS 4. EXISTING ELEVATION TOP OF STRUCTURAL SLAB VARIES AS INDICATED. ALL ELEVATIONS AND 7. ALL HARDSCAPE AND PLANTER AREAS NOT SPECIFICALLY NOTED TO HAVE 2" FULLY BONDED TOPPING PER NOTE 10. SEE BID FORM FOR ALL OTHER ITEMS NOTE SHOWN ON PLAN. Scale: 3/32" = 1'-0"
PREPARED BY WILLIAM M. FRIEDMAN & ASSOCIATES ARCHITECTS, INC AND BREITERMAN JUARDO & ASSOCIATES DIMENSIONS SHALL BE VERIFIED BY THE CONTRACTOR. 6 SHALL RECIEVE CONCRETE TOPPING TO ACHIEVE REQUIRED ELEVATIONS AND SLOPE FOR DRAINAGE. SPOT
(CONSULTING ENGINEERS), DATED 08-22-1979 AND A LIMITED FIELD INVESTIGATION CONDUCTED BY MORABITO ELEVATIONS PROVIDED ON THIS SHEET FOR ELEVATION TOP OF CONCRETE TOPPINGS NOTED AS "X.XX± TOS". 11. TOPPING SLAB SHALL HONOR ALL EXISTING FEATURES TO REMAIN (STEPS, SIDEWALK, BUILDING Sheet Title:
CONSULTANTS. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND CONTACT MORABITO 5. FOR ELEVATION TOP OF EXISTING FINISHED SURFACES, REFER TO 'BOUNDARY SURVEY' BY J. BONFILL & WHERE NO SPOT ELEVATIONS ARE PROVIDED, PROVIDE MINIMUM 1/8" PER FOOT SLOPE. ENTRANCE, ETC.). CONTRACTOR TO ADJUST TOPPING SLAB TO ENSURE SMOOTH, CODE-COMPLIANT
CONSULTANTS PRIOR TO CONSTRUCTION IF CONDITIONS VARY FROM WHAT IS SHOWN ON PLAN. ASSOCIATES, INC. DATED AUGUST 7, 2020. TRANSITIONS TO EXISTING CONDITIONS AT FINISHED SURFACE. LEVEL 1 BONDED
8. ALL ABANDONDED DRAINS SHALL BE SAW-CUT FROM SLAB AND REPAIRED FULL-DEPTH. NOTE THAT NOT ALL OVERLAY AND TOPPING
2. EXISTING FIRST FLOOR (LOBBY LEVEL) FRAMING IS A 9 1/2" THICK CAST-IN-PLACE CONCRETE TWO-WAY FLAT 6. FULLY BONDED CONCRETE OVERLAY AREAS ARE NOTED ON PLAN THUS: SEE SHEET S2C-1.0 EXISTING PLANTER DRAIN LOCATIONS ARE KNOWN. WHERE FOUND, ABANDON AND REPAIR SLAB FULL-DEPTH. 12. LEVEL RIDGES TO BE UNIFORM ELEVATION ACROSS SHOWN AS:
PLATE FLOOR SLAB REINFORCED WITH A BOTTOM MAT OF #4 AT 12"o/c AND TOP BARS AS INDICATED ON 'S5' OF FOR STRUCTURAL STRENGTHENING BONDED OVERLAY AREAS. STRUCTURAL BONDED TOPPING AREAS
ELEVATIONS
THE EXISTING DRAWINGS. SHALL BE CAST INTEGRALLY WITH TYPICAL SLOPED BONDED TOPPINGS 9. ONCE CONCRETE REPAIRS AND PLACEMENT OF BONDED OVERLAYS AND TOPPINGS HAVE BEEN COMPLETED, THE 13. SLOPED RIDGES BETWEEN DRAINAGE PLANES SHOWN AS:
HOT APPLIED WATERPROOFING SYSTEM SHALL BE APPLIED OVER THE ENTIRE DECK PER APPROVED DETAILS. Sheet No.:
3. EXISTING CONDITIONS ARE SHOWN HALF-TONE. IMMEDIATELY PROTECT WATERPROOFING WITH PROTECTION BOARD, INSTALLED PER MANUFACTURERS
REQUIREMENTS.
S2C-1.1
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
A B D E H I K L M 8.130
N O O.1 P
8" ±
9'-0" ± 21'-0" ± 14'-6" ± 32'-6" ± 5'-0" ± 23'-0" ± 21'-6" ± 22'-6" ± 19'-8" ± 20'-4" ± 10'-4" ±

1 1

EX. BM 30x42 1.1

EX. BM 36x42

EX. BM 36x42
21'-0" ±

24'-4" ±

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


EX. BM 8x18
2

EX. BM 36x42 3

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
EX. BM 8x18

REPAIR & RESTORATION


EX. BM 36x42

13'-8" ±
22'-4" ±

EX. BM 36x42

EX. BM 36x42

14'-6" ±
EX. BM 36x42
11'-0" ±

EX. BM 36x42

EX. BM 36x42 6
EX. BM 8x18

7'-6" ±
8
17'-6" ±

EX. BM 36x42

22'-0" ±
EX. BM 36x42

EX. BM 36x42

SEAL License: 89035


Expires: 02/28/23
EX. BM 8x38

9
12'-6" ±

9.1

EX. BM 36x42 10
11
This item has been digitally signed and sealed by Robert J. Miller on the
date adjacent to the seal. Printed copies of this document are not
EX. BM 8x18

considered signed and sealed and the signature must be verified on


any electronic copies.
EX. BM 36x42

EX. BM 36x42
17'-6" ±

NOTE 5

2
S2C-3.2
PLAN NOTES Structural Engineers | Remediation & Parking Consultants
206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
EX. BM 36x42 561.316.7660 | www.morabitoconsultants.com
1. EXISTING BUILDING FRAMING AND CONDITIONS INDICATED ON PLAN ARE BASED ON EXISTING © Copyright Morabito Consultants, Inc.
12 DRAWINGS PREPARED BY WILLIAM M. FRIEDMAN & ASSOCIATES ARCHITECTS, INC AND BREITERMAN
JUARDO & ASSOCIATES (CONSULTING ENGINEERS), DATED 08-22-1979 AND A LIMITED FIELD
INVESTIGATION CONDUCTED BY MORABITO CONSULTANTS. THE CONTRACTOR SHALL VERIFY ALL
7'-2" ±

EX. BM 30x42 EX. BM 30x42 EXISTING CONDITIONS AND CONTACT MORABITO CONSULTANTS PRIOR TO CONSTRUCTION IF No. Date Revisions
CONDITIONS VARY FROM WHAT IS SHOWN ON PLAN.

13 2. EXISTING SECOND FLOOR FRAMING IS A 8" THICK CAST-IN-PLACE CONCRETE TWO-WAY FLAT PLATE
FLOOR SLAB REINFORCED WITH A BOTTOM MAT OF #4 AT 13"o/c AND TOP BARS AS INDICATED ON 'S6'
OF THE EXISTING DRAWINGS.
EX. BM 36x42

EX. BM 36x42
3. EXISTING ELEVATION TOP OF STRUCTURAL SLAB IS 24'-5"±. ALL ELEVATIONS AND DIMENSIONS SHALL
2 SIM
BE VERIFIED BY THE CONTRACTOR.
S2C-3.2
EX. BM 36x42
17'-4" ±

4. EXISTING CONDITIONS ARE SHOWN HALF-TONE.

5. AREA OF EXISTING SOFFIT AND INT. CEILING TO BE REMOVED NOTED ON PLAN THUS: SEE 1
S2C-3.2
6. SEE BID FORM FOR ALL OTHER ITEMS NOTE SHOWN ON PLAN.
EX. BM 36x42 EX. BM 36x42 EX. BM 36x42 EX. BM 36x42

14
3'-0"

DESIGNED DRAWN
HR/JB/RM HR/JB/RM
CHECKED APPROVED
2 RM FPM
S2C-3.2
Project No.: 18217
EX. BM 36x42

NOTE 5
23'-8" ±

Date: 04/26/21

Scale: 1/8" = 1'-0"


Sheet Title:
LEVEL 2 FRAMING PLAN
EX. BM 30x42 EX. BM 30x42 EX. BM 30x42 EX. BM 30x42

15
Sheet No.:

S2C-1.2
Ldh HOOK
HOOK

SOUTH CONDOMINIUM
ACI STANDARD HOOKS COMPRESSION DEVELOPMENT & SPLICE

CHAMPLAIN TOWERS
STIRRUPS AND TIES
OTHER THAN BEAM & COLUMN TIES / STIRRUPS
BEAMS AND COLUMNS
D
LENGTHS [Ldc & Lsc] (in)

SURFSIDE, FLORIDA 33154


180° HOOK 90° HOOK

d
D F'c = 3 ksi 5 ksi > F'c > 3 ksi F'c = 5 ksi (or greater)
BAR

8777 COLLINS AVENUE


d
HOOK HOOK 180° HOOK 90° HOOK 135° HOOK
SIZE MINIMUM BEND MINIMUM BEND
EXTENSION
DIAMETER, "D"
EXTENSION
DIAMETER, "D" BAR HOOK ENCLOSED ENCLOSED ENCLOSED
LENGTH, "Lext" LENGTH, "Lext" SIZE HOOK HOOK HOOK EXTENSION BAR WITH #4 TIES OTHER WITH #4 TIES OTHER WITH #4 TIES OTHER
MINIMUM BEND MINIMUM BEND MINIMUM BEND
EXTENSION EXTENSION EXTENSION Lext SIZE AT <= 4" o/c AT <= 4" o/c AT <= 4" o/c
DIAMETER, "D" DIAMETER, "D" DIAMETER, "D"
#3 3" 2-1/4" 5" 2-1/4" HOOK EXTENSION, Lext LENGTH, "Lext" LENGTH, "Lext" LENGTH, "Lext"
180° HOOK Ld Ls Ld Ls Ld Ls Ld Ls Ld Ls Ld Ls
180° HOOK #3 3" 1-1/2" 3" 1-1/2" 3" 1-1/2" HOOK
#4 3" 3" 6" 3"
#3 8 12 9 12 8 12 8 12 8 12 8 12
#5 3" 3-3/4" 8" 3-3/4" #4 3" 2" 3" 2" 3" 2"
#4 8 13 11 15 8 13 10 15 8 13 9 15
Ldh HOOK #5 3" 2-1/2" 4" 2-1/2" 3-3/4" 2-1/2"
#6 3" 4-1/2" 9" 4-1/2"

EXTENSION
#5 11 16 14 19 9 16 12 19 9 16 11 19

D
d

HOOK
#6 3" 4-1/2" 9" 4-1/2" 4-1/2" 4-1/2"

Lext
#7 4" 5-1/4" 11" 5-1/4" 13 19 17 23
#6 11 19 14 23 10 19 14 23
#8 4" 6" 12" 6" #7 4" 5-1/4" 11" 5-1/4" 5-1/4" 5-1/4"
90° HOOK #7 15 22 20 27 13 22 17 26 11 22 16 26

D
d
#9 5" 9" 14" 9" NOTES: HOOK #8 17 25 22 30 14 25 19 30 14 25 18 30
1. ALL REINFORCING BARS SHALL BE MEASURED, CUT, BENT, AND INSTALLED TO WITHIN THE ALLOWABLE
#10 5" 10" 15" 10" D = MINIMUM INSIDE BEND DIAMETER TOLERANCES INDICATED IN THE ACI 318, ACI 317, ACI 315/315R, AND CONCRETE REINFORCING STEEL INSTITUTE #9 19 28 25 34 16 28 22 34 15 28 20 34
d = BAR DIAMETER (CRSI) MANUAL.
#11 6" 11" 17" 11" 2. ALL BARS SHALL BE BENT COLD UNLESS APPROVED BY ENGINEER-OF-RECORD. #10 21 32 28 38 18 32 24 38 17 32 23 38

EXTENSION

N
3. REINFORCING BARS SHALL NOT BE FIELD BENT AFTER BEING PARTIALLY EMBEDDED IN CONCRETE U.N.O. D

Le NS K
xt IO
TE OO
d
#11 23 35 31 42 20 35 27 42

HOOK
90° HOOK 19 35 26 42

Lext
D = MINIMUM INSIDE BEND DIAMETER

EX H
45°
d = BAR DIAMETER
NOTES:
MINIMUM HOOK DEVELOPMENT LENGTH, Ldh 1. EPOXY REBAR NOR LIGHTWEIGHT CONCRETE DOES NOT AFFECT COMPRESSION DEVELOPMENT
OR LAP LENGTH.
MULTIPLE ALL VALUES BY 1.5 FOR EPOXY COATED REINFORCEMENT

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


2. Fy = 60 ksi ONLY
BAR 135° HOOK
F'c = 3 ksi 5 ksi > F'c > 3 ksi F'c = 5 ksi OR GREATER NOTES:
SIZE
1. ALL REINFORCING BARS SHALL BE MEASURED,
#3 9" 8" 7" CUT, BENT, AND INSTALLED TO WITHIN THE
ALLOWABLE TOLERANCES INDICATED IN THE
#4 11" 10" 9" ACI 318, ACI 317, ACI 315/315R, AND CONCRETE
REINFORCING STEEL INSTITUTE (CRSI) MANUAL.

PHASE IIC: OVERALL BUILDING


#5 14" 12" 11" 2. ALL BARS SHALL BE BENT COLD UNLESS
APPROVED BY ENGINEER-OF-RECORD

REPAIR AND RESTORATION


#6 17" 15" 13" 3. REINFORCING BARS SHALL NOT BE FIELD BENT
AFTER BEING PARTIALLY EMBEDDED IN

REPAIR & RESTORATION


#7 20" 17" 15" CONCRETE U.N.O.
4. WHERE BAR BEND LENGTH IS INDICATED AS
#8 22" 19" 17" "STD" OR "STANDARD", BEND BAR PER ACI
25" 22" 20" STANDARD HOOKS TABLE.
#9 5. WHERE LIGHT WEIGHT CONCRETE IS USED, THE
#10 28" 25" 22" HOOK DEVELOPMENT LENGTHS (Ldh) SHOWN IN
THE SCHEDULE SHALL BE MULTIPLIED BY 1.33.
#11 31" 27" 24"

TENSION LAP SPLICE LENGTHS [Ls] (in)


F'c = 3 ksi & 3.5 ksi F'c = 4 ksi & 4.5 ksi F'c = 5 ksi OR GREATER

BAR MAY USE REDUCED LENGTH WHEN: MAY USE REDUCED LENGTH WHEN: MAY USE REDUCED LENGTH WHEN: RN TYPICAL CONCRETE REPAIR PROCEDURES AND NOTES
LOCATION
SIZE MINIMUM MINIMUM MINIMUM
MEMBERS WITH CONCRETE MEMBERS WITH CONCRETE MEMBERS WITH CONCRETE MEMBERS WITH CONCRETE MEMBERS WITH CONCRETE MEMBERS WITH CONCRETE 1. AREAS OF UNSOUND CONCRETE AND DETERIORATED REINFORCING SHALL BE IDENTIFIED AND MARKED BY
(UNO) COVER > = 3/4" AND (BAR COVER > = 1 1/2" AND (BAR (UNO) COVER > = 3/4" AND (BAR COVER > = 1 1/2" AND (BAR (UNO) COVER > = 3/4" AND (BAR COVER > = 1 1/2" AND (BAR CONTRACTOR. THE CONTRACTOR SHALL PROVIDE A UNIT PRICE FOR ALL WORK SHOWN ON THESE DRAWINGS
SPACING > = 4" OR > = 6db) SPACING > = 4" OR > = 6db) SPACING > = 4" OR > = 6db) SPACING > = 4" OR > = 6db) SPACING > = 4" OR > = 6db) SPACING > = 4" OR > = 6db) AND DETAILS AS REQUIRED BY SPEC SECTIONS 002113, 004100, 012200 AND 012300. WHERE POSSIBLE, REMOVAL
AREAS SHALL BE RECTANGULAR IN SHAPE IN PLAN/ELEVATION VIEW. SEE SPECIFICATION SECTIONS 024119 AND
TOP BARS 42 17 17 37 15 15 33 13 13 030100. IT IS IN THE INTEREST OF THE OWNER TO REPAIR ALL CONCRETE FACADE DEFECTS WITHIN THE WORK
#3 LIMITS SHOWN REGARDLESS OF WHETHER OR NOT ALL DEFECTS ARE INDICATED ON THE CONTRACT DOCUMENTS
OTHER BARS 32 13 13 28 12 12 25 12 12
AND/OR IDENTIFIED BY THE CONTRACTOR.
TOP BARS 56 28 23 49 24 20 43 22 18
#4 2. TEMPORARILY SHORE ALL EXISTING CONCRETE SLABS, BEAMS, WALLS AND COLUMNS WHICH ARE DAMAGED PRIOR
OTHER BARS 43 22 18 37 19 15 34 17 14 TO PERFORMING THE NECESSARY REPAIRS. SEE SPECIFICATION SECTIONS 31 40 00 AND 03 01 00. AS DEMOLITION
PROGRESSES, THE CONTRACTOR SHALL NOTIFY THE SHORING ENGINEER WHEN DEMOLITION LIMITS ARE
TOP BARS 70 41 28 61 36 24 54 32 22
#5 EXPECTED TO EXTEND BEYOND CURRENT SHORING LIMITS. WORK SHALL CEASE UNTIL SHORING HAS BEEN RE-
OTHER BARS 54 32 22 47 28 19 42 25 17 EVALUATED. SHORING SHALL BE DESIGNED BY A REGISTERED PROFESSIONAL ENGINEER RETAINED BY THE
CONTRACTOR UNO. SHORING SHALL BE DESIGNED FOR ALL SUPERIMPOSED LOADS DURING CONSTRUCTION IN
TOP BARS 84 56 34 73 49 29 65 43 26 ADDITION TO SELF-WEIGHT OF STRUCTURE. SHORING ENGINEER SHALL BE RESPONSIBLE FOR ALL REQUIRED
#6 SEQUENCING AND RE-SHORING AS REQUIRED. SHORING PLANS AND CALCULATIONS SHALL BE SUBMITTED TO THE
OTHER BARS 65 43 26 56 37 23 50 34 20
ENGINEER OF RECORD FOR REVIEW.
TOP BARS 122 90 55 106 78 48 95 70 43
#7 3. REMOVE ALL UNSOUND CONCRETE WITH CHIPPING HAMMERS. USE 30 POUND CHIPPING HAMMERS FOR ALL SEAL License: 89035
OTHER BARS 94 69 43 81 60 37 73 54 33 SELECTIVE DEMOLITION UNLESS OTHERWISE APPROVED. DO NOT HAMMER AROUND REBAR WITH LARGER THAN 15 Expires: 02/28/23

TOP BARS 139 112 70 121 97 61 108 86 54 POUND HAMMERS.


#8
OTHER BARS 107 86 54 93 74 47 83 67 42 4. WHERE EXPOSED PORTIONS OF THE EXISTING REINFORCING ARE NOT SOUNDLY BONDED TO THE REMAINING
CONCRETE, OR IF MORE THAN 1/2 OF THE REBAR DIAMETER / THICKNESS IS EXPOSED, THE CONTRACTOR SHALL
TOP BARS 157 135 89 136 117 77 122 105 69 REMOVE CONCRETE AROUND AND UNDER THE REINFORCING. ALL FREELY EXPOSED REINFORCING SHALL BE NO
#9 CLOSER THAN 3/4" TO EXISTING CONCRETE. WHEN EXISTING REINFORCING IS NOT PROPERLY EXPOSED (OR NO
OTHER BARS 121 104 68 105 90 59 94 81 53
REBAR IS PRESENT) THE CONTRACTOR SHALL INSTALL STAINLESS STEEL THREADED RODS SET IN EPOXY AT 6" ON
TOP BARS 177 162 112 153 140 97 137 126 87 CENTER EACH WAY (3" MINIMUM EMBEDMENT INTO SOUND CONCRETE) UNLESS OTHERWISE SHOWN IN DETAILS OR
#10 DIRECTED IN FIELD. REMOVE ALL OILS FROM RODS PRIOR TO SETTING IN EPOXY.
OTHER BARS 136 125 87 118 108 75 106 97 67
TOP BARS 196 190 138 170 165 120 152 147 107 5. REMOVE ALL DIRT, GREASE, OIL, LAITANCE AND CURING COMPOUNDS FROM EXISTING CONCRETE SURFACES AND
#11 SUBSTRATES BY SANDBLASTING OR MECHANICAL ROUGHENING. PROVIDE MANUFACTURER-REQUIRED CRSI
OTHER BARS 151 146 107 131 127 92 117 113 83 CONCRETE SURFACE PROFILE (CSP) FOR EACH REPAIR PRODUCT TO BE USED. FOR CONVENTIONAL PORTLAND This item has been digitally signed and sealed by Robert J. Miller on the
date adjacent to the seal. Printed copies of this document are not
CONCRETE REPAIR, NO LESS THAN CSP-6 (1/4" AMPLITUDE) SHALL BE USED. REMOVE GREASE, OIL, RUST AND MILL considered signed and sealed and the signature must be verified on
SCALING FROM EXISTING EMBEDDED STEEL, ANCHOR PLATES AND REINFORCING STEEL BY SANDBLASTING OR any electronic copies.

WIRE BRUSHING. COAT ALL EXPOSED REINFORCING STEEL WITH 7 WET MILS OF ECB ANTI-CORROSION
PROTECTION, BY CONPROCO.
TENSION DEVELOPMENT LENGTHS [Ld] (in) 6. ADD NEW REBAR AND/OR EPOXY COATED WIRE MESH TO REPLACE ANY RUSTED OR DEFECTIVE EXISTING
F'c = 3 ksi & 3.5 ksi F'c = 4 ksi & 4.5 ksi F'c = 5 ksi OR GREATER REINFORCING AS DIRECTED BY MORABITO CONSULTANTS INC. SEE EXISTING FRAMING PLANS AND DETAILS FOR
ESTIMATED EXISTING REINFORCEMENT. ALL WIRE MESH SHALL BE EPOXY-COATED. PROVIDE PROPER
MAY USE REDUCED LENGTH WHEN: MAY USE REDUCED LENGTH WHEN: MAY USE REDUCED LENGTH WHEN: REINFORCING LAP SPLICES AS REQUIRED. SEE SPECIFICATIONS FOR FURTHER INFORMATION.
BAR
LOCATION Structural Engineers | Remediation & Parking Consultants
SIZE MINIMUM MINIMUM MINIMUM 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
MEMBERS WITH CONCRETE MEMBERS WITH CONCRETE MEMBERS WITH CONCRETE MEMBERS WITH CONCRETE MEMBERS WITH CONCRETE MEMBERS WITH CONCRETE 7. PRESOAK ALL EXISTING HORIZONTAL AND VERTICAL CONCRETE SURFACES TO RECEIVE REPAIR CONCRETE TO
(UNO) COVER > = 3/4" AND (BAR COVER > = 1 1/2" AND (BAR (UNO) COVER > = 3/4" AND (BAR COVER > = 1 1/2" AND (BAR (UNO) COVER > = 3/4" AND (BAR COVER > = 1 1/2" AND (BAR
561.316.7660 | www.morabitoconsultants.com
ACHIEVE A SATURATED SURFACE DRY (SSD) CONDITION BEFORE APPLYING CEMENTITIOUS REPAIR © Copyright Morabito Consultants, Inc.
SPACING > = 4" OR > = 6db) SPACING > = 4" OR > = 6db) SPACING > = 4" OR > = 6db) SPACING > = 4" OR > = 6db) SPACING > = 4" OR > = 6db) SPACING > = 4" OR > = 6db) CONCRETE/MORTAR. INSTALL PROPRIETARY CONCRETE REPAIR MATERIAL PER MANUFACTURER'S REQUIREMENTS
AND RECOMMENDATIONS. APPLY "SCRUB", "SLURRY", OR "PEANUT BUTTER" COAT ON SSD CONCRETE IF
TOP BARS 32 13 13 28 12 12 25 12 12
RECOMMENDED BY MANUFACTURER'S WRITTEN DATA SHEET. DO NOT WET CONCRETE PRIOR TO INSTALLATION
#3 No. Date Revisions
OTHER BARS 25 12 12 22 12 12 20 12 12 OF EPOXY-SAND (NON-CEMENTITIOUS) MATERIALS. ALLOW EPOXY ANCHORING GROUTS TO FULLY CURE PRIOR TO
WETTING SURFACES. PROPRIETARY CONCRETE BONDING AGENTS MAY ONLY BE USED AS APPROVED BY THE
TOP BARS 43 22 18 37 19 15 34 17 14 ENGINEER. FOR POOL FLOOR AND WALL REPAIRS, APPLY SIKA SWELL S2 IN ACCORDANCE WITH MANUFACTURER'S
#4 GUIDELINES AT PERIMETER COLD JOINT PRIOR TO CONCRETE PLACEMENT. CONTRACTOR TO ENSURE SIKASWELL
OTHER BARS 33 17 14 29 15 12 26 13 12
S2 REMAINS CLEAN AND DRY PRIOR TO CONCRETE PLACEMENT.
TOP BARS 54 32 22 47 28 19 42 25 17
#5 8. WHEN CONCRETE PATCH DEPTH IS LESS THAN 2 1/2", INSTALL APPROVED SURFACE REPAIR MORTAR. EXTEND
OTHER BARS 42 25 17 36 21 15 32 19 13 MORTAR WITH AGGREGATE WHERE REQUIRED BY SPECIFICATIONS. ALLOW REPAIR MORTAR TO BE CURED PER
SPEC SECTION 030100.
TOP BARS 65 43 26 56 37 23 50 34 20
#6
OTHER BARS 50 33 20 43 29 18 39 26 16 9. WHEN CONCRETE PATCH DEPTH IS GREATER THAN OR EQUAL TO 2 1/2", INSTALL APPROVED PRE-MIX CONCRETE
(BAG MIX) OR READY MIX CONCRETE. BAG MIX REPAIR CONCRETE/MORTAR SHALL BE SHRINKAGE-COMPENSATING
TOP BARS 94 69 43 81 60 37 73 54 33 WITH FIBERS. READY MIX CONCRETE SHALL BE DESIGNED TO THE LIMITATIONS IN SECTION 030100. REPAIR
#7 CONCRETE SHALL BE CURED PER SPEC SECTION 030100.
OTHER BARS 72 53 33 63 46 29 56 41 26
TOP BARS 107 86 54 93 74 47 83 67 42 10. AFTER ALL CONCRETE REPAIR PATCHES HAVE FULLY CURED, AND IF REQUIRED BY THE BID FORM, ALL SURFACES
#8 SHALL BE COATED WITH A ACRYLIC CONCRETE COATING WITH COLOR TO MATCH EXISTING. PRESSURE WASH AND
OTHER BARS 83 66 42 72 57 36 64 51 32 PREPARE EXISTING SURFACES TO RECEIVE COATING PER MANUFACTURER'S REQUIREMENTS AND
TOP BARS 121 104 68 105 90 59 94 81 53 RECOMMENDATIONS.
DESIGNED DRAWN
#9
OTHER BARS 93 80 53 81 69 46 72 62 41 11. ALL EXISTING CONNECTIONS, ANCHORS, AND PLATES THAT ARE EXPOSED DURING REPAIRS SHALL BE PROPERLY HR/JB/RM HR/JB/RM
SAND BLASTED OR MECHANICALLY CLEANED AND COATED WITH ECB ANTI-CORROSION PROTECTION (ORANGE
TOP BARS 136 125 87 118 108 75 106 97 67 CHECKED APPROVED
COLORED) BY CONPROCO CORP. PER SPEC SECTION 030100.
#10 RM FPM
OTHER BARS 105 96 67 91 83 58 81 75 52
12. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
TOP BARS 151 146 107 131 127 92 117 113 83 Project No.: 18217
#11
OTHER BARS 116 113 82 101 98 71 90 87 64
Date: 04/26/21
NOTES:
1. TOP BARS = HORIZONTAL BARS WITH MORE THAN 12 IN. OF CONCRETE BELOW. Scale: As indicated
2. db = REINFORCING BAR DIAMETER.
3. BAR SPACING = CENTER TO CENTER SPACING BETWEEN BARS. WHEN MULTIPLE BARS LOCATED IN THE SAME PLANE ARE Sheet Title:
SPLICED AT THE SAME SECTION, THE CENTER TO CENTER SPACING IS THE MINIMUM DISTANCE BETWEEN ADJACENT SPLICES.
4. NORMAL WEIGHT CONCRETE ONLY, WHERE LIGHT WEIGHT CONCRETE IS USED, THE SPLICE LENGTHS SHOWN IN THE TYPICAL
SCHEDULE SHALL BE MULTIPLIED BY 1.33. REINFORCEMENT &
5. WHERE EPOXY BARS ARE USED, THE SPLICE LENGTHS IN THE SCHEDULE SHALL BE MULTIPLIED BY 1.5. REPAIR NOTES
6. Fy = 60 KSI ONLY.
7. MINIMUM LENGTHS ARE BASED ON MEMBERS WITH BAR SPACING > = 2db. Sheet No.:

S2C-2.0
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS
• SLAB THICKNESSES UPTO 9-1/2" - SEE BID LINE ITEM SF-3
RN
• FOR TYPICAL REPAIR NOTES, SEE
• PARTIAL DEPTH REPAIRS UP TO 4" THICK • STRUCTURE SHOWN IS GENERIC S2C-2.0

SURFSIDE, FLORIDA 33154


• STRUCTURE SHOWN IS GENERIC AND WILL DIFFER PER PLANS #5 BAR HOOKS
AT 2'-0" o/c

8777 COLLINS AVENUE


• SLAB SOFFIT REPAIRS SHALL ONLY BE AND WILL DIFFER PER PLANS SEALANT JOINT • STRUCTURE SHOWN IS GENERIC
PERFORMED ON SLAB THICKNESSES OF 6" #4 x 1'-0" DOWELS AT 12" o/c AND WILL DIFFER PER PLANS
NOTES 8 & 9 SET IN EPOXY (6" EMBED) SEALANT JOINT
OR GREATER AND ONLY WITH EXPLICIT SEE PLANS FOR SEE PLANS FOR EXISTING NOTE 8
PRE-APPROVAL OF ENGINEER EXISTING SLAB SLAB REINFORCEMENT NOTE 5 • PERFORM FULL DEPTH EDGE #4 DOWELS AT SEE PLANS FOR
NOTE 7 REINFORCEMENT NOTE 3
REPAIRS SIMILAR TO NOTE 5 12" o/c SET IN EXISTING SLAB
SF
EPOXY (8" EMBED) REINFORCEMENT
EX. SLAB

S2C-2.1 NOTE 6
PLAN
SEE

CONTRACTOR SHALL CONFIRM

EX SLAB

PLAN
CONTINUOUS BARS AT SLAB EDGE. IF NO

SEE
EXISTING BARS ARE LOCATED, PROVIDE
NOTE 3 NOTE 7 (2) - #5 BARS AT EDGE OF SLAB. DOWEL
NOTE 5 NOTE 10
NOTE 4 NOTE 10 INTO ENDS OF REPAIR (8" MIN. EMBED)
NOTE 6
NOTE 6 NOTE 7
DRIP INSERT NOTE 10
SEE PLAN
EX. BEAM

NOTES 8 & 9
3"
• DRIP INSERT STRIP MAY BE NOTE 3
NOTE 10 SHORING WHERE 1'-0"
PVC OR WOOD. APPLY FORM
REQUIRED BY RELEASE TO STRIP TO ALLOW (x CONT.)
SHORING WHERE PLANS, SEE SHORING WHERE
REQUIRED BY 1 REMOVAL REQUIRED BY
PLANS, SEE S2C-3.4 PLANS, SEE
1
S2C-3.4 • FOR ANCHORING OF 1 1
RAILING TO SLAB SEE S2C-2.2 S2C-3.4
RN RN
• FOR TYPICAL REPAIR NOTES, SEE • FOR TYPICAL REPAIR NOTES, SEE
S2C-2.0 S2C-2.0
• SLAB THICKNESSES UPTO 9-1/2" - SEE BID LINE ITEM SE

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


SLAB SOFFIT REPAIR SLAB FULL-DEPTH REPAIR SLAB FULL-DEPTH DECK EDGE REPAIR
SU 1 1/2" = 1'-0" SF 1 1/2" = 1'-0" SE 1 1/2" = 1'-0"

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
• PARTIAL DEPTH REPAIRS UP TO 3" THICK NOTE 10 • STRUCTURE SHOWN IS GENERIC
AND WILL DIFFER PER PLANS • STRUCTURE SHOWN IS GENERIC
• SLAB TOP SURFACE REPAIRS SHALL ONLY NOTE 5 NOTES 8 & 9
AND WILL DIFFER PER PLANS
BE PERFORMED ON SLAB THICKNESSES SEE PLANS FOR • DEEP PARTIAL DEPTH & FULL
OF 6" OR GREATER AND ONLY WITH NOTE 6 NOTE 4 EXISTING SLAB DEPTH, SEE BID LINE ITEM SEE PLANS FOR
EXPLICIT PRE-APPROVAL OF ENGINEER REINFORCEMENT CS EXISTING SLAB • PROVIDE APPROVED PEA
NOTE 3 NOTE 10
REINFORCEMENT GRAVEL CONCRETE MIX
EX. SLAB

EX. SLAB
• WHERE BONDED TOPPING SLOPES • ROUGHEN EXISTING CONCRETE
PLAN

PLAN
SEE

SEE
TO EXISTING SLAB, PROVIDE 2" x 1'-0" TO CSP-5 OR BETTER
CONTINUOUS PARTIAL DEPTH PATCH DOWELS IF
TO LOCK IN TOPPING. REQUIRED PER
WIRE MESH PER
PLAN & BID FORM

1" CLEAR
PLANS & BID FORM

1-1/2" MIN
NOTE 7 SEALANT JOINT
SEE PLAN
1'-0" MIN R PLANS
NOTE 2 SLOPE PE

2" MIN
NOTE 10
SEE PLAN

SEE PLAN
EX. BEAM

EX. BEAM
SHORING WHERE • FOR SHORNG,
REQUIRED BY SEE

EX. SLAB
PLANS, SEE NOTE 8 & 9

PLAN
1

SEE
S2C-3.4 NOTE 6

SEE PLAN
NOTE 5
CSP-5 MINIMUM
RN ENGINEER TO PROFILE
• FOR TYPICAL REPAIR NOTES, SEE DETERMINE IN
S2C-2.0 SEAL License: 89035

SEE PLAN
EX. BEAM
FIELD WHETHER SHORING WHERE Expires: 02/28/23
"A" TIES REQUIRE REQUIRED BY
REPLACEMENT PLANS, SEE 1
NOTE 3 NOTE 7 S2C-3.4
COUPLER
DETAIL "A"
NOTE 4 • STRUCTURE SHOWN IS GENERIC
NOTE 6
• DO NOT REMOVE MORE THAN 25% OF AND WILL DIFFER PER PLANS
COLUMN SECTION AT ONE TIME
WITHOUT APPROVAL OF ENGINEER &
NOTE 8 & 9 INSTALLATION OF SHORING RN EXISTING STRUCTURE
• FOR TYPICAL REPAIR NOTES, SEE VARIES
S2C-2.0
RN
• WHEN LAP SPLICING IS NOT PRACTICAL, • FOR TYPICAL REPAIR NOTES, SEE
S2C-2.0
PROVIDE BAR COUPLERS TO DEVELOP This item has been digitally signed and sealed by Robert J. Miller on the
125% OF BAR STRENGTH date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.

SLAB TOP SURFACE REPAIR COLUMN SPALL REPAIR BONDED TOPPING TERMINATION
ST 1 1/2" = 1'-0" CS 1 1/2" = 1'-0" BT 1 1/2" = 1'-0"

Structural Engineers | Remediation & Parking Consultants


• CRACKS TO BE REPAIRED MUST BE PRE-APPROVED BY ENGINEER. 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
• PRIOR TO CHEMICAL GROUT OR EPOXY INSTALLATION, ROUT CRACK & CLEAN © Copyright Morabito Consultants, Inc.
SURFACE TO RECEIVE GROUT OF ANY LOOSE MATERIALS, DIRT, DUST, LAITANCE, PRIME EDGES
ETC. CLEANING SHALL BE DONE BY POWER WASHING FOLLOWED BY BLASTING • ROUT ALL NON-STRUCTURAL CRACKS TO
WITH OIL-FREE COMPRESSIVE AIR. NO CLEANING SOLVENTS SHALL BE USED. 3/4" DEEP BY 3/8" WIDE
No. Date Revisions
• SEAL ALL FULL-DEPTH CRACKS AS SHOWN WITH EPOXY GEL PRIOR TO INJECTION • CLEAN JOINT TO ALLOW BOND
AND PROVIDE ADEQUATE PRESSURE INJECTION POINTS.
• PROVIDE CONTINUOUS DEBONDING
• CLEAN SURFACE OF EXCESS GEL MATERIAL AFTER CURE IS COMPLETE. MATERIAL AT BOTTOM OF CRACK PREVENT BOND WITH
SILICONE OR TAPE
• SEE SPEC. SECTION 030100 FOR APPROVED INJECTION MATERIAL. CONTRACTOR • PRIMER EDGES OF JOINT WITH
~

SHALL INSTALL REPAIR PRODUCTS IN STRICT ACCORDANCE PER THE MANUFACTURER'S APPROVED PRIMER
MANUFACTURER'S REQUIREMENTS AND RECOMMENDATIONS. SOUND CONCRETE
• INSTALL APPROVED 1 OR 2-PART
• AFTER TOPSIDE INJECTION HAS BEEN COMPLETED, CRACK TO BE ROUTED AND POLYURETHANE SEALANT PER SPEC
SEALED WITH APPROVED POLYURETHANE SEALANT SECTION 07 9200

FULL-THICKNESS
CRACK GRAVITY FED GRAVITY FED
EPOXY EPOXY

DESIGNED DRAWN
HR/JB/RM HR/JB/RM
EPOXY GEL PARTIAL PARTIAL THICKNESS CHECKED APPROVED
THICKNESS CRACK NON-STRUCTURAL RM FPM
CRACK
EPOXY GEL INJECTION PORTS Project No.: 18217
EXISTING STRUCTURE
FULL-THICKNESS • STRUCTURE SHOWN IS GENERIC VARIES
CRACK AND WILL DIFFER PER PLANS Date: 04/26/21
• STRUCTURE SHOWN IS GENERIC
NOTE 10 EXISTING STRUCTURE
AND WILL DIFFER PER PLANS Scale: 1 1/2" = 1'-0"
VARIES

• FOR TYPICAL REPAIR NOTES, SEE


RN Sheet Title:
S2C-2.0
PARTIAL THICKNESS CONCRETE REPAIR
CRACK DETAILS

STRUCTURAL CRACK REPAIR (EPOXY INJECTION) NON-STRUCTURAL CRACK REPAIR (CRACK SEALANT) Sheet No.:
EI 1 1/2" = 1'-0" JS 1 1/2" = 1'-0"
S2C-2.1
• DO NOT CUT EXISTING • SEE PROJECT WATERPROOFING DETAILS
REINFORCEMENT WITHOUT FOR REQUIRED DETAILING AT DRAINS

SOUTH CONDOMINIUM
APPROVAL OF ENGINEER

CHAMPLAIN TOWERS
• DO NOT CUT EXISTING REINFORCEMENT • SEE LANDSCAPE AND MEP PLANS • SEE LANDSCAPE AND MEP PLANS
WITHOUT APPROVAL OF ENGINEER FOR DRAIN TYPE FOR DRAIN TYPE
• ALL CONSTRUCTION JOINTS BETWEEN NEW AND • CONTINUOUSLY BOND WATERSTOP TO

SURFSIDE, FLORIDA 33154


• RECESS DRAIN 1/2" BELOW DECK & • SEE PROJECT WATERPROOFING DETAILS • RECESS DRAIN 1/2" BELOW DECK & EXISTING CONSTRUCTION BELOW THE DESIGN SUBSTRATE WITH TRIANGULAR BEAD OF SIKA

8777 COLLINS AVENUE


SLOPE REPAIR CONCRETE FOR REQUIRED DETAILING AT DRAINS SLOPE REPAIR CONCRETE FLOOD ELEVATION SHALL HAVE A CONTINUOUS "S-2" SEALANT. PREPARE SUBSTRATE

SEE LANDSCAPE
HYDROPHYLLIC WATERSTOP PERMANUFACTURER REQUIREMENTS.
SF • DO NOT CUT EXISTING REINFORCEMENT • FOR FULL-DEPTH REPAIR - SEE SF FILTER FABRIC WRAPPED SF
• FOR FULL-DEPTH REPAIR - SEE • PAVER INSTALLATION REFERENCE S2C-2.1 • FOR FULL-DEPTH REPAIR - SEE
S2C-2.1 SHEET WP-6 WITHOUT APPROVAL OF ENGINEER AROUND STAND PIPE S2C-2.1 • WATERSTOPS SHALL BE "SIKASWELL A" BY SIKA • COORDINATE PROPER WATERSTOP
CORP, OR APPROVED EQUAL (NON-BENDONITE) PLACEMENT WITH CONCRETE
• RECESS DRAIN 1/2" BELOW DECK & POORLY GRADED GRAVEL
SEE PLAN AND DETAILS FOR REINFORCEMENT AND DOWELS.
VARIES

SLOPE REPAIR CONCRETE


SEALANT FINISH. SLOPE TO DRAIN • PROVIDE 3-1/4" MINIMUM CLEAR COVER TO
SEALANT
WATERSTOP FROM ALL EDGES
SEALANT

1/2"
1/2"
SUBSTRATE MATERIAL

EX. SLAB
EX SLAB
(CONCRETE OR MASONRY)
EX SLAB

REBAR PER PROJECT DETAILS

PLAN

PLAN
PLAN

SEE

SEE
SEE

8" MIN
3 1/4"
MIN

MIN

MIN

7 1/4"
2"

2"

2"

3 1/4"
SEE PLANS FOR SEE PLANS FOR
1" CLR

SEE PLANS FOR

1" CLR

1" CLR

3-1/4" CLEAR MIN


CLEAN, DRY
SUBSTRATE
EXISTING SLAB EXISTING SLAB EXISTING SLAB
#4 AT 6" o/c E.W. REINFORCEMENT REINFORCEMENT #4 AT 6" o/c E.W. REINFORCEMENT
2'-0" x 2'-0" MIN #4 AT 6" o/c E.W. 2'-0" x 2'-0" MIN
2'-0" x 2'-0" MIN
• PROVIDE 2" MIN CLEAR TO BOTTOM OF DRAIN BODY • PROVIDE 2" MIN CLEAR TO BOTTOM OF DRAIN BODY
• PROVIDE 2" MIN CLEAR TO BOTTOM OF DRAIN BODY

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


PROMENADE DECK DRAIN PARKING DECK DRAIN PLANTER DRAIN WATERSTOP
DD1 1 1/2" = 1'-0" DD2 1 1/2" = 1'-0" DD3 1 1/2" = 1'-0" WS 1" = 1'-0"

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
EX. MASONRY

REPAIR & RESTORATION


BLOCK WALL

NOTE 3
6'-0" o/c MAX. 6'-0" o/c MAX.
NOTE 5

NOTE 6

3/8"⌀ STAINLESS
STEEL "U" BAR
.

PLAN
SEE
EXISTING RAILING POST 1 1/2" CLEAR MIN.
HOLE OR SLEEVE IN
EXISTING CONCRETE SLAB 1/4"⌀ x 1 3/4" TAPCON

1"
SCREWS (1" EMBEDMENT)
EX. RAILING POST 4 PER PATCH MINIMUM APPLY NEW THIN PATCH
NOTES 9 & 10 SAWCUT EDGE OF NEW V/O REPAIR MORTAR
COAT EMBEDDED SECTION OF NOTE 7 MASONRY PATCH (STUCCO FINISH NOT TYPICAL CONTROL JOINT IN CONCRETE WALLS
RAILING AROUND ENTIRE PERIMETER SHOWN FOR CLARITY) 4 3/4" = 1'-0"
WITH SIKA ARMATEC 110 EPOCEM

SIKA SIKALASTIC 735AL REMOVE EXISTING GROUT


TRAFFIC COATING FILL AND REPLACE WITH
1 1/2"

REPAIR MORTAR
TYPICAL POST PLAN VIEW
NEW 3/8"⌀ STAINLESS STEEL
EX. SLAB

"U" BAR EPOXY GROUTED 3"


PLAN
SEE

INTO EXISTING CONCRETE

1/4"⌀ x 1 3/4" TAPCON


3" (2) - 304 SS 1/4"Ø x 1 3/4" SCREWS (1" EMBEDMENT) SEAL License: 89035
TAPCON SCREWS (MIN.) EXISTING RAILING POST 4 PER PATCH MINIMUM Expires: 02/28/23

• FOR ADDITIONAL INFORMATION OR ADHESIVE DOWEL HOLE OR SLEEVE IN


ON FULL DEPTH SLAB EDGE EXISTING CONCRETE SLAB
REPAIRS, SEE IN LIEU OF TAPSON SCREWS AS SHOWN, THE NOTE 3
SE
CONTRACTOR MAY OPTION TO USE AN ADHESIVE
S2C-2.1 NOTE 5
DOWEL AS NOTED BELOW;
OPTION 1: FILL MASONRY BLOCK CELL
• FOR TYPICAL REPAIR ADHESIVE DOWEL SHALL BE 3/8" DIAMETER NOTE 6 SAWCUT EDGE OF NEW WITH APPROVED REPAIR
NOTES, SEE STAINLESS STEEL THREADED ROD ANCHORED
RN NOTES 9 & 10 MASONRY PATCH MORTAR (STUCCO FINISH
WITH HY-200 ADHESIVE MANUFACTURED BY HILTI 3/8"Ø STAINLESS
S2C-2.0 NOT SHOWN FOR CLARITY)
OR APPROVED EQUAL (2" MINIMUM EMBEDMENT) STEEL "U" BAR
OPTION 2:
ADHESIVE DOWEL SHALL BE #3 MINIMUM PARTIAL DEPTH MASONRY WALL REPAIR
DEFORMED REBAR (GRADE 60) ANCHORED WITH NOTE 7 2 3/4" = 1'-0"
This item has been digitally signed and sealed by Robert J. Miller on the
date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
HY-200 ADHESIVE MANUFACTURED BY HILTI OR NEW 8" POURED any electronic copies.
CONCRETE WALL
APPROVED EQUAL (2" MINIMUM EMBEDMENT) CORNER POST PLAN VIEW
• FOR STUCCO FINISH ON
RAILING CONNECTION CONCRETE SPALL REPAIR CONCRETE/ MASONRY • PROVIDE CONTROL
1 1 1/2" = 1'-0" SUBSTRATE, SEE
2 JOINTS, SEE 4
S2C-3.1 S2C-2.2
• IF PLANTER AREA IS LARGE,
Structural Engineers | Remediation & Parking Consultants
PROVIDE CONTROL JOINTS IN 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
BONDED TOPPING AT 20'-0" o/c #4 HORIZONTAL REINFORCING BAR AT 12" O.C. 561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

SEE ARCHITECTURAL AND LANDSCAPING PLANS


EX. MASONRY • TERMINATE WATERPROOFING • AT WALLS LESS THAN 4'-0" TALL, PROVIDE #4
WALL TO REMAIN SYSTEM AT PLANTER WALLS AT 16" o/c DOWELED INTO EXISTING No. Date Revisions
PER CARLISLE DETAILS STRUCTURAL SLAB (6" MIN. EMBEDMENT)
TUCK-POINTING MASONRY NOTES:
• AT WALLS TALLER THAN 4'-0" PROVIDE #4 AT
1. REMOVE ALL LOOSE AND CRACKED MORTAR WITH CHISELS, GEOFOAM 8" o/c

PLANTER WALL HEIGHT


GRINDING WHEELS, ADN OTHER APPROPRIATE EQUIPMENT
DOWN TO A MINIMUM DEPTH OF 1/2". THE REPAIRED JOINTS
PLANTER PAVER SYSTEM, SEE
SHALL BE CLEANED WITH A STIFF BRUSH ALONG WITH A LIGHT
HOSE STREAM LANDSCAPING AND SHEET WP-6
DETAIL CCW-500-8C AROUND
PENETRATIONS, SEE CARLISLE 1/2" JOINT FILLER, CAULK JOINT
EX. CRACK 2. THE REPAIR MORTAR SHALL BE TYPE 'N' PRE-HYDRATED TO WITH APPROVED SEALANT
IN MASONRY REDUCE EXCESSIVE SHRINKAGE. THE PROPER PRE-HYDRATION DETALS FOR ADDITIONAL
PROCESS IS AS FOLLOWS: INFORMATION AND REQUIREMENTS CCW MIRADRAIN
A. ALL DRY INGREDIENTS SHALL BE THROUGHLY MIXED PRIOR DRAINAGE COMPOSITE
TO ADDITION OF WATER
B. ONLY ENOUGH CLEAN WATER SHALL BE ADDED TO THE DRY CCW PROTECTION BOARD
MIX TO PRODUCE A DAMP, WORKABLE CONSISTENCY WHICH HILTI HUS 3/8" X 5" (3-1/4" MIN. 1" SETTING BED
WILL RETAIN ITS SHAPE WHEN FORMED INTO A BALL EMBEDMENT). SPACE PINS AT 18"o/c IN
C. THE MORTAR SHALL STAND IN THIS DAMPENED CONDITION EACH DIRECTION IN BONDED OVERLAY
FOR 1 TO 1-1/2 HOURS AND 36"o/c IN TOPPING SLAB
DESIGNED DRAWN
3. THE JOINTS TO BE TUCK-POINTED SHALL BE DAMPENED TO A HR/JB/RM HR/JB/RM

. 5" MAX.
SATURATED SURFACE DRY CONDITION. TO ENSURE A GOOD CHECKED APPROVED
BOND, THE BRICKWORK MUST ABSORB ALL SURFACE WATER
RM FPM
BRICKS WITH SPALLED
4. WATER SHOULD BE ADDED TO THE PRE-HYDRATED MORTAR TO
FRONT FACE SHALL BE
BRING IT TO A WORKABLE CONSISTANCY (SOMEWHAT DRIER Project No.: 18217
REPLACED
THAN CONVENTIONAL MORTAR)
Date: 04/26/21
5. THE MORTAR SHALL BE PACKED TIGHTLY INTO THE JOINTS IN
THIN LAYERS (1/4" MAXIMUM). EACH LAYER SHALL BECOME
EX. DAMAGED MASONRY MORTAR AREA OF DETERIORATED AND
"THUMBPRINT" HARD BEFORE APPLYING THE NEXT LAYER BONDED OVERLAY = 1'-6" o/c E.W. CARLISLE CCW-500 Scale: As indicated
JOINT TO BE RE-POINTED PER CRACKED MASONRY TO BE TOPPING SLAB = 3'-0" o/c E.W. WATERPROOFING (TYP.)
TUCK-POINTING NOTES REMOVED, AND RE-TOOTHED WITH Sheet Title:
NEW MASONRY, AS REQUIRED 6. THE JOINTS SHALL BE TOOLED TO A CONCAVE PROFILE AFTER • ALL DOWELING INTO EXISTING • PAVER INSTALLATION
• ROUT ALL DETERIORATED JOINTS THE LAST LAYER OF MORTAR IS "THUMBPRINT" HARD RUN CARLISLE CCW-500
AND TOOL IN NEW MORTAR SEE
CONCRETE SHALL USE HILTI-HY 200 WATERPROOFING BELOW REFERENCE SHEET WP-6 CONCRETE/MASONRY
EPOXY ADHESIVE OR APPROVED EQUAL INTERIOR WALLS REPAIR DETAILS
TUCK-POINTING NOTES

EXISTING MASONRY BLOCK REPAIRS BONDED OVERLAY / TOPPING SLAB AT NEW POURED PLANTER WALL Sheet No.:
3 3/4" = 1'-0" 5 1 1/2" = 1'-0"
S2C-2.2
EXISTING PLANTER
WALL TO REMAIN PROVIDE PLANTER AREA
DRAIN, SEE LANDSCAPE AND NEW 8"
SEE LANDSCAPE PLANS FOR

SOUTH CONDOMINIUM
MEP PLANS FOR DRAIN TYPE CMU WALL

CHAMPLAIN TOWERS
REQUIRED SOIL HEIGHT. SLOPE
AND MOUND AS REQUIRED
• FOR STUCCO FINISH ON • FOR POURED

SURFSIDE, FLORIDA 33154


CONCRETE/ MASONRY ALTERNATE, SEE

8777 COLLINS AVENUE


SEE PLANS AND SPECS.
SUBSTRATE, SEE

FOR ALLOWABLE SOIL


DEPTH AND WEIGHT
2 5
• CONTRACTOR SHALL SURVEY THE EXISTING SLAB S2C-3.1 S2C-2.2
• FOR STUCCO FINISH ON • IF PLANTER AREA IS LARGE,
CONCRETE/ MASONRY PRIOR TO INSTALLATION OF BONDED OVERLAY /
TOPPING SLAB AND PERFORM ANY REQUIRED PROVIDE CONTROL JOINTS
SUBSTRATE, SEE IN BONDED TOPPING AT • AT WALLS LESS THAN 4'-0" TALL, PROVIDE #4
2 REPAIRS. FOR REPAIRS, SEE
SU ST SF 20'-0" o/c AT 16" o/c DOWELED INTO EXISTING
S2C-3.1 STRUCTURAL SLAB (6" MIN. EMBEDMENT)
S2C-2.1 S2C-2.1 S2C-2.1

SEE ARCHITECTURAL AND LANDSCAPING PLANS


• TERMINATE WATERPROOFING
CUSTOM STANDPIPE TO • AT WALLS TALLER THAN 4'-0" PROVIDE #4 AT
SYSTEM AT PLANTER WALLS
ACCOMODATE DEPTH OF 8" o/c
• NEW MASONRY WALL PER CARLISLE DETAILS
SECTIONS TO BE TOOTHED PLANTER. COORDINATE
PLANTER WITH LANDSCAPE PLANS • GROUT ALL CELLS SOLID
INTO EXISTING
GEOFOAM

PLANTER WALL HEIGHT


• FOR TYPICAL REPAIR

VARIES - FIELD VERIFY


NOTES, SEE
PAVER SYSTEM, SEE RN FILTER FABRIC
• FOR ADDITIONAL PAVER SYSTEM, SEE
LANDSCAPING AND SHEET WP-6 S2C-2.0 WRAPPED AROUND LANDSCAPING AND SHEET WP-6
INFORMATION AT
GEOFOAM STAND PIPE DETAIL CCW-500-8C AROUND
NEW PLANTER DRAIN, 1/2" JOINT FILLER, CAULK JOINT
PENETRATIONS, SEE CARLISLE

BONDED OVERLAY = 2" MIN.


TOPPING SLAB = 1 1/4" MIN.
CCW MIRADRAIN NOTE 7 SEE • GEOFOAM NOT WITH APPROVED SEALANT
DD3 DETALS FOR ADDITIONAL
CCW MIRADRAIN SHOWN FOR CLARITY PLANTER
CCW ROOT BARRIER HILTI HUS 3/8" X 5" (3-1/4" MIN. S2C-2.2 INFORMATION AND REQUIREMENTS CCW MIRADRAIN
DRAINAGE COMPOSITE
EMBEDMENT). SPACE PINS AT 18"o/c IN DRAINAGE COMPOSITE
CCW PROTECTION CCW PROTECTION EACH DIRECTION IN BONDED OVERLAY POORLY GRADED FILTER FABRIC
BOARD AND 36"o/c IN TOPPING SLAB GRAVEL OVER GRAVEL CCW PROTECTION BOARD
BOARD
HILTI HUS 3/8" X 5" (3-1/4" MIN. 1" SETTING BED
6"x6" - W4.0 / W4.0 NOTE 9 SEALANT EMBEDMENT). SPACE PINS AT 18"o/c IN

CLR.
WELDED WIRE FABRIC

3/4"
EACH DIRECTION IN BONDED OVERLAY

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


NOTE 6 AND 36"o/c IN TOPPING SLAB
1% MIN
. 5" MAX.

. 5" MAX.
.

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
1" SETTING BED CARLISLE CCW-500
EX. STRUCTURAL SLAB WATERPROOFING (TYP.) • DO NOT CUT EXISTING
CARLISLE CCW-500 • FOR FULL-DEPTH REINFORCEMENT WITHOUT BONDED OVERLAY = 1'-6" o/c E.W. CARLISLE CCW-500
WATERPROOFING (TYP.) ROUGHENED SURFACE BONDED OVERLAY = 1'-6" o/c E.W. • EXISTING CONCRETE SURFACE IS TO BE HEAVY APPROVAL OF ENGINEER
REPAIR, SEE TOPPING SLAB = 3'-0" o/c E.W. WATERPROOFING (TYP.)
(CSP 5), NOTE 5 TOPPING SLAB = 3'-0" o/c E.W. SF
SHOTBLASTED TO REMOVE ALL CONTAMINENTS
S2C-2.1 • LOW POINTS SHALL BE LOCATED TO
• SHORE EXISTING SLAB AS REQUIRED AND PRODUCE A CONCRETE SURFACE PROFILE • ALL DOWELING INTO EXISTING CONCRETE SHALL USE RUN CARLISLE CCW-500 WATERPROOFING
• BONDED OVERLY AND TOPPING SLAB CSP 5 THAT MEETS THE REQUIREMENTS OF ICRI FACILITATE DRAINAGE, SEE PLANS
PRIOR TO POURING BONDED OVERLAY HILTI-HY 200 EPOXY ADHESIVE OR APPROVED EQUAL BELOW INTERIOR WALLS
SHALL BE 4000 PSI CONCRETE WITH GUIDELINE NO.310.2R-2013. LIMIT THE DEPTH OF FOR TOP OF BONDED OVERLAY AND
OR TOPPING SLAB, SEE SPECIFICATION TOPPING SLAB ELEVATIONS
APPROVED AGGREGATE SIZE BASED FOR ADDITIONAL INFORMATION. THE CONCRETE REMOVAL TO 3/8"
ON MINIMUM ALLOWABLE THICKNESS 2'-0" x 2'-0" MIN.
• PRESOAK EX. SLAB TO A SATURATED SURFACE-
DRY (SSD) CONDITION IMMEDIATELY PRIOR TO
POURING BONDED OVERLAY OR TOPPING SLAB

BONDED OVERLAY / TOPPING SLAB AT EXISTING PLANTER WALL BONDED OVERLAY / TOPPING SLAB AT PLANTER DRAIN BONDED OVERLAY / TOPPING SLAB AT NEW CMU PLANTER WALL
1A NOT TO SCALE
1B NOT TO SCALE
1C NOT TO SCALE
• PROVIDE SAW-CUT IN TOPPING • PROVIDE NEOPRENE REINFORCED
• FOR ADDITIONAL INFORMATION AT EXISTING PLANTER WITHIN 8-HOURS OF POUR CCW-500 JOINT AND SEALANT AT
NEW PLANTER DRAIN, SEE WALL TO REMAIN SAW CUT
1B DD3 • TOPPING OVER GEOFOAM SHALL
BE 3" MIN, 4" MAX 3/4" DEEP x 1/4" WIDE SAWCUT
S2C-2.3 S2C-2.2 • FOR ADDITIONAL INFORMATION
JOINT IN TOPPING
• TERMINATE WATERPROOFING AT TOPPING SLAB AT EXISTING
WALL, SEE • WIRE MESH OVER GEOFOAM AT

3" MIN TOPPING


SYSTEM AT PLANTER WALLS 1A PAVER SYSTEM, SEE
DRIVEWAY SHALL BE PLACED 1-1/2" #4 x 1'-6" AT 2'-0" o/c CCW MIRADRAIN
PER CARLISLE DETAILS S2C-2.3 LANDSCAPING AND SHEET WP-6
FROM BOTTOM OF SLAB CENTERED OVER JOINT DRAINAGE COMPOSITE
• FOR STUCCO FINISH ON PLANTER 6"x6" - W4.0 / W4.0
PAVER SYSTEM, SEE GEOFOAM WELDED WIRE FABRIC CCW PROTECTION
CONCRETE/ MASONRY
LANDSCAPING AND SHEET WP-6 BOARD
SUBSTRATE, SEE CCW MIRADRAIN TOP OF TOPPING
2
S2C-3.1 CCW MIRADRAIN SLAB ELEV - SEE
CCW ROOT BARRIER DRAINAGE COMPOSITE 1 / S2C-1.1
CCW PROTECTION BOARD CCW PROTECTION
6" LONG #3 BARS AT 24" o/c IN BOARD
SEAL License: 89035
WALLS (3" MIN. EMBEDMENT) 6"x6" - W4.0 / W4.0 Expires: 02/28/23

1 1/2"
WELDED WIRE FABRIC

EX. SLAB DROP


GEOFOAM
3"
EX. SLAB DROP

CARLISLE CCW-500 1" SETTING BED


WATERPROOFING (TYP.)
2" COVER

• FOR ADDITIONAL INFORMATION


AT TOPPING SLAB, SEE HILTI HUS 3/8" X 5" (3-1/4" MIN.
1A 1C This item has been digitally signed and sealed by Robert J. Miller on the

S2C-2.3 S2C-2.3 EMBEDMENT). SPACE PINS AT date adjacent to the seal. Printed copies of this document are not
2" COVER CARLISLE CCW-500 1" SETTING BED 18"o/c IN EACH DIRECTION IN
considered signed and sealed and the signature must be verified on
any electronic copies.
WATERPROOFING (TYP.) BONDED OVERLAY AND 36"o/c
IN TOPPING SLAB
HILTI HUS 3/8" X 5" (3-1/4" MIN. • EXISTING CONCRETE SURFACE IS TO BE HEAVY
EMBEDMENT). SHOTBLASTED TO REMOVE ALL CONTAMINENTS
AND PRODUCE A CONCRETE SURFACE PROFILE
CSP 5 THAT MEETS THE REQUIREMENTS OF ICRI
• SHORE EXISTING SLAB AS REQUIRED GUIDELINE NO.310.2R-2013. LIMIT THE DEPTH OF
PRIOR TO POURING BONDED OVERLAY THE CONCRETE REMOVAL TO 3/8" Structural Engineers | Remediation & Parking Consultants
OR TOPPING SLAB, SEE SPECIFICATION
TOPPING SLAB AT PAVER SYSTEM AT SLAB DROP 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
• DETAIL CCW-GR500-6 AT PLANTER DRAIN, SEE CARLISLE • DO NOT CUT EXISTING FOR ADDITIONAL INFORMATION. • PRESOAK EX. SLAB TO A SATURATED SURFACE-
DRY (SSD) CONDITION IMMEDIATELY PRIOR TO
3 1 1/2" = 1'-0"
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.
DETALS FOR ADDITIONAL INFORMATION AND REQUIREMENTS REINFORCEMENT WITHOUT
APPROVAL OF ENGINEER POURING BONDED OVERLAY OR TOPPING SLAB • PROVIDE SAW-CUT IN TOPPING • PROVIDE NEOPRENE REINFORCED
WITHIN 8-HOURS OF POUR CCW-500 JOINT AND SEALANT AT
SAW CUT No. Date Revisions
TOPPING SLAB & PAVER SYSTEM AT EXISTING PLANTER WALL AT SLAB DROP • TOPPING OVER GEOFOAM SHALL
2 1 1/2" = 1'-0"
BE 3" MIN, 4" MAX 3/4" DEEP x 1/4" WIDE SAWCUT
JOINT IN TOPPING
PAVER SYSTEM, SEE
• WIRE MESH OVER GEOFOAM AT LANDSCAPING AND SHEET WP-6

3" MIN TOPPING


• CONTRACTOR SHALL SURVEY THE EXISTING SLAB
DRIVEWAY SHALL BE PLACED 1-1/2" #4 x 1'-6" AT 2'-0" o/c CCW MIRADRAIN
PRIOR TO INSTALLATION OF BONDED OVERLAY
• BONDED OVERLAY MAY BE INTEGRAL WITH ADJACENT FOR GEOFOAM, PAVERS, AND FROM BOTTOM OF SLAB CENTERED OVER JOINT DRAINAGE COMPOSITE
AND DROP PANEL AND PERFORM ANY REQUIRED
TOPPING SLABS, REFER TO ADDITIONAL DETAILS AND REPAIRS. FOR REPAIRS, SEE PLANTERS ABOVE BONDED 6"x6" - W4.0 / W4.0
SU ST SF GEOFOAM WELDED WIRE FABRIC CCW PROTECTION
ELEVATIONS ON S2C-1.1 FOR LOCATIONS OVERLAY SEE SPECIFIC DETAILS
S2C-2.1 S2C-2.1 S2C-2.1 BOARD
TOP OF TOPPING
SLAB ELEV - SEE
2" MIN.

1 / S2C-1.1
EQ.

1 1/2"
EQ.

EX. SLAB DROP


EX. SLAB
6" EMBED

DESIGNED DRAWN
HR/JB/RM HR/JB/RM
CHECKED APPROVED
RM FPM
2"

BONDED OVERLAY, REFER TO CARLISLE CCW-500 1" SETTING BED


4"

S2C-1.0 FOR LOCATIONS AND 2 WATERPROOFING (TYP.) Project No.: 18217


TOP DOWELS - SEE
REQUIRED REINFORCING S2C-2.9
HILTI HUS 3/8" X 5" (3-1/4" MIN.
1" CLR.

• FOR ADDITIONAL INFORMATION EMBEDMENT). SPACE PINS AT Date: 04/26/21


DROP PANEL, • SHORE EXISTING SLAB AS REQUIRED ON TOPPING SLAB, SEE
FOR DROP PANEL REFER TO S2C-1.0 PRIOR TO POURING BONDED OVERLAY 1A 1C 18"o/c IN EACH DIRECTION IN
DOWELS - SEE FOR LOCATIONS OR TOPPING SLAB, SEE SPECIFICATION S2C-2.3 S2C-2.3 BONDED OVERLAY AND 36"o/c Scale: 1 1/2" = 1'-0"
3 IN TOPPING SLAB
• DROP PANEL SHALL BE AND REQUIRED FOR ADDITIONAL INFORMATION.
4000 PSI CONCRETE
S2C-2.9 REINFORCING Sheet Title:
• FOR ADDITIONAL INFORMATION BONDED OVERLAY, REFER TO
PLAZA DETAILS
ON BONDED OVERLAY, SEE S2C-1.0 FOR LOCATIONS AND
DROP PANEL WIDTH 4
(SEE S2C-1.0) S2C-2.3 REQUIRED REINFORCING

Sheet No.:
BONDED OVERLAY AND DROP PANEL BONDED OVERLAY / TOPPING SLAB AT PAVER SYSTEM AT SLAB DROP
4 5
1 1/2" = 1'-0" 1 1/2" = 1'-0" S2C-2.3
PAVER SYSTEM, SEE CCW MIRADRAIN
LANDSCAPING AND SHEET WP-6 DRAINAGE COMPOSITE HILTI HUS 3/8" X 5" (3-1/4" MIN.

SOUTH CONDOMINIUM
EMBEDMENT). SPACE PINS AT 18"o/c IN SEE LANDSCAPE PLANS FOR
CCW PROTECTION

CHAMPLAIN TOWERS
6"x6" - W4.0 / W4.0 EACH DIRECTION IN BONDED OVERLAY
BOARD REQUIRED SOIL HEIGHT. SLOPE

INTEGRAL STRUCTURAL AND


GEOFOAM 1" SETTING BED WELDED WIRE FABRIC AND 36"o/c IN TOPPING SLAB
HILTI HUS 3/8" X 5" (3-1/4" MIN. AND MOUND AS REQUIRED
TOP OF TOPPING EMBEDMENT). SPACE PINS AT 18"o/c IN PAVER SYSTEM, SEE

SURFSIDE, FLORIDA 33154


SLAB ELEV - SEE EACH DIRECTION IN BONDED OVERLAY LANDSCAPING AND SHEET WP-6

8777 COLLINS AVENUE


1 / S2C-1.1 AND 36"o/c IN TOPPING SLAB

SLOPED TOPPING
CCW MIRADRAIN PLANTER
DRAINAGE COMPOSITE CCW MIRADRAIN
• FOR ADDITIONAL INFORMATION
GEOFOAM

3" MIN
ON TOPPING SLAB, SEE CCW PROTECTION CCW ROOT BARRIER
1A 1C 6"x6" - W4.0 / W4.0
CARLISLE CCW-500 S2C-2.3 S2C-2.3 BOARD
1" SETTING BED WELDED WIRE FABRIC
WATERPROOFING (TYP.) CCW PROTECTION BOARD
TOP OF TOPPING TOP OF TOPPING
SLAB ELEV - SEE SLAB ELEV - SEE
1 / S2C-1.1 1 / S2C-1.1

2 1/8"
2"

2" MIN.
2" MIN.
EX. SLAB

EX. SLAB

EX. SLAB
BONDED OVERLAY, REFER TO • FOR ADDITIONAL BONDED OVERLAY, REFER TO BONDED OVERLAY, REFER TO
4"

4"

4"
S2C-1.0 FOR LOCATIONS AND INFORMATION ON S2C-1.0 FOR LOCATIONS AND CARLISLE CCW-500 S2C-1.0 FOR LOCATIONS AND CARLISLE CCW-500
REQUIRED REINFORCING TOPPING SLAB, REQUIRED REINFORCING WATERPROOFING (TYP.) REQUIRED REINFORCING WATERPROOFING (TYP.)
SEE
1A 1C • FOR ADDITIONAL

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


DROP PANEL, REFER TO • FOR ADDITIONAL INFORMATION DROP PANEL, REFER TO • FOR ADDITIONAL INFORMATION DROP PANEL, REFER TO • FOR ADDITIONAL INFORMATION
S2C-1.0 FOR LOCATIONS AND ON DROP PANEL AND BONDED S2C-2.3 S2C-2.3 INFORMATION ON
S2C-1.0 FOR LOCATIONS AND ON DROP PANEL AND BONDED S2C-1.0 FOR LOCATIONS AND ON DROP PANEL AND BONDED
REQUIRED REINFORCING OVERLAY, SEE TOPPING SLAB,
4 REQUIRED REINFORCING OVERLAY, SEE REQUIRED REINFORCING OVERLAY, SEE
4 4 SEE
S2C-2.3 1A 1C
S2C-2.3 S2C-2.3
S2C-2.3 S2C-2.3

BONDED OVERLAY / TOPPING SLAB AT RAISED PAVERS INTEGRAL BONDED OVERLAY / TOPPING SLAB AT PAVERS INTEGRAL BONDED OVERLAY / TOPPING SLAB AT PLANTER

PHASE IIC: OVERALL BUILDING


1 1 1/2" = 1'-0" 2 1 1/2" = 1'-0" 3 1 1/2" = 1'-0"

REPAIR AND RESTORATION


REPAIR & RESTORATION
• TERMINATE WATERPROOFING • NEW MASONRY WALL
• FOR ADDITIONAL INFORMATION • FOR TYPICAL STUCCO NEW GLASS STORE FRONT, SYSTEM AT EXTERIOR WALL SECTIONS TO BE TOOTHED
ON BONDED OVERLAY / TERMINATION AT BASE, SEE ARCHITECTURAL MATCH EXISTING NEW 8" PER CARLISLE DETAILS INTO EXISTING
TOPPING SLAB, SEE SEE DRAWINGS FOR ADDITIONAL WALL HEIGHT CMU WALL
1A 1C 8 INFORMATION • FOR ADDITIONAL INFORMATION
S2C-2.3 S2C-2.3 S2C-3.1
AT TOPPING SLAB, SEE PAVER SYSTEM, SEE
1A 1C
LANDSCAPING AND SHEET WP-6
• FOR STUCCO FINISH ON S2C-2.3 S2C-2.3 CCW MIRADRAIN
CONCRETE/ MASONRY • FOR STUCCO FINISH ON DRAINAGE COMPOSITE
SUBSTRATE, SEE #4 AT 8" o/c 1" SETTING BED
2 CONCRETE/ MASONRY
S2C-3.1 SUBSTRATE, SEE 6"x6" - W4.0 / W4.0 CCW PROTECTION
2 WELDED WIRE FABRIC BOARD TOP OF TOPPING
SEE LANDSCAPE PLANS FOR
S2C-3.1 SLAB ELEV - SEE
REQUIRED SOIL HEIGHT. SLOPE • TERMINATE WATERPROOFING
AND MOUND AS REQUIRED 1 / S2C-1.1
SYSTEM AT EXTERIOR WALL • FOR TYPICAL STUCCO
PER CARLISLE DETAILS TERMINATION AT BASE,
EX. SLAB DROP

SEE
8
S2C-3.1

PLANTER CONT. 2#6 BARS


CCW MIRADRAIN
GEOFOAM CCW ROOT BARRIER

CCW PROTECTION
TOP OF TOPPING BOARD
SLAB ELEV - SEE CARLISLE CCW-500
1 / S2C-1.1 WATERPROOFING (TYP.)

EXISTING SIDEWALK
TO REMAIN
SEAL License: 89035
Expires: 02/28/23
HILTI HUS 3/8" X 5" (3-1/4" MIN.
2'-0" EMBEDMENT). SPACE PINS AT 18"o/c IN
WS EACH DIRECTION IN BONDED OVERLAY
• FOR WATERSTOP - SEE #4 AT 12" o/c DOWELED
S2C-2.2 AND 36"o/c IN TOPPING SLAB
INTO STRUCTURAL SLAB (6" MIN.
EMBEDMENT)

CARLISLE CCW-500 6"x6" - W4.0 / W4.0


WATERPROOFING (TYP.) WELDED WIRE FABRIC
GARAGE

HILTI HUS 3/8" X 5" (3-1/4" MIN.


This item has been digitally signed and sealed by Robert J. Miller on the
EMBEDMENT). SPACE PINS AT 18"o/c IN date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
EACH DIRECTION IN BONDED OVERLAY any electronic copies.
AND 36"o/c IN TOPPING SLAB

TOPPING SLAB AND PLANTER AT STORE FRONT AT SLAB DROP TOPPING SLAB AT NEW EXTERIOR CMU WALL
4 1 1/2" = 1'-0" 6 1 1/2" = 1'-0"
Structural Engineers | Remediation & Parking Consultants
206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.
NEW GLASS STORE FRONT, SEE
ARCHITECTURAL DRAWINGS
FOR ADDITIONAL INFORMATION • ALL STAIR TREAD AND RISER • FOR ADDITIONAL INFORMATION PAVER SYSTEM, SEE
CCW MIRADRAIN
No. Date Revisions
• TERMINATE WATERPROOFING • FOR TYPICAL STUCCO PAVERS TO BE MORTAR SET AT TOPPING SLAB, SEE LANDSCAPING AND SHEET WP-6
1A 1C DRAINAGE COMPOSITE
SYSTEM AT EXTERIOR WALL TERMINATION AT BASE, SEE SHEET WP-6 FOR DETAILS
S2C-2.3 S2C-2.3
PER CARLISLE DETAILS SEE 1" SETTING BED CCW PROTECTION CARLISLE CCW-500
8
BOARD WATERPROOFING (TYP.)
• FOR STUCCO FINISH ON S2C-3.1
7" MAX

CONCRETE/ MASONRY
• FOR ADDITIONAL INFORMATION
EQ.

SUBSTRATE, SEE
ON BONDED OVERLAY / 2
TOPPING SLAB, SEE S2C-3.1
1C • TOPPING SLAB AND SHALL
S2C-2.3 CCW MIRADRAIN BE SLOPED AS REQUIRED TO
EX. SLAB DROP

DRAINAGE COMPOSITE FACILITATE DRAINAGE, SEE


7" MAX

PLANS FOR ELEVATION OF


EQ.

PAVER SYSTEM,
CCW PROTECTION TOPPING SLAB AT STAIRS
SEE LANDSCAPING
BOARD
TOP OF TOPPING TOP OF TOPPING
SLAB ELEV - SEE SLAB ELEV - SEE
1 / S2C-1.1 1 / S2C-1.1

DESIGNED DRAWN
HILTI HUS 3/8" X 5" (3-1/4" MIN. HR/JB/RM HR/JB/RM
EMBEDMENT). SPACE PINS AT 18"o/c IN CHECKED APPROVED
EACH DIRECTION IN BONDED OVERLAY
AND 36"o/c IN TOPPING SLAB
RM FPM
Project No.: 18217

Date: 04/26/21
6"x6" - W4.0 / W4.0 SLOPED TOPPING SLAB ON STAIRS
CARLISLE CCW-500
HILTI HUS 3/8" X 5" (3-1/4" MIN.
WELDED WIRE FABRIC AS REQUIRED TO ACHIEVE PAVER Scale: 1 1/2" = 1'-0"
6"x6" - W4.0 / W4.0 WATERPROOFING (TYP.) ELEVATION FOR EQUAL RISERS
EMBEDMENT). SPACE PINS AT 18"o/c IN
WELDED WIRE FABRIC Sheet Title:
1" SETTING BED EACH DIRECTION IN BONDED OVERLAY
AND 36"o/c IN TOPPING SLAB
PLAZA DETAILS

TOPPING SLAB AND PAVERS AT STORE FRONT AT SLAB DROP TOPPING SLAB AND PAVERS AT EXISTING STAIRS AT SLAB DROP
5 1 1/2" = 1'-0" 7 1 1/2" = 1'-0" Sheet No.:

S2C-2.4
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


PAVERS AROUND DRAINS SHALL BE SET
• FOR ADDITIONAL INFORMATION

8777 COLLINS AVENUE


ON A MINIMUM 8" WIDE BAND OF MORTAR
TO PREVENT TYPICAL DRY SAND SETTING AT NEW DECK DRAIN, SEE • FOR ADDITIONAL INFORMATION • FOR ADDITIONAL INFORMATION
DD1
BED FROM CLOGGING DRAIN WEEPS S2C-2.2 AT NEW DECK DRAIN, SEE AT TOPPING SLAB, SEE
DD1 1A 1C
CCW MIRADRAIN PAVER SYSTEM, SEE S2C-2.2 S2C-2.3 S2C-2.3
DRAINAGE COMPOSITE • DETAIL CCW-500-6 AT DECK, LANDSCAPING AND SHEET WP-6 • FOR ADDITIONAL INFORMATION AT
SEE CARLISLE DETALS FOR • DETAIL CCW-500-6 AT DECK,
CCW PROTECTION PLANTER NEW PLANTER DRAIN, SEE
ADDITIONAL INFORMATION SEE CARLISLE DETALS FOR • WHERE FINAL ELEVATIONS REQUIRE 1B DD3
BOARD 1" SETTING BED ADDITIONAL INFORMATION
TOP OF TOPPING AND REQUIREMENTS RECESSED DRAIN BODY, SEE S2C-2.3 S2C-2.2
AND REQUIREMENTS 5
SLAB ELEV - SEE S2C-2.5
1 / S2C-1.1 NOTE 1: MINIMUM BONDED TOPPING SLAB • DETAIL CCW-500-6 AT DECK, SEE
HILTI HUS 3/8" X 5" (3-1/4" MIN. CCW MIRADRAIN THICKNESS AT DRAINS SHALL BE 1-1/4" CARLISLE DETALS FOR ADDITIONAL
EMBEDMENT). SPACE PINS AT 18"o/c IN PAVER SYSTEM, SEE DRAINAGE COMPOSITE TYPICAL AND 2" WITHIN STRUCTURAL INFORMATION AND REQUIREMENTS
EACH DIRECTION IN BONDED OVERLAY LANDSCAPING AND SHEET WP-6
CCW PROTECTION BONDED TOPPING AREAS
AND 36"o/c IN TOPPING SLAB BOARD CCW MIRADRAIN
CARLISLE CCW-500 TOP OF TOPPING 1" SETTING BED

3" MIN.
WATERPROOFING (TYP.) • FOR ADDITIONAL INFORMATION
SLAB ELEV - SEE CCW ROOT BARRIER
TOP OF TOPPING AT TOPPING SLAB, SEE
1 / S2C-1.1 1A 1C
SLAB ELEV - SEE S2C-2.3 S2C-2.3 CCW PROTECTION BOARD
1 / S2C-1.1

2" COVER
6"x6" - W4.0 / W4.0 T/ EX. SLAB
WELDED WIRE FABRIC

1 1/4" MIN.

NOTE 1
EX. SLAB
6"x6" - W4.0 / W4.0
EX. SLAB

2" COVER 2" COVER WELDED WIRE FABRIC

EX. SLAB
6"x6" - W4.0 / W4.0
WELDED WIRE FABRIC
GEOFOAM

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


CARLISLE CCW-500 SAWCUT EDGE OF
• DO NOT CUT EXISTING • FOR ADDITIONAL INFORMATION WATERPROOFING (TYP.) CONCRETE PATCH
REINFORCEMENT WITHOUT ON TOPPING SLAB, SEE CARLISLE CCW-500 SAWCUT EDGE OF
1A 1C PAVERS AROUND DRAINS SHALL BE SET • LOCATE DRAIN TO AVOID EXISTING CONCRETE PATCH
APPROVAL OF ENGINEER WATERPROOFING (TYP.)
S2C-2.3 S2C-2.3 ON A MINIMUM 8" WIDE BAND OF MORTAR REINFORCEMENT. DO NOT CUT
2'-0" x 2'-0" MIN.

PHASE IIC: OVERALL BUILDING


TO PREVENT TYPICAL DRY SAND SETTING EXISTING REINFORCEMENT • LOCATE DRAIN TO AVOID EXISTING
BED FROM CLOGGING DRAIN WEEPS 2'-0" x 2'-0" MIN. REINFORCEMENT. DO NOT CUT

REPAIR AND RESTORATION


WITHOUT APPROVAL OF ENGINEER
EXISTING REINFORCEMENT
WITHOUT APPROVAL OF ENGINEER

REPAIR & RESTORATION


HILTI HUS 3/8" X 5" (3-1/4" MIN.
EMBEDMENT). SPACE PINS AT 18"o/c IN
EACH DIRECTION IN BONDED OVERLAY
AND 36"o/c IN TOPPING SLAB
DRAIN IN TOPPING SLAB AT RAISED PAVER SYSTEM AT SLAB DROP DRAIN IN TOPPING SLAB AT PAVER SYSTEM (TYPICAL)
1 1 1/2" = 1'-0" 2 1 1/2" = 1'-0" DRAIN IN TOPPING SLAB AT PLANTERS
3 1 1/2" = 1'-0"

• WHERE TOPPING SLAB SLOPES TO EXISTING TOP OF


SLAB ELEVATION AT DRAINS, PROVIDE 2" DEEP PARTIAL
DEPTH PATCH AT ALL SIDES TO LOCK IN TOPPING.
PARTIAL DEPTH PATCH SHALL EXTEND UNTIL TOPPING
THICKNESS ABOVE THE EXISTING SLAB IS 1 1/4" MINIMUM.

• FOR ADDITIONAL INFORMATION • DETAIL CCW-500-6 AT DECK, SEE


• AT WALLS LESS THAN 4'-0" TALL, PROVIDE #4
AT NEW DECK DRAIN, SEE CARLISLE DETALS FOR ADDITIONAL
AT 16" o/c DOWELED INTO EXISTING • FOR ADDITIONAL INFORMATION DD1 INFORMATION AND REQUIREMENTS
STRUCTURAL SLAB (6" MIN. EMBEDMENT) AT TOPPING SLAB, SEE S2C-2.2
1A 1C PAVERS AROUND DRAINS SHALL
BE SET ON A MINIMUM 8" WIDE CCW MIRADRAIN
• AT WALLS TALLER THAN 4'-0" PROVIDE #4 AT S2C-2.3 S2C-2.3 PAVER SYSTEM, SEE
BAND OF MORTAR TO PREVENT DRAINAGE COMPOSITE
8" o/c 6"x6" - W4.0 / W4.0 LANDSCAPING AND SHEET WP-6
TYPICAL DRY SAND SETTING BED CCW PROTECTION
TOP OF TOPPING WELDED WIRE FABRIC
FROM CLOGGING DRAIN WEEPS BOARD
• GROUT ALL CELLS SOLID SLAB ELEV - SEE 1" SETTING BED
SEE LANDSCAPE PLANS FOR 1 / S2C-1.1
• NEW MASONRY WALL REQUIRED SOIL HEIGHT. SLOPE
• FOR STUCCO FINISH ON
SECTIONS TO BE TOOTHED AND MOUND AS REQUIRED
CONCRETE/ MASONRY
INTO EXISTING SUBSTRATE, SEE SEAL License: 89035
2

1 1/4" MIN.
Expires: 02/28/23
• ALL INTEGRAL PIERS IN PLANTER
S2C-3.1

2"
EX. SLAB
WALLS TO BE OF SIMILAR
CONSTRUCTION AND HAVE 4 #5 • FOR TYPICAL STUCCO
BARS ANCHORED TO SLAB TERMINATION AT BASE,
SEE PLANTER
8
• TERMINATE WATERPROOFING S2C-3.1
SYSTEM AT EXTERIOR WALL GEOFOAM
PER CARLISLE DETAILS SAWCUT EDGE OF
• FOR ADDITIONAL INFORMATION CARLISLE CCW-500 8"
AT TOPPING SLAB, SEE WATERPROOFING (TYP.) CONCRETE PATCH
NEW 8" 1A 1C ALL SIDES
HILTI HUS 3/8" X 5" (3-1/4" MIN.
CMU WALL S2C-2.3 S2C-2.3 • LOCATE DRAIN TO AVOID EXISTING
CCW-500 CONTINOUS EMBEDMENT). SPACE PINS AT 18"o/c IN
CCW MIRADRAIN REINFORCEMENT. DO NOT CUT
UNDER INTERIOR WALLS EACH DIRECTION IN BONDED OVERLAY
2'-0" x 2'-0" MIN. EXISTING REINFORCEMENT This item has been digitally signed and sealed by Robert J. Miller on the
AND 36"o/c IN TOPPING SLAB date adjacent to the seal. Printed copies of this document are not
CCW ROOT BARRIER WITHOUT APPROVAL OF ENGINEER considered signed and sealed and the signature must be verified on
any electronic copies.

CCW PROTECTION BOARD


6"x6" - W4.0 / W4.0 DRAIN IN TOPPING SLAB AT PAVER SYSTEM (ALTERNATE)
WELDED WIRE FABRIC
TOP OF TOPPING
SLAB ELEV - SEE
5 1 1/2" = 1'-0"
1 / S2C-1.1

EXISTING SIDEWALK
TO REMAIN Structural Engineers | Remediation & Parking Consultants
• VEHICULAR PAVEMENT AREA AT TRANSITION TO 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
SIDEWALK / ROADWAY SHALL BE MORTAR SET ON 561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.
DRAINAGE BOARD FOR MINIMUM 3'-6" WIDTH.
MORTAR SET PAVERS SHALL HAVE GROUTED • PROVIDE NEOPRENE REINFORCED
JOINTS. SEE SPECIFICATION SECTION 32 14 00 FOR CCW-500 JOINT AND SEALANT AT
MORTAR AND GROUT REQUIREMENTS. SEE SHEET SAW CUT
BEGIN BONDED 3/4" DEEP x 1/4" WIDE SAWCUT No. Date Revisions
WP-6 FOR PAVER INSTALLATION. TOPPING #4 x 1'-6" AT 2'-0" o/c
JOINT IN TOPPING
CENTERED OVER JOINT
3'-6"
PAVER SYSTEM, SEE CCW PROTECTION BOARD
MORTAR SET PAVERS LANDSCAPING AND SHEET WP-6
CARLISLE CCW-500 PROVIDE SEALANT TOP OF TOPPING
WATERPROOFING (TYP.) JOINT CCW MIRADRAIN 1" SETTING BED SLAB ELEV - SEE

3 1/2"
DRAINAGE COMPOSITE 1 / S2C-1.1
EXISTING SIDEWALK
DROP PANEL, REFER TO BONDED OVERLAY, REFER TO TO REMAIN
S2C-1.0 FOR LOCATIONS AND S2C-1.0 FOR LOCATIONS AND
GARAGE REQUIRED REINFORCING REQUIRED REINFORCING
• FOR ADDITIONAL INFORMATION
ON DROP PANEL AND BONDED HILTI HUS 3/8" X 5" (3-1/4" MIN.
OVERLAY, SEE EMBEDMENT). SPACE PINS AT 18"o/c IN
4 EACH DIRECTION IN BONDED OVERLAY 6x6-W4.0xW4.0
S2C-2.3 AND 36"o/c IN TOPPING SLAB

DESIGNED DRAWN
BONDED OVERLAY / TOPPING SLAB AT NEW EXTERIOR & INTERIOR CMU WALLS CARLISLE CCW-500 GEOFOAM (2" MIN
HR/JB/RM HR/JB/RM
4 1 1/2" = 1'-0"
WATERPROOFING (TYP.) THICKNESS)
CHECKED APPROVED
RM FPM
HILTI HUS 3/8" X 5" (3-1/4" MIN.
EMBEDMENT). SPACE PINS AT 18"o/c IN Project No.: 18217
EACH DIRECTION IN BONDED OVERLAY
AND 36"o/c IN TOPPING SLAB
Date: 04/26/21

Scale: As indicated
Sheet Title:
8" ±
PLAZA DETAILS

EXISTING DRIVEWAY RAMP AT FOUNDATION


6 1" = 1'-0" Sheet No.:

S2C-2.5
• VEHICULAR PAVEMENT AREAS AT TRANSITIONS TO SIDEWALK /
ROADWAY SHALL BE MORTAR SET ON DRAINAGE BOARD FOR
MINIMUM 2'-0" WIDTH. MORTAR SET PAVERS SHALL HAVE CCW MIRADRAIN

SOUTH CONDOMINIUM
DRAINAGE COMPOSITE CCW MIRADRAIN

CHAMPLAIN TOWERS
GROUTED JOINTS. SEE SPECIFICATION SECTION 32 14 00 FOR DRAINAGE COMPOSITE
MORTAR AND GROUT REQUIREMENTS. SEE SHEET WP-6 FOR
PAVER INSTALLATION. CCW PROTECTION
BOARD CCW PROTECTION

SURFSIDE, FLORIDA 33154


PAVER SYSTEM,
SEE LANDSCAPING BOARD

8777 COLLINS AVENUE


PROVIDE SEALANT 1" SETTING BED PAVER SYSTEM, SEE
AND SHEET WP-6 LANDSCAPING AND SHEET WP-6
JOINT 1" SETTING BED
2'-0" • SEE PLAN FOR NEW SLAB

3/4" CLR
EXISTING SIDEWALK REINFORCEMENT COLUMN REINFORCEMENT
TO REMAIN TO REMAIN

3/4" CLR
9 1/2"

9 1/2"
MIN.

MIN
3/4" CLR
CARLISLE CCW-500
WATERPROOFING (TYP.) CARLISLE CCW-500

6" MAX
3/4" CLR
EXISTING FOUNDATION WATERPROOFING (TYP.)
DOWELS INTO SLAB TO
REMAIN
CONTINUOUS
WATERSTOP • SEE PLAN FOR NEW SLAB • SAWCUT TOP OF EXISTING COLUMN TO
WS
• FOR WATERSTOP - SEE REINFORCEMENT GREATER THAN 6" LOWER THAN
S2C-2.2
SOFFIT OF NEW SLAB.
• TAPER NEW SLAB TO MEET
EXISTING TOP OF FOUNDATION • TAPER NEW SLAB TO BEAR ON
WALL EXISTING COLUMN AS SHOWN
LATERALLY SHORE EXISTING • TRANSITION PAVER OVER SETTING BED TO

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


BASEMENT WALL PRIOR TO SLAB PAVER/SETTING BED OVER BONDED
DEMOLITION TOPPING PER PLANS
EXISTING 12x16 CONCRETE COLUMN

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
8" ±

REPAIR & RESTORATION


NEW DRIVEWAY RAMP AT FOUNDATION RAMP SLAB AT EXISTING COLUMN
1 1" = 1'-0" 2 1" = 1'-0"
SEE LANDSCAPE PLANS FOR
REQUIRED SOIL HEIGHT. SLOPE
• FOR ADDITIONAL INFORMATION ON AND MOUND AS REQUIRED
TOPPING SLAB, SEE
1A 1C
S2C-2.3 S2C-2.3
EXISTING
MASONRY WALL

1'-8" ± 1'-0"
CONSTRUCTION JOINT WALL/BEAM PLANTER • FOR STUCCO FINISH ON
• NEW MASONRY WALL CONCRETE/ MASONRY
• FOR STUCCO FINISH ON CONCRETE/
SECTIONS TO BE TOOTHED SUBSTRATE, SEE 2
SEE LANDSCAPE PLANS FOR MASONRY SUBSTRATE, SEE 2
REQUIRED SOIL HEIGHT. SLOPE INTO EXISTING S2C-3.1
S2C-3.1 GEOFOAM
AND MOUND AS REQUIRED
• FOR TYPICAL STUCCO
8
TERMINATION AT BASE, SEE
S2C-3.1

PROVIDE 12" BLOCK OVER


PLANTER UPTURNED BEAM CCW MIRADRAIN

CCW ROOT BARRIER


• AT WALLS LESS THAN 4'-0" TALL, PROVIDE #4 AT 16"
SLOPED TOPPING -
GEOFOAM o/c DOWELED INTO EXISTING STRUCTURAL SLAB (6"
TOP OF TOPPING CCW PROTECTION BOARD SEE S2C-1.1
MIN. EMBEDMENT)
SLAB ELEV - SEE
• AT WALLS TALLER THAN 4'-0" PROVIDE #4 AT 8" o/c 1 / S2C-1.1 • EXISTING REINFORCEMENT FROM
BEAM SHALL REMAIN AND EXTEND INTO SEAL License: 89035
• GROUT ALL CELLS SOLID NEW CONCRETE MINIMUM OF 2'-0" Expires: 02/28/23

VARIES FROM 22" TO 37-1/2"


CCW MIRADRAIN

EX. UPTURNED BEAM


CCW ROOT BARRIER SLOPED TOPPING - 2#7 TOP & BTM CCW MIRADRAIN
SEE S2C-1.1 #3 CLOSED STIRRUPS AT 10" o/c CARLISLE CCW-500 DRAINAGE COMPOSITE
PAVER SYSTEM,

1'-0 1/2"
TOP OF TOPPING CCW PROTECTION BOARD WATERPROOFING (TYP.) SEE LANDSCAPING CCW PROTECTION
SLAB ELEV - SEE #5 BARS PER PLAN IN AND SHEET WP-6 BOARD
1 / S2C-1.1 TOPPING
1" SETTING BED
#5 AT 12" o/c WITH 90°

3/4" CLR
HOOK INTO BEAM • PROVIDE NEW #5 REBAR

VARIES FROM 22" TO 37-1/2"


DOWELS INTO BEAM WITH 8"
2#5 EMBEDMENT IN EPOXY This item has been digitally signed and sealed by Robert J. Miller on the

UPTURNED BEAM
date adjacent to the seal. Printed copies of this document are not
8"
EX. SLAB

considered signed and sealed and the signature must be verified on


CARLISLE CCW-500 CCW MIRADRAIN
9 1/2" ±

any electronic copies.


TRIM EX. REBAR WITHIN
WATERPROOFING (TYP.) EX. #5 AT 12" o/c NEW BEAM DRAINAGE COMPOSITE
1'-3 1/2" MAX

9 1/2" (MIN)
HILTI HUS 3/8" X 5" (3-1/4" MIN.
CCW PROTECTION
PAVER SYSTEM, BOARD VARIES EMBEDMENT). SPACE PINS AT 18"o/c IN
EACH DIRECTION IN BONDED OVERLAY CARLISLE CCW-500
SEE LANDSCAPING WATERPROOFING (TYP.)
1 1/2" CLR 1" SETTING BED AND 36"o/c IN TOPPING SLAB
AND SHEET WP-6
3/4" CLR
4"

Structural Engineers | Remediation & Parking Consultants

3/4" CLR
206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
2'-0" 561.316.7660 | www.morabitoconsultants.com
EX. #4 AT 12" o/c © Copyright Morabito Consultants, Inc.
DROP PANEL, REFER TO (E.W.)
S2C-1.0 FOR LOCATIONS AND #5 x 1'-8" AT 12" o/c
9 1/2" (MIN)

REQUIRED REINFORCING
EXISTING UPTURN BEAM AT ENTRANCE RAMP
CARLISLE CCW-500
WATERPROOFING (TYP.)
4 1 1/2" = 1'-0"
No. Date Revisions
• PROVIDE SAW-CUT IN TOPPING • PROVIDE NEOPRENE REINFORCED
TAPER SLAB TO COLUMN WITHIN 8-HOURS OF POUR CCW-500 JOINT AND SEALANT AT
AS REQUIRED SAW CUT
3/4" CLR
3"

HILTI HUS 3/8" X 5" (3-1/4" MIN. PAVER SYSTEM, SEE 3/4" DEEP x 1/4" WIDE SAWCUT
EMBEDMENT). SPACE PINS AT 18"o/c IN • FOR ADDITIONAL INFORMATION LANDSCAPING AND SHEET WP-6 CCW MIRADRAIN JOINT IN TOPPING
AT TOPPING SLAB, SEE DRAINAGE COMPOSITE
3"

EACH DIRECTION IN BONDED OVERLAY • SEE PLAN FOR NEW SLAB 1A 1C


AND 36"o/c IN TOPPING SLAB REINFORCEMENT S2C-2.3 S2C-2.3 6"x6" - W4.0 / W4.0 CCW PROTECTION
TOP OF TOPPING
3"

WELDED WIRE FABRIC BOARD


• COLUMN f'c = 4,000 PSI THICKEN AND SLOPE NEW SLAB ELEV - SEE #4 x 1'-6" AT 2'-0" o/c
• IN LIEU OF CASTING THICKER RAMP, CENTERED OVER JOINT
CONTRACTOR MAY ELECT TO POUR CONCRETE RAMP TO MAINTAIN 1 / S2C-1.1
• FOR ADDITIONAL INFORMATION ON • 6#6 COLUMN VERTICALS
SECONDARY BONDED TOPPING PROPER PAVER SETTING BED
TOPPING SLAB, SEE • #3 COLUMN TYPES AS SHOWN THICKNESS
1A 1C
1'-0" o/c

S2C-2.3 S2C-2.3 • EXTEND COLUMN BARS INTO


TYP

SLAB/BEAM 6" WITH 90° HOOKS


• CAST REPLACEMENT SLAB TOGETHER 1" SETTING BED

3" MIN
WITH DROP PANEL DESIGNED DRAWN
HR/JB/RM HR/JB/RM
• FOR ADDITIONAL INFORMATION
ON DROP PANEL AND BONDED
CHECKED APPROVED

9 1/2" ±
CARLISLE CCW-500
OVERLAY, SEE WATERPROOFING (TYP.)
RM FPM
4
S2C-2.3 1 1/2" CLR Project No.: 18217

Date: 04/26/21
GEOFOAM (2" MIN
THICKNESS) Scale: As indicated
3/4" CLR

HILTI HUS 3/8" X 5" (3-1/4" MIN.


2'-0" MIN EMBEDMENT). SPACE PINS AT 18"o/c IN Sheet Title:
EACH DIRECTION IN BONDED OVERLAY • EXISTING REINFORCEMENT SHALL
AND 36"o/c IN TOPPING SLAB REMAIN AND EXTEND INTO NEW PLAZA DETAILS
1'-4" (x 12") CONCRETE MINIMUM OF 2'-0"
NEW COLUMN

NEW UPTURN BEAM AT ENTRANCE RAMP TOPPING SLAB RAMP TRANSITION Sheet No.:
3 1 1/2" = 1'-0" 5 1 1/2" = 1'-0"
S2C-2.6
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS
3

SURFSIDE, FLORIDA 33154


S2C-2.6

8777 COLLINS AVENUE


• TOPPING SLAB AND SHALL BE SLOPED AS
REQUIRED TO FACILITATE DRAINAGE, SEE PLANS NEW UP-TURN BEAM
STEPS SHALL BE MORTAR SET ON DRAINAGE FOR ELEVATION OF TOPPING SLAB
BOARD. MORTAR SET PAVERS SHALL HAVE
GROUTED JOINTS. SEE SPECIFICATION SECTION 32 3'-0" • CAREFULLY DEMO REQUIRED PORTION OF
CCW MIRADRAIN EXISTING UP-TURN BEAM AND ALLOW LIGHT BOLLARD - SEE LANDSCAPE
14 00 FOR MORTAR AND GROUT REQUIREMENTS. DRAINAGE COMPOSITE 1" SETTING BED
SEE SHEET WP-6 FOR PAVER INSTALLATION. EXISTING TOP & BOTT BARS TO REMAIN AND FOR LOCATIONS
EXTEND 3'-0" FROM EXISTING CONCRETE
PAVER SYSTEM, SEE CCW PROTECTION • CARLISLE CCW-500 WATERPROOFING
LANDSCAPING AND SHEET WP-6 BOARD #3 TIES AT 10" o/c CONTINUOUS UNDER PEDESTAL
• 10" DIAMETER CONCRETE PEDESTAL
TOP OF TOPPING
SLAB ELEV - SEE • 4#6 VERTICALS ANCHORED TO SLAB
• AT ALL STEPS, ADHERE MIRADRAIN TO 2#7 TOP AND BOTTOM SPLICE BARS
CCW-500 PROTECTION BOARD WITH 1 / S2C-1.1 TOP OF PEDESTAL = TOP OF WITH 6" EMBEDMENT

7" MAX
APPROVED CONTACT ADHESIVE ADJACENT CMU WALLS (VIF)

EQ.
• #3 TIES AS SHOWN
11" EXISTING #7 BEAM BARS

VE
RI

9 1/2" ±
CARLISLE CCW-500 FY
SLOPED BONDED
7" MAX

WATERPROOFING (TYP.)
EQ.

EXISTING SIDEWALK TOPPING - SEE PLAN


PLANTER CCW MIRADRAIN

3'-
TO REMAIN

0"
CCW ROOT BARRIER
TOP OF TOPPING
EXISTING UP- SLAB ELEV - SEE
CCW MIRADRAIN TURN BEAM CCW PROTECTION BOARD 1 / S2C-1.1
CELL VENTS AT 24" o/c DRAINAGE COMPOSITE
GEOFOAM

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


GARAGE

EX. SLAB
• PROVIDE PAVER JOINT
CELL VENTS AT 24" o/c
MAXIMUM, BY HECKMANN

PHASE IIC: OVERALL BUILDING


BUILDING PRODUCTS

REPAIR AND RESTORATION


HILTI HUS 3/8" X 5" (3-1/4" MIN.
EMBEDMENT). SPACE PINS AT 18"o/c IN

REPAIR & RESTORATION


EACH DIRECTION IN BONDED OVERLAY
EXISTING STEPS AT FOUNDATION WALL CONCRETE BEAM TIE-IN TO EXISTING BEAM AND 36"o/c IN TOPPING SLAB
1 1 1/2" = 1'-0" 2 3/4" = 1'-0"

TYPICAL PLANTER BOLLARD


3 1" = 1'-0"

SEAL License: 89035


• RAILING FABRICATOR SHALL EVALUATE Expires: 02/28/23
AS-BUILT CONDITIONS/MEASUREMENTS ALUMINUM HANDRAIL EACH SIDE - DESIGNED BY
34"-38" FROM FFE
PRIOR TO SUBMITTING SHOP DRAWINGS FABRICATOR'S REGISTERED ENGINEER TO MEET
REQUIREMENTS OF FBC-2020. SUBMIT SIGNED
• NEW MASONRY WALL • EXTEND GRAB RAIL AND SEALED SHOP DRAWINGS
SECTIONS TO BE TOOTHED BEYOND RAMP ENDS 1'-0"
INTO EXISTING • AT WALLS LESS THAN 4'-0" TALL, PROVIDE #4
AT 16" o/c DOWELED INTO EXISTING
STRUCTURAL SLAB (6" MIN. EMBEDMENT)
• SIMILAR DETAIL OPPOSITE RAMP SIDE • FOR ADDITIONAL INFORMATION
AT TOPPING SLAB, SEE • AT WALLS TALLER THAN 4'-0" PROVIDE #4 AT
1A 1C 2 1/4"
• FOR STUCCO FINISH ON CONCRETE/ 16" o/c
MASONRY SUBSTRATE, SEE S2C-2.3 S2C-2.3
2
S2C-3.1 • GROUT ALL CELLS SOLID SEE LANDSCAPE PLANS FOR This item has been digitally signed and sealed by Robert J. Miller on the
date adjacent to the seal. Printed copies of this document are not
REQUIRED SOIL HEIGHT. SLOPE considered signed and sealed and the signature must be verified on
• FOR TYPICAL STUCCO AND MOUND AS REQUIRED
any electronic copies.

TERMINATION AT BASE, SEE 8


S2C-3.1
• TOPPING SLAB AND SHALL BE SLOPED AS
REQUIRED TO FACILITATE DRAINAGE, SEE PLANS
CONNECTION BAND AND FOR ELEVATION OF TOPPING SLAB PLANTER CCW MIRADRAIN
WIRE BRACES BY OTHERS
• ADA RAMP SHALL HAVE ALL PAVERS MORTAR CCW ROOT BARRIER
Structural Engineers | Remediation & Parking Consultants
SET AND JOINTS GROUTED 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
• MOUNDING SOIL THICKER THAN 18" IS CCW PROTECTION 561.316.7660 | www.morabitoconsultants.com
PERMITTED AROUND TREES AND PALMS. CCW-500 CONTINUOUS © Copyright Morabito Consultants, Inc.
BOARD
SEE LANDSCAPE FOR MORE INFO. MORTAR SET AND GROUT JOINTS UNDER NEW WALL TOP OF TOPPING
45°

OF VERTICAL PAVERS SLAB ELEV - SEE


PAVER SYSTEM, SEE CCW MIRADRAIN 1 / S2C-1.1
LANDSCAPING AND SHEET WP-6 DRAINAGE COMPOSITE
No. Date Revisions
• FOR NEW PLANTER SEE LANDSCAPE PLANS FOR
DRAINS, SEE DD3 REQUIRED SOIL HEIGHT. SLOPE CCW PROTECTION BOARD
#5 AT 12" o/c
#4

9 1/2" ±
AND MOUND AS REQUIRED
S2C-2.2 (EA. WAY TOP)
BTM) 1" MORTAR BED

VARIES
EXTEND 6#5 BARS INTO
18" MAX

EXISTING SLAB WITH 12"


EMBEDMENT IN EPOXY

COLD-BEND EX.

9 1/2"
BOTTOM BARS
REBAR COUPLER
(TYP)
GEOFOAM
VARIES

• PROVIDE LENTON COUPLERS

3/4" CLR
TO ALL EXISTING
CCW MIRADRAIN CARLISLE CCW-500 REINFORCEMENT
WATERPROOFING (TYP.) DESIGNED DRAWN
CARLISLE CCW • WHERE SPACING OF NEW HR/JB/RM HR/JB/RM
ROOT BARRIER #5 AT 12" o/c
#4 1'-8" REINFORCEMENT IS SMALLER THAN
(EA. WAY BTM) CHECKED APPROVED
EXISTING, DOWEL NEW REINFORCEMENT
INTO EXISTING SLAB WITH 12" EMBEDMENT
RM FPM
#5 AT 12" o/c
2'-0" Project No.: 18217

Date: 04/26/21

TREE PIT NEW CARLISLE CCW-500 Scale: As indicated


SEE LANDSCAPE
WATERPROOFING (TYP.)
DRAWINGS FOR SIZE/LOCATION Sheet Title:
CCW PROTECTION BOARD
PLAZA DETAILS

TYPICAL LARGE TREE PIT SECTION THRU ADA RAMP


4 NOT TO SCALE
5 1 1/2" = 1'-0" Sheet No.:

S2C-2.7
• ALLOW EXISTING SLAB REINFORCEMENT TO
1'-0" RAMP EXTEND INTO NEW SLAB MINIMUM OF 2'-0"

SOUTH CONDOMINIUM
5" VIF 5" = SIDEWALK ELEV. • ADA RAMP SHALL HAVE ALL PAVERS MORTAR

CHAMPLAIN TOWERS
PAINT ANY EXPOSED
PORTION OF WALL EXISTING SLAB SET ON DRAIN BOARD AND JOINTS GROUTED 2'-0" LAP
PROFILE (REMOVED)
SEE LANDSCAPE CCW MIRADRAIN #5 AT 12" o/c
#4

SURFSIDE, FLORIDA 33154


FOR TOP SOIL DRAINAGE COMPOSITE (EA. WAY TOP)
BTM)

8777 COLLINS AVENUE


1" MORTAR BED

3"

1" CLR
PROVIDE SEALANT JOINT
#5 AT 12" o/c
#4
• 5" THICK CONCRETE WALLS AT CCW PROTECTION BTM)
(EA. WAY TOP)
4 SIDES OF OPENING 1" MORTAR BED
CCW MIRADRAIN EX. SIDEWALK BOARD
T/SLAB= 7.71±
• REINFORCE WALLS WITH #4 AT 10"
o/c EACH WAY CENTERED IN WALL CCW ROOT BARRIER

9 1/2" ±
GEOFOAM • ANCHOR VERTICAL BARS TO SLAB CCW PROTECTION BOARD

3/4" CLR
WITH 6" EMBEDMENT IN EPOXY

9 1/2"
TOP OF TOPPING
• SEE MECHANICAL PLANS FOR NEW FAN.
SLAB ELEV - SEE TRIM TOP OF EX. CARLISLE CCW-500
PROPERLY FLASH AND SEAL FAN TO
NEW CONCRETE WALLS
1 / S2C-1.1 FOUNDATION WALL AS WATERPROOFING (TYP.)
REQ. FOR SLAB BEARING

ALLOW EXISTING EXISTING SLAB #5 AT 12" o/c


#4

3/4" CLR
FOUNDATION REBAR TO PROFILE (REMOVED) (EA. WAY BTM)
• FOR ADDITIONAL INFORMATION ON EXTEND INTO NEW SLAB
TOPPING SLAB, SEE CARLISLE CCW-500 #5 AT 12" o/c
#4
EX. SLAB

6"
1A 1C
WATERPROOFING (TYP.) (EA. WAY BTM)
S2C-2.3 S2C-2.3 • FOR WATERSTOP - SEE WS GARAGE
S2C-2.2
• FOR ADDITIONAL INFORMATION
CONTINUOUS
AT TOPPING SLAB, SEE
WATERSTOP 1A 1C
S2C-2.3 S2C-2.3
HILTI HUS 3/8" X 5" (3-1/4" MIN.

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


EMBEDMENT). SPACE PINS AT 18"o/c IN
EACH DIRECTION IN BONDED OVERLAY
AND 36"o/c IN TOPPING SLAB
ADA RAMP AT FOUNDATION
3 1 1/2" = 1'-0" • RAILING FABRICATOR SHALL EVALUATE
AS-BUILT CONDITIONS/MEASUREMENTS
34"-38" FROM FFE PRIOR TO SUBMITTING SHOP DRAWINGS

PHASE IIC: OVERALL BUILDING


NEW AIR SHAFT WALLS

REPAIR AND RESTORATION


1 1 1/2" = 1'-0" 44" CLEAR

REPAIR & RESTORATION


ALUMINUM HANDRAIL EACH SIDE - DESIGNED BY
FABRICATOR'S REGISTERED ENGINEER TO MEET
REQUIREMENTS OF FBC-2020. SUBMIT SIGNED
AND SEALED SHOP DRAWINGS
CONTRACTOR & RAILING ENGINEER TO
2 1/4"
VERIFY EXISTING WALL CONSTRUCTION

PAVER SYSTEM BEYO


FOR SUITABLE ANCHORING
3/4" CHAMFERS
• EXTEND GRAB RAIL
BEYOND RAMP ENDS 1'-0"

BEAM DEPTH VARIES


PROVIDE SEALANT
JOINT • FOR STUCCO FINISH ON CONCRETE/
MASONRY SUBSTRATE, SEE STUCCO
EXISTING SIDEWALK 2

ND
TO REMAIN S2C-3.1 4'-3 1/2" OUT-TO-OUT
• FOR TYPICAL STUCCO
8

2'-0"
TERMINATION AT BASE, SEE #4 AT 12" o/c • CONTROL JOINTS FILLED WITH
S2C-3.1 EACH WAY SEALANT IN RAMP AT 5'-0" o/c MAX

BEYOND
SLAB
5" CONCRETE WALL

CCW-500 CONTINUOUS
UNDER WALL 6x6-W2.9xW2.9 ISOLATION JOINT AND
1 1/2" CLR

CCW PROTECTION BOARD SEALENT

CCW MIRADRAIN
EXISTING FOUNDATION TOP OF TOPPING
DOWELS INTO SLAB TO SLAB ELEV - SEE 1 / S2C-1.1
REMAIN
CONTINUOUS
WATERSTOP
WS
• FOR WATERSTOP - SEE • TAPER NEW BEAM TO MEET
S2C-2.2 EXISTING TOP OF FOUNDATION SEAL License: 89035
Expires: 02/28/23
WALL AS REQUIRED

6"
• FOR BEAM REINFORCEMENT -
SEE
3
LATERALLY SHORE EXISTING
BASEMENT WALL PRIOR TO SLAB &
S2C-2.6
CARLISLE CCW-500 GEOFOAM (2" MIN
BEAM DEMOLITION WATERPROOFING (TYP.) THICKNESS)

• FOR ADDITIONAL INFORMATION ON • ANCHOR VERTICAL BARS TO SLAB


TOPPING SLAB, SEE WITH 6" EMBEDMENT IN EPOXY
1A 1C HILTI HUS 3/8" X 5" (3-1/4" MIN. This item has been digitally signed and sealed by Robert J. Miller on the
8" ± S2C-2.3 S2C-2.3 EMBEDMENT). SPACE PINS AT 18"o/c IN date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
EACH DIRECTION IN BONDED OVERLAY any electronic copies.
AND 36"o/c IN TOPPING SLAB

BASEMENT WALL AT NEW BEAM ADA RAMP AT ENTRANCE


2 1" = 1'-0" 4 1 1/2" = 1'-0"

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
• PROVIDE CONTROL JOINTS IN 4,000 PSI CONCRETE TOPPING WITH PROVIDE SEALANT JOINT © Copyright Morabito Consultants, Inc.
NEW EXPOSED TOPPING AT 8'-0" CORROSION INHIBITOR AND
o/c MAX PER DETAIL PENETRATING SILANE SEALER
JS
CONTROL JOINT AT
TRANSITION
S2C-2.1 No. Date Revisions
4'-0" 6x6-W4.0xW4.0
#4 x 1'-6" AT 2'-0" o/c PREVENT BOND
1 1/2" CLR

THICKENED SLAB WITH DOUBLE LAYER MESH CENTERED OVER JOINT • FOR STUCCO FINISH ON CONCRETE/
EXISTING CONCRETE
MASONRY SUBSTRATE, SEE 2
CURB/WALL 8" ±
PROVIDE SEALANT CCW MIRADRAIN CCW PROTECTION S2C-3.1
JOINT DRAINAGE COMPOSITE BOARD 6x6-W4.0xW4.0
• FOR TYPICAL STUCCO
6x6-W4.0xW4.0 TERMINATION AT BASE, SEE 8
5"

EXISTING SIDEWALK 4,000 PSI CONCRETE TOPPING WITH


TO REMAIN TOP OF TOPPING S2C-3.1
CORROSION INHIBITOR AND PROVIDE
SLAB ELEV - SEE PENETRATING SILANE SEALER SEALANT COVE ASSUMED EXISTING • EXPOSED TOPPING SLAB SHALL
1 / S2C-1.1 REBAR TO REMAIN HAVE SAME SLOPE AS SLOPED
PREVENT BOND BONDED TOPPING
PROVIDE

5"
SEALANT COVE
6x6-W4.0xW4.0 CCW
GEOFOAM PREVENT BOND PROTECTION
BOARD

4" MIN
TOP OF TOPPING CCW MIRADRAIN DESIGNED DRAWN
SLAB ELEV - SEE DRAINAGE COMPOSITE HR/JB/RM HR/JB/RM
1 / S2C-1.1 CHECKED APPROVED
GEOFOAM
SLOPED BONDED (2" MIN) GEOFOAM
RM FPM
TOPPING CARLISLE CCW-500
WATERPROOFING (TYP.) Project No.: 18217
HILTI HUS 3/8" X 5" (3-1/4" MIN.
EMBEDMENT). SPACE PINS AT 18"o/c IN
• NEW BI-LEVEL DRAIN SHALL HAVE SOLID (NON- Date: 04/26/21
GRATED) TOP.
EACH DIRECTION IN BONDED OVERLAY
AND 36"o/c IN TOPPING SLAB • FOR ADDITIONAL DRAIN INFORMATION - SEE
DD1 Scale: As indicated
S2C-2.2
6x6-W4.0xW4.0 Sheet Title:
SLOPED BONDED
HILTI HUS 3/8" X 5" (3-1/4" MIN. PLAZA DETAILS
TOPPING
EMBEDMENT). SPACE PINS AT 18"o/c IN
8" ± EACH DIRECTION IN BONDED OVERLAY
AND 36"o/c IN TOPPING SLAB

Sheet No.:
EXISTING SERVICE DRIVEWAY RAMP EXISTING SERVICE DRIVEWAY RAMP
5 1" = 1'-0" 6 1" = 1'-0" S2C-2.8
R
• BONDED TOPPING NOT SHOWN
FOR CLARITY

SOUTH CONDOMINIUM
1'-0" (x 16") EXPOSE VERTICAL BARS OF

CHAMPLAIN TOWERS
NEW COLUMN WS EXISTING COLUMN FOR DEPTH OF
• FOR WATERSTOP - SEE S2C-2.2 DROP PANEL (4 SIDES)
EXISTING 16x12

SURFSIDE, FLORIDA 33154


• COLUMN f'c = 4,000 PSI

9 1/2" ±
1 1/2" CLR COLUMN

8777 COLLINS AVENUE


• 6#6 COLUMN VERTICALS

0" (TYP)
3/4" CLR
4 1/2"
• #3 COLUMN TYPES AS SHOWN EXISTING SLAB 2"

WS • EXTEND COLUMN BARS INTO REINFORCEMENT TO


• FOR WATERSTOP - SEE 4#6 TOP BARS REMAIN
S2C-2.2 GRADE BEAM 6" WITH 90° HOOKS CONTINUOUS

4"
• DO NOT CUT ANY EXISTING SLAB WATERSTOP
• GRADE BEAM f'c = 4,000 PSI
REINFORCEMENT WITHOUT
• 4#6 TOP BARS

1'-0" o/c
PRIOR APPROVAL OF ENGINEER SEE

9" ±
TYP
• 5#10 BTM BARS PLAN #4 @18" o/c
• CONTRACTOR'S PRICE TO BUILD • STIRRUPS AS INDICATED FOR 5-FT
GRADE BEAM SHALL INCLUDE 2 #4 SEE PLAN SEE PLAN
FROM EACH BEAM SUPPORT 8

1'-8"
ALL DE-WATERING COSTS,
COMPACTION, AND @ 18" o/c EACH SIDE OF COLUMN

48°
4-LEG #3 CLOSED

3" 3" 3"


SEALANT JOINT (TYP)

VIF
GEOTECHNICAL TESTING CONTINUOUS STIRRUPS AT 8" o/c FOR LENGTH OF DROP SLAB

VERIFY
WATERSTOP EXISTING SLAB
EACH SIDE REINFORCEMENT TO REMAIN • SECURE #4 DOWELS INTO HEAVY SAND BLAST TO
BOTTOM OF EXISTING SLAB WITH CSP-3 FOR BONDING OF
AC100+ GOLD BY POWFERS (4 1/2 NEW CONCRETE
5#10 BTM BARS 1' MINIMUM EMBEDMENT)
-0
9" ±

" EXISTING PILE CAP


• TRIM EXISTING PILE CAP AS
1'-8"

SHOWN FOR WIDTH OF NEW


4-LEG #3 CLOSED GRADE BEAM
2 1/2"
STIRRUPS AT 8" o/c NEW SLAB DROP PANEL
• PROVIDE 6#3 x 2'-0" DOWELS INTO
EXISTING PILE CAP WITH 12"
3 1" = 1'-0"
EMBEDMENT

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


ASSUMED (1) EX. 150 TON
2V:1H SLOPE MAX
3" CLR

P.I.F. FRANKI PILE (TYP)

• NEW CONTROL JOINTS SHALL BE SPACED • EXISTING CONCRETE SURFACE IS TO BE HEAVY • PRESOAK EX. SLAB TO A SATURATED SURFACE-DRY
4'-0"
AT 12' - 0" EACH WAY MAXIMUM SHOTBLASTED TO REMOVE ALL CONTAMINENTS (SSD) CONDITION IMMEDIATELY PRIOR TO POURING
AND PRODUCE A CONCRETE SURFACE PROFILE BONDED OVERLAY

PHASE IIC: OVERALL BUILDING


• NEW WIRE MESH SHALL BE 6"x6" - W4.0/W4.0 CSP 5 THAT MEETS THE REQUIREMENTS OF ICRI
WELDED WIRE FABRIC (TYP.) GUIDELINE NO.310.2R-2013. LIMIT THE DEPTH OF • THIS DETAIL APPLIES TO HATCHED

REPAIR AND RESTORATION


THE CONCRETE REMOVAL TO 3/8"
NEW GRADE BEAM AT COLUMN NEW GRADE BEAM AT EXISTING PILE CAP REGIONS ON PLANS
4 5

REPAIR & RESTORATION


1" = 1'-0" 1" = 1'-0" • PROVIDE 3/8"Ø x 5" HILTI HUS SCREWS AT 18"
EACH WAY MAXIMUM THROUGHOUT
STRUCTURAL BONDED SLAB FOOTPRINT (3-1/4"
MINIMUM EMBEDMENT)

1 1/4" PROJECTION
NEW GLASS STORE
FRONT, SEE NEW WIRE MESH NEW CONCRETE SHOT BLAST EXISTING
• FOR STUCCO FINISH ON
ARCHITECTURAL TOPPING SLAB SUBSTRATE
CONCRETE/ MASONRY
SUBSTRATE, SEE 2 DRAWINGS FOR
ADDITIONAL INFORMATION
S2C-3.1

MIN.
2"
• FOR TYPICAL STUCCO
• EXPOSED TOPPING SLAB SHALL • PROVIDE CONTROL JOINTS IN TERMINATION AT BASE,
HAVE SAME SLOPE AS SLOPED NEW EXPOSED TOPPING AT 8'-0" SEE
BONDED TOPPING o/c MAX PER DETAIL 8
JS

3-1/4" MIN
S2C-3.1
S2C-2.1
PROVIDE SEALANT 6x6-W4.0xW4.0
JOINT CCW 4,000 PSI CONCRETE TOPPING WITH
PROVIDE
EXISTING SIDEWALK CCW MIRADRAIN PROTECTION CORROSION INHIBITOR AND
SEALANT COVE
DRAINAGE COMPOSITE BOARD PENETRATING SILANE SEALER
TO REMAIN
4" MIN

TOP OF TOPPING 1'-6"


SLAB ELEV - SEE ON-CENTERS EACH WAY
1 / S2C-1.1
PREVENT BOND

EXISTING CONCRETE SLAB • WORK THIS DETAIL WITH TYPICAL NON-


STRUCTURAL SLOPED BONDED TOPPING

STRUCTURAL BONDED TOPPING


2 3" = 1'-0"
SEAL License: 89035
Expires: 02/28/23
SLOPED BONDED
TOPPING • FOR ADDITIONAL DRAIN INFORMATION - SEE DD1 CARLISLE CCW-500
S2C-2.2 WATERPROOFING (TYP.)
HILTI HUS 3/8" X 5" (3-1/4" MIN.
EMBEDMENT). SPACE PINS AT 18"o/c IN 6x6-W4.0xW4.0
EACH DIRECTION IN BONDED OVERLAY
AND 36"o/c IN TOPPING SLAB • AT WALLS LESS THAN 4'-0" TALL, PROVIDE #4
AT 16" o/c DOWELED INTO EXISTING
STRUCTURAL SLAB (6" MIN. EMBEDMENT)
• FOR STUCCO FINISH ON
• NEW MASONRY WALL CONCRETE/ MASONRY • AT WALLS TALLER THAN 4'-0" PROVIDE #4 AT
SECTIONS TO BE TOOTHED SUBSTRATE, SEE 2 8" o/c
GAS METER AND RELATED PIPING
INTO EXISTING S2C-3.1 This item has been digitally signed and sealed by Robert J. Miller on the
8" ± date adjacent to the seal. Printed copies of this document are not
• GROUT ALL CELLS SOLID considered signed and sealed and the signature must be verified on
any electronic copies.

SEE LANDSCAPE PLANS FOR • FOR TYPICAL STUCCO


REQUIRED SOIL HEIGHT. SLOPE TERMINATION AT BASE,
EXISTING SERVICE DRIVEWAY RAMP AND MOUND AS REQUIRED SEE
8
1 1" = 1'-0" NEW 8" POURED WALL S2C-3.1
EQ EQ • TERMINATE WATERPROOFING CCW-500 CONTINOUS
SYSTEM AT EXTERIOR WALL • FOR ADDITIONAL INFORMATION UNDER INTERIOR WALLS
PER CARLISLE DETAILS AT TOPPING SLAB, SEE
1A 1C Structural Engineers | Remediation & Parking Consultants
206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
S2C-2.3 S2C-2.3 561.316.7660 | www.morabitoconsultants.com

HEIGHT FOR HEIGHT VARIES AT REMAINDER OF WALL


© Copyright Morabito Consultants, Inc.

FOR 5 FOOT WIDTH CCW MIRADRAIN


2'-9" AT 5' WIDTH CENTERED AT GAS METER CENTERED AT GAS LINE:
CCW ROOT BARRIER
#6 AT 16" SPACING No. Date Revisions
HOOK AND LAP 29" CCW PROTECTION BOARD
ONTO SLAB STEEL
ALL OTHER LOCATIONS:
MASONRY WALL WITH #4
AT 16" SPACING. GROUT
ALL CELLS SOLID.
• (4) THREADED ROD SET IN
EPOXY (8" EMBEDMENT). USE
AVAILABLE DIAMETER IN #4 AT 8" SPACING FILTER FABRIC OVER 6"
PRE-ENGINEERED SUN GRAVEL BASE
• 5"Ø STD PIPE FILLED WITH MANUFACTURER'S BASE PLATE SHADE SCREEN
GROUT, GALVANIZED AND STRUCTURE OR LIGHT
PAINTED YELLOW POST • REPAIR SIDEWALK
• PAVER INSTALLATION
AS REQUIRED
• 1'-0" x 1'-0" x 3/4" BASE PLATE REFERENCE SHEET WP-6
2'-6"

• (4) 3/4"Ø THREADED ROD SET IN 1/4


EPOXY (7" EMBEDMENT)
EXISTING SIDEWALK
CARLISLE CCW-500 CARLISLE CCW-500 TO REMAIN DESIGNED DRAWN
WATERPROOFING WATERPROOFING HR/JB/RM HR/JB/RM
PAVER SYSTEM PAVER SYSTEM
CCW MIRADRAIN CCW MIRADRAIN CHECKED APPROVED
DRAINAGE COMPOSITE DRAINAGE COMPOSITE DROP PANEL, REFER TO BONDED OVERLAY, REFER TO RM FPM
1" SETTING BED 1" SETTING BED S2C-1.0 FOR LOCATIONS AND S2C-1.0 FOR LOCATIONS AND
GARAGE REQUIRED REINFORCING REQUIRED REINFORCING Project No.: 18217
• FOR ADDITIONAL INFORMATION
ON DROP PANEL AND BONDED Date: 04/26/21
OVERLAY, SEE
4
7"

CARLISLE CCW-500 CARLISLE CCW-500


8"

BONDED TOPPING - WATERPROOFING BONDED TOPPING - WATERPROOFING


S2C-2.3 Scale: As indicated
SEE PLAN SEE PLAN
• DETAIL BELOW AND ABOVE • DETAIL BELOW AND ABOVE Sheet Title:
BASE PLATE WITH CCW-500 BASE PLATE WITH CCW-500 #6 DOWELS AT 16" SPACING EPOXY DOWEL 4" INTO
GARAGE WALL HOOK AND LAP 29" ONTO SLAB STEEL
PLAZA & FOUNDATION
DETAILS

Sheet No.:
BOLLARD AND STRUCTURE SLAB ANCHORING EXPANDED GAS LINE SLAB AND WALL EXTENSION
6 7
1" = 1'-0" 1 1/2" = 1'-0" S2C-2.9
EX. POOL DECK

SOUTH CONDOMINIUM
CHAMPLAIN TOWERS
EX. POOL DECK
NOTE 10 • STRUCTURE SHOWN IS GENERIC

SURFSIDE, FLORIDA 33154


AND WILL DIFFER PER PLANS
NOTE 5 NOTES 8 & 9
RN

8777 COLLINS AVENUE


• FOR TYPICAL REPAIR NOTES, SEE SEE PLANS FOR

9 1/2"
S2C-2.0 NOTE 6 NOTE 4
RN EXISTING SLAB
• FOR TYPICAL REPAIR NOTES, SEE REINFORCEMENT
S2C-2.0 NOTE 10
NOTE 3
9 1/2"

EX. SLAB
EXISTING REBAR

PLAN
SEE
NOTES 4, 5 & 6

NOTE 7

NOTE 10 POOL
DETERIORATED
(TYP.) RN SHORING WHERE
CONCRETE, NOTE 3 PUMP • FOR TYPICAL REPAIR NOTES, SEE
S2C-2.0 REQUIRED
ROOM
1
• PARTIAL DEPTH REPAIRS UP TO 3" THICK S2C-3.4
NEW CONCRETE PATCH

DETERIORATED
CONCRETE,
SAWCUT EDGE OF

PUMP • SLAB TOP SURFACE REPAIRS SHALL ONLY


ROOM NOTE 3
BE PERFORMED ON SLAB THICKNESSES
3/4" CLR. (MIN.) OF 6" OR GREATER AND ONLY WITH
POOL
EXPLICIT PRE-APPROVAL OF ENGINEER

)
IN.
POOL SLAB TOP SURFACE REPAIR

(M
NOTE 10 (TYP.)

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


NEW CONCRETE
4

R.
(f'c = 4500 PSI) 1 1/2" = 1'-0"

CL
NOTES 7, 8 & 9 EXISTING REBAR

1"
NOTES 4, 5 & 6
NOTE 6, WHERE EXISTING
REINFORCEMENT IN CONCRETE • DOWEL BARS MAY BE • STRUCTURE SHOWN IS GENERIC

PHASE IIC: OVERALL BUILDING


CORBEL IS SEVERELY DETERIORATED ONE CONT. 'U' SHAPED AND WILL DIFFER PER PLANS
OR NOT FOUND, PROVIDE NEW BENT # DETERIORATED
NEW CONCRETE

REPAIR AND RESTORATION


BEND BAR OR TWO 'L' CONCRETE, NOTE 3 SEALANT JOINT
4 BARS AT 12" o/c DOWELED INTO SHAPED BARS (f'c = 4500 PSI) #4 x 1'-0" DOWELS AT 12" o/c
NOTES 8 & 9 SET IN EPOXY (6" EMBED)

REPAIR & RESTORATION


SOLID CONCRETE USING HILIT HY-200 NOTE 10 NOTES 7, 8 & 9 SEE PLANS FOR EXISTING
EPOXY ADHESIVE AS SHOWN. • NOTE 2, TEMPORARILY (TYP.) IF EXISTING VERTICAL BARS EXHIBIT NOTE 5
SAWCUT EDGE OF SLAB REINFORCEMENT NOTE 3
(5" MIN. EMBEDMENT) SHORE EXISTING SEVERE DETERIORATION, ADD NEW
STRUCTURE AS NEW CONCRETE PATCH
VERTICAL BARS (SIZE TO MATCH
REQUIRED PRIOR TO EXISTING) IN TWO PIECES WITH CLASS
DEMOLITION • NOTE 2, TEMPORARILY SHORE 'A' TENSION LAP SPLICE. EPOXY GROUT
PLAN OF EXISTING WALL EXISTING WALL AS REQUIRED
PRIOR TO DEMOLITION
BARS 6" MIN. INTO EXISTING WALL. THE
CONTRACTOR SHALL EXPAND THE
DEMOLISHED AREA SUCH THAT NEW NOTE 7
EPOXIED BARS CAN ACHIEVE THE NOTE 10
PROPER LAP SPLICE. NEW VERTICAL
SIKASWELL NOTE 6
BARS SHALL HAVE A MINIMUM OF 1 1/2"
S2 TYP.
WS COVER AND EXISTING CONCRETE
• FOR WATERSTOP - SEE S2C-2.2 AROUND DETERIORATED REBAR SHALL
BE REMOVED SO THAT SECTIONS OF
BARS TO REMAIN CAN BE PROPERLY
CLEANED SHORING WHERE
REQUIRED

CONCRETE CORBEL REPAIR AT POOL POOL WALLS CONCRETE SPALL REPAIR


1 1 1/2" = 1'-0" 2 1 1/2" = 1'-0" • FOR TYPICAL REPAIR NOTES, SEE
RN
S2C-2.0 WS
• FOR WATERSTOP - SEE S2C-2.2

POOL SLAB FULL-DEPTH REPAIR


3 1 1/2" = 1'-0"

APPLY SIKA SWELL S2 TO


COLD JOINT PERIMETER
(TYP.)

COPING PAVERS TO BE SEAL License: PE89035


BONDED AND INSTALLED 1 EX. POOL DECK IF EXISTING HORIZONTAL BARS EXHIBIT SEVERE Expires: 02/28/21
RN WP-6 DETERIORATION, ADD NEW HORIZONTAL BARS (SIZE TO
• FOR TYPICAL REPAIR NOTES, SEE IN ACCORDANCE WITH:
S2C-2.0 MATCH EXISTING) IN TWO PIECES WITH CLASS 'A' TENSION
LAP SPLICE. EPOXY GROUT BARS 6" MIN. INTO EXISTING SLAB.
EX. POOL DECK THE CONTRACTOR SHALL EXPAND THE DEMOLISHED AREA
SUCH THAT NEW EPOXIED BARS CAN ACHIEVE THE PROPER
LAP SPLICE. NEW VERTICAL BARS SHALL HAVE A MINIMUM OF
1 1/2" COVER AND EXISTING CONCRETE AROUND
DETERIORATED REBAR SHALL BE REMOVED SO THAT
9 1/2"

SECTIONS OF BARS TO REMAIN CAN BE PROPERLY CLEANED

EXISTING REBAR
NOTES 4, 5 & 6
9 1/2"

NEW CONCRETE
(f'c = 4500 PSI)
NOTES 7, 8 & 9 EXISTING REBAR
NOTES 4, 5 & 6

NOTE 10 POOL
DETERIORATED
(TYP.)
CONCRETE, NOTE 3 GARAGE Structural Engineers | Remediation & Parking Consultants
206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
HILTI HUS 3/8" X 5" © Copyright Morabito Consultants, Inc.
STAINLESS ANCHOR
NEW CONCRETE PATCH

EMBED 3-1/4"
SAWCUT EDGE OF

PUMP STAGGER SPACING DETERIORATED


ROOM AT 12" O.C. CONCRETE, NOTE 3 No. Date Revisions

RN
• FOR TYPICAL REPAIR NOTES, SEE
S2C-2.0
NOTE 10 (TYP.) NEW CONCRETE
POOL (f'c = 4500 PSI)
NOTES 7, 8 & 9
EXISTING REBAR
NOTES 4, 5 & 6

WS
• FOR WATERSTOP - SEE S2C-2.2 WS
• FOR WATERSTOP - SEE S2C-2.2
• NOTE 2, TEMPORARILY IF EXISTING VERTICAL BARS EXHIBIT
SHORE EXISTING SEVERE DETERIORATION, ADD NEW
STRUCTURE AS VERTICAL BARS (SIZE TO MATCH
REQUIRED PRIOR TO
DESIGNED DRAWN
• NOTE 2, TEMPORARILY SHORE
EXISTING) IN TWO PIECES WITH CLASS Designer Author
DEMOLITION 'A' TENSION LAP SPLICE. EPOXY GROUT
EXISTING WALL AS REQUIRED BARS 6" MIN. INTO EXISTING WALL. THE CHECKED APPROVED
PRIOR TO DEMOLITION CONTRACTOR SHALL EXPAND THE Checker Approver
DEMOLISHED AREA SUCH THAT NEW
EPOXIED BARS CAN ACHIEVE THE Project No.: 18217
PROPER LAP SPLICE. NEW VERTICAL
APPLY SIKA SWELL S2 TO BARS SHALL HAVE A MINIMUM OF 1 1/2"
COVER AND EXISTING CONCRETE
Date: 04/26/21
COLD JOINT PERIMETER
(TYP.) AROUND DETERIORATED REBAR SHALL
BE REMOVED SO THAT SECTIONS OF Scale: 1 1/2" = 1'-0"
BARS TO REMAIN CAN BE PROPERLY
CLEANED Sheet Title:
POOL REPAIR DETAILS
CONCRETE GUTTER REPAIR AT POOL POOL WALLS CONCRETE FULL DEPTH REPAIR
5 1 1/2" = 1'-0" 6 1 1/2" = 1'-0"
Sheet No.:

S2C-3.0
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS
• PROVIDE FLUID APPLIED
MEMBRANE AIR BARRIER

SURFSIDE, FLORIDA 33154


PER SPECIFICATION

8777 COLLINS AVENUE


EXISTING SPALLED OR
HOLLOW SOUNDING
GALVANIZED METAL STUD STUCCO TO BE REPAIRED
FRAMING AT 24" o/c MAX.

STAINLESS STEEL SCREWS


~ SURFACE ELEVATION
• ALL SCREWS SHALL BE 1/2"
FROM EDGES OF CEMENT 1. PRIOR TO COMMENCEMENT OF STUCCO REPAIRS, THE CONTRACTOR SHALL HIRE AN
BOARD. PROVIDE DOUBLE ~ EXPERIENCED TESTING LABORATORY TO COMPLETE A CHEMICAL AND MICROSCOPIC
JOISTS / STUDS AS REQUIRED
TO MAINTAIN 1/2" EDGE
~ FINISH COAT TO MATCH
EXISTING COLOR AND
ANALYSIS OF THE EXISTING STUCCO.
DISTANCE TEXTURE FINISH COAT TO MATCH 2. CHIP-OFF ALL DELAMINATED STUCCO WITH CHISEL AND HAMMER.
EXISTING THICKNESS
~ AND TEXTURE 3. PROPERLY CLEAN EXISTING SURFACE TO RECEIVE STUCCO REPAIR.
NEW BROWN COAT
~
METAL STUD
TRACK RUNNER
~ 4. MECHANICALLY ROUGHEN EXISTING BROWN COAT SURFACE WITH SAND BLASTING OR
LIGHT CHIPPING HAMMER OR HAMMER AND CHISEL TO REMOVE LOOSE MATERIAL TO
~ NEW SCRATCH COAT BROWN COAT TO MATCH ASSURE PROPER BONDING. SURFACE MUST BE STRUCTURALLY SOUND AND CLEAN, FREE
OF ANY AND ALL OIL, GREASE, WAX, DUST, SAND, DIRT, LAITANCE, PAINT.
~ ~ EXISTING THICKNESS
EFFLORESCENCE, CURING COMPOUNDS, FORM RELEASE AGENTS AND BASE MATERIALS

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


NEW METAL LATHE OF ANY KIND.

NEW WATERPROOF MEMBRANE EXISTING EXTERIOR 5. COAT PREPARED SURFACE WITH AN APPROVED BONDING AGENT CONFORMING TO ASTM
MASONRY BLOCK WALL C-932.
NEW CEMENT BOARD
6. STUCCO REPAIR MATERIALS SHALL MATCH THE EXISTING STUCCO AS DETERMINED BY
THE LABORATORY ANALYSIS. SUBMIT PRODUCT DATA FOR APPROVAL.

PHASE IIC: OVERALL BUILDING


• PROVIDED 3/8" x 3.4 lbs/yd3 GALVANIZED EXTERIOR • PROVIDE 3/4" ARMOROC STRUCTURAL MORTAR JOINTS • PRIOR TO INSTALLATION OF BROWN COAT, WALL
RIB EXPANDED METAL LATHE SECURED TO CEMENT CEMENT BOARD - FASTEN ALL EDGES AND STRUCK FLUSH

REPAIR AND RESTORATION


SURFACE SHALL BE CLEANED OR ALL LOOSE AND 7. TOUCH-UP BROWN COAT AND INSTALL NEW FINISH COAT OF STUCCO TO MACH EXISTING
BOARD WITH 1 1/2" x 11 GAUGE S.S. SCREWS WITH INTERIOR SUPPORTS WITH 1 5/8" x #10 FOREIGN CONTAMINATES AND THE ENTIRE EXPOSED IN COLOR, THICKNESS AND APPEARANCE. SEE SPECIFICATIONS FOR ADDITIONAL
7/16"Ø PAN WAFER HEAD FABRICATED PER ASTM SELF-DRILLING CEMENT BOARD SCREWS

REPAIR & RESTORATION


SURFACE SHALL BE COATED WITH AN APPROVED PROJECT REQUIREMENTS.
C-954 OR ASTM C-1002 SPACED AT 6" o/c E.W. AT 6" o/c MAX. SPACING BONDING AGENT CONFORMING TO ASTM C-932

NEW STUCCO OVER LIGHTGAGE / CEMENT BOARD SURFACES NEW STUCCO OVER MASONRY / CONCRETE SURFACES STUCCO REPAIR OVER MASONRY / CONCRETE SURFACES
1 3/4" = 1'-0" 2 3/4" = 1'-0" 3 3/4" = 1'-0"

GREATER THAN 1/8"


EXISTING
STUCCO

EX. EXTERIOR WALL

EX. FLOOR SLAB


EXISTING CONCRETE WALL
FLOOR LINE

EXTENTS - 16" MIN


STUCCO REPAIR
EXISTING • CONTINUOUS #36 SILL SCREED

SEE PLANS
EX. SLAB
SUBSTRATE (SI36) BY CLARKDIETRICH AND
LATHE STRIP 4" STRIP OF GALVANIZED LATHE

1. CRACKS TO BE REPAIRED SHALL BE ROUTED TO A MINIMUM • FASTEN TO CONCRETE WALL PER


WIDTH AND DEPTH OF 1/4" TO ACCOMMODATE STUCCO FILL. ASTM A1063 & MANUFACTURER AT
THE EDGES OF THE CRACK SHALL BE UNDERCUT WHERE NOT MORE THAN 6" o/c
POSSIBLE. BRUSH CRACKS CLEAN OF LOOSE DEBRIS WITH A
SOFT BRUSH. • SIMILAR CONDITION WHERE STUCCO SEAL License: 89035
TERMINATES AT CONCRETE DECK Expires: 02/28/23

2. THE AREA TO RECEIVE THE STUCCO FILL SHALL BE • REGARDLESS OF SOUNDNESS OF STUCCO, WEEP SILL POLYURETHANE
FABRIC MESH SCREED SEALANT • SEE SPECIFICATIONS FOR
THOROUGHLY WETTED TO PREVENT DEHYDRATION OF THE REPLACE STUCCO AT ALL FLOOR LINES
AND INSTALL GLASS FABRIC DETAIL MESH ADDITIONAL STUCCO INFORMATION
STUCCO. RE-WET AS NECESSARY.
BY STO INTO STUCCO BROWN COAT
3. USING THE APPROVED STUCCO MIX, FILL THE CRACK AND • PROVIDE TWO (2) 9.5" WIDE MESH STRIPS, ACRYLIC CONCRETE
WORK STUCCO IN AS TIGHTLY AS POSSIBLE UNTIL FLUSH WITH EACH CENTERED OVER THE TOP AND COATING BELOW
ADJOINING SURFACE. REMOVE EXCESS STUCCO. BOTTOM EDGES OF SLAB
4. PROTECT FILLED AREAS WITH PLASTIC SHEETING AND RE-WET
PERIODICALLY TO ALLOW A FULL CURE.

REPAIR OF STUCCO CRACKS GREATER THAN 1/8" WIDE STUCCO REINFORCEMENT AT FLOOR LINES STUCCO WEEP SCREED AT BASE/FOUNDATION This item has been digitally signed and sealed by Robert J. Miller on the

4 3/4" = 1'-0" 6 3/4" = 1'-0" 8 3/4" = 1'-0"


date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

LESS THAN 1/8" No. Date Revisions


EXISTING
STUCCO

• WHERE STUCCO REPAIRS EXTEND ACROSS


CMU/CONCRETE COLUMN JOINTS, INSTALL
GLASS FABRIC DETAIL MESH BY STO INTO
STUCCO BROWN COAT
• PROVIDE MINIMUM 4" MESH DEVELOPMENT
BEYOND JOINT EX. COLUMN

WALL/COLUMN JOINT EX. EXTERIOR WALL


EXISTING
SUBSTRATE

1. CRACK SHOULD BE FREE FROM DIRT, GREASE, AND


VEGETATION. BLOW CRACKS CLEAN WITH COMPRESSED DESIGNED DRAWN
AIR, NOT TO EXCEED 150 PSI.
HR/JB/RM HR/JB/RM
2. COAT CRACK WITH A BONDING AGENT CONFORMING TO CHECKED APPROVED
ASTM C-932 IN ACCORDANCE WITH MANUFACTURER'S RM FPM
INSTRUCTIONS.
Project No.: 18217
3. PREPARE A SLURRY COAT OF STUCCO TO MATCH THE
COLOR AND FINISH OF THE EXISTING STUCCO. APPLY A
LIGHT COAT OF THE SLURRY ALONG THE CRACK AND Date: 04/26/21
4" MIN FABRIC MESH
WORK TO MATCH EXISTING STUCCO.
Scale: 3/4" = 1'-0"
REPAIR OF STUCCO CRACKS LESS THAN 1/8" WIDE STUCCO REINFORCEMENT AT WALL AND COLUMN JOINTS Sheet Title:
5 3/4" = 1'-0" 7 3/4" = 1'-0"
STUCCO REPAIR DETAILS

Sheet No.:

S2C-3.1
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
• CONTRACTOR TO SCAN EXISTING CONCRETE PRIOR TO PRE-
DRILLING FOR TAPCON SCREWS - ADJUST FRAMING LAYOUT AS
REQUIRED TO AVOID CONFLICTS BETWEEN SCREW LOCATIONS
AND SLAB/WALL REINFORCEMENT - ADJUSTED FRAMING SHALL NOT • UL DESIGN No. U403, 2 HOUR FIRE RATED.
EXCEED THE SPACING LIMITATIONS SPECIFIED FOR THE NEW
FRAMING MEMBERS - PROVIDE ADDITIONAL FRAMING AS REQUIRED • PROVIDE FIRE TAPING/MUDDING AT JOINTS IN DRWWALL
ASSEMBLY, AND AT FASTENER HEADS, AS REQUIRED.
• PROVIDE (2) 3/16" DIAMETER x 1 3/4" TAPCON SCREWS AS SHOWN • FOR STUCCO CONSTRUCTION INCLUDING
IN UNDERSIDE OF EXISTING SLAB THROUGH TRACK AT EACH WATERPROOFING MEMBRANE AND AIR • SUPPLEMENT DRILL SCREWS AT CRITICAL CONNECTIONS OF
EXTERIOR STUD AND HANGER - COAT SCREWS IN AN APPROVED BARRIER, EXPANDED METAL LATHE AND NEW RCKW5.5 & RCKW 5.5S (STIFFNER) BY SIMPSON STONG-TIE AT EACH FRAMING, AND AS DIRECTED BY THE ENGINEER IN THE FIELD.
EPOXY ADHESIVE PRIOR TO INSTALLATION TO ENSURE ADEQUATE OTHER REQUIREMENTS, SEE 358SW14 HANGER/STUD (@ MAX. 1-0" O.C.), USING FASTENER PATTERN 4B FOR
SCREW ENGAGEMENT WITH EXISTING CONCRETE LEVEL 2 ATTACHEMENT; CONSISTS OF TWO (2)-1/2" DIA. TYPE 316-S.S. STRONG BOLT 2 • CONSULT WITH ENGINEER ON RCKW RIGID CONNECTIONS PRIOR LEVEL 2
WEDGE ANCHOR BOLTS BY SIMPSON STRONG-TIE, WITH MINIMUM 4" TO INSTALLATION.
EMBENDMENT IN CONCRETE, & TEN (10)-#12 DRILL SCREWS AT STUDS (TYP.)

EX. TRACK (TYP.)

(1) #10 SCREW BASE LAYER: 5/8" TYPE X GYPSUM WALLBOARD APPLIED PARALLEL TO ONE SIDE
CONT. 358T18 (TYP.) LAYER OF DUPONT TYVEK WRB AT FACE OF OUTER LAYER OF EXTERIOR
EACH SIDE (TYP.) OF 3-5/8" STL. HANGER/STUDS WITH 1" TYPE S DRYWALL SCREWS 32" O.C
DENGLASS-X (TYP.) MIN. 6" OVERLAP FROM BOTTOM TO TOP OF WALL (AS
REQUIRED), PROVIDE 3" TYVEK TAPE AT VERTICAL AND HORIZONTAL SEAMS SECOND LAYER: 1/2" TYPE X GYPSUM WALLBOARD APPLIED PARALLEL HANGER
358SW18 HANGER AT STUDS WITH 1-5/8" TYPE S DRYWALL SCREWS 24" O.C AT INTERMEDIATE STUDS
24" MAX. SPACING • ALL SCREWS SHALL FACE LAYER: 5/8" EXTERIOR DENGLASS-X APPLIED PARALLEL
BE STAINLESS STEEL TO ONE SIDE WITH 1-5/8" TYPE S DRYWALL SCREWS 12" O.C. FACE LAYER: 1/4" (OR 3/8") REGULAR GYPSUM WALLBOARD LAMINATED PARALLEL TO

4'-0" +/-
358SW18 STUDS AT

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


24" MAX. SPACING AT EDGES AND 24" O.C. AT INTERMEDIATE HANGER/STUDS HANGER STUDS WITH 3/4" DAUBS OF ADHESIVE SPACED 12" O.C EACH DIRECTION

1'-10"
• BEAM/WALL CONNECTION: BASE LAYER: 5/8" EXTERIOR DENGLASS-X APPLIED 2" GLASS FIBER INSULATION, 0.9 PCF, STAPLED
(2) #10 SCREW (1) #10 SCREW EACH SIDE
358SW18 JOIST AT 3x3x18 GUAGE PER LEG (TYP.) PARALLEL TO ONE SIDE OF 3-5/8" STL. HANGER/STUDS TO ONE SIDE IN KICKER SPACE (TYP.)
AT JOIST TO TRACK WITH 1" TYPE S DRYWALL SCREWS 32" O.C
24" MAX. SPACING CONT. ANGLE (TYP.) NEW 358SW14 STL. HANGER/STUDS AT MAX. 12" O.C. (TYP.) SISTER
CONNECTION - (2) 3/16"
DIAMETER x 1 3/4" TAPCON NEW HANGER/STUDS TO EX. STUDS WHERE REQUIRED
SCREWS THROUGH TRACK

PHASE IIC: OVERALL BUILDING


AT EACH JOIST - COAT
TAPCONS IN AN APPROVED EX. TRACK (TYP.)

REPAIR AND RESTORATION


EPOXY ADHESIVE

REPAIR & RESTORATION


(4) #10 SCREW (TYP.) REMOVE AND REPLACE EXT. SOFFIT CEILING, MAX. 3'-0" WIDE REMOVE AND REPLACE INT. CEILING, MAX. 3'-0" WIDE (AS
NEW STUCCO FINISH EX. INTERIOR SOFFIT
(AS REQUIRED) TO ACCOMPLISH HEADER DETAIL WORK REQUIRED) TO ACCOMPLISH HEADER DETAIL WORK CEILING (TYP.) TO REMAIN
TO MATCH EXISTING
3'-0" 3'-0"

3/4" ARMOROC STRUCTURAL CEMENT BOARD OR NEW STUCCO FINISH REPLACE LIGHT GAUGE FRAMING AS
EX. EXTERIOR SOFFIT TO MATCH EXISTING NECESSARY TO COMPLETE WORK (TYP.)
APPROVED EQUAL - FASTEN AT ALL EDGES AND CEILING (TYP.) TO REMAIN
INTERIOR SUPPORTS WITH 1 5/8" x #10 SELF-DRILLING NEW GLAZING (TYP.) ANCHOR IN ACCORDANCE • PROVIDE WATERPROOFING/FLASHING AT GLAZING
CEMENT BOARD SCREWS AT 6" MAX SPACING WITH APPROVED NOA, PROVIDE (STRUCTURAL) OPENING(S) FOR NEW WINDOW/DOOR INSTALLATIONS, AS
PT WOOD BUCKING, AS/IF REQUIRED REQUIRED. REF. SECTION 1
3/4" ARMOROC STRUCTURAL CEMENT BOARD OR S2C-3.3
APPROVED EQUAL - FASTEN AT ALL EDGES AND
INTERIOR SUPPORTS WITH 1 5/8" x #10 SELF-DRILLING
CEMENT BOARD SCREWS AT 6" MAX SPACING

REPLACE LIGHT GAUGE FRAMING AS


.

NECESSARY TO COMPLETE WORK (TYP.)


1/4"

. S.S. CASING BEAD S.S. CASING BEAD .


1/4" SEALANT SEALANT
3/8"

HUNG SOFFIT REPLACEMENT FIRST FLOOR COMMON AREA GLAZING HEADER REINFORCEMENT
1 1 1/2" = 1'-0" 2 1 1/2" = 1'-0"

EX. HANDRAIL SPLICE - TYP.

EX. HANDRAIL - TYP.

#10 x 1" SELF-DRILLING (TYPE BSD) SCREWS UNSLOTTED SEAL License: 89035
Expires: 02/28/23
HEX WASHER HEAD 316 SS BY FASTENERSUPERSTORE (OR
B ENGINEER APPROVED EQUAL) - TYP. AT HORIZ. RAIL AND
PICKET CONNECTIONS

2-3/4 x 2-3/4 x WIDTH OF RAIL POST BY 1/4" THK., 6063-T5


(ALLOY) ALUM. OR 300 SERIES SS CLIP ANGLE - TYP. PRE-
DRILL HOLES IN CLIP ANGLES 1/16" LARGER THAN
• FOR ADDITIONAL RAIL FASTENER DIMENSION, AS REQ'D.
REPAIR/INSTALLATION NOTES,
SEE 1 EX. 1-3/4" x 3/4" SOLID ALUM. BAR BY

3/4"
4'-2"+/- (POSTS), ALLOY 6061-T6 - TYP.

1 7/8"
S2C-2.2

1" 3"
• STRUCTURE SHOWN IS GENERIC This item has been digitally signed and sealed by Robert J. Miller on the
AND WILL DIFFER PER PLANS EX. RAIL
date adjacent to the seal. Printed copies of this document are not

3/4"
considered signed and sealed and the signature must be verified on

2 1/4"
any electronic copies.
POST - TYP.
• FOR TYPICAL REPAIR #14 x 1" SELF-DRILLING (TYPE CSD) SCREWS UNSLOTTED HEX
3'-6"

NOTES, SEE WASHER HEAD 316 SS BY FASTENERSUPERSTORE (OR


RN 3/4" 1" 3/4" ENGINEER APPROVED EQUAL) - TYP. AT VERTICAL RAIL POST
S2C-2.0 1 7/8" 3" 2 1/4"

EX. 3/4" SQ. x 1/8" THK. ALUM. TUBE BY CONNECTIONS


3'-8"+/- @ 6" o/c MAX., ALLOY 6063-T5 - TYP.
B TYPICAL RAIL POST TO HORIZ. RAIL REPAIR DETAIL
• PERFORM FULL DEPTH
EDGE REPAIRS AS Structural Engineers | Remediation & Parking Consultants
SPECIFIED IN • RAIL POST TO TOE-RAIL AND RAIL POST TO HANDRAIL REPAIR 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
SE DETAILING IS THE SAME 561.316.7660 | www.morabitoconsultants.com
S2C-2.1 © Copyright Morabito Consultants, Inc.

• CONSULT WITH ENGINEER IF


SIGNIFICANT RAIL POST EMBED No. Date Revisions
DAMAGE/ DETERIORATION IS EX. 2" x 1" x 1/8" ALUM. - TYP.
UNCOVERED DURING SLAB
REPAIR WORK
C
3/4" 1"
1 7/8" 3"
3/4"
2 1/4"

#10 x 1" SELF-DRILLING (TYPE BSD) SCREWS UNSLOTTED


3"

HEX WASHER HEAD 316 SS BY FASTENERSUPERSTORE (OR


ENGINEER APPROVED EQUAL) - TYP. AT HORIZ. RAIL AND
EX SLAB
3"

PLAN

PICKET CONNECTIONS
SEE

1" 3/4"
3/4" 2 1/4"
3"

5"
1 7/8"

EX. PICKET - TYP.


2-3/4 x 2-3/4 BY WIDTH OF RAIL POST BY 1/4" THK., 6063-T5
(ALLOY) ALUM. OR 300 SERIES SS CLIP ANGLE - TYP. PRE-
1/4"

DRILL HOLES IN CLIP ANGLES 1/16" LARGER THAN


FASTENER DIMENSION, AS REQ'D. DESIGNED DRAWN
7/8"
1 1/8"
3/4"

EX. TOE-RAIL - TYP. HR/JB/RM HR/JB/RM


3 3/8"

7/8"
2 5/8" 2 5/8"

1/4" CHECKED APPROVED


2-3/4"

A
3/4" 3/4"

#10 x 1" SELF-DRILLING (TYPE BSD) SCREWS UNSLOTTED RM FPM


1 1/2"
8 1/4"

EX. 1-3/4" x 3/4" SOLID ALUM. HEX WASHER HEAD 316 SS BY FASTENERSUPERSTORE (OR
4 1/2"

BAR BY 4'-2"+/- (POSTS), ENGINEER APPROVED EQUAL) - TYP. AT HORIZ. RAIL AND
ALLOY 6061-T6 - TYP. PICKET CONNECTIONS
Project No.: 18217
1 1/8"

Date: 04/26/21
C TYPICAL PICKET TO HORIZ. RAIL REPAIR DETAIL
3/8"

EX. TYP. EX. ALUM. F.B. 1/2" x 1/4"


EX. TYP. • PICKET TO TOE-RAIL AND PICKET TO HANDRAIL REPAIR
1/8 1 1/2 x 2-3/4" L. - TYP. 1 1/2" = 1'-0"
1/8 1 1/2 DETAILING IS THE SAME Scale:
Sheet Title:
A EX. POST EMBED SECTION SOFFIT AND RAIL REPAIR
DETAILS

RAIL REPAIR Sheet No.:


3 1 1/2" = 1'-0"
S2C-3.2
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS
GENERAL NOTES: SILL CONSTRUCTION GENERAL PROCEDURE:

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
1. SLIDING GLASS DOOR INSTALLATION TO BE IN ACCORDANCE WITH MIAMI-DADE NOA 20-0429.03 1. REMOVE AND DISPOSE EXISTING SLIDING GLASS DOOR, FRAME, AND BUCKING. REPAIR CONCRETE IF NECESSARY. PREPARE FLOOR SLAB TO
ICRI CSP-7.
2. IF BUCKING AT HEADER OR JAMB REQUIRES LESS THAN 2X, ATTACH BUCKING WITH MINIMAL NUMBER
OF FASTENERS TO ENSURE TIGHT BOND TO CONCRETE SUBSTRATE. INSTALL REQUIRED NUMBER OF 2. REMOVE ALL DUST AND DEBRIS. WET PREPARED FLOOR SLAB TO SSD CONDITION.
CONCRETE FASTENERS FOR SLIDING GLASS DOOR FRAME THROUGH BUCKING TO ACHIEVE MINIMUM
EMBEDMENT INTO SUBSTRATE REQUIRED BY MIAMI-DADE NOA. EMBEDMENT DEPTH DOES NOT 3. MIX SIKAQUICK 1000 IN ACCORDANCE WITH MANUFACTURER'S GUIDELINES. APPLY BONDCOAT OF SIKAQUICK 1000 TO PREPARED SSD FLOOR
INCLUDE BUCKING. SLAB USING STIFF BRISTLE IMMEDIATELY POUR GROUT BED LEVEL. 1/2' MINIMUM. HEIGHT DICTATED BY SLIDING GLASS DOOR INSTALLER. IF
PRIMARY SEALANT 1/2" GROUT BED EXCEEDS 2", EXTEND PER MANUFACTURER GUIDELINES. 3/4" MINIMUM GROUT BEDHEIGHT. FINAL GROUT BED HEIGHT
CANT BEAD SIKA 2C NS 3. IF BUCKING AT HEADER OR JAMB IS EQUAL TO A 2X OR GREATER, ATTACH BUCKING (SEE FASTENING DETERMINED BY SLIDING GLASS DOOR INSTALLER.
SCHEDULE THIS SHEET) USING 1/4" ELCO CRETEFLEX SS4 FASTENERS AT 1" CONCRETE EDGE
DISTANCE AND 1-3/4" EMBEMENT. ATTACH SLIDING GLASS DOOR FRAME TO STRUCTURAL WOOD 4. ALLOW 6 HOURS TO CURE THEN APPLY SIKA EVERFLASH 102 TO TOP AND OUTSIDE VERTICAL FACE OF GROUT BED IN ACCORDANCE WIHT
EXISTING REINFORCED MANUFACTURER GUIDELINES. ENSURE 4% OR LESS MOISTURE CONTENT.
BUCKING USING REQUIRED FASTENERS UNDER GROUP D INTO WOOD SUBSTRATE ONLY (DO NOT
STUCCO RETURN CONCRETE FLOOR SLAB
PENERTRATE CONCRETE SUBSTRATE) PER NOA.
BEAUTY BEAD 1/2" CANT 5. OPTIONAL: ALLOW EVERFLASH 2 HOURS TO CURE THEN SET ALUMINUM PAN INTO EVERFLASH 102 IN FULL BED OF EVERFLASH 102 O SIKA 2C
BEAD SIKA 2C NS KILN DRIED PRESSURE TREATED BLOCKING ADHERE TO SIKA 4. BUCKING TO BE KILN DRIED PRESSURE TREATED #2 SOUTHERN YELLOW PINE 4% OR LESS MOISTURE NS. ALUMINUM PAN TO BE 0.060" THICKNESS AND FACTORY COLOR MATCHED TO SLIDING GLASS DOOR FRAME. PAN TO HAVE END DAMS 1/4"
EVERFLASH 102 ON CEILING IN 3 RIBBONS OF SIKA 2C NS. CONTENT REQUIRED. VERTICAL AND
HIGH AT OVERHEAD
COLUMN SIDESWATERPROOFING GENERAL
AND INTERIOR SIDE, PROCEDURE
CORNERS (REINFORCED
TO BE WELDED. CONCRETE
PAN TO HAVE SUBSTRATE):
3/16" DRIP EDGE AT OUTSIDE
APPLY SIKA EVERFLASH 102 OR SIKA 2C NS TO OUTSIDE FACE
BRAKE METAL STUCCO AND FACE FACING SLIDING GLASS DOOR LEAVE SIDE FACING 5. MAXIMUM SHIM SPACING OF 1/4" PER NOA. 1. REMOVE
6. ALLOW AND DISPOSE
EVERFLASH EXISTING
2 HOURS SLIDING
TO CURE GLASS
THEN SETDOOR,
FRAMEFRAME, AND(OR
ONTO PAN BUCKING. REPAIR
DIRECTLY CONCRETE IF NECESSARY
TO WATERPROOFED CURB) IN FULL BED OF EVERFLASH
STOP ADHERED TO INTERIIOR EXPOSED 102 OR SIKA 2C NS.
BUCK AND SGD FRAME 6. ALL FASTENER HOLES TO BE VACUUMED CLEAN AND INJECTED WITH APPROVED SEALANT. AFTER 2. REMOVE ALL DUST AND DEBRIS FROM SUBSTRATE. CUT BACK STUCCO AT JAMBS AND HEADER MINIMAL AMOUNT TO ACCOUNT FOR NEW
FASTENERS ARE DRIVEN INTO HOLES, SIKA 2C NS SEALANT TO BE APPLIED TO HEADS OF SIL 7. FRAME
INSTALLWIDTH AND INSTALLATION
FASTENERS OF PRIMARY SEALANT.
PER NOA REQUIREMENTS. CONFIRM
EMBEDMENT DOES LOCATION
NOT TAKE WITH SLIDING GLASS
INTO ACCOUNT GROUTDOOR
BED INSTALLER.
THICKNESS ONLY DEPTH INTO
FASTENERS. APPROVED SEALANT AT ALL OTEHR FASTENERS. STRUCTURAL SLAB BENEATH GROUT BED.
3. VERIFY SUBSTRATE IS 4% OR LESS MOISTURE CONTENT. APPLY SIKA EVERFLASH 102 TO COLUMNS AND CEILING CONSTRAINING INTERIOR TO
INSIDE LOCATIN OF BUCK PLACEMENT.

4. ALLOW EVERFLASH 2 HOURS TO CURE. APPLY 3 RIBBONS OF SIKA 2C NS COMPLETELY TO FACE OF BUCK ATTACHING TO SUBSTRATE. BUCK TO
BE SET FLUSH WITH OUTSIDE FACE OF SLIDING GALSS DOOR FRAME. INSTALL PRIMARY SEALANT. BUCK MAY NEED TO BE RIPPED DOWN IN

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


WIDTH TO MATCH FRAME WIDTH. SEE BUCK REQUIREMENTS AND INSTALLATION UNDER GENERAL NOTES 2-4 OF SKS-01.

5. APPLY SIKA EVERFLASH OR SIKA 2C NS COMPLETELY TO OUTSIDE FACE AND SIDE FACING SLIDING GLASS DOOR FRAME. IF CAVITY EXISTS
BETWEEN BOTTOM OF BUCK AND SILL PAN, INJECT EVERFLASH INTO CAVITY FULLY. ALLOW EVERFLASH TO CURE 2 HOURS.

6. INSTALL SLIDING GLASS DOOR FRAME PER MANUFACTURER'S GUIDELINES. FOLLOW GENERAL NOTE 6 REGARDING FASTENER INSTALLATIONS.

PHASE IIC: OVERALL BUILDING


INTERIOR 7. ATTACH BREAK METAL STUCCO STOPS AT JAMBS AND HEADER TO EXISTING SLIDING GLASS DOOR FRAME. ALL BREAK METAL STUCCO STOPS
TO HAVE FACTORY APPLIED FINISH TO MATCH DOOR FRAME.

REPAIR AND RESTORATION


INTERIOR

REPAIR & RESTORATION


8. REPLACE REMOVED STUCCO.

9. APPLY BEAUTY BEAD BETWEEN STUCCO AND STUCCO STOP.

SIKA 2C NS BEAD AT 3/8"


CHAMFERED EDGE PGT TRACK SET IN FULL BED OF
SIKA 102 EVERFLASH OF SIKA 2C NS
SIKA 2C NS 1/2" OPTIONAL: ALUMINUM PAN SET IN FULL BED BRAKE METAL STUCCO STOP ADHERED WITH
CANT BEAD OF SIKA 102 EVERFLASH OR SIKA 2C NS SEALANT TO BUCK AND SGD FRAME
SIKA SIKALASTIC 735AL
TRAFFIC COATING SIKA 102 EVERFALSH FULL
ADHERED TO CURB
KILN DRIED PRESSURE TREATED BLOCKING ADHERE TO SIKA
PRIMARY SEALANT 1/2" EVERFLASH 102 ON COLUMN IN 3 RIBBONS OF SIKA 2C NS APPLY SIKA
ROUGHEN SURFACE SIKA QUICK 1000 CANT BEAD SIKA 2C NS
(3/4" MINIMUM) EVERFLASH 102 OR SIKA 2C NS TO OUTSIDE FACE AND FACE FACING
TO ICRI CSP-7 SLIDING GLASS DOOR LAEAVVE SIDE FACING INTERIOR EXPOSED

BEAUTY BEAD 1/2" CANT


BEAD SIKA 2C NS

STUCCO RETURN

EXISTING REINFORCED
CONCRETE FLOOR SLAB
DOOR SILL, HEAD & JAMB WATERPROOFING
1 1/4" = 1'-0"
SEAL License: 89035
Expires: 02/28/23

INTERIOR

This item has been digitally signed and sealed by Robert J. Miller on the
date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.
SIKA 2C NS BEAD AT 3/8"
CHAMFERED EDGE PGT TRACK SET IN FULL BED OF
SIKA 102 EVERFLASH OF SIKA 2C NS 2" 10" 10" 10" 10"
OPTIONAL: ALUMINUM PAN SET IN FULL BED
8" 3'-4" 3'-4" 3'-4" 3'-4"

OF SIKA 102 EVERFLASH OR SIKA 2C NS


SIKA 2C NS 1/2" SIKA 102 EVERFALSH FULL
CANT BEAD ADHERED TO CURB
SIKA SIKALASTIC 735AL Structural Engineers | Remediation & Parking Consultants
TRAFFIC COATING
2"

206 Via Condado Way | Palm Beach Gardens, FL 33418-1701


8"

561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.
SIKA QUICK 1000
EXTENDED WITH
PEAGRAVEL
No. Date Revisions
EXISTING REINFORCED
CONCRETE FLOOR SLAB
2" 8"

ROUGHEN SURFACE
TO ICRI CSP-7

3/8" x 4" HILTI HUS (3-1/4" MINIMUM EMBED)


BUCK FASTENING SCHEDULE
STAGGERED 12" LOCATE TO AVOID SLIDING GLASS
DOOR TRACK FASTENERS TO BE PLACED MAINTAIN
2 3/4" = 1'-0"
1-1/2" CLEAR COVER

REINFORCED DOOR CURB


3 1/4" = 1'-0"

DESIGNED DRAWN
HR/JB/RM HR/JB/RM
CHECKED APPROVED
RM FPM
Project No.: 18217

Date: 04/26/21

Scale: As indicated
Sheet Title:
BALCONY DOOR
WATERPROOFING

Sheet No.:

S2C-3.3
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


THESE DETAILS ARE CONCEPTUAL ONLY. IT IS THE SOLE

8777 COLLINS AVENUE


RESPONSIBILITY OF THE DELEGATED SHORING ENGINEER TO VERIFY EXISTING
STRUCTURE VARIES
CAPACITIES OF BEAMS, SLABS, ETC IN ORDER TO DETERMINE
SHORING SYSTEM TYPE / CONFIGURATION AND SPACING.
ALUMINUM OR CARBON BOLT/SCREW BEAMS TO EXISTING
STEEL BEAMS PER SHORING STRUCTURE IF REQUIRED BY
ENGINEER DESIGN SHORING ENGINEER

FILL ALL HOLES WITH ASTM


A307 BOLTS WITH SAME
DIAMETER AS SHORING
PLATE HOLES
• FOR SHORING INFORMATION
SEE SPEC SECTION 314100 AND
TYPICAL REPAIR NOTES ON

EXISTING FILL ALL HOLES WITH CONCRETE


STRUCTURE VARIES SCREWS WITH MINIMUM 1-1/2"
EMBEDMENT, SAME DIAMETER
AS SHORING PLATE HOLES (TYP

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


TOP & BOTTOM)
• UNLESS OTHERWISE AGREED UPON,

VERIFY IN FIELD
THE SHORING ENGINEER SHALL BE
RESPONSIBLE FOR THE INSPECTION
OF SHORING INSTALLATION.
• FOR SHORING INFORMATION

PHASE IIC: OVERALL BUILDING


SEE SPEC SECTION 314100 AND
TYPICAL REPAIR NOTES ON

REPAIR AND RESTORATION


VERIFY IN FIELD
ADJUSTABLE SHORING POSTS

REPAIR & RESTORATION


BY DOKA OR EQUAL SPECIFIED
BY SHORING ENGINEER • UNLESS OTHERWISE AGREED UPON, THE
SHORING ENGINEER SHALL BE RESPONSIBLE FOR
THE INSPECTION OF SHORING INSTALLATION.

SHORING TOWER BY DOKA OR


EQUAL SPECIFIED BY SHORING
ENGINEER

FILL ALL HOLES WITH LAG HEAVY DUTY CRANE CRIBBING MAT
SCREWS WITH MINIMUM 3"" OR OTHER LOAD DISTRIBUTION
EMBEDMENT, SAME DIAMETER AS STRUCTURE WHERE REQUIRED BY
BASE CONDITIONS VARY.
SHORING PLATE HOLES SHORING ENGINEER DESIGN
DESIGN SUPPORT AS
REQUIRED.
THRU-BOLTING WITH
BEARING PLATES
EACH END

• IT IS THE RESPONSIBILITY OF THE SHORING


ENGINEER TO EVALUATE THE BEARING CAPACITY
FOR SHORING AND SPECIFY CRIBBING OR OTHER
MEANS TO PROVIDE ADAQUATE BEARING
• IT IS THE RESPONSIBILITY OF THE SHORING
ENGINEER TO EVALUATE THE BEARING CAPACITY
FOR SHORING AND SPECIFY CRIBBING OR OTHER
MEANS TO PROVIDE ADAQUATE BEARING
SEAL License: 89035

SHORING REQUIREMENTS FOR CONCRETE REPAIRS Expires: 02/28/23

1 3/4" = 1'-0"

This item has been digitally signed and sealed by Robert J. Miller on the
date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

DESIGNED DRAWN
HR/JB/RM HR/JB/RM
CHECKED APPROVED
RM FPM
Project No.: 18217

Date: 04/26/21

Scale: 3/4" = 1'-0"


Sheet Title:
SHORING DETAILS

Sheet No.:

S2C-3.4
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
FLORIDA PRODUCT APPROVAL FL16355.4-R3 REFERENCE DOOR DRAWINGS:

CECO DOOR PRODUCTS


GLAZED SINGLE COMMERCIAL STEEL DOORS
DRAWING 20-34881 SHEETS 1-16
DATED 12/21/2020

SINGLE DOOR SERIES TRIO ASSEMBLY 1 WITH LIGHT QUANTITY


SCHEDULE
Level Doors per Level Total Doors at Level(s)
Garage 0 0
1 (Lobby) 1 1
2-8 2 14
9-11 2 6
12 2 2

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


Low Roof & PH 5 5
High Roof 0 0

PHASE IIC: OVERALL BUILDING


GENERAL NOTES:

REPAIR AND RESTORATION


1. CONTRACTOR TO FIELD VERIFY EXISTING MASONRY OPENING SIZES AT EACH DOOR OPENING.

REPAIR & RESTORATION


2. CONTRACTOR SHALL REPLACE EXTERIOR FIRE DOORS NOTED ON THESE PLANS WITH SERIES TRI SINGLE DOOR WITH
LIGHT BY CECO DOOR PRODUCTS A DIVISION OF ASSA ABLOY DOOR GROUP, INC. SEE CECO DOOR PRODUCTS DRAWING
No. 20-34881, SHEETS 1-16 DATED 12/21/2020 FOR ADDITIONAL INFORMATION AND REQUIREMENTS. SEE PLANS FOR DOOR
LOCATIONS.
3. WIND CALCULATIONS ON THIS SHEET.
4. ALL METAL TO MASONRY/CONCRETE/STUCCO SURFACES SHALL BE SEALED WITH AN APPROVED URETHANE SEALANT.
5. SEE DETAIL ON THIS SHEET FOR REQUIRED REINFORCEMENT OF EXISTING DOOR MASONRY JAMBS AND HEADS.
6. ALL NEW FIRE-RATED DOORS SHALL BE 90 MINUTE LABEL DOORS AND BE FIBERGLASS BAT FILLED.
7. ALL NEW FIRE-RATED DOORS SHALL CONTAIN STAINLESS STEEL HINGES, AND DOOR CLOSURES TO ASSURE THAT ALL
DOORS ARE SELF-CLOSING AND SELF-LATCHING. ALL EXISTING DOOR LEAVERS SHALL BE REPLACED IN-KIND WITH NEW.
8. THE CONTRACTOR SHALL COMPLETE THIS WORK IN SUCH A WAY TO ASSURE THAT THE PRESENT LEVEL OF LIFE-SAFETY
INCLUDING THE MEANS OF EGRESS WILL REMAIN ACCESSIBLE AT ALL LEVELS. THE REMOVAL AND INSTALLATION OF A
FIRE DOOR MUST TAKE PLACE ON THE SAME DAY, AND WORK SHALL BE IN ONLY ONE STAIR TOWER AT A TIME. ONE STAIR
TOWER SHALL BE COMPLETELY ACCESSIBLE IN CASE OF AN EMERGENCY.
9. ALL NEW FIRE-RATED DOORS SHALL BE SECURED TO BLOCK WALL JAMBS AND CONCRETE FLOOR SLABS WITH 3/8"
DIAMETER HILTI KWIK BOLT 3 EXPANSION ANCHOR WITH 1 1/2" MINIMUM EMBEDMENT AND 4" MINIMUM EDGE DISTANCE.
MINIMUM EMBEDMENT AND EDGE DISTANCE EXCLUDES STUCCO, FOAM, BLOCK AND OTHER WALL FINISHES. KWIK BOLTS
AT JAMBS SHAL BE 6" MAXIMUM AT EVERY CORNER AND SPACED A MAXIMUM OF 21" o/c. MINIMUM ANCHOR QUANTITY PER
NOA. SEE CECO DOOR PRODUCTS DRAWINGS FOR ADDITIONAL REQUIREMENTS.
10. USE 1/4" TAPCONS AT SILLS. TAPCONS SHALL BE 6" MINIMUM AT EVERY CORNER AND SPACED AT 12" o/c. TAPCONS AT
JAMBS SHALL BE 6" MINIMUM AT EVERY CORNER AND SPACED AT 21" o/c. SEE CECO DOOR PRODUCTS DRAWINGS FOR
ADDITIONAL REQUIREMENTS.
11. ALL DOORS SLABS AND FRAMES (INTERIOR, EXTERIOR, AND INSIDE) SHALL BE FINISHED USING PPG PAINTS (OR
APPROVED EQUAL) INSTALLED PER THE FOLLOWING PROCEDURE:
11.1. PRETREATMENT: WASH WITH DEGREASER
11.2. PRETREATMENT: SAND TO CREATE PROFILE
11.3. PRETREATMENT: SOLVENT WIPE WITH DENATURED ALCOHOL
11.4. PRIMER COAT: PROVIDE ONE (1) FULL COAT OF 90-912 PITT TECH PLUS DTM INDUSTRIAL PRIMER
11.5. FINISH COAT: PROVIDE ONE (1) FULL COAT OF BREAK-THROUGH 250 SATIN WATER-BOURNE ACRYLIC (V50 SERIES)

DOOR CALCULATION NOTES:

1. THIS PRESSURES SHOWN IN THE TABLE ABOVE ARE LRFD LOADS FROM ASCE 7-16 FOR COMPONENTS AND CLADDING BASED SEAL License: 89035
Expires: 02/28/23
ON VARIOUS EFFECTIVE AREAS. THEREFORE, THE LOADS FROM THE TABLE ABOVE MUST MULTIPLIED BY A FACTOR OF 0.6
TO CORRELATE TO THE ASD DESIGN PRESSURE RATING NOTED ON DAYBAR INDUSTRIES LTD DRAWING No 20-156 SHEET 3.

2. THE DOOR IN QUESTION APPROXIMATELY 6'-8" BY 3'-4" FOR A TOTAL SQUARE FOOTAGE OF 25 SQUARE FEET. BASED ON
TABLE 30.6-1 IN ASCE 7-10, THE AMOUNT OF C&C LOADING DECREASES AS A FUNCTION OF AREA UNDER CONSIDERATION
AND THIS TABLE RETURNS A VALUE CALLED 'EXTERNAL PRESSURE COEFFICIENT, GCp' WHICH IS USED IN EQUATION 30.5-1
TO DETERMINE THE NET WIND PRESSURE. THIS TABLE ALLOWS FOR INTERPOLATION ALONG THE PROPER LINE AND THE
CONTROLLING LINE IN THIS CASE CORRESPONDS TO DESIGN ZONE 4. USING TABLE 30.5-1:
THE EXTERNAL PRESSURE COEFFICIENT ALONG LINE 4 AT 25 SQFT IS 0.88

3. USING THE PEAK VELOCITY PRESSURE CALCULATED ABOVE (99.8 PSF) AND THE NET PRESSURE EQUATION (ASCE 7-16
EQUATION 30.5-1) THE NET PRESSURE CAN BE FORMULATED TO BE:
NET PRESSURE = PEAK * (GCp + GCpi) * (ASD FACTOR)
This item has been digitally signed and sealed by Robert J. Miller on the
OR, IN NUMBERS date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
q_net = 99.8 * (0.88 + 0.18) * 0.6 = 63.5 PSF any electronic copies.

4. AS SHOWN NOTED ON CECO DOOR PRODUCTS DRAWING No 20-34881 SHEET 2, THE MAXIMUM ASD ALLOWABLE LOAD ON
VERIFY

THE DOOR IS 70 PSF. SINCE THE NET PRESSURE CALCULATED IN NOTE 3 IS 70 PSF, THIS DOOR WORKS IN THIS APPLICATION.

• VERIFY EXISTING DOOR


HEAD TO CONTAIN
BOND BEAM
Structural Engineers | Remediation & Parking Consultants
• DOOR JAMBS SHALL 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
CONTAIN 16" X 8" © Copyright Morabito Consultants, Inc.
CONCRETE FILLED
BLOCK AS SHOWN

• CONTRACTOR SHALL EXAMINE No. Date Revisions


EXISTING DOOR JAMBS TO
VERIFY EXISTENCE OF EXISTING
CONCRETE FILLED BLOCKS. IF NO
CONCRETE FILLED BLOCKS EXISTS,
CONTRACTOR SHALL CUT
EXISTING BLOCK AND ADD NEW
CONCRETE FILL (Fc' = 3000 PSI)

CONDITION 1 - WALL
PERPENDICULAR TO
DOOR

CONDITION 2 CONDITION 2 CONDITION 1 DESIGNED DRAWN


CONDITION 2 - WALL HR/JB/RM HR/JB/RM
PARALLEL TO
CHECKED APPROVED
DOOR
RM FPM
Project No.: 18217

(x 16") (x 8") Date: 04/26/21

Scale: As indicated
Sheet Title:
FIRE DOOR
FIRE DOOR JAMB REINFORCEMENT ELEVATION VIEW REPLACEMENT DETAILS
FD NOT TO SCALE
CONDITION 1

FIRE DOOR JAMB REINFORCEMENT PLAN VIEW


3 1/2" = 1'-0" Sheet No.:

S2C-3.5
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS
LIGHT FIXTURES TO BE REPLACED AFTER WALL NEW
WALL CAP RE-CONSTRUCTION WORK IS COMPLETE

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
PROVIDE SLOPE TO DRAIN

2" 4" 2"


REMOVE EX. FRAMED WALL CAP, PERFORM NECESSARY CONC. NEW CONC. CAP TO INCLUDE
DEMO, AND CAST A NEW CONC. CAP REINFORCED w/ 2-#4 BARS CL CL INTERMEDIATE COLUMNS IN WALL
CONT. & #3 DOWELS w/ 3" EMBEDMENT STAGGARD @ 2'-0" O.C. - CONSTRUCTION.
TYP. WORK SHALL INCLUDE NEW STUCCO INSTALLATION,
PROVIDE SLOPE TO DRAIN, NEW CAP CONSTRUCTION TO

2" 2"

1 5/8"
INCLUDE INTERMEDIATE COLUMN LOCATIONS CL

4"

COVER - TYP.
1 1/2" CONC.
2"

3"
SAW-CUT AND REMOVE EX.
STUCCO AS REQUIRED TO
PERFORM THE WORK

EX. COLUMN(S) BEYOND

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
EX. SOUTH PERIMETER WALL

SAW-CUT, REMOVE AND REPLACE


EX. STUCCO AS REQUIRED TO
PERFORM THE WORK.

STUCCO SCREED
MIN. 4"

EX. SLAB SEAL License: 89035


Expires: 02/28/23
EX. EDGE BEAM

This item has been digitally signed and sealed by Robert J. Miller on the
date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.

EX. GARAGE WALL

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701

SOUTH PERIMETER WALL REPAIR 561.316.7660 | www.morabitoconsultants.com


© Copyright Morabito Consultants, Inc.
1 1 1/2" = 1'-0"
No. Date Revisions

DESIGNED DRAWN
HR/JB/RM HR/JB/RM
CHECKED APPROVED
RM FPM
Project No.: 18217

Date: 04/26/21

Scale: 1 1/2" = 1'-0"


Sheet Title:
SOUTH WALL REPAIR

Sheet No.:

S2C-3.6
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
R

SIKALASTIC TRAFFIC SYSTEM R

BASE COAT AND TOP COAT(S) SIKALASTIC TRAFFIC SYSTEM GRIND EDGE
R
R
SIKAFLEX SEALANT BASE COAT AND TOP COAT(S)
SIKALASTIC TRAFFIC SYSTEM R

BASE COAT AND TOP COAT(S) 4" 4" 4" TERMINATE SIKALASTIC TRAFFIC
R

SIKALASTIC DETAIL COAT SYSTEM AT DRAIN BASE COAT


R
TOP COAT(S) KEYED IN JOINT
SIKAFLEX SEALANT R

TOP COAT(S) (CRACK ROUTED TO 1/ " X 1/2") R SIKALASTIC TRAFFIC SYSTEM R

2 SIKALASTIC DETAIL COAT SIKAFLEX SEALANT AT BASE COAT


BASE COAT PERIMETER OF DRAIN
4" DETAIL COAT UNCOATED AREAS

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


REINFORCED
CONCRETE
REINFORCED METAL DRAIN
REINFORCED CONTROL JOINT BACKER ROD OR CONCRETE
REINFORCED
CONCRETE LESS THAN 1" BOND BEAKER TAPE SAWCUT 1/4" x 1/4" MIN.
BOND BREAKER CRACK OVER 1/ " CRACK LESS THAN 1/ " CONCRETE
16 16
(IF MOVEMENT NOTE:
IS ANTICIPATED) PROVIDE 4" DETAIL COAT AT DRAIN PERIMETER.

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
DETAIL TITLE DETAIL TITLE DETAIL TITLE DETAIL TITLE
CONTROL
CRACK DETAIL DRAIN DETAIL TERMINATION DETAIL
JOINT DETAIL
® ® ® ®
1-800-933-SIKA (7452) SCALE: DATE: DRW. NO.: 1-800-933-SIKA (7452) SCALE: DATE: DRW. NO.: 1-800-933-SIKA (7452) SCALE: DATE: DRW. NO.: 1-800-933-SIKA (7452) SCALE: DATE: DRW. NO.:
WWW.SIKAUSA.COM N.T.S. 9/13 TR-1 WWW.SIKAUSA.COM N.T.S. 9/13 TR-2 WWW.SIKAUSA.COM N.T.S. 9/13 TR-3 WWW.SIKAUSA.COM N.T.S. 9/13 TR-12
TILE
PAVERS THIN SET MORTAR

TOP COAT(S)
BASE COAT
NOTE: NOTE:
4" DETAIL COAT • CARE SHOULD BE TAKEN TO AVOID APPLYING THE • CARE SHOULD BE TAKEN TO AVOID APPLYING THE
PRIMER ONTO THE SEALANT. PRIMER ONTO THE SEALANT.
R

COVE SIKAFLEX
LIMITS OF SURFACE • PROVIDE 4" VERTICAL TERMINATION OF • TYPICAL VERTICAL TERMINATION OF
SEALANT 1_2"x1_2" TYP. PREPARATION WATERPROOFING AS DIRECTED BY ENGINEER, OR WATERPROOFING.
R
AS REQUIRED.
SIKALASTIC TRAFFIC
SYSTEM

1" - TYP.

4" - TYP.
EX. VERT. SURFACE, EX. STUCCO WALL
AS REQUIRED SURFACE - TYP. R

REINFORCED SIKALASTIC SYSTEM PER NOTES


LIMITS OF SURFACE CONCRETE
PREP. 1" - TYP. NOTES:
1. APPLY ONE COAT OF SIKAFLOOR FTP PRIMER AT 5 MILS (300 SQ. FT/GAL).

4" - TYP. 2. WATERPROOFING OPTIONS


LIMITS OF SURFACE A. APPLY ONE COAT OF SIKALASTIC 710 BASE COAT AT 32 MILS (50 SQ.FT/GAL) OR
PREP. 1" - TYP. B. APPLY ONE COAT OF SIKALASTIC 720 BASE COAT AT 23 MILS (73 SQ.FT/GAL)
1/2" - TYP.
3. TOP COAT OPTIONS
R R
CANT BEAD WITH SIKAFLEX CANT BEAD WITH SIKAFLEX A. APPLY ONE COAT OF SIKALASTIC 715 POLYURETHANE TOP COAT AT 14-16 MILS, (100-115 SQ.FT/GAL, SECOND COAT OPTIONAL) OR,
SEALANT (1/2"-1/2" DEEP) SEALANT (1/2"-1/2" DEEP) B. APPLY ONE COAT OF SIKALASTIC 745 POLYURETHANE TOP COAT AT 12-18 MILS, (90-133SQ.FT/GAL, SECOND COAT OPTIONAL) OR,
C. APPLY ONE COAT OF SIKALASTIC 710 POLYURETHANE TOP COAT AT 16 MILS, (100 SQ.FT/GAL, SECOND COAT OPTIONAL) OR, SEAL License: 89035
POURED IN D. APPLY ONE COAT OF SIKALASTIC 720 POLYURETHANE TOP COAT AT 12 MILS, (133SQ.FT/GAL, SECOND COAT OPTIONAL) Expires: 02/28/23
PLACE SLEEVE POST EMBEDDED
IN CONCRETE PRIMER PRIMER 4. BROADCAST OPTIONS
A. FOR A TOPCOAT FOLLOWED BY THE OPTIONAL SECOND TOPCOAT, BROADCAST 20/40 GRIT SAND INTO THE WET TOPCOAT UNTIL REFUSAL. AFTER
DETAIL COAT DETAIL COAT
NOTE: CURE, REMOVE EXCESS AGGREGATE BEFORE PROCEEDING WITH THE OPTIONAL SECOND TOP COAT.
PROVIDE 4" DETAIL COAT AT COVE SEALANT. BASE COAT BASE COAT B. FOR A TOPCOAT FOLLOWED BY THE THIN SET, BROADCAST 16/20 MESH, CRACK ANGULAR SAND INTO THE WET TOPCOAT UNTIL REFUSAL. AFTER
CURE, REMOVE EXCESS AGGREGATE BEFORE PROCEEDING WITH THE THIN SET.
CONCRETE SLAB TOP COAT(S) CONCRETE SLAB TOP COAT(S)
5. APPLY THIN SET MORTAR AND INSTALL TILE. MC ADVISES THE USE OF MAPEI CORP. OR LATICRETE INT., INC. PRE-BLENDED POLYMER
MODIFIED SETTING MATERIALS (MORTAR, GROUT, ETC.) FOR ALL TILE INSTALLATION. PERFORM WORK IN ACCORDANCE WITH MIAMI-DADE
COUNTY PRODUCT APPROVAL, NOTICE OF ACCEPTANCE (NOA) No. 16-0203.02 (EXP. DATE: 11/17/21).

DETAIL TITLE DETAIL TITLE DETAIL TITLE DETAIL TITLE


VERTICAL VERT. WALL/SLAB THIN SET
PROJECTION DETAIL SURFACE/SLAB JOINT DETAIL TILE DETAIL This item has been digitally signed and sealed by Robert J. Miller on the
® ® ® ® date adjacent to the seal. Printed copies of this document are not
1-800-933-SIKA (7452) SCALE: DATE: DRW. NO.: 1-800-933-SIKA (7452) SCALE: DATE: JOINT DETAIL DRW. NO.: 1-800-933-SIKA (7452) SCALE: DATE: DRW. NO.: 1-800-933-SIKA (7452) SCALE: DATE: DRW. NO.: considered signed and sealed and the signature must be verified on
WWW.SIKAUSA.COM N.T.S. 9/13 TR-7 WWW.SIKAUSA.COM N.T.S. 3/9/20 TR-8.1 WWW.SIKAUSA.COM N.T.S. 3/9/20 TR-8.2 WWW.SIKAUSA.COM N.T.S. 9/13 TR-11 any electronic copies.

BALCONY WATERPROOFING GENERAL SEQUENCE

1. AT TOP SIDE AND OUTSIDE VERTICAL FACE OF BALCONY DECKS, PROPERLY PREPARE Structural Engineers | Remediation & Parking Consultants
206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
CONCRETE SUBSTRATE FOR APPLICATION OF NEW WATERPROOFING MEMBRANES, 561.316.7660 | www.morabitoconsultants.com
GRIND OFF ANY EXISTING SURFACES AND SHOT BLAST/WATER BLAST TO ACHEIVE © Copyright Morabito Consultants, Inc.
CONCRETE SURFACE PROFILE AS REQUIRED BY THE NEW COATING MANUFACTURER.
2. FLOOD RESIDENTIAL BALCONY DECKS AND OUTLINE AREAS OF PONDING.
3. ALLOW DECKS TO DRY.
4. PRIME LOW SPOTS WITH SIKADUR 21 No. Date Revisions
5. WHILE SIKADUR 21 IS WET AND TACKY, FILL LOW SPOTS WITH A 4.5 TO 1 MIXTURE OF
UNIMIN 20/40 SAND TO SIKADUR 22 LO-MOD EPOXY
6. APPLY SIKALASTIC 710/715 MEMBRANE TO TOP SIDE OF DECK IN ACCORDANCE WITH
MIAMI DADE NOA 16-0203.02 SYSTEM TYPE A(1) FOR WATERPROOFING AS THE FINISH
OR SYSTEM TYPE A(4) FOR TILE AS THE FINISH
A. WHERE APPLYING MEMBRANE OVER ORIGINAL CONCRETE USE SIKA FTP PRIMER
B. WHERE APPLYING MEMBRANE OVER SIKADUR 22 LO-MOD/SAND MIXTURE, SAND
AND XYLENE WIPE BEFORE APPLICATION OF MEMBRANE
7. WHILE APPLYING SYSTEM TO TOP SIDE OF DECK, CARRY SYSTEM TO OUTSIDE
VERTICAL FACE OF CONCRETE DECK, SAND TOP COAT TO REFUSAL, AND PAINT TO
MATCH FACADE

DESIGNED DRAWN
HR/JB/RM HR/JB/RM
CHECKED APPROVED
RM FPM
Project No.: 18217

Date: 04/26/21

Scale: 3/4" = 1'-0"


Sheet Title:
TRAFFIC BEARING
WATERPROOFING
MEMBRANE & FINISH
Sheet No.:

TBM-1
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
RUBBER OR URETHANE
ROD STOCK (BY OTHERS)
CCW-201 SEALANT
METAL CAP (BY OTHERS)
CCW-201 SEALANT OR
CCW-704 MASTIC
METAL COUNTER FLASHING
(BY OTHERS)
CCW-500 @ 125 mils
CCW-500 @ 125 mils CCW-500 @ 125 mils

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


CCW-711-90 mil OR
CCW-711-90 mil OR CCW-711-90 mil OR
CCW UNCURED NEOPRENE
FLASHING CCW UNCURED NEOPRENE CCW UNCURED NEOPRENE
FLASHING FLASHING
CCW-500 @ 90 mils
CCW-500 @ 90 mils

PHASE IIC: OVERALL BUILDING


CCW-500 @ 90 mils
CCW-550 PRIMER OR

REPAIR AND RESTORATION


CCW-CONTACT ADHESIVE CCW-550 PRIMER OR CCW-550 PRIMER OR
CCW-CONTACT ADHESIVE CCW-CONTACT ADHESIVE

REPAIR & RESTORATION


CCW-PROTECTION CCW-PROTECTION
BOARD H OR HS BOARD H OR HS NOTES:
CCW-PROTECTION
NOTES: 1. FASTEN METAL COUNTER
BOARD H OR HS
1. DIAMETER OF ROD STOCK MUST FLASHING TO SUBSTRATE 12
EXCEED WIDTH OF REGLET GAP. INCHES ON CENTER.
2. FASTEN MEMBRANE TO SUBSTRATE 12 2. IF FASTENER PENETRATES
INCHES ON CENTER. METAL COUNTER FLASHING,
3. IF FLASHING MEMBRANE EXTENDS USE NEOPRENE WASHER.
ABOVE FINAL GRADE, COUNTER APPLY WATER CUT-OFF MASTIC
FLASHING MUST BE PROVIDED. OR CAULK FASTENER HEAD.
DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR
WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY.

VERTICAL TERMINATION VERTICAL TERMINATION VERTICAL TERMINATION


500-9A R
500-9B R

500-9C R

REGLET FLASHING COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION CAP FLASHING COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION COUNTERFLASHING COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION

CCW-201 SEALANT
OR 704 MASTIC

1"
CCW SURE-SEAL
TERMINATION BAR

NAIL-IN OR RAMSET ANCHOR


CCW-500 @ 125 mils

CCW-500 @ 125 mils CCW-711-90 mil OR SEAL License: 89035


CCW UNCURED NEOPRENE Expires: 02/28/23
CCW-711-90 mil OR FLASHING
CCW UNCURED NEOPRENE
CCW-500 @ 90 mils
FLASHING

CCW-550 PRIMER OR
CCW-500 @ 90 mils CCW-CONTACT ADHESIVE

CCW-550 PRIMER OR CCW-PROTECTION


CCW-CONTACT ADHESIVE BOARD H OR HS
NOTES:
CCW-PROTECTION 1. APPLY ON HARD SMOOTH
BOARD H OR HS SURFACE ONLY; NOT FOR NOTES:
This item has been digitally signed and sealed by Robert J. Miller on the
USE ON WOOD. 1. IF CCW-711-90 FLASHING OR date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
2. FLASHING MUST BE HELD CCW UNCURED NEOPRENE any electronic copies.
UNDER CONSTANT FLASHING EXTENDS ABOVE
COMPRESSION. FINAL GRADE, METAL
COUNTER FLASHING MUST
BE USED.
DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR
WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY.

VERTICAL TERMINATION VERTICAL TERMINATION


500-9D R
500-9E R
Structural Engineers | Remediation & Parking Consultants
206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
MECHANICAL COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION EMBEDDED TERMINATION COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION


561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

NOTE: IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ENGAGE THE MANUFACTURER TO


VERIFY THE SUITABILITY OF ALL DETAILS TO BE USED ON THE JOB. THE CONTRACTOR SHALL SUBMIT ALL No. Date Revisions
ADDITIONAL DETAILS THAT THE MANUFACTURER REQUIRES TO COMPLETE THE WORK.

DESIGNED DRAWN
HR/JB/RM HR/JB/RM
CHECKED APPROVED
RM FPM
Project No.: 18217

Date: 04/26/21

Scale: 3" = 1'-0"


Sheet Title:
CCW-500 WALL DETAILS

Sheet No.:

WP-1
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
CCW-PRIMER CCW-201 SEALANT
CCW BARRISEAL @ 40 DRY MILS MINIMUM
CCW-705 CCW SURE-SEAL TERMINATION BAR
CCW SURE-SEAL TERMINATION BAR
CCW-201 OR CCW-LM-800XL CANT CONCRETE SUBSTRATE
CCW-500 @ 125 mils SURE-SEAL 115 mil FLEECEBACK EPDM
CCW SURE-SEAL TERMINATION BAR
CCW-711-90 FLASHING 303839 OR SURE-WELD 120 mil
CCW-500 @ 125 mils FLEECEBACK TPO 3037275
CCW-500 @ 90 mils OR UV STABLE CAP SHEET
CCW-711-90 FLASHING SET INTO CCW-500 WHILE HOT
CCW MIRADRAIN
CCW-500 @ 90 mils CCW-500 @ 125 mils
CCW-711-90 FLASHING

8" MIN.
CCW MIRADRAIN
CCW-PROTECTION BOARD-H OR HS

8" MIN.
CCW-PROTECTION BOARD-H OR HS CCW-500 @ 90 mils
CCW-500 @ 125 mils CCW MIRADRAIN
CCW-500 @ 125 mils

8" MIN.
CCW-500 REINFORCING FABRIC

APPROX.
CCW-PROTECTION BOARD H OR HS
CCW-500 REINFORCING FABRIC
CCW-500 @ 90 mils CCW-500 @ 125 mils

1"
CCW-500 @ 90 mils
CCW-500 REINFORCING FABRIC
CCW-550 PRIMER OR
CCW-500 @ 90 mils
CCW-CONTACT ADHESIVE
CCW-550 PRIMER OR CCW-PRIMER OR CCW-CONTACT ADHESIVE
6" CCW-CONTACT ADHESIVE CONCRETE SUBSTRATE

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


6"

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
TERMINATION OF WATERPROOFING ON
DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR
WALL SHALL BE BELOW FINISH COURSE

REPAIR & RESTORATION


WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY.

BARRISEAL AT WALL TO CCW-500R/ CCW-705 EXPOSED CURB &


500-7D R
500-7E R
500-4A R

500R DECK TIE-IN COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION WALL TIE-IN COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION PARAPET FLASHING COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION

EPDM BONDING ADHESIVE


OR OTC COMPLIANT CCW-PROTECTION BOARD-H OR HS
CCW-201 SEALANT 125 MILS OF CCW-500

CCW SURE-SEAL TERMINATION BAR CCW-500 REINFORCING FABRIC

CONCRETE SUBSTRATE 90 MILS OF CCW-500 TERMINATION BAR


MINIMUM 12" OF CCW-711-90 125 MILS OF CCW-500
SURE-SEAL 60 mil STANDARD EPDM FLASHING OR CCW-
SURE-SEAL HP-250 PRIMER UNCURED NEOPRENE FLASHING CCW-500 REINFORCING FABRIC
OR OTC COMPLIANT 90 MILS OF CCW-500 90 MILS OF CCW-500
6" PRESSURE-SENSITIVE SECURTAPE CCW-550 PRIMER OR CCW MIRADRAIN 9000, 9800 OR 9900
CCW-500 @ 125 mils CCW-CONTACT ADHESIVE
CCW-711-90 FLASHING CCW-PROTECTION BOARD-H OR HS
CCW-MIRADRAIN 9000 or 9900
CCW-500 @ 90 mils 125 MILS OF CCW-500
8" MIN.

CCW-703V LIQUISEAL CLEAN CCW-711-90 FLASHING


& PRIME EPDM & TPO
CCW MIRADRAIN 90 MILS OF CCW-500
APPROX.

CCW-PROTECTION BOARD H OR HS CCW-550 PRIMER OR


CCW-500 @ 125 mils CCW-CONTACT ADHESIVE
1"

CCW-500 REINFORCING FABRIC


CCW-500 @ 90 mils
CCW-PRIMER OR CCW-CONTACT ADHESIVE

SEAL License: 89035


Expires: 02/28/23
CONCRETE SUBSTRATE

TERMINATION OF SHEET FLASHING ON


DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR WALL SHALL BE BELOW FINISH COURSE DETAIL IS INTENDED TO BE A GUIDE FOR
WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY.

EXPOSED CURB & NON-EXPOSED FOUNDATION WALL /FOOTING


500-4A.2 R
500-4B R
500-4C R

PARAPET FLASHING COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION CURB & PARAPET COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION TERMINATION COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION


This item has been digitally signed and sealed by Robert J. Miller on the
date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.

CCW-201 SEALANT
METAL COUNTER FLASHING
CCW SURE-SEAL TERMINATION BAR
STOREFRONT NAIL-IN OR RAMSET ANCHOR
METAL COUNTER FLASHING
Structural Engineers | Remediation & Parking Consultants
FLOOR SYSTEM 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
CCW-500 @ 125 mils © Copyright Morabito Consultants, Inc.
CCW-711-90 FLASHING CCW-500 @ 125 mils
CCW-500 @ 90 mils CCW-711-90 FLASHING
8" MIN.

CCW MIRADRAIN 9000, CCW-500 @ 90 mils No. Date Revisions


9800 OR 9900 CCW MIRADRAIN 9000, 9800 OR 9900
CCW-PROTECTION BOARD- CCW-PROTECTION BOARD-H OR HS
H OR HS CCW-500 @ 125 mils
CCW-500 @ 125 mils CCW-500 REINFORCING FABRIC
CCW-500 REINFORCING FABRIC CCW-500 @ 90 mils
CCW-500 @ 90 mils
CCW-550 PRIMER OR
CCW-CONTACT ADHESIVE CCW-550 PRIMER OR
6" MIN. CCW-CONTACT ADHESIVE
CONCRETE SUBSTRATE

TERMINATION OF SHEET FLASHING ON


WALL SHALL BE BELOW FINISH COURSE OR DESIGNED DRAWN
DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR
PROTECT WITH METAL COUNTER FLASHING HR/JB/RM HR/JB/RM
WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY. AS SHOWN
CHECKED APPROVED
RM FPM
500-4D WINDOW FLASHING COATINGS & WATERPROOFING
R
500-4E FLASHING TERMINATION COATINGS & WATERPROOFING
R

Project No.: 18217


c 2012 CARLISLE CORPORATION c 2012 CARLISLE CORPORATION

Date: 04/26/21
NOTE: IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ENGAGE THE MANUFACTURER TO
VERIFY THE SUITABILITY OF ALL DETAILS TO BE USED ON THE JOB. THE CONTRACTOR SHALL SUBMIT ALL Scale: 3" = 1'-0"
ADDITIONAL DETAILS THAT THE MANUFACTURER REQUIRES TO COMPLETE THE WORK. Sheet Title:
CCW-500 SLAB-WALL
DETAILS

Sheet No.:

WP-2
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
CCW MIRADRAIN
CCW MIRADRAIN CCW MIRADRAIN
CCW-PROTECTION BOARD-H OR HS
CCW-PROTECTION BOARD-H OR HS
CCW PROTECTION BOARD-HS CCW-500 AT 125 MILS THICK
CCW-500 AT 125 MILS THICK
125 MILS OF CCW-500 CCW-500 REINFORCING FABRIC
CCW-500 REINFORCING FABRIC
CCW-500 AT 90 MILS THICK
CCW-500 AT 90 MILS THICK CCW-500 REINFORCING FABRIC
CCW-711-90 FLASHING
CCW-711-90 FLASHING 90 MILS OF CCW-500
CCW-500 AT 90 MILS THICK
CCW-500 AT 90 MILS THICK
125 MILS OF CCW-500 CCW-550 PRIMER OR
CCW-550 PRIMER OR
CCW-CONTACT ADHESIVE CCW-711-90 CCW-CONTACT ADHESIVE

CCW-711-90 FLASHING 90 MILS OF CCW-500 CCW-711-90 FLASHING


6" MIN.
CCW-MIRASTOP WATERSTOP 6" MIN. CCW-MIRASTOP WATERSTOP
CCW-550 PRIMER OR
CCW-CONTACT ADHESIVE

CCW MIRASTOP

CCW TERMINATION BAR AND


NAIL-IN OR RAMSET ANCHOR

MIN.
LAP THE CCW-711-90 & THE LAP THE CCW-711-90 & THE

4"
CCW-500 ONTO THE CCW MIRADRI CCW-500 ONTO THE CCW
860/861 A MINIMUM OF 12" BARRICOAT A MINIMUM OF 12"

4" MIN.
LAP CCW-711-90 ONTO CCW MIRACLAY
WATERPROOFING A MINIMUM OF 1'-0"

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


CCW MIRADRI 860/861
CCW-CONTACT ADHESIVE
CCW TERMINATION BAR AND CCW BARRICOAT @ 60 DRY MILS
CCW MIRADRAIN NAIL-IN OR RAMSET ANCHOR
CCW MIRADRAIN

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR

REPAIR & RESTORATION


WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY.

500R - MIRADRI 500R-BARRICOAT


500-7A R
500-7B 500R-MIRACLAY TIE-IN R
500-7C R

860/861 TIE-IN COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION


COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION TIE-IN COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION

SURE-SEAL 90-8-90A BONDING ADHESIVE CCW-CONTACT ADHESIVE


EXISTING COAL TAR WATERPROOFING
SURE-SEAL BUTYL OR EPDM CCW-MIRADRI 860/861
CCW-703V LIQUISEAL
CCW-201 OR SURE-SEAL LAP SEALANT CCW-201 OR SURE-SEAL LAP SEALANT
TERMINATION BAR
TERMINATION BAR TERMINATION BAR
CCW-703V LIQUISEAL AT 60 MILS
CCW-CONTACT ADHESIVE CCW-CONTACT ADHESIVE
GALVINIZED METAL FLASHING
CCW-711-90 FLASHING CCW-711-90 FLASHING
12" WIDE 12" WIDE CCW PROTECTION BOARD-H OR HS
90 MILS OF CCW-500 90 MILS OF CCW-500 125 MILS OF CCW-500
CCW PROTECTION BOARD-H OR HS CCW PROTECTION BOARD-H OR HS
CCW-500 REINFORCING FABRIC
125 MILS OF CCW-500 125 MILS OF CCW-500
90 MILS OF CCW-500
CCW-500 REINFORCING FABRIC CCW-500 REINFORCING FABRIC
CCW-550 PRIMER OR
90 MILS OF CCW-500 90 MILS OF CCW-500 CCW-CONTACT ADHESIVE
CCW-550 PRIMER CCW-550 PRIMER
OR CCW-CONTACT OR CCW-CONTACT
ADHESIVE ADHESIVE

SEAL License: 89035


Expires: 02/28/23

DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR
WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY.

CCW-500R/ BUTYL OR CCW-500R/ DECK TIE-IN CCW-500 / EXISTING


500-7F R

500-7G R
500-7H R

EPDM TIE-IN COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION TO CCW MIRADRI 860/861 COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION COAL TAR TIE-IN COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION


This item has been digitally signed and sealed by Robert J. Miller on the
date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.
CCW MIRADRAIN CCW MIRADRAIN
CCW MIRADRAIN CCW-PROTECTION BOARD-H OR HS
CCW PROTECTION BOARD-H OR HS
CCW PROTECTION BOARD-H OR HS CCW-500 AT 125 MILS THICK
125 MILS OF CCW-500
125 MILS OF CCW-500 CCW-500 REINFORCING FABRIC
CCW-500 REINFORCING FABRIC
CCW-500 REINFORCING FABRIC CCW-500 AT 90 MILS THICK
90 MILS OF CCW-500 CCW-711-90 FLASHING
90 MILS OF CCW-500 Structural Engineers | Remediation & Parking Consultants
125 MILS OF CCW-500 CCW-500 AT 90 MILS THICK 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701

CCW-711-90 125 MILS OF CCW-500 CCW-550 PRIMER OR


561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.
CCW-711-90 CCW-CONTACT ADHESIVE
90 MILS OF CCW-500
6" MIN. 90 MILS OF CCW-500 CCW-711-90 FLASHING
CCW-550 PRIMER OR 6" MIN.

CCW-CONTACT ADHESIVE 6" MIN.


CCW-550 PRIMER OR
CCW-MIRASTOP WATERSTOP No. Date Revisions
CCW-CONTACT ADHESIVE
CCW MIRASTOP WATERSTOP
CCW MIRASTOP WATERSTOP CCW 703-V LIQUISEAL AT 30 MILS
CCW TERMINATION BAR AND
4"

NAIL-IN OR RAMSET ANCHOR CCW SURE-SEAL TERMINATION BAR AND


NAIL-IN OR RAMSET ANCHOR
4"

LAP THE CCW-711-90 & THE

MIN.
LAP CCW-711-90 ONTO EXISTING

4"
WATERPROOFING A MINIMUM OF 1'-0" CCW-500 ONTO THE CCW 703-V
A MINIMUM OF 12"
LAP CCW-711-90 ONTO CCW MIRAPLY
CCW-CONTACT ADHESIVE WATERPROOFING A MINIMUM OF 1'-0"
CCW-CONTACT ADHESIVE CCW MIRASEAL @ 60 mils
CCW TERMINATION BAR AND
NAIL-IN OR RAMSET ANCHOR CCW TERMINATION BAR AND
NAIL-IN OR RAMSET ANCHOR CCW MIRADRAIN
EXISTING WATERPROOFING COMPATIBLE MIRAPLY
WITH CCW-500R

DESIGNED DRAWN
DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR
HR/JB/RM HR/JB/RM
WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY.
CHECKED APPROVED
RM FPM
500R-EXISTING 500R - MIRASEAL
500-7I R
500-7J 500R-MIRAPLY TIE-IN R
500-7K R

Project No.: 18217


WATERPROOF TIE-IN COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION


COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION TIE-IN COATINGS & WATERPROOFING

c 2013 CARLISLE CORPORATION

Date: 04/26/21
NOTE: IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ENGAGE THE MANUFACTURER TO 3" = 1'-0"
Scale:
VERIFY THE SUITABILITY OF ALL DETAILS TO BE USED ON THE JOB. THE CONTRACTOR SHALL SUBMIT ALL
ADDITIONAL DETAILS THAT THE MANUFACTURER REQUIRES TO COMPLETE THE WORK. Sheet Title:
CCW-500 TIE-IN TO OTHER
MEMBRANES

Sheet No.:

WP-4
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
NOTES: ADJUSTABLE COLLAR
SURE-SEAL LAP-SEALANT NOTES:
1. METAL SCUPPER BOX MUST HAVE GRAVEL NOTES:
1. METAL SCUPPER BOX MUST HAVE
SURE-SEAL BONDING ADHESIVE CONTINUOUS SIDES, METAL FLANGE SURE-SEAL BONDING ADHESIVE CLAMPING RING 1. CLEAN FLANGE. APPLY
CONTINUOUS SIDES, METAL FLANGE MUST
SURE-SEAL/BRITE-PLY UNCURED MUST BE CONTINUOUS WITH ROUND SURE-SEAL/BRITE-PLY CCW-550 PRIMER OR
BE CONTINUOUS WITH ROUND CORNERS. CCW-500R @ 125 MILS
ELASTOFORM FLASHING OR CORNERS. UNCURED ELASTOFORM CCW-CONTACT ADHESIVE TO
2. WATER CUT-OFF MASTIC MUST BE HELD CCW-500 REINFORCING FABRIC
PRESSURE-SENSITIVE UNCURED 2. WATER CUT-OFF MASTIC MUST BE FLASHING OR PRESSURE- FLANGE AND 18" ONTO DECK.
FLASHING (IN CONJUNCTION SENSITIVE UNCURED FLASHING UNDER CONSTANT COMPRESSION. CCW-500R @ 90 MILS
HELD UNDER CONSTANT ALLOW PRIMER TO DRY.
WITH PRIMER) (IN CONJUNCTION WITH PRIMER) 3. METAL SCUPPER FLANGE ON WALL MUST
COMPRESSION. MIRADRAIN DRAINAGE COMPOSITE 2. APPLY 90 MILS OF HOT
SURE-SEAL WATER BE TOTALLY COVERED BY UNCURED
SURE-SEAL WATER 3. METAL SCUPPER FLANGE ON WALL CCW PROTECTION BOARD CCW-500 TO THE DRAIN
CUT-OFF MASTIC. ELASTOFORM FLASHING.
CUT-OFF MASTIC. MUST BE TOTALLY COVERED BY - H OR HS FLANGE AND 18" OUT ONTO
SURE-SEAL LAP-SEALANT 4. UNCURED ELASTOFORM FLASHING MUST
UNCURED ELASTOFORM FLASHING. THE DECK.
SURE-SEAL LAP-SEALANT OVERLAP WALL FLASHING 3" (8 cm) MIN.
4. UNCURED ELASTOFORM FLASHING 3. INSTALL CCW-711-90
5. A MIN. 2" (5 cm) FLASHING SPLICE IS
CCW-711-90 OR CCW- MUST OVERLAP WALL FLASHING 3" FLASHING, IN A SINGLE 3'x3'
UNCURED NEOPRENE FLASHING. REQUIRED PAST THE NAIL HEAD ON THE
(8cm) MIN. PIECE, TO THE DRAIN
METAL FLANGE OF THE SCUPPER.

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


5. A MIN. 2" (5cm) FLASHING SPLICE IS FLANGE AND DECK. CUT OUT
METAL FLASHING REQUIRED PAST THE NAIL HEAD ON CENTER OF FLASHING FLUSH
(BY OTHERS)
CCW-201 THE METAL FLANGE OF THE TO THE INSIDE OF THE DRAIN
SEALANT SCUPPER. FLANGE.
CCW-201 METAL FLASHING PAVER SYSTEM 4. APPLY 125 MILS OF HOT
SEALANT (BY OTHERS)
CCW MIRADRAIN DRAINAGE COMPOSITE CCW-500 COVERING THE
SURE-SEAL H.P. PROTECTIVE MAT CCW-711-90 FLASHING.
CCW-711-90

PHASE IIC: OVERALL BUILDING


RIGID INSULATION SECURE FLASHING IN PLACE
CCW-500 AT 90 MILS

REPAIR AND RESTORATION


UNDER CLAMP RING.
CCW MIRADRAIN DRAINAGE COMPOSITE CCW PROTECTION BOARD-H OR HS 5. APPLY CCW-500R HOT

REPAIR & RESTORATION


CCW-PROTECTION BOARD H OR HS CCW-500 AT 125 MILS APPLIED WATERPROOFING
CCW-500 REINFORCING FABRIC SYSTEM.
CCW-500 AT 125 MILS CCW-550 PRIMER OR 6. INSTALL CCW PROTECTION
CCW-500 AT 90 MILS CCW-CONTACT ADHESIVE BOARD-H
CCW-500 REINFORCING FABRIC
CCW-500 AT 90 MILS CCW-550 PRIMER OR CCW-711-90 FLASHING 7. INSTALL CCW MIRADRAIN
6"
CCW-CONTACT ADHESIVE DRAINAGE COMPOSITE.
CCW-PRIMER OR CCW-CONTACT ADHESIVE 90 MILS OF HOT CCW-500
CCW-201 SEALANT IN
1/4"X1/4" SAW CUT
DRAIN FLANGE
DETAIL IS INTENDED TO BE A GUIDE FOR
DETAIL IS INTENDED TO BE A GUIDE FOR WATERPROOFING INSTALLATION ONLY. DETAIL IS INTENDED TO BE A GUIDE FOR WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY.

OVERFLOW METAL OVERFLOW METAL


500-18A R
500-18B R
500-6 DOUBLE DRAIN R

SCUPPER COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION SCUPPER COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION


COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION

CLAMPING RING
CCW-500 @ 90 MILS
CCW-500 REINFORCEMENT FABRIC
CCW-500 @ 125 MILS
SOIL AND PLANTS AS REQUIRED
SOIL AND PLANTS AS REQUIRED
FILTER FABRIC OVER DRAIN BASKET FILTER FABRIC OVER DRAIN BASKET
AND EXTEND OUT ONTO GR9400 FABRIC AND EXTEND OUT ONTO GR9400 FABRIC
A MINIMUM OF 6" AND COVER WITH A A MINIMUM OF 6" AND COVER WITH A
LAYER OF WASHED #57 GRAVEL LAYER OF WASHED #57 GRAVEL
CCW MIRADRAIN GR9400
CLAMPING RING WITH WEEPS
CLAMPING RING WITH WEEPS
CCW MIRADRAIN 9000, 9800 RIGID INSULATION
OR 9900
CCW MIRADRAIN 9800
CCW ROOT BARRIER CCW ROOT BARRIER
SEAL License: 89035
CCW PROTECTION BOARD-HS CCW PROTECTION BOARD-HS DRAINAGE Expires: 02/28/23
CCW-500R 215 REINFORCED FLANGE
CCW-500R 215 REINFORCED HOT APPLIED MEMBRANE
HOT APPLIED MEMBRANE

CCW-550 PRIMER OR
CCW-CONTACT ADHESIVE
CCW-550 PRIMER OR
CCW-CONTACT ADHESIVE PROTECTION BOARD HS NOTES:
CCW-711-90 FLASHING 1. CLEAN AND PRIME FLANGE.
CCW-711-90 FLASHING CCW ROOT BARRIER
2. INSTALL CCW-711-90 FLASHING, IN A
90 MILS OF HOT CCW-500 90 MILS OF HOT CCW-500 CCW MIRADRAIN GR9400 SINGLE PIECE, UNDER FLANGE AND
CCW-201 SEALANT IN CCW-201 SEALANT IN CCW-550 PRIMER OR 6" ONTO DECK.
1/4"X1/4" SAW CUT 1/4"X1/4" SAW CUT CCW-CONTACT ADHESIVE 3. APPLY CCW-500R HOT APPLIED
DRAIN FLANGE CCW-711-90 FLASHING MEMBRANE. This item has been digitally signed and sealed by Robert J. Miller on the
DRAIN FLANGE date adjacent to the seal. Printed copies of this document are not
SECURE UNDER CLAMPING RING considered signed and sealed and the signature must be verified on
any electronic copies.
CCW-201 SEALANT
IN 1/4" x 1/4" SAW CUT
DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR
WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY.

GR 500-6 PLANTER DRAIN COATINGS & WATERPROOFING


R

GR 500-6B PLANTER DRAIN COATINGS & WATERPROOFING


R

GR 500-6C GREEN ROOF DRAIN COATINGS & WATERPROOFING


R

Structural Engineers | Remediation & Parking Consultants


c 2013 CARLISLE CORPORATION c 2013 CARLISLE CORPORATION c 2013 CARLISLE CORPORATION
206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.
NOTE: IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ENGAGE THE MANUFACTURER TO
VERIFY THE SUITABILITY OF ALL DETAILS TO BE USED ON THE JOB. THE CONTRACTOR SHALL SUBMIT ALL
ADDITIONAL DETAILS THAT THE MANUFACTURER REQUIRES TO COMPLETE THE WORK. No. Date Revisions

DESIGNED DRAWN
HR/JB/RM HR/JB/RM
CHECKED APPROVED
RM FPM
Project No.: 18217

Date: 04/26/21

Scale: 3" = 1'-0"


Sheet Title:
CCW-500 DRAINS

Sheet No.:

WP-5
• SET PAVING UNITS BASED ON APPROVED PATTERN, PLACING TO ALLOW FOR JOINT WIDTHS OF 1/16" TO 3/8”.
REVIEW SPECIFIC JOINT WIDTH WITH MANUFACTURER OF APPROVED PAVERS, DESIGNATED FOR THE WORK,
BEFORE PROCEEDING WITH PAVER INSTALLATION WORK.

SOUTH CONDOMINIUM
CHAMPLAIN TOWERS
• GROUT JOINTS SHALL BE UNIFORM AND STRAIGHT IN ALL DIRECTIONS AS INDICATED ON THE DRAWINGS.

• MAINTAIN NO GREATER THAN 1/16” HEIGHT DIFFERENCE BETWEEN ADJACENT PAVERS.


PAVER

SURFSIDE, FLORIDA 33154


GROUT JOINT • GROUT/MORTAR JOINTS IN ACCORDANCE WITH ANSI A1108.10.

8777 COLLINS AVENUE


CONCRETE TOPPING SLAB PAVERS (TYP.)
MORTAR BED (1 3/4" MIN)
CCW-300HV PROTECTION FABRIC REINFORCING WIRE OR CLOTH (OPTIONAL) ULTRACOLOR PLUS FA GROUT (TYP.)
RIGID INSULATION CCW MIRADRAIN DRAINAGE COMPOSITE PAVERS (TYP.)
CCW MIRADRAIN DRAINAGE COMPOSITE UP TO 1/2" THICK ULTRAFLEX LFT
CCW PROTECTION BOARD H OR HS ULTRACOLOR PLUS FA GROUT (TYP.) RAPID R.S. MORTAR (TYP.)
CCW PROTECTION BOARD H OR HS 125 MILS OF CCW-500 UP TO 1/2" THICK ULTRAFLEX LFT NEW WATERPROOFING WITH
125 MILS OF CCW-500 CCW-500 REINFORCING FABRIC RAPID R.S. MORTAR (TYP.) DRAINAGE MEDIUM (TYP.)
CCW-500 REINFORCING FABRIC 90 MILS OF CCW-500
90 MILS OF CCW-500 CCW-550 PRIMER OR
CCW-550 PRIMER OR CCW-CONTACT ADHESIVE
CCW-CONTACT ADHESIVE

NOTES:
NOTES: 1. APPLY CCW-550 PRIMER OR
1. APPLY CCW-550 PRIMER OR CCW-CONTACT ADHESIVE TO ENTIRE BONDED PAVER INSTALLATION WITH UNBONDED PAVER INSTALLATION
CCW-CONTACT ADHESIVE TO ENTIRE SURFACE AREA. MORTAR-BED UP TO 1/2" THICK WITH MORTAR-BED UP TO 1/2" THICK
SURFACE AREA. 2. APPLY CCW-500R HOT APPLIED LIQUID
2. APPLY CCW-500R HOT APPLIED MEMBRANE TO ENTIRE SURFACE AREA.
WATERPROOFING SYSTEM TO ENTIRE 3. INSTALL CCW PROTECTION BOARD. • ALL SURFACES WHERE BONDED PAVERS ARE TO BE INSTALLED ARE TO BE STRUCTURALLY SOUND, • MIX ULTRAFLEX LFT RAPID R.S. MORTAR (BY MAPEI) PER MANUFACTURER WRITTEN GUIDELINES.
SURFACE AREA. 4. INSTALL CCW MIRADRAIN DRAINAGE STABLE, DRY, CLEAN, AND FREE OF ANY SUBSTANCE OR CONDITION THAT MAY REDUCE OR PREVENT • WITH THE APPROPRIATE NOTCHED TROWEL, AND WITH PRESSURE, APPLY A COAT OF ULTRAFLEX LFT
3. INSTALL CCW PROTECTION BOARD. PROPER ADHESION. RAPID R.S. MORTAR. SPREAD ONLY AS MUCH MORTAR AS CAN BE COVERED WITH PAVERS BEFORE
COMPOSITE.

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


• MIX ULTRAFLEX LFT RAPID R.S. MORTAR (BY MAPEI) PER MANUFACTURER WRITTEN GUIDELINES. PRODUCT SKINS OVER. OPEN TIMES FOR MATERIAL (MORTAR) USAGE CAN VARY WITH JOBSITE
4. INSTALL CCW MIRADRAIN DRAINAGE
TILE / PAVER INSTALLATION SHALL BE AS • WITH THE APPROPRIATE NOTCHED TROWEL, AND WITH PRESSURE, APPLY A COAT OF ULTRAFLEX LFT CONDITIONS.
COMPOSITE.
RECOMMENDED BY TILE COUNCIL OF AMERICA RAPID R.S. MORTAR. SPREAD ONLY AS MUCH MORTAR AS CAN BE COVERED WITH PAVERS BEFORE • PLACE THE PAVERS FIRMLY IN THE WET MORTAR. PUSH PAVERS BACK AND FORTH IN A DIRECTION
PRODUCT SKINS OVER. OPEN TIMES FOR MATERIAL (MORTAR) USAGE CAN VARY WITH JOBSITE PERPENDICULAR TO THE TROWEL LINES, TO COLLAPSE THE MORTAR RIDGES AND HELP ACHIEVE
CONDITIONS. MAXIMUM COVERAGE. ENSURE MINIMUM 95% CONTACT OF MORTAR TO THE PAVER ON
DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR • PLACE THE PAVERS FIRMLY IN THE WET MORTAR. PUSH PAVERS BACK AND FORTH IN A DIRECTION INSTALLATION. PERIODICALLY LIFT A FEW PAVERS TO CHECK FOR ACCEPTABLE COVERAGE.
WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY.
PERPENDICULAR TO THE TROWEL LINES, TO COLLAPSE THE MORTAR RIDGES AND HELP ACHIEVE • ENSURE THAT PAVERS ARE PRE-SEALED (BY MANUFACTURER) AND OR SEALED IN THE FIELD WITH

PHASE IIC: OVERALL BUILDING


MAXIMUM COVERAGE. ENSURE MINIMUM 95% CONTACT OF MORTAR TO BOTH THE PAVER AND ENGINEER APPROVED SILANE/SILOXANE PENETRATING SEALER PRIOR TO GROUT WORK (WHERE
MORTAR BED W/ PAVER SUBSTRATE ON INSTALLATION. PERIODICALLY LIFT A FEW PAVERS TO CHECK FOR ACCEPTABLE SPECIFIED/REQUIRED).

REPAIR AND RESTORATION


500-10A INSULATED PLAZA DECK R

500-10C R
COVERAGE. • ALLOW 3-4 HOURS OF MORTAR-BED CURE PRIOR TO COMMENCING WITH GROUT WORK.
COATINGS & WATERPROOFING

PLAZA DECK COATINGS & WATERPROOFING


• ENSURE THAT PAVERS ARE PRE-SEALED (BY MANUFACTURER) AND OR SEALED IN THE FIELD WITH • REMOVE EXCESS MORTAR FROM THE JOINT AREAS SO THAT AT LEAST 2/3 OF THE PAVER DEPTH IS

REPAIR & RESTORATION


c 2012 CARLISLE CORPORATION c 2012 CARLISLE CORPORATION
ENGINEER APPROVED SILANE/SILOXANE PENETRATING SEALER PRIOR TO GROUT WORK (WHERE AVAILABLE FOR GROUTING. GROUT JOINTS MUST BE CLEAN AND FREE OF STANDING WATER, DUST,
SPECIFIED/REQUIRED). DIRT AND FOREIGN MATTER PRIOR TO INTENDED GROUT WORK.
• ALLOW 3-4 HOURS OF MORTAR-BED CURE PRIOR TO COMMENCING WITH GROUT WORK. • MIX ULTRACOLOR PLUS FA GROUT (BY MAPEI) PER MANUFACTURER WRITTEN GUIDELINES. REVIEW
• REMOVE EXCESS MORTAR FROM THE JOINT AREAS SO THAT AT LEAST 2/3 OF THE PAVER DEPTH IS “GROUTING IN HOT WEATHER” SECTION OF PRODUCT APPLICATION ON DATA SHEET TO ACCOMPLISH
AVAILABLE FOR GROUTING. GROUT JOINTS MUST BE CLEAN AND FREE OF STANDING WATER, DUST, THE BEST RESULTS.
DIRT AND FOREIGN MATTER PRIOR TO INTENDED GROUT WORK. • SLIGHTLY MOISTEN PAVER JOINT SURFACES WITH A DAMP SPONGE JUST PRIOR TO GROUT
PAVER CONCRETE TOPPING SLAB
• MIX ULTRACOLOR PLUS FA GROUT (BY MAPEI) PER MANUFACTURER WRITTEN GUIDELINES. REVIEW APPLICATION (TO AID APPLICATION). DO NOT FLOOD/SATURATE PAVERS, OR ALLOW FOR STANDING
SAND BED CCW MIRADRAIN DRAINAGE COMPOSITE “GROUTING IN HOT WEATHER” SECTION OF PRODUCT APPLICATION ON DATA SHEET TO ACCOMPLISH WATER AT UN-GROUTED JOINT AREAS.
CCW MIRADRAIN DRAINAGE COMPOSITE THE BEST RESULTS. • SPREAD GROUT IMMEDIATELY INTO THE DAMP JOINTS WITH A RUBBER GROUT FLOAT. MAKE SURE THAT
CCW PROTECTION BOARD H OR HS
• SLIGHTLY MOISTEN PAVER JOINT SURFACES WITH A DAMP SPONGE JUST PRIOR TO GROUT ALL JOINTS ARE WELL COMPACTED AND FREE OF VOIDS AND/OR GAPS.
CCW PROTECTION BOARD H OR HS 125 MILS OF CCW-500 APPLICATION (TO AID APPLICATION). DO NOT FLOOD/SATURATE PAVERS, OR ALLOW FOR STANDING • REMOVE EXCESS GROUT FROM THE PAVER SURFACE BY MOVING THE GROUT FLOAT DIAGONALLY TO
WATER AT UN-GROUTED JOINT AREAS. THE JOINTS WHILE GROUT MATERIAL IS STILL FRESH, SMOOTH SURFACES WITH A DAMP SPONGE, AS
125 MILS OF CCW-500 CCW-500 REINFORCING FABRIC • SPREAD GROUT IMMEDIATELY INTO THE DAMP JOINTS WITH A RUBBER GROUT FLOAT. MAKE SURE THAT NECESSARY.
CCW-500 REINFORCING FABRIC 90 MILS OF CCW-500 ALL JOINTS ARE WELL COMPACTED AND FREE OF VOIDS AND/OR GAPS. • CLEAN GROUTED JOINTS PER MANUFACTURER GUIDELINES TO ACHIEVE DESIRED COLOR-
• REMOVE EXCESS GROUT FROM THE PAVER SURFACE BY MOVING THE GROUT FLOAT DIAGONALLY TO CONSISTENCY.
90 MILS OF CCW-500 CCW-550 PRIMER OR
CCW-CONTACT ADHESIVE THE JOINTS WHILE GROUT MATERIAL IS STILL FRESH, SMOOTH SURFACES WITH A DAMP SPONGE, AS • APPLY ULTRACARE PENETRATING PLUS STONE TILE/GROUT SEALER (BY MAPEI) AT GROUTED JOINTS
CCW-550 PRIMER OR NECESSARY. AFTER SUFFICIENT CURE.
CCW-CONTACT ADHESIVE CONCRETE STRUCTURAL SLAB • CLEAN GROUTED JOINTS PER MANUFACTURER GUIDELINES TO ACHIEVE DESIRED COLOR-
CONSISTENCY.
• APPLY ULTRACARE PENETRATING PLUS STONE TILE/GROUT SEALER (BY MAPEI) AT GROUTED JOINTS
AFTER SUFFICIENT CURE.
NOTES:
NOTES: 1. APPLY CCW-550 PRIMER OR
1. APPLY CCW-550 PRIMER OR CCW-CONTACT ADHESIVE TO ENTIRE PAVERS (TYP.) PAVERS (TYP.)
CCW-CONTACT ADHESIVE TO ENTIRE SURFACE AREA.
SURFACE AREA. 2. APPLY CCW-500R HOT APPLIED ULTRACOLOR PLUS FA GROUT (TYP.) ULTRACOLOR PLUS FA GROUT (TYP.)
2. APPLY CCW-500R HOT APPLIED LIQUID WATERPROOFING SYSTEM TO ENTIRE
MEMBRANE TO ENTIRE SURFACE AREA. SURFACE AREA. UP TO 1/2" THICK ULTRAFLEX LFT UP TO 1/2" THICK ULTRAFLEX LFT
3. INSTALL CCW PROTECTION BOARD. 3. INSTALL CCW PROTECTION BOARD. RAPID R.S. MORTAR (TYP.) RAPID R.S. MORTAR (TYP.)
4. INSTALL CCW MIRADRAIN DRAINAGE 4. INSTALL CCW MIRADRAIN DRAINAGE 4 TO 1 MUD BED MIX MORTAR, 4 TO 1 MUD BED MIX MORTAR,
COMPOSITE. COMPOSITE. THICKNESS AS REQUIRED (TYP.) THICKNESS AS REQUIRED (TYP.)
UP TO 1/2" THICK ULTRAFLEX LFT NEW WATERPROOFING WITH
SEAL License: 89035
RAPID R.S. MORTAR (TYP.) DRAINAGE MEDIUM (TYP.) Expires: 02/28/23

DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR


WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY.

SAND BED W/ PAVER


500-10D R
500-10E CONCRETE TOPPING SLAB R

PLAZA DECK COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION


COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION

NOTE: IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ENGAGE THE MANUFACTURER TO


VERIFY THE SUITABILITY OF ALL DETAILS TO BE USED ON THE JOB. THE CONTRACTOR SHALL SUBMIT ALL BONDED PAVER INSTALLATION WITH UNBONDED PAVER INSTALLATION WITH
MORTAR-BED GREATER THAN 1/2" THICK MORTAR-BED GREATER THAN 1/2" THICK
ADDITIONAL DETAILS THAT THE MANUFACTURER REQUIRES TO COMPLETE THE WORK. This item has been digitally signed and sealed by Robert J. Miller on the
date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.
• ALL SURFACES WHERE BONDED PAVERS ARE TO BE INSTALLED ARE TO BE STRUCTURALLY SOUND, • MIX 4 TO 1 MUD BED MIX MORTAR (BY MAPEI) PER MANUFACTURER WRITTEN GUIDELINES.
STABLE, DRY, CLEAN, AND FREE OF ANY SUBSTANCE OR CONDITION THAT MAY REDUCE OR PREVENT • APPLY 4 TO 1 MORTAR TO DESIRED/REQUIRED THICKNESS (PRIOR TO APPLICATION OF ULTRAFLEX LFT
PROPER ADHESION. MORTAR AND PAVER INSTALLATION).
• MIX ULTRAFLEX LFT RAPID R.S. MORTAR (BY MAPEI) PER MANUFACTURER WRITTEN GUIDELINES. • AFTER MIXING, WITH THE APPROPRIATE NOTCHED TROWEL, AND WITH PRESSURE, APPLY A ¼”-½” THICK
• WITH THE APPROPRIATE NOTCHED TROWEL, AND WITH PRESSURE, APPLY A ¼”-½” THICK COAT OF COAT OF ULTRAFLEX LFT RAPID R.S. MORTAR. SPREAD ONLY AS MUCH MORTAR AS CAN BE COVERED
ULTRAFLEX LFT RAPID R.S. MORTAR AS A BOND-COAT MORTAR LAYER. SPREAD ONLY AS MUCH WITH PAVERS BEFORE PRODUCT SKINS OVER. OPEN TIMES FOR MATERIAL (MORTAR) USAGE CAN VARY
MORTAR AS CAN BE COVERED BEFORE PRODUCT SKINS OVER. OPEN TIMES FOR MATERIAL (MORTAR) WITH JOBSITE CONDITIONS.
USAGE CAN VARY WITH JOBSITE CONDITIONS. • PLACE THE PAVERS FIRMLY IN THE WET MORTAR. PUSH PAVERS BACK AND FORTH IN A DIRECTION
Structural Engineers | Remediation & Parking Consultants
• MIX 4 TO 1 MUD BED MIX MORTAR (BY MAPEI) PER MANUFACTURER WRITTEN GUIDELINES. PERPENDICULAR TO THE TROWEL LINES, TO COLLAPSE THE MORTAR RIDGES AND HELP ACHIEVE 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
• WORK A FLOAT-COAT LAYER OF 4 TO 1 MORTAR INTO (WET) BOND-COAT MORTAR LAYER OF ULTRAFLEX MAXIMUM COVERAGE. ENSURE MINIMUM 95% CONTACT OF MORTAR TO BOTH THE PAVER AND 561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.
LFT WITH A WOOD OR MAGNESIUM FLOAT. IMMEDIATELY FOLLOW WITH MORE 4 TO 1 TO ACHIEVE THE SUBSTRATE ON INSTALLATION. PERIODICALLY LIFT A FEW PAVERS TO CHECK FOR ACCEPTABLE
DESIRED/REQUIRED THICKNESS (PRIOR TO FINAL APPLICATION OF ULTRAFLEX LFT MORTAR AND PAVER COVERAGE.
INSTALLATION). • ENSURE THAT PAVERS ARE PRE-SEALED (BY MANUFACTURER) AND OR SEALED IN THE FIELD WITH
• AFTER MIXING, WITH THE APPROPRIATE NOTCHED TROWEL, AND WITH PRESSURE, APPLY A ¼”-½” THICK ENGINEER APPROVED SILANE/SILOXANE PENETRATING SEALER PRIOR TO GROUT WORK (WHERE No. Date Revisions
COAT OF ULTRAFLEX LFT RAPID R.S. MORTAR. SPREAD ONLY AS MUCH MORTAR AS CAN BE COVERED SPECIFIED/REQUIRED).
WITH PAVERS BEFORE PRODUCT SKINS OVER. • ALLOW 3-4 HOURS OF MORTAR-BED CURE PRIOR TO COMMENCING WITH GROUT WORK.
• PLACE THE PAVERS FIRMLY IN THE WET MORTAR. PUSH PAVERS BACK AND FORTH IN A DIRECTION • REMOVE EXCESS MORTAR FROM THE JOINT AREAS SO THAT AT LEAST 2/3 OF THE PAVER DEPTH IS
PERPENDICULAR TO THE TROWEL LINES, TO COLLAPSE THE MORTAR RIDGES AND HELP ACHIEVE AVAILABLE FOR GROUTING. GROUT JOINTS MUST BE CLEAN AND FREE OF STANDING WATER, DUST,
MAXIMUM COVERAGE. ENSURE MINIMUM 95% CONTACT OF MORTAR TO BOTH THE PAVER AND DIRT AND FOREIGN MATTER PRIOR TO INTENDED GROUT WORK.
SUBSTRATE ON INSTALLATION. PERIODICALLY LIFT A FEW PAVERS TO CHECK FOR ACCEPTABLE • MIX ULTRACOLOR PLUS FA GROUT (BY MAPEI) PER MANUFACTURER WRITTEN GUIDELINES. REVIEW
COVERAGE. “GROUTING IN HOT WEATHER” SECTION OF PRODUCT APPLICATION ON DATA SHEET TO ACCOMPLISH
• ENSURE THAT PAVERS ARE PRE-SEALED (BY MANUFACTURER) AND OR SEALED IN THE FIELD WITH THE BEST RESULTS.
ENGINEER APPROVED SILANE/SILOXANE PENETRATING SEALER PRIOR TO GROUT WORK (WHERE • SLIGHTLY MOISTEN PAVER JOINT SURFACES WITH A DAMP SPONGE JUST PRIOR TO GROUT
SPECIFIED/REQUIRED). APPLICATION (TO AID APPLICATION). DO NOT FLOOD/SATURATE PAVERS, OR ALLOW FOR STANDING
• ALLOW 3-4 HOURS OF MORTAR-BED CURE PRIOR TO COMMENCING WITH GROUT WORK. WATER AT UN-GROUTED JOINT AREAS.
• REMOVE EXCESS MORTAR FROM THE JOINT AREAS SO THAT AT LEAST 2/3 OF THE PAVER DEPTH IS • SPREAD GROUT IMMEDIATELY INTO THE DAMP JOINTS WITH A RUBBER GROUT FLOAT. MAKE SURE THAT
AVAILABLE FOR GROUTING. GROUT JOINTS MUST BE CLEAN AND FREE OF STANDING WATER, DUST, ALL JOINTS ARE WELL COMPACTED AND FREE OF VOIDS AND/OR GAPS.
DIRT AND FOREIGN MATTER PRIOR TO INTENDED GROUT WORK. • REMOVE EXCESS GROUT FROM THE PAVER SURFACE BY MOVING THE GROUT FLOAT DIAGONALLY TO
• MIX ULTRACOLOR PLUS FA GROUT (BY MAPEI) PER MANUFACTURER WRITTEN GUIDELINES. REVIEW THE JOINTS WHILE GROUT MATERIAL IS STILL FRESH, SMOOTH SURFACES WITH A DAMP SPONGE, AS
“GROUTING IN HOT WEATHER” SECTION OF PRODUCT APPLICATION ON DATA SHEET TO ACCOMPLISH NECESSARY.
THE BEST RESULTS. • CLEAN GROUTED JOINTS PER MANUFACTURER GUIDELINES TO ACHIEVE DESIRED COLOR-
• SLIGHTLY MOISTEN PAVER JOINT SURFACES WITH A DAMP SPONGE JUST PRIOR TO GROUT CONSISTENCY.
APPLICATION (TO AID APPLICATION). DO NOT FLOOD/SATURATE PAVERS, OR ALLOW FOR STANDING • APPLY ULTRACARE PENETRATING PLUS STONE TILE/GROUT SEALER (BY MAPEI) AT GROUTED JOINTS
DESIGNED DRAWN
WATER AT UN-GROUTED JOINT AREAS. AFTER SUFFICIENT CURE.
• SPREAD GROUT IMMEDIATELY INTO THE DAMP JOINTS WITH A RUBBER GROUT FLOAT. MAKE SURE THAT HR/JB/RM HR/JB/RM
ALL JOINTS ARE WELL COMPACTED AND FREE OF VOIDS AND/OR GAPS. CHECKED APPROVED
• REMOVE EXCESS GROUT FROM THE PAVER SURFACE BY MOVING THE GROUT FLOAT DIAGONALLY TO RM FPM
THE JOINTS WHILE GROUT MATERIAL IS STILL FRESH, SMOOTH SURFACES WITH A DAMP SPONGE, AS
NECESSARY. Project No.: 18217
• CLEAN GROUTED JOINTS PER MANUFACTURER GUIDELINES TO ACHIEVE DESIRED COLOR-
CONSISTENCY.
• APPLY ULTRACARE PENETRATING PLUS STONE TILE/GROUT SEALER (BY MAPEI) AT GROUTED JOINTS Date: 04/26/21
AFTER SUFFICIENT CURE.
Scale: As indicated
Sheet Title:
CCW-500 PAVERS

Sheet No.:
BONDED VS UNBONDED PAVER INSTALLATIONS
1 1 1/2" = 1'-0" WP-6
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
CCW-703-V LIQUISEAL CCW-550 PRIMER NEW HOT PIPE (BY OTHERS) NOTES:
CCW-201 SEALANT OR 90 MILS OF CCW-500 HEAT RESISTANT SEALANT (BY OTHERS) 1. REMOVE ALL LEAD AND OTHER
CCW-704 MASTIC
CCW-711-90 FLASHING RAIN HOOD (BY OTHERS) FLASHING BEFORE INSTALLING
STAINLESS STEEL FIELD-FABRICATED PIPE SEAL.
PIPE CLAMP 125 MILS OF CCW-500 METAL COLLAR (BY OTHERS) (NOTE 1) 2. FLASHING WRAPPED AROUND
CCW PROTECTION CCW-500 REINFORCING CCW-711-90 OR CCW OR CCW-UNCURED PIPE SHALL HAVE 3" (8CM) REBAR, DOWEL, ROD - CLEAN WITH
BOARD H OR HS FABRIC NEOPRENE FLASHING MINIMUM MEMBRANE SPLICE. WIRE BRUSH REMOVING ALL RUST
CCW-201 90 MILS OF CCW-500 CCW-500R HOT APPLIED 3. TEMPERATURE MUST NOT EXCEED 125 MILS OF CCW-500 A MINIMUM OF
LIQUID MEMBRANE 180°F (82°C) 4" HIGH ON PENETRATION AND 4" OUT
CCW MIRADRAIN CCW-550 PRIMER OR CCW CONTACT ADHESIVE CCW PROTECTION BOARD H OR HS ONTO CONCRETE DECK
CCW MIRADRAIN DRAINAGE COMPOSITE
NOTES: CCW PROTECTION BOARD- H OR HS
1. INSTALL CCW-201 SEALANT. CCW-500 AT 125 MILS
TOOL SEALANT TO FORM A 1"
FACE, 45 DEGREE CANT. LET CCW-500 REINFORCING FABRIC
CURE OVER NIGHT. CCW-500 AT 90 MILS
2. APPLY CCW-550 PRIMER OR
CCW-550 PRIMER OR
CCW-CONTACT ADHESIVE. CCW-CONTACT ADHESIVE
APPLY CCW-500R HOT APPLIED
SURE-SEAL H.P. MAT CONCRETE SUBSTRATE
MEMBRANE.
3. INSTALL CCW-711-90 FLASHING RIGID INSULATION
AND CLAMPING RING TO
SPECIFIED HEIGHT AND 4" MIN. CCW-550 @ 125 MILS

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


ONTO CURED CCW-500.
4. APPLY CCW-500 HOT APPLIED
6" CCW-550 REINFORCING FABRIC
MEMBRANE OVER CCW-711-90
TERMINATION OF SHEET FLASHING ON
FLASHING. CCW-550 @ 90 MILS
VERTICAL PENETRATIONS SHALL BE BELOW
5. INSTALL CCW PROTECTION
THE FINISH COURSE.
BOARD- H OR HS. CCW-550 PRIMER OR
6. INSTALL CCW MIRADRAIN

PHASE IIC: OVERALL BUILDING


CCW-CONTACT ADHESIVE
DRAINAGE COMPOSITE.

REPAIR AND RESTORATION


REPAIR & RESTORATION
DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR
WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY.

PIPE AND FIELD FABRICATED


500-8A R
500-8B R
500-8C SMALL PENETRATIONS R

PENETRATION FLASHING COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION NEW HOT STACK COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION


COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION

METAL COUNTER FLASHING


CCW-201 SEALANT AND BACKER ROD NOTES:
STAINLESS STEEL PIPE CLAMP CCW-703V LIQUISEAL, STAINLESS STEEL CLAMPING RING 1. 180°F (82°C) MAXIMUM
CCW-500 @ 125 mils CCW-201 SEALANT OR CCW 190FR PROTECTION CAP TEMPERATURE.
CCW-711-90 FLASHING CCW-704 MASTIC CCW-500 2. CCW-500 MUST
APPROVED CCW - PRIMER PENETRATION CONTACT FLASHING AND
CCW-500 @ 90 mils
CCW MIRADRAIN DRAINAGE COMPOSITE CCW PROTECTION DECK MEMBRANE.
CCW MIRADRAIN 9000, 9800 OR 9900 SURE-SEAL
BOARD H OR HS 3. DECK FLANGE MUST BE
CCW-PROTECTION BOARD-H OR HS CCW PROTECTION BOARD H OR HS H.P. MAT
MIRADRAIN DRAINAGE CONTINUOUS WITH
CCW-500 @ 125 mils COMPOSITE RIGID
125 MILS OF CCW-500 INSULATION ROUNDED CORNERS.
CCW-500 REINFORCING FABRIC 4. CCW-500 POCKET MAY
CCW-500 @ 90 mils CCW-500 REINFORCING FABRIC BE ROUND
CCW-550 PRIMER OR 90 MILS OF CCW-500 5. CCW-500 POCKET TO BE
CCW-201 SEALANT 8"
CCW-CONTACT ADHESIVE 1" (25 CM) MIN. FROM
CANT BEAD MIN. CCW-550 PRIMER OR CCW CONTACT PENETRATION ON ANY
ADHESIVE SIDE.
6. CCW-500 MUST

2"
NOTES:
NOTES: COMPLETELY FILL
1. PRIOR TO INSTALLATION, UNROLL
1. APPLY CCW-550 PRIMER OR CCW-500 POCKET TO
CCW 190FR PROTECTION CAP OUT
CCW-CONTACT ADHESIVE. PREVENT PONDING OF
ON ROOF AND ALLOW IT TO RELAX,
APPLY CCW-500 HOT APPLIED WATER.
THEN BACKROLL THE PRODUCT
MEMBRANE. 7. CCW-500 TO BE MIN. 2" (5
ONCE IN POSITION FOR
2. INSTALL CCW-711-90 CCW-711-90 OR CM) DEEP.
INSTALLATION AT THE DESIRED
FLASHING TO SPECIFIED CCW-UNCURED 6" 8. CCW-500 MUST
6" MIN. 6" MIN. POSITION.
HEIGHT AND 4" MIN. ONTO NEOPRENE CONTACT THE BARE
2. CCW 190FR PROTECTION CAP IS
CURED CCW-500. FLASHING SURFACE OF THE SEAL License: 89035
HEAT WELDED TO THE PRIMED
3. APPLY CCW-500 HOT APPLIED PENETRATION. ALL Expires: 02/28/23
SUBSTRATE FOR EXPOSED
MEMBRANE OVER CCW-711-90 DEBRIS (PAINT, RUST,
FLASHING CONDITIONS.
FLASHING. LEAD, OTHER FLASHING,
3. HEAT AND SCRAE GRANULES
4. INSTALL CCW PROTECTION ETC.) MUST BE REMOVED
FROM CCW 190FR PRIOR TO
BOARD-H OR HS. METAL DAM (BY OTHERS) FROM THE
MAKING TIE-IN WITH CCW-500.
5. INSTALL MIRADRAIN PENETRATION.
DRAINAGE COMPOSITE.
DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR DETAIL IS INTENDED TO BE A GUIDE FOR
WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY. WATERPROOFING INSTALLATION ONLY.

PIPE SLEEVE CCW 190FR PROTECTION CAP - FIELD FABRICATED


500-8D R
500-8E R
500-16A R

PENETRATION FLASHING COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION ROOF DAVIT COATINGS & WATERPROOFING

c 2019 CARLISLE CORPORATION CCW-500 POCKET COATINGS & WATERPROOFING

c 2012 CARLISLE CORPORATION This item has been digitally signed and sealed by Robert J. Miller on the
date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.

SEALANT
ABOVE

RAIN HOOD (BY OTHERS)


OVER-BURDEN
CURB HEIGHT

TUBE STEEL / PENETRATION (BY OTHERS)


CONDUIT (BY OTHERS)
MIN. 2"

Structural Engineers | Remediation & Parking Consultants


CCW-500 (COMPLETELY FILL PITCH POCKET) 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
METAL PITCH PAN (BY OTHERS) © Copyright Morabito Consultants, Inc.

NOTCH RAIN HOOD AS REQUIRED (BY OTHERS)

No. Date Revisions


CCW 300 H/V
RIGID INSULATION
CCW MIRADRAIN DRAINAGE
COMPOSITE

CCW PROTECTION BOARD HS


CCW-500 @ 125 MILS

CCW-500 REINFORCING FABRIC

CCW-500 @ 90 MILS

1" 6" 6" CCW 711-90


CCW-500 @ 90 MILS
CCW-550 PRIMER OR
CCW-CONTACT ADHESIVE
DESIGNED DRAWN
HR/JB/RM HR/JB/RM
DETAIL IS INTENDED TO BE A GUIDE FOR
WATERPROOFING INSTALLATION ONLY. CHECKED APPROVED
RM FPM
FIELD FABRICATED
500-16B R Project No.: 18217
PITCH POCKET COATINGS & WATERPROOFING

c 2013 CARLISLE CORPORATION


Date: 04/26/21
NOTE: IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ENGAGE THE MANUFACTURER TO Scale: 3" = 1'-0"
VERIFY THE SUITABILITY OF ALL DETAILS TO BE USED ON THE JOB. THE CONTRACTOR SHALL SUBMIT ALL
ADDITIONAL DETAILS THAT THE MANUFACTURER REQUIRES TO COMPLETE THE WORK. Sheet Title:
CCW-500 PENETRATIONS

Sheet No.:

WP-7
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
SEAL License: 89035
Expires: 02/28/23

This item has been digitally signed and sealed by Robert J. Miller on the
date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

DESIGNED DRAWN
Designer Author
CHECKED APPROVED
Checker Approver
Project No.: 18217

Date: 04/26/21

Scale:
Sheet Title:
MIRACOTE POOL
MEMBRANE

Sheet No.:

WP-8
RAMP DOWN

SERVICE PATIO
ENTRANCE

KITCHEN
TRANSFER
VAULT GENERATOR
DRIVEWAY
RECREATION
ROOM Unit B PATIO

WOMEN ROOM

STAIR #2
ELETRICAL
ROOM
LAUNDRY
ROOM
MEN
WASTE
ROOM
CORRIDOR

OFFICE MEN WOMEN

FRONT
DESK

ELEV. Unit C Unit A PATIO


GYM MANAGEMENT
LOBBY
DRIVEWAY OFFICE
UP
ELEV.

STAIR #1

UP

SITTING PARKING
AREA AREA

DRIVEWAY

POOL DECK

SWIMMING
POOL

PARKING PARKING JACUZZI


AREA AREA
Unit H Unit H Unit C Unit B

STAIR #2

CORRIDOR

Unit E
STORAGE

STORAGE
Unit G

ELEV. Unit D Unit C Unit A

CORRIDOR
ELEV.

STAIR #1

Unit G

Unit F

Unit I
Unit H Unit H Unit C Unit B

STAIR #2

CORRIDOR

Unit E
STORAGE

STORAGE
Unit G

ELEV. Unit D Unit C Unit A

CORRIDOR
ELEV.

STAIR #1

Unit G

Unit F

Unit I
Unit H Unit H Unit C Unit B

STAIR #2

CORRIDOR

Unit E
STORAGE

STORAGE
Unit G

ELEV. Unit D Unit C Unit A

CORRIDOR
ELEV.

STAIR #1

Unit G

Unit F

Unit I
±

STAIR #2

±
ELEV.

CORRIDOR

ELEV.

STAIR #1

±
±

±
± ± ± ± ± ±

± ±

±
±

±
±
±

± ± ±

±
±

±
±

± ± ±

±
±

±
±

±
±
±

± ± ±
±
±

±
±

±
±

± ± ±

± ± ±

± ±
±

±
±

±
±

±
±
±

± ±
±
±

±
±

±
±

±
±

±
±

± ±
±

± ±
±

±
±

±
±

±
±
±

±
±

± ±
±
±

±
±
±

±
±
±

± ±
±

±
±
I
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
SEAL Henry A. Vidal, P.E.
PE #56204

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

DESIGNED DRAWN
G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
Project No.: 18217

Date: 04-01-2021

Scale: AS SHOWN
Sheet Title:
ELECTRICAL SYMBOL
CONSULTING ENGINEERS
241 N.W. SOUTH RIVER DRIVE LEGEND AND NOTES
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861
INFO@VIDALENGINEERING.COM
H.VIDAL
& ASSOCIATES VIDALENGINEERING.COM
E-0
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


1.6 1.5 1.5 1.4 1.4 1.5 1.6 1.6 1.6 1.5 1.4 1.4 1.4 1.5 1.6 1.6 1.5 1.3 1.2 1.2 1.3 1.4 1.5 1.5 1.4 1.5 2.2 2.4 2.3 1.7 1.4 1.8 1.8 1.8 1.8 1.8 1.9 1.9 1.8 1.8 1.7 1.7 1.7 1.7 1.4

8777 COLLINS AVENUE


2.0 2.2 2.4 2.4 2.2 2.0 2.0 2.2 2.4 2.6 2.5 2.3 2.0 2.0 2.1 2.3 2.5 2.4 2.2 1.9 1.7 1.7 1.9 2.2 2.4 2.5 2.2 2.4 3.5 3.8 3.8 2.7 2.3 2.7 2.8 2.7 2.6 2.7 2.9 2.9 2.8 2.6 2.5 2.6 2.7 2.6 2.4
MAINTENANCE MAINT.
ROOM ROOM
2.8 3.4 3.9 3.9 3.5 3.1 3.0 3.4 3.9 4.2 4.0 3.5 3.0 2.9 3.1 3.7 4.1 4.0 3.5 2.8 2.4 2.4 2.8 3.5 4.0 4.1 3.7 3.7 5.2 5.3 5.4 4.2 3.8 4.5 4.5 4.2 4.0 4.2 4.5 4.7 4.4 4.0 3.9 4.1 4.3 4.4 3.8

2.7 3.8 4.8 5.1 5.3 5.1 4.4 4.3 4.8 5.3 5.4 5.4 5.0 4.2 3.9 4.5 5.1 5.3 5.3 4.9 4.0 3.3 3.2 4.0 4.9 5.3 5.4 5.4 4.9 5.7 5.3 5.7 5.2 5.4 6.0 6.1 6.0 5.8 6.0 6.1 6.0 6.1 5.8 5.6 5.8 5.9 5.8 5.3

3.2 4.6 5.1 4.9 5.3 5.8 5.5 5.3 5.9 5.7 5.3 5.5 5.9 5.3 4.9 5.5 5.7 5.2 5.2 5.5 5.0 4.0 4.0 5.0 5.5 5.2 5.5 6.2 5.4 5.9 5.1 5.7 5.5 5.9 6.1 6.4 7.2 7.3 7.2 6.4 6.0 6.5 7.1 7.0 6.8 6.1 5.9 5.9
G-1
MH: 11
2.1 3.4 5.0 5.1 4.8 G-1 5.2 6.1 6.0 5.9 6.3 5.8 5.2G-1 5.5 6.2 5.7 5.4 6.0 5.9 5.1 G-15.1 5.7 5.4 4.4 4.4 5.4 5.7 5.2 5.3
G-1 6.4 5.3 6.2 5.6 5.9 5.5 6.1 6.0G-1 6.6 7.6 8.1 7.7 6.6 5.9
G-1 6.7 7.6 7.7 7.3 6.3 5.8
G-1 6.1
MH: 11 MH: 11 MH: 11 MH: 11 MH: 11 MH: 11 MH: 11
2.1 3.3 4.9 5.5 5.5 5.8 6.2 5.9 5.7 6.3 6.3 5.9 6.0 6.3 5.6 5.2 5.9 6.2 5.8 5.7 5.9 5.3 4.3 4.3 5.3 6.0 5.8 6.0 6.6 4.7 5.9 6.0 6.0 5.1 6.1 6.6 7.1 7.7 7.8 7.8 7.1 6.8 7.1 7.6 7.5 7.5 6.8 6.5 6.3

1.9 2.9 4.4 5.6 6.1 6.2 5.9 5.3 5.1 5.7 6.4 6.6 6.5 5.9 5.0 4.8 5.3 6.1 6.4 6.3 5.8 4.8 4.0 4.0 4.8 5.8 6.3 6.5 6.2 3.9 4.9 5.2 5.1 4.1 5.6 6.9 7.4 7.2 7.0 7.2 7.5 7.5 7.4 7.0 6.7 7.0 7.2 7.1 6.5

1.8 2.7 3.8 5.0 5.8 5.9 5.3 4.8 4.7 5.1 5.9 6.3 6.1 5.3 4.6 4.4 4.8 5.5 6.0 6.0 5.2 4.3 3.8 3.7 4.3 5.2 5.9 6.1 5.5 3.5 4.5 4.7 4.5 3.2 7.0 6.6 6.4 6.6 7.1 7.3 7.0 6.4 6.1 6.4 6.8 6.8 6.0

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


2.2 2.9 4.0 5.2 6.0 6.0 5.5 4.9 4.8 5.3 6.0 6.4 6.2 5.4 4.7 4.5 4.9 5.7 6.2 6.1 5.4 4.5 3.8 3.9 4.4 5.4 6.1 6.2 5.6 3.9 5.2 5.4 5.3 3.5 7.3 6.9 6.6 6.9 7.4 7.6 7.2 6.6 6.4 6.7 7.1 7.1 6.2

STAIRS
2.5 3.3 4.7 5.9 6.4 6.5 6.3 5.7 5.5 6.2 6.7 6.8 6.8 6.2 5.3 5.0 5.7 6.4 6.6 6.6 6.2 5.1 4.3 4.3 5.1 6.1 6.5 6.7 6.6 4.9 6.2 6.0 6.1 4.4 7.8 7.8 7.6 7.9 7.7 7.6 7.7 7.6 7.3 7.5 7.3 7.2 6.8

RAMP UP
2.8 3.8 5.3 5.8 5.8 6.1 6.7 6.5 6.3 6.8 6.7 6.3 6.5 6.5 6.0 5.7 6.3 6.5 6.1 6.1 6.4 5.8 4.8 4.8 5.8 6.3 6.1 6.3 7.0 5.6 6.2 5.6 5.9 4.8 7.4 8.3 8.6 8.3 7.4 7.0 7.5 8.2 8.2 7.9 7.0 6.6 6.7

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
2.9 4.0 5.6 5.8 5.5 G-1 6.0 6.8 6.8 6.6 7.1 6.7 6.1G-1 6.4 6.6 6.2 5.9 6.7 6.6 5.9 G-15.9 6.4 6.1 5.1 5.1 6.1 6.4 5.9 6.0
G-1 7.1 5.8 6.2 G-1 5.8
5.2 5.8 6.8 6.7G-1 7.5 8.5 8.9 8.5 7.4 G-1 7.5
6.8 8.4 8.5 8.0 7.0 G-1
6.4 6.6

REPAIR & RESTORATION


MH: 11 MH: 11 MH: 11 MH: 11
MH: 11 MH: 11 MH: 11 MH: 11
2.9 3.9 5.5 6.3 6.3 6.7 7.1 6.7 6.5 7.1 7.3 7.1 5.1 6.3 6.9 6.7 6.7 6.8 6.0 5.0 4.9 6.0 6.7 6.6 6.8 7.3 5.5 6.4 5.7 6.1 5.7 7.4 7.9 8.1 8.5 8.4 8.5 8.0 7.8 8.0 8.2 8.0 8.0 7.6 7.3 7.1

2.8 3.7 5.2 6.6 7.4 7.5 7.0 6.3 6.1 6.8 7.7 8.2 5.2 5.6 6.8 7.5 7.5 6.9 5.7 4.8 4.8 5.6 6.8 7.5 7.6 7.2 4.6 5.9 6.4 5.9 4.9 7.3 8.3 8.3 7.9 7.6 7.9 8.4 8.5 8.2 7.6 7.3 7.6 8.0 7.9 7.1

MAINTENANCE
2.7 3.6 5.0 6.6 7.5 7.6 6.9 6.1 6.0 6.7 7.7 8.4 5.3 ROOM 5.5 6.8 7.7 7.6 6.7 5.5 4.7 4.6 5.4 6.7 7.6 7.7 6.9 4.0 5.3 5.6 5.5 4.2 6.9 8.1 8.1 7.7 7.4 7.7 8.3 8.5 8.1 7.4 7.1 7.3 7.8 7.8 7.0

2.9 3.8 5.4 6.8 7.5 7.7 7.3 6.5 6.4 7.2 8.1 8.6 5.5 6.3 7.3 7.7 7.7 7.1 5.9 4.9 4.9 5.8 6.9 7.4 7.5 7.2 5.7 5.2 5.0 5.5 6.0 7.3 8.0 8.2 8.2 8.0 8.2 8.4 8.4 8.3 8.0 7.6 7.9 8.0 7.8 7.3

3.1 4.2 5.9 6.6 6.6 7.0 7.6 7.2 7.1 7.8 8.0 8.2 5.2 7.4 7.7 7.3 7.1 7.2 6.4 5.3 5.2 6.2 6.8 6.6 6.6 7.0 6.8 5.3 5.0 5.7 7.0 7.2 7.1 7.7 8.6 8.8 8.7 7.9 7.5 8.0 8.5 8.4 8.1 7.4 7.0 7.1 6.3

ELEV.

VESTIBULE
3.3 4.5 6.2 6.6 6.4 G-1 6.9 7.7 7.6 7.5 8.2 8.1 8.1G-1 5.3 8.9 8.6 7.1
7.6 G-1 7.3 6.7 5.5 5.4 6.4 6.7 6.2 6.2
G-1 7.0 7.0 5.7 5.2 6.0 7.3 7.2 6.7G-1 7.4 8.7 9.1 8.8 7.7 G-1 7.7
7.0 8.6 8.7 8.2 7.1 6.4
G-1 6.8 6.3
MH: 11 MH: 11 MH: 11 MH: 11 MH: 11 MH: 11 MH: 11
3.3 4.5 6.4 7.4 7.6 7.9 8.2 7.7 7.5 8.3 8.8 9.1 5.8 10.5 10.5 9.3 8.3 7.7 6.6 5.4 5.3 6.2 7.0 6.9 7.0 7.4 7.0 5.9 5.5 6.2 7.5 7.8 7.6 8.0 8.6 8.7 8.7 8.1 7.7 8.1 8.5 8.3 8.3 7.6 7.1 7.2 6.4
STORAGE ROOM ELEV.

3.3 4.4 6.4 8.3 9.2 9.3 8.6 7.6 7.3 8.3 9.5 10.2 6.8 10.9 11.7 11.3 9.7 8.0 6.3 5.1 5.0 5.8 7.0 7.8 8.1 7.8 7.0 6.3 6.1 6.6 7.6 8.5 8.7 8.6 8.3 8.0 8.3 8.6 8.6 8.5 8.0 7.7 8.0 8.2 7.9 7.3 5.9

3.3 4.5 6.5 8.2 9.0 9.2 8.7 7.6 7.3 8.1 9.0 9.4 8.6 4.8 10.5 11.5 11.9 10.2 8.1 6.1 5.0 4.8 5.6 6.8 8.0 8.4 8.1 7.6 7.4 7.4 7.8 8.3 8.9 9.1 8.7 8.1 7.6 8.0 8.5 8.7 8.3 7.6 7.3 7.6 8.1 8.1 7.2 5.7

G-1
3.5 4.7 6.6 7.4 7.5 7.9 8.3 7.8 7.4 7.9 7.8 7.4 7.6 6.0 STAIRS 10.71111.6 11.6 10.1 8.2 6.4 5.1 5.0 5.8 7.1 7.9 8.5 8.9 9.0 8.7 8.7 9.2 9.8 9.7 9.3 9.0 8.5 8.1 8.4 8.6 8.7 8.5 8.0 7.7 8.0 8.2 8.0 7.4 6.0
MH:

3.5 4.8 6.6 7.2 7.1 G-1 7.5 8.1 7.7 7.3 7.6 7.0 6.2G-1 6.6 6.0 11.0 11.1 10.0 8.6 7.8 6.6 5.3 5.2 6.2 7.0 7.1 7.8 9.3 10.1 9.1 8.6 9.5 10.7 9.9 8.7 8.5 8.9 8.9 8.8 8.2 7.9 8.2 8.7 8.5 8.3 7.6 7.2 7.3 6.6 SEAL Henry A. Vidal, P.E.
PE #56204
MH: 11 MH: 11

3.5 4.7 6.9 8.2 8.3 8.5 8.4 7.4 6.8 7.0 6.9 6.5 6.5 6.5 3.8 6.4 9.7 9.5 8.1 7.2 7.1 6.4 5.2 5.1 6.2 6.6 6.5 7.1 9.0 10.3 9.0 8.1 9.3 10.7 9.7 8.0 8.0 8.8 9.2 8.9 7.8 7.3 8.0 8.9 9.0 8.5 7.3 6.7 7.0 6.6
G-1 G-1 G-1 G-1 G-1 G-1
MH: 11 MH: 11 MH: 11 MH: 11 MH: 11 MH: 11
3.7 5.4 7.4 9.1 9.9 9.7 8.6 7.0 5.9 5.9 6.2 6.2 6.0 5.4 4.6 6.8 8.1 8.0 7.2 6.7 6.6 5.8 4.7 4.6 5.7 6.4 6.5 7.1 8.7 9.6 8.7 8.2 9.1 10.3 9.4 8.0 7.9 8.5 8.8 8.9 8.3 8.0 8.5 8.9 8.9 8.7 7.9 7.5 7.5 6.8

6.9 7.2 7.1 6.6 6.8 7.0 6.9 6.8 6.7 6.2 6.4 7.7 8.7 8.9 8.9 8.2 6.6 5.2 4.7 4.7 4.7 4.5 3.9 4.0 5.0 5.9 6.7 6.8 6.5 5.8 4.7 4.0 3.9 4.7 5.8 6.5 7.0 7.6 8.0 7.9 8.0 8.4 8.8 8.5 7.9 7.7 7.6 7.8 8.5 9.2 9.4 9.3 8.8 8.4 8.8 9.0 8.8 8.2 6.5

6.6 7.2 7.7 7.6 7.6 7.0 6.3 6.5 7.2 6.9 6.8 7.6 7.6 7.2 7.3 7.3 6.3 4.8 3.9 3.6 3.4 3.2 3.0 3.3 3.7 4.2 4.8 5.1 4.9 4.3 3.6 3.2 3.1 3.6 4.3 5.0 5.4 5.6 5.7 5.9 6.1 6.3 6.4 6.4 6.3 6.2 6.2 6.8 8.0 9.1 9.5 9.3 8.5 8.2 8.6 9.1 9.1 8.3 6.3

G-1 G-1 G-1


6.6 6.9 7.2
MH: 11 7.8 7.8 7.8 7.2 6.5MH:6.7
11 7.2 7.0 6.8 7.4 7.3 6.7 MH:6.8
11 6.9 6.0 4.4 3.5 3.1 2.9 2.7 2.6 2.8 2.9 3.2 3.5 3.7 3.6 3.3 2.9 2.6 2.7 2.9 3.3 3.7 4.0 4.1 4.1 4.2 4.4 4.5 4.6 4.7 4.7 4.8 5.2 6.3 7.6 8.0 8.1 8.5 8.6 8.4 8.5 8.1 7.8 7.5 6.3

7.1 7.6 7.7 7.7 7.4 7.6 7.7 7.5 7.4 7.3 6.6 6.3 7.0 7.5 7.4 7.2 6.9 5.6 4.2 3.5 3.2 3.0 2.9 2.7 2.7 2.7 2.9 3.1 3.3 3.2 3.0 2.7 2.5 2.5 2.7 3.0 3.4 3.5 3.5 3.5 3.5 3.6 3.8 4.0 4.0 4.1 4.2 4.7 5.9 7.0 6.7 6.6 7.4 8.4 8.4 8.0 7.0 6.4 6.6 6.2

G-1 G-1
7.3 8.0 7.9 7.3 6.8 7.1 7.8 8.2 7.9 7.0 6.0 5.8 6.4 7.4 7.9 7.6 6.6 5.3 4.3 3.9 3.9 3.9 3.7 3.4 3.1 3.0 3.2 3.6 3.9 3.8 3.4 3.0 2.6 2.6 3.0 3.5 3.9 4.1 3.9 3.6 3.4 3.6 4.0 4.3 4.4 4.3 4.1 4.5 5.5 6.5 6.3 MH: 116.9
6.2 7.7 7.9 7.5 6.5 MH: 116.1
5.9 5.7

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
6.0 7.2 7.8 7.8 7.2 6.7 7.0 7.7 8.0 7.8 6.9 5.9 5.7 6.3 7.3 7.8 7.6 6.6 5.4 4.8 4.8 5.2 5.3 5.1 4.6 3.9 3.7 4.1 4.8 5.2 5.1 4.5 3.7 3.1 3.1 3.7 4.6 5.2 5.3 5.0 4.3 4.0 4.3 4.9 5.4 5.6 5.2 4.6 4.4 5.0 6.0 6.3 6.4 6.7 6.7 6.5 6.7 6.5 6.2 5.9 5.0 561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

6.0 6.8 7.0 7.3 7.5 7.1 7.4 7.5 7.3 7.3 7.1 6.3 5.9 6.7 7.1 7.0 7.0 6.8 5.9 5.4 5.8 5.9 5.7 5.7 5.6 4.8 4.5 5.1 5.6 5.5 5.5 5.5 4.6 3.7 3.7 4.6 5.4 5.5 5.6 5.8 5.3 4.8 5.1 5.8 5.8 5.7 5.8 5.3 4.2 4.2 4.7 5.4 5.8 5.7 5.3 5.1 5.4 5.8 5.7 5.1 3.9

No. Date Revisions


6.0 5.9 5.7 6.4 7.3 7.4 7.4 6.8 6.1 6.3 6.8 6.5 6.1 6.7 6.4 5.9 6.1 6.6 6.3 5.9 6.2 5.7 5.1 5.3 5.9 5.4 5.1 5.7 5.6 5.0 5.0 5.5 5.1 4.1 4.1 5.1 5.5 5.0 5.0 5.7 5.8 5.3 5.7 5.9 5.3 5.2 5.6 5.3 3.7

G-1 G-1 G-1 G-1 G-1 G-1 G-1


5.8 5.6 5.3 6.0
MH: 11 6.9 7.0 7.1 6.5 5.7MH:5.8
11 6.4 6.1 5.8 6.3 6.1 5.5MH:5.7
11 6.2 6.0 5.7 6.1 5.6 5.0MH: 5.3
11 5.8 5.4 5.0 5.6 5.5 4.9 MH:
4.9
11 5.4 5.0 4.0 4.1 5.0 5.4 4.9 4.911 5.6
MH: 5.7 5.2 5.6 5.8 5.3 5.1 11 5.5
MH:

POOL
5.1 5.5 5.6 5.9 6.1 5.9 6.1 6.2 5.9 5.8 5.8 5.1 4.9 5.5 5.8 5.7 5.7 5.7 5.1 4.8 5.4 5.6 5.4 5.4 5.4 4.6 4.3 4.9 5.4 5.3 5.2 5.1 4.4 3.5 3.5 4.4 5.2 5.2 5.3 5.4 5.0 4.4 4.8 5.5 5.5 5.4 5.4 ABOVE

3.7 4.6 4.9 4.9 4.6 4.3 4.5 5.0 5.2 5.0 4.5 3.8 3.7 4.1 4.7 5.0 4.9 4.4 3.8 3.6 4.0 4.6 4.9 4.7 4.1 3.5 3.2 3.7 4.3 4.7 4.6 4.1 3.3 2.7 2.7 3.2 4.1 4.6 4.7 4.4 3.7 3.3 3.6 4.2 4.6 4.7 4.3
JACUZZI
ABOVE
3.0 3.2 3.2 3.0 2.9 3.0 3.2 3.4 3.3 3.0 2.6 2.6 2.8 3.1 3.3 3.2 2.9 2.6 2.5 2.7 3.0 3.2 3.1 2.7 2.4 2.3 2.5 2.8 3.1 3.0 2.7 2.2 2.0 2.0 2.2 2.7 3.0 3.1 2.9 2.5 2.3 2.4 2.7 3.0 3.0 2.7

2.1 2.0 2.0 2.0 2.0 2.0 2.1 2.2 2.1 2.0 1.9 1.8 1.9 2.0 2.1 2.1 2.0 1.8 1.8 1.9 2.0 2.0 2.0 1.8 1.7 1.6 1.7 1.8 2.0 1.9 1.8 1.6 1.4 1.4 1.6 1.8 1.9 2.0 1.9 1.7 1.6 1.6 1.8 1.8 1.8 1.6 POOL EQUIPMENT

DESIGNED DRAWN
G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
Luminaire Schedule CHAMPLAIN TOWERS BASEMENT REV2 EM Project No.: 18217
Calculation Summary CHAMPLAIN TOWERS BASEMENT REV2 EM
BASEMENT PARKING PLAN - LIGHTING Date: 04-01-2021
Symbol Qty Label Description Lumens/Lamp LLF Lum. Watts Total Watts SCALE: 3/32"=1'-0"
Label Avg Max Min Avg/Min Max/Min Scale: AS SHOWN

21 G-1 E SVPG-140L-1675-NW-G2-5 N.A. 0.900 75.5 1585.5


Sheet Title:
Room_1_Floor 3.32 9.3 0.3 11.07 31.00
BASEMENT PARKING
CONSULTING ENGINEERS
241 N.W. SOUTH RIVER DRIVE PLAN - LIGHTING
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861
INFO@VIDALENGINEERING.COM
H.VIDAL
& ASSOCIATES VIDALENGINEERING.COM
E-1
0.9 0.9 0.9 1.2 1.2 1.2 1.2 0.9 0.9 0.8 0.7 0.6

SOUTH CONDOMINIUM
CHAMPLAIN TOWERS
1.1 1.2 1.2 1.2
1.3 1.4 1.5 1.6 1.6 1.6 1.6 1.5 1.3 1.0 0.9 0.8
1.5 1.7 1.8

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
1.7 1.8 2.0 1.9 2.0 2.0 1.9 2.0 1.7 1.3 1.1 0.8
1.9 2.7 3.1
2.3 3.0 3.3 2.7 2.2 2.3 2.7 3.4 2.9 1.8 1.1 0.8
1.7 2.4 4.0 4.9
2.5 3.7 4.0 3.1 2.2 2.1 2.9 3.9 3.5 1.9 1.1 0.8
1.5 2.4 3.9 W
W W 1.1
MH: 11 MH: 12
MH: 12
1.4 2.0 2.7 3.2

1.8 2.4 2.6 A 2.2


MH: 11
2.0 2.5 2.4 2.0

1.3 1.6 1.8 2.0 1.8 1.6

1.9 2.1 2.1 1.9 1.5 3

1.6 2.5 3.1 3.2 2.9 2.3 1.6

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


A
MH: 11
1.1 1.9 3.0 3.6 3.8 3.3 2.5 1.6

4
1.1 1.7 2.5 3.0 3.1 2.8 2.1 1.5

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
BOLLARD LIGHTS1.0 1.6 2.3 2.7 2.8 2.5 2.0 1.4

REPAIR & RESTORATION


B
MH: 3.5

0.2
1.2 1.9 2.8 3.3 3.4 3.1 2.3 1.6
B
0.1 0.6 1.4 1.9
MH: 3.5 B
MH: 3.5
6
0.1 0.3 0.6 0.9 0.8 0.6 1.0
1.3 2.1 3.2 3.8 4.0 3.5 A 2.6 1.7
MH: 11
0.2 0.2 0.2 0.5 1.0 1.5 1.1 0.6 0.6 1.1 1.5 1.0
1.2 1.9 2.7 3.2 3.3 3.0 2.3 1.6 8

1.1 1.7 2.4 2.8 2.9 2.6 2.1 1.5

1.2 1.9 2.8 3.4 3.5 3.1 2.4 1.6


A
MH: 11
1.3 2.2 3.3 4.0 4.1 3.6 2.7 1.8

1.3 2.0 2.9 3.5 3.6 3.2 2.4 1.7


9.1
1.2 1.9 2.6 3.1 3.2 2.8 2.2 1.6

1.3 2.1 3.0 3.6 3.7 3.3 2.5 1.7 0.2 0.5 0.3 0.1 0.1 0.6 1.0
B
0.3 0.1 0.0 0.1 0.5
A MH: 3.5
MH: 11 0.7 1.4 0.8 0.6 1.1 2.0 1.7 1.6 0.6 0.2 0.2 0.9

1.3 2.2 3.2 3.9 4.0 3.5 2.6 1.7


BOLLARD LIGHTS
B
1.3 1.5 1.2 0.5 0.6 1.0 1.1 0.7 0.3 0.1 0.1 0.5
MH: 3.5
B
B
1.2 MH:1.5
3.5 1.2 0.4 0.2 0.3 0.3 0.2 0.1 0.1 0.2 0.6 1.4 1.9 1.5 0.7 0.3 0.3 1.2 1.5 1.6 2.0 0.5
MH: 3.5
1.2 1.9 2.6 3.1 3.1 2.8 2.1 1.5
0.8 1.5 0.7 0.3 0.1 0.1 0.1 0.1 0.0 0.0 0.1 0.3 0.6 0.8 1.0 0.5 0.4 0.4 0.9 1.7 1.9 1.7 1.7
11.1 SEAL License: 0000000
Expires: 00/00/00

1.2 1.6 2.2 2.5 2.6 2.3 1.8 1.4 1.2 0.8 0.4 0.4 0.6 0.7 0.6 1.0 1.8 1.2 0.5 0.1 0.2 0.8 1.8 1.1 0.5 0.1 0.1 0.6 1.5 1.7 0.7 0.1 0.1 0.6 1.3 1.8 0.8 0.2 0.1 0.5 1.0 1.8 0.9 0.2 0.1 0.5 1.1 1.8 0.9 0.2
B B B B B B
MH: 3.5 MH: 3.5 MH: 3.5 MH: 3.5 MH: 3.5 MH: 3.5
1.5 1.6 0.6 0.2 0.2 0.3 0.7 1.6 1.4 1.9 1.2 0.5 0.6 1.5 1.4 1.8 1.2 0.5 0.6 1.4 1.6 1.6 1.4 0.6 0.5 1.3 1.8 1.4 1.5 0.6 0.5 1.2 1.9 1.4 1.6 0.7 0.5 1.2 1.9 1.3 1.6 0.6

1.3 1.8 2.5 2.9 3.0 2.7 2.1 1.5 1.3 1.7 1.8 1.5 1.5 1.7 1.7 1.1 PRELIMINARY
1.3 1.4 1.5 B
1.5 1.9 POOL DECK
0.7 0.2 0.1 0.1 0.3 0.8 1.2 1.1 0.6 0.3 0.3 0.7 1.2 1.1 0.6 0.3 0.3 0.7 1.2 1.2 0.7 0.3 0.3 0.6 1.1 1.2 0.7 0.3 0.3 0.6 1.1 1.2 0.8 0.4 0.3 0.6 1.1 1.2 0.8 0.3
MH: 3.5

1.9 1.2 0.5 0.1 0.0 0.0 0.1 0.3 0.4 0.4 0.2 0.1 0.1 0.3 0.4 0.4 0.2 0.1 0.1 0.2 0.4 0.4 0.2 0.1 0.1 0.2 0.4 0.4 0.3 0.1 0.1 0.2 0.4 0.4 0.3 0.1 0.1 0.2 0.4 0.4 0.3 0.1
NOT FOR
1.8 2.0 2.1 2.0 1.9 1.8 1.5 2.2 3.1 3.7 3.8 3.3
A
2.4 1.6 1.8 2.4 2.6 2.1 2.0 2.4 2.4 1.7
0.6 0.7 0.5 0.3 0.1 0.1 0.1 0.2 0.3 0.3 0.2 0.3 0.3 0.1 0.1 0.1 0.2 0.3 0.3 0.1 0.1 0.3 0.3 0.2 0.1 0.1 0.1 0.3 0.0 0.1 0.3 0.3 0.2 0.1
CONSTRUCTION
MH: 11
2.4 2.8 3.0 2.8 2.6 2.5 2.2 2.0 1.8 1.5 2.1 2.8 3.3 3.4 3.0 2.3 1.6 2.1 2.9 3.0 2.4 2.3 2.8 2.8 2.0 0.4 0.8 1.0 0.9 0.5 0.2 0.3 0.6 1.0 0.9 0.6 1.0 0.9 0.5 0.2 0.2 0.6 1.0 1.1 0.2 0.5 0.9 0.9 0.6 0.2 0.2 0.5 0.9 0.1 0.5 0.9 1.0 0.6 0.2
13.1
0.6 1.4 1.2 1.5 1.0 0.4 0.6 1.3 1.3 1.6 1.3 1.3 1.5 1.1 0.5 0.5 1.2 1.5 1.7 0.4 1.1 1.5 1.3 1.3 0.6 0.4 1.0 1.5 0.3 1.0 1.5 1.2 1.3 0.6

2.3 3.1 3.9 4.1 3.8 3.4 3.2 2.8 2.5 2.1 1.7 1.5 1.3 1.7 2.1 2.2 2.3 2.2 1.8 1.5 2.1 2.7 2.8 2.4 2.3 2.6 2.6 1.9
0.1 0.2 B 0.1 0.0 0.0 0.0 0.1 0.2 B 0.2 0.1 0.1 0.0 0.1 0.2 B 0.1 0.0 0.0 0.0 0.1 0.2 B0.3 0.2 0.1 0.0 0.0 0.1 B0.1 0.1 0.0 0.0 0.1 0.2 0.6
B 0.3 0.1 0.0 0.0 0.1 0.1
B 0.1 0.0
MH: 3.5 MH: 3.5 MH: 3.5 MH: 3.5 MH: 3.5 MH: 3.5 MH: 3.5
1.5 1.8 1.9 1.0 0.4 0.6 1.4 1.9 1.9 1.1 0.5 0.6 1.3 1.9 1.9 1.1 0.5 0.5 1.2 1.9 1.9 1.3 0.5 0.5 1.1 1.9 1.9 1.3 0.5 0.4 1.0 1.9 1.9 1.5 0.6 0.5 1.0 1.9 1.8 1.4 0.5
3.7 5.0 5.2 4.8 4.0 3.8 3.3 2.9 2.4 1.9 1.5 1.4 1.4 1.5 1.7 1.8 1.8 1.7 1.5 1.6 1.6 1.5 1.5 1.6 1.7 1.7 2.0 2.4 2.5 2.2 2.1 2.3 2.1 1.6
0.7 1.0 0.9 0.5 0.2 0.3 0.6 1.0 0.9 0.5 0.2 0.3 0.6 1.0 0.9 0.5 0.2 0.2 0.6 0.9 0.9 0.6 0.2 0.2 0.5 0.9 1.0 0.6 0.2 0.2 0.5 0.9 1.0 0.6 0.3 0.2 0.5 0.9 1.0 0.6 0.3

4.9 4.1 4.2 3.8 3.4 2.8 2.1 1.6 1.4 1.4 1.5 1.8 2.1 2.3 2.0 2.0 2.1 2.2 1.9 1.9 2.1 2.2 2.1 2.2 2.6 2.6 2.3 2.2 2.3 2.2 1.7 0.2 0.3 0.3 0.2 0.1 0.1 0.2 0.3 0.3 0.2 0.1 0.1 0.2 0.3 0.3 0.2 0.1 0.1 0.2 0.3 0.3 0.2 0.1 0.1 0.1 0.3 0.3 0.2 0.1 0.1 0.1 0.3 0.3 0.2 0.1 0.1 0.1 0.2 0.3 0.2 0.1

SA
0.3 0.5 0.4 0.2 0.1 0.1 0.3 0.5 0.4 0.2 0.1 0.1 0.3 0.5 0.4 0.2 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
MH: 12 Structural Engineers | Remediation & Parking Consultants
2.1 3.6 4.1 3.8 3.2 2.4 1.8 1.5 1.5 1.6 2.1 2.8 3.1 2.7 2.6 3.0 3.1 2.6 2.5 3.0 3.2 2.7 2.7 3.2 3.3 2.7 2.6 2.9 2.8 2.1 206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
0.9 1.2 1.1 0.6 0.2 0.4 0.8 1.2 1.1 0.7 0.3 0.3 0.8 1.2 1.1 0.7 0.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.
1.6 1.1 1.3 1.2 0.5 0.7 1.5 1.1 1.2 1.3 0.5 0.6 1.5 1.1 1.2 1.3 0.4 0.1 0.0 0.0 0.0 0.0
3.1 4.9 4.6 3.7 2.7 2.1 1.7 1.5 1.8 2.5 3.4 3.8 3.2 3.1 3.8 3.9 3.2 3.1 3.8 4.0 3.3 3.2 3.9 3.9 3.2 3.0 3.5 3.5 2.5
B B B
1.7 1.3 1.3 1.0 0.3 0.4 1.6 1.3 1.3 1.1 0.3 0.4 1.5 1.3 1.2 1.2 0.3 0.0 0.0 0.0 0.0 0.0
MH: 3.5 MH: 3.5 MH: 3.5
No. Date Revisions
5.2 4.1 3.0 2.2 1.7 1.6 1.8 2.6 3.7 4.1 3.4 3.3 4.1 4.2 3.4 3.3 4.1 4.3 3.5 3.4 4.1 4.2 3.3 3.1 3.7 3.7 2.6 1.3 1.9 1.7 0.9 0.4 0.5 1.2 1.8 1.7 0.9 0.4 0.5 1.1 1.8 1.7 0.9 0.3 0.1 0.0 0.0 0.0 0.0

0.5 0.8 0.7 0.4 0.2 0.2 0.5 0.7 0.7 0.4 0.2 0.2 0.5 0.7 0.7 0.4 0.1 0.0 0.0 0.0 0.0 0.0
SA
1.7 1.7 2.5 3.5 3.9 3.2 3.2 3.9 4.0 3.3 3.2 3.9 4.1 3.3 3.2 3.9 3.9 3.1 2.9 3.5 3.5 2.5
MH: 12 5.2 4.0 2.9 2.2 1.6 0.1 0.2 0.2 0.2 0.1 0.1 0.1 0.1 0.2 0.2 0.1 0.0 0.2 0.2 0.3 0.2 0.1 0.0 0.0 0.0 0.0 0.1 0.1

0.0 0.2 0.2 0.2 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.2 0.2 0.2 0.2 0.0 0.0 0.0 0.2 0.2
3.8 3.2 2.5 1.9 1.6 1.4 1.6 2.1 2.9 3.2 2.7 2.6 3.2 3.3 2.7 2.6 3.2 3.3 2.7 2.7 3.2 3.2 2.6 2.4 2.8 2.8 2.0

SIGN LIGHT 0.0 0.4 0.3 0.3 0.2 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.4 0.4 0.4 0.4 0.0 0.0 0.0 0.0 0.0 0.2 0.2 0.3 0.3 0.4

1.9 2.4 1.9 1.6 1.4 1.2 1.2 1.6 2.0 2.1 1.9 1.9 2.2 2.2 1.9 1.9 2.2 2.2 1.9 1.9 2.2 2.1 1.8 1.7 1.9 1.8 1.4 0.0 0.6 0.5 0.4 0.3 0.1 0.1 0.0 0.0 0.0 0.8 0.7 0.8 0.0 0.0 0.1 0.5 0.5 0.6 0.7

C 0.0 1.1 0.7 0.5 0.3 0.2 0.1 0.2 0.0 0.0 1.1 1.1 1.3 0.4 0.2 0.1 0.6 0.8 1.0 1.1
MH: 0.25
0.7 1.4 1.5 1.3 1.1 0.9 1.2 1.2 1.2 1.2 1.3 1.3 1.2 1.2 1.3 1.3 1.2 1.2 1.2 1.1 1.0 1.1 1.0
0.0 1.5 0.9 0.6 0.3 0.1 0.1 0.2 0.4 0.7 1.1 1.1 1.7 1.4 0.9 0.5 0.2 0.1 0.1 0.2 0.4 0.7 1.0 1.6 1.2 1.1 1.0 1.4 1.5 0.9 0.5 0.3 0.2 0.2 0.4 0.7 1.2 1.6 1.1

A A A A
MH: 5 MH: 5 MH: 5 MH: 5

DESIGNED DRAWN
(4) COLUMN LIGHTS EC EC

R S T A.1 B.2 D.1 F.1 G.1 I FIRST FLOOR PARKING PLAN - LIGHTING CHECKED
RJM
APPROVED
FPM
SCALE: 3/32"=1'-0"
Project No.: 18217
Luminaire Schedule Calculation Summary Luminaire Schedule Calculation Summary
Date: 11/03/2020
Symbol Qty Label Description Lumens/Lamp LLF Lum. Watts Total Watts Label Avg Max Min Avg/Min Max/Min Project: CHAMPLAIN TOWERS SOUTH - POOL AREA_REV 1 02/02/2021 Project: CHAMPLAIN TOWERS SOUTH - POOL AREA_REV 1 02/02/2021

Scale: 3/32" = 1'-0"


269 A SC24-5_0_DRY_A 93.5 1.000 5.42 1457.98 G_Planar 2.46 5.4 1.0 2.46 5.40 Label Units Avg Max Min
Symbol Qty Label Arrangement Manufacturer Description Luminaire Lumens LLF Luminaire Watts Assembly Watts CalcType Avg/Min Max/Min
Sheet Title:
3 W VSX-1-T4-48LC-5-TS-UNV N.A. 0.900 78 234 OPEN PARKING & ENTRANCE_Planar 2.50 5.2 0.7 3.57 7.43
4 A SINGLE Luminis Canada Inc. SR135-L2W18K2A-xxx-BKT-APS MH: COLUMN MOUNT A.F.F. (bottom of fixture) 4493 0.148 34 34 POOL DECK Illuminance Fc 0.56 2.0 0.0 N.A. N.A.
FIRST FLOOR PARKING
CONSULTING ENGINEERS
2 SA ECF-S-64L-600-AM-G2-4 N.A. 1.000 93.9 187.8 OPEN PARKING_Planar_1 1.80 4.0 0.6 3.00 6.67
24 B SINGLE Luminis Canada Inc. MA30 L1W112A-R5 MH: 42'' BOLLARD 274 0.855 11.3 11.3 TOP LEFT AREA Illuminance Fc 0.75 1.9 0.1 7.50 19.00 241 N.W. SOUTH RIVER DRIVE PLAN - LIGHTING
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
1 C SINGLE Lithonia Lighting DSXF1 LED P2 30K WFL MVOLT IS xxx MH: GROUND MOUNT A.F.G. 4753 0.855 42 42 CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861

H.VIDAL
& ASSOCIATES
INFO@VIDALENGINEERING.COM

VIDALENGINEERING.COM
E-2
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
MAINTENANCE MAINT.

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


STAIRS

RAMP UP

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
MAINTENANCE
ROOM

ELEV.

VESTIBULE
ELEV.

STAIRS
SEAL Henry A. Vidal, P.E.
PE #56204

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

POOL

JACUZZI

POOL EQUIPMENT DESIGNED DRAWN


G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
Project No.: 18217

Date: 04-01-2021

Scale: AS SHOWN
BASEMENT PARKING PLAN - POWER Sheet Title:
SCALE: 3/32"=1'-0" BASEMENT PARKING
CONSULTING ENGINEERS
241 N.W. SOUTH RIVER DRIVE PLAN - POWER
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861
INFO@VIDALENGINEERING.COM
H.VIDAL
& ASSOCIATES VIDALENGINEERING.COM
E-3
A B D E H I K L M N O O.1 P
8"

SOUTH CONDOMINIUM
CHAMPLAIN TOWERS
9'-0" 21'-0" 14'-6" 23'-0" 14'-6" 23'-0" 21'-6" 22'-6" 19'-8" 20'-4" 10'-4"

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
EX. WALL BELOW

1 1

8"
EL.124'-2"± 1.1
21'-0"

24'-4"
2
STAIR #2
3

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


13'-8"
22'-4"

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
4

REPAIR & RESTORATION


5

14'-6"
11'-0"

6
7

7'-6"
8
17'-6"

EX. WALL BELOW

ELEV.

22'-0"
EL.124'-2"±
9
12'-6"

ELEV. 9.1

8"
SEAL Henry
License:
A. Vidal,
0000000
P.E.
PEExpires:
#5620400/00/00
10
11 STAIR #1
17'-6"

12
12'-6"

EL.124'-2"±
Structural Engineers | Remediation & Parking Consultants
206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

13
No. Date Revisions
12'-0"

14
24'-0"

DESIGNED DRAWN
G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
Project No.: 18217

Date: 04-01-2021
15
Scale: AS SHOWN
EX. WALL BELOW
PENTHOUSE II - LOWER ROOF PLAN Sheet Title:
1
SCALE: 8"=1'-0"
CONSULTING ENGINEERS PENTHOUSE FLOOR
241 N.W. SOUTH RIVER DRIVE PLAN / LOWER ROOF
MIAMI, FL 33128
24'-4" 23'-8" 13'-6" 22'-6" HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861
A C F G J
H.VIDAL
& ASSOCIATES
INFO@VIDALENGINEERING.COM

VIDALENGINEERING.COM
E-4
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
SEAL Henry A. Vidal, P.E.
PE #56204

GENERATOR ROOM PLAN MAIN ELECTRICAL ROOM PLAN Structural Engineers | Remediation & Parking Consultants
206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
SCALE: 1/4" = 1'-0" SCALE: 1/2" = 1'-0" © Copyright Morabito Consultants, Inc.

No. Date Revisions

DESIGNED DRAWN
G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
Project No.: 18217

Date: 04-01-2021

Scale: AS SHOWN
Sheet Title:
GENERATOR ROOM
CONSULTING ENGINEERS
241 N.W. SOUTH RIVER DRIVE PLAN
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861

H.VIDAL
& ASSOCIATES
INFO@VIDALENGINEERING.COM

VIDALENGINEERING.COM
E-5
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
SCOPE OF WORK (ELECTRICAL ROOM) NOTE: ALL EXISTING EQUIPMENT IS TO
EXISTING SERVICE MAINS WILL BE REMOVED. REMAIN UNLESS OTHERWISE NOTED
SERVICE MAINS WILL BE COMPILED AND
RELABELED ACCORDINGLY UNDER NEW WORK.
REFER TO ELECTRICAL RISER DIAGRAM

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
SEAL Henry A. Vidal, P.E.
PE #56204

NOTE: FIRE PUMP INSTALLATION TO COMPLY


WITH NEC 2017 ART 695 AND NFPA 20.

NOTE: GENERATOR APPLICATION SHALL


COMPLY WITH NEC 2017 ART 700, NFPA 110
LATEST EDITION AND THE STANDARD U.L. 2200

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

DESIGNED DRAWN
G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
Project No.: 18217

Date: 04-01-2021

Scale: AS SHOWN
Sheet Title:
ELECTRICAL NOTES
CONSULTING ENGINEERS
241 N.W. SOUTH RIVER DRIVE
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861
INFO@VIDALENGINEERING.COM
H.VIDAL
& ASSOCIATES VIDALENGINEERING.COM
E-6
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
SEAL Henry A. Vidal, P.E.
PE #56204

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

DESIGNED DRAWN
G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
Project No.: 18217

Date: 04-01-2021

Scale: AS SHOWN
Sheet Title:
ELECTRICAL
CONSULTING ENGINEERS
241 N.W. SOUTH RIVER DRIVE GEAR SPECIFICATIONS
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861
INFO@VIDALENGINEERING.COM
H.VIDAL
& ASSOCIATES VIDALENGINEERING.COM
E-7
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS
- A.
50% - A.
1 200%

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING
10.9 9.0 9.4

29.3 81

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
- A. - A. - A.
50% - A. 50% - A. 50% - A.
1 200% 1 200% 4X 200%

SEAL Henry A. Vidal, P.E.


PE #56204

5.6 4.8 4.8 5.9 3.0 7.3 5.0 5.0 5.0

15.2 42 16.2 45 15.0 42

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

DESIGNED DRAWN
G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
Project No.: 18217

Date: 04-01-2021

Scale: AS SHOWN
Sheet Title:
ELECTRICAL PANELS
CONSULTING ENGINEERS
241 N.W. SOUTH RIVER DRIVE
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861
INFO@VIDALENGINEERING.COM
H.VIDAL
& ASSOCIATES VIDALENGINEERING.COM
E-8
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
SEAL Henry A. Vidal, P.E.
PE #56204

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

DESIGNED DRAWN
G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
Project No.: 18217

Date: 04-01-2021

Scale: AS SHOWN
Sheet Title:
ELECTRICAL DETAILS
CONSULTING ENGINEERS
241 N.W. SOUTH RIVER DRIVE
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861
INFO@VIDALENGINEERING.COM
H.VIDAL
& ASSOCIATES VIDALENGINEERING.COM
E-9
GENERAL NOTES

SOUTH CONDOMINIUM
CHAMPLAIN TOWERS
1.- FIRE PROTECTION MATERIALS, DESIGNS & HYDRAULIC CALCULATIONS SHALL
COMPLY WITH APPLICABLE CODES AND STANDARDS. ALL DRAWINGS ILLUSTRATING
FIRE PROTECTION SHALL COMPLY TO NFPA 13, 14, 20, 24, THE FLORIDA STATE FIRE

SURFSIDE, FLORIDA 33154


PREVENTION CODE, AND THE AUTHORITY HAVING JURISDICTIONS (AHJ) MINIMUM

8777 COLLINS AVENUE


REQUIREMENTS FOR INSTALLING FIRE SPRINKLER SYSTEM. REFER TO APPLICABLE
CODES ( THIS SHEET) FOR ANY SPECIAL CONDITIONS AND/OR ADDITIONAL
REQUIREMENTS THAT SHALL BE CONSIDERED.

2.- CONTRACTOR SUBMITTAL PACKAGE SHALL BE SUBMITTED , COORDINATED AND


APPROVED BY THE ARCHITECT/ENGINEER OF RECORD, PRIOR TO SUBMITTING
SHOP DRAWINGS, HYDRAULIC CALCULATIONS, & EQUIPMENT DATA SHEETS TO THE
AHJ FOR FINAL APPROVAL PERMITTING PURPOSES.

3.- AFTER AS BUILTS ARE APPROVED BY THE ENGINEER OF RECORD, THE


CONTRACTOR SHALL RECEIVE CONTRACT CONFIRMATION COMPLIANCE
DOCUMENTATION. THE CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY BY
PROVIDING THE ENGINEER/ARCHITECT OF RECORD AN ADDITIONAL COMPLETE SET
OF SHOP DRAWINGS MODIFIED SHOP DRAWINGS OR AS BUILTS AND HYDRAULIC
CALCULATIONS INCLUDING ANY AND ALL ADDITIONAL FITTINGS THAT MAY BE
ADDED DUE TO COORDINATION ISSUES.

4.- PIPE ROUTING SHOWN IS FOR INFORMATION ONLY. IT IS THE RESPONSIBILITY OF


THIS CONTRACTOR TO PROVIDE ANY ADDITIONAL MODIFICATIONS TO THE
EXISTING FIRE SPRINKLER SYSTEM AND HYDRAULIC CALCULATIONS, AS REQUIRED
FOR COMPLAINT MATERIAL INSTALLATION AND COORDINATION WITH OTHER
TRADES.

5.- PIPING IN AREAS WITH EXPOSED STRUCTURE SHALL BE INSTALLED AS HIGH AS


POSIBLE TO ALOW THE OWNER MAXIMUM USE OF THE SPACE.

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


6.- CONTRACTOR SHALL SLEEVE AND/OR FIRESTOP ALL PENETRATIONS THROUGH
RATED WALLS, CEILINGS AND FLOORS WITH UL/LISTED ASSEMBLIES. FIRESTOP
ASSEMBLIES SHALL BE EQUAL OR EXCEED THE RATING OF THE WALL, CEILING OR
FLOOR.

APPLICABLE CODES AND STANDARDS

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
FLORIDA ADMINISTRATIVE CODE 61G15-32.003 A-M (LATEST REVISION)

REPAIR & RESTORATION


FLORIDA BUILDING CODE
NFPA 1
NFPA 13 (2013 EDITION)
NFPA 14 (2013 EDITION)
NFPA 24 (2013 EDITION)

SCOPE OF WORK
PROJECT CONSIST IN REPLACING THE EXISTING FIRE PUMP WITH A NEW ELECTRIC FIRE
PUMP THAT MEETS NEW CODE REQUIREMENTS. NEW PUMP SHALL BE 750 GPM @ 130 PSI
WITH TRANSFER SWITCH. VOLTAGE SHALL BE 208
3 PHASE. CONTRACTOR SHALL SUBMIT
FIRE PUMP AND CONTROLERS SPECS PRIOR CITY PERMIT SUBMITTAL. INSTALL NEW
PRESSURE REDUCING VALVES WHERE PRESSURE EXCEEDS 175 PSI. INSTALL NEW
BACKFLOW PREVENTER TO MEET NEW CODE REQUIREMENTS.

SEAL Henry A. Vidal, P.E.


PE #56204

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

HANGER SCHEDULE
NOMINAL PIPE SIZE (in.)
STANDPIPE #1 SCALE 81" = 1'-0"
STANDPIPE #2 SCALE 81" = 1'-0"

WATER SUPPLY INFORMATION


STATIC: 55 DESIGNED DRAWN
RESIDUAL: 45 G.V. / H.O. G.V. / H.O.
FLOW 1400 CHECKED APPROVED
LOCATION: H.V. H.V.
TEST BY:
TIME: 10:00 AM Project No.: 18217
DATE:
Date: 04-01-2021

Scale: AS SHOWN
Sheet Title:
FIRE PROTECTION NOTES,
FIGURE A.9.2.3.5 FIGURE A.9.2.3.5.2 CONSULTING ENGINEERS
MAXIMUM LENGTH FOR UNSUPPORTED ARMOVER N.T.S. MAXIMUM LENGTH OF UNSUPPORTED AMROVER WHERE
THE MAXIMUM PRESSURE EXCEEDS 100 PSI (6.9 bar)
N.T.S.
241 N.W. SOUTH RIVER DRIVE SCHEDULES AND DETAILS
AND A BRANCH LINE ABOVE A CEILING SUPPLIES PENDENT
MIAMI, FL 33128
FIRE SPRINKLER CONTRACTOR SHALL SPRINKLERS BELOW CEILING

HENRY VIDAL, P.E., PE #56204


CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
SUBMIT SHOP DRAWINGS FOR APPROVAL AND PERMITTING PHONE: (305) 571-1860 FAX: (305)571-1861
INFO@VIDALENGINEERING.COM
H.VIDAL
& ASSOCIATES VIDALENGINEERING.COM
FP-1
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
SEAL License: 0000000
Expires: 00/00/00

PRELIMINARY
NOT FOR
CONSTRUCTION

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

DESIGNED DRAWN
EC EC
CHECKED APPROVED
R S T A.1 B.2 D.1 F.1 G.1 I RJM FPM
Project No.: 18217

Date: 11/03/2020

Scale: 3/32" = 1'-0"


Sheet Title:
FIRST FLOOR PLAN - FIRE
FIRST FLOOR PARKING PLAN - FIRE PROTECTION CONSULTING ENGINEERS
241 N.W. SOUTH RIVER DRIVE PROTECTION
MIAMI, FL 33128
SCALE: 3/32"=1'-0" HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861

H.VIDAL
& ASSOCIATES
INFO@VIDALENGINEERING.COM

VIDALENGINEERING.COM
FP-2
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
AIRFLOW
AIRFLOW
TOP VIEW

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


63.79 SQ.
INLET 91.99

5.43 76.00 5.43

91.99

PHASE IIC: OVERALL BUILDING


END VIEW SIDE VIEW

REPAIR AND RESTORATION


REPAIR & RESTORATION
DUCT DIMENSIONS ARE LARGEST POSSIBLE DUCT TO FIT THROUGH CURB.
CONSULT SYSTEM DESIGN ENGINEER FOR RECOMMENDED DUCT SIZE.

OVERALL HEIGHT MAY BE GREATER DEPENDING ON MOTOR, ADAPTER, AND/OR


HINGE BASE.

SEAL Henry A. Vidal, P.E.


PE #56204

CAJ1047

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

DESIGNED DRAWN
G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
Project No.: 18217

Date: 04-01-2021

Scale: AS SHOWN
Sheet Title:
MECHANICAL NOTES
CONSULTING ENGINEERS
241 N.W. SOUTH RIVER DRIVE AND SCHEDULES
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861
INFO@VIDALENGINEERING.COM
H.VIDAL
& ASSOCIATES VIDALENGINEERING.COM
M-0
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
MAINTENANCE MAINT.

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


STAIRS

RAMP UP

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
MAINTENANCE
ROOM

ELEV.

VESTIBULE
ELEV.

STAIRS
SEAL Henry A. Vidal, P.E.
PE #56204

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

POOL

JACUZZI
AIRFLOW

POOL EQUIPMENT DESIGNED DRAWN


AIRFLOW AIRFLOW
G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
1. EXISTING BUILDING FRAMING AND CONDITIONS INDICATED ON PLAN ARE BASED ON 5. THE REPAIR CONTRACTOR SHALL SUBMIT A CONSTRUCTION SCHEDULE WITH
EXISTING DRAWINGS PREPARED BY WILLIAM M. FRIEDMAN & ASSOCIATES PHASING AND TRAFFIC CONTROL PLANS TO OWNER AND ENGINEER FOR REVIEW Project No.: 18217
ARCHITECTS, INC AND BREITERMAN JUARDO & ASSOCIATES, DATED 08-22-1979 AND A AND APPROVAL PRIOR TO COMMENCEMENT OF WORK.
LIMITED FIELD INVESTIGATION CONDUCTED BY MORABITO CONSULTANTS. EXISTING STANDARD PARKING THIS LEVEL = 120 SPACES
CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND CONTACT MORABITO Date: 04-01-2021
CONSULTANTS PRIOR TO CONSTRUCTION IF CONDITIONS VARY FROM WHAT IS EXISTING PARKING THIS LEVEL = 120 SPACES
SHOWN ON PLAN. Scale: AS SHOWN
2. EXISTING STRUCTURE CONSISTS OF CAST-IN-PLACE CONCRETE TWO-WAY FLAT Sheet Title:
PLATE ELEVATED FLOOR SLABS BEARING ON CAST-IN-PLACE CONCRETE COLUMNS
OVER A FRAMED CONCRETE SLAB ON GRADE SUPPORTED BY PILE CAPS. MECHANICAL - HVAC
CONSULTING ENGINEERS
3. EXISTING ELEVATION TOP OF STRUCTURAL SLAB VARIES. 241 N.W. SOUTH RIVER DRIVE GARAGE PLAN
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
4. EXISTING CONDITIONS ARE SHOWN HALF-TONE. CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861
INFO@VIDALENGINEERING.COM
H.VIDAL
& ASSOCIATES VIDALENGINEERING.COM
M-1
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
SEAL Henry A. Vidal, P.E.
PE #56204

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

DESIGNED DRAWN
1. EXISTING BUILDING FRAMING AND CONDITIONS INDICATED ON PLAN ARE BASED ON 5. THE REPAIR CONTRACTOR SHALL SUBMIT A CONSTRUCTION SCHEDULE WITH G.V. / H.O. G.V. / H.O.
EXISTING DRAWINGS PREPARED BY WILLIAM M. FRIEDMAN & ASSOCIATES PHASING AND TRAFFIC CONTROL PLANS TO OWNER AND ENGINEER FOR REVIEW CHECKED APPROVED
ARCHITECTS, INC AND BREITERMAN JUARDO & ASSOCIATES, DATED 08-22-1979 AND A AND APPROVAL PRIOR TO COMMENCEMENT OF WORK. H.V.
H.V.
R S T A.1 B.2 D.1 F.1 G.1 I LIMITED FIELD INVESTIGATION CONDUCTED BY MORABITO CONSULTANTS.
CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND CONTACT MORABITO Project No.: 18217
CONSULTANTS PRIOR TO CONSTRUCTION IF CONDITIONS VARY FROM WHAT IS
SHOWN ON PLAN.
Date: 04-01-2021
2. EXISTING STRUCTURE CONSISTS OF CAST-IN-PLACE CONCRETE TWO-WAY FLAT
PLATE ELEVATED FLOOR SLABS BEARING ON CAST-IN-PLACE CONCRETE COLUMNS Scale: AS SHOWN
OVER A FRAMED CONCRETE SLAB ON GRADE SUPPORTED BY PILE CAPS.

3. EXISTING ELEVATION TOP OF STRUCTURAL SLAB VARIES.


Sheet Title:
MECHANICAL GROUND
4. EXISTING CONDITIONS ARE SHOWN HALF-TONE. CONSULTING ENGINEERS
241 N.W. SOUTH RIVER DRIVE FLOOR PLAN
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861

H.VIDAL
& ASSOCIATES
INFO@VIDALENGINEERING.COM

VIDALENGINEERING.COM
M-2
A B D E H I K L M N O O.1 P
8"

SOUTH CONDOMINIUM
CHAMPLAIN TOWERS
9'-0" 21'-0" 14'-6" 23'-0" 14'-6" 23'-0" 21'-6" 22'-6" 19'-8" 20'-4" 10'-4"

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
EX. WALL BELOW

1 1

8"
EL.124'-2"± 1.1
21'-0"

24'-4"
2
STAIR #2
3

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


13'-8"
22'-4"

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
4

REPAIR & RESTORATION


5

14'-6"
11'-0"

6
7

7'-6"
8
17'-6"

EX. WALL BELOW

ELEV.

22'-0"
EL.124'-2"±
9
12'-6"

ELEV. 9.1

8"
SEAL Henry A. Vidal,
License: P.E.
0000000
PEExpires:
#5620400/00/00
10
11 STAIR #1
17'-6"

12
12'-6"

EL.124'-2"±
Structural Engineers | Remediation & Parking Consultants
206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

13
No. Date Revisions
12'-0"

14
24'-0"

DESIGNED DRAWN
G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
Project No.: 18217

Date: 04-01-2021
15
Scale: AS SHOWN
EX. WALL BELOW
PENTHOUSE II - LOWER ROOF PLAN Sheet Title:
1
SCALE: 8"=1'-0"
LOW ROOF
CONSULTING ENGINEERS
241 N.W. SOUTH RIVER DRIVE HVAC REPLACEMENT
24'-4" 23'-8" 13'-6" 22'-6"
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
PLAN
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861
A C F G J
H.VIDAL
& ASSOCIATES
INFO@VIDALENGINEERING.COM

VIDALENGINEERING.COM
M-3
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
GENERAL PLUMBING NOTES: PLUMBING SYMBOL LEGEND

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


PLANTER DRAIN DETAIL

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
CAJ1047

TYPICAL CLEANOUT DETAIL TYPICAL CONDENSATE DRAIN TRAP DOMESTIC WATER DUPLEX PUMP
N.T.S. N.T.S. N.T.S.

SEAL Henry A. Vidal, P.E.


PE #56204

WATER METER ENCLOSURE & BACKFLOW PREVENTER DETAIL

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

DESIGNED DRAWN
G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
Project No.: 18217

Date: 04-01-2021

Scale: AS SHOWN
Sheet Title:
PLUMBING GENERAL
CONSULTING ENGINEERS
241 N.W. SOUTH RIVER DRIVE NOTES AND DETAILS
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861
INFO@VIDALENGINEERING.COM
H.VIDAL
& ASSOCIATES VIDALENGINEERING.COM
P-0
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
GAS PIPING UNDER SLAB DETAIL

14.1

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
R S

SEAL Henry A. Vidal, P.E.


PE #56204

GENERAL PLUMBING NOTES:

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

DESIGNED DRAWN
G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
Project No.: 18217

Date: 04-01-2021

Scale: AS SHOWN
Sheet Title:
NATURAL GAS
CONSULTING ENGINEERS
241 N.W. SOUTH RIVER DRIVE BASEMENT PARKING
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
PLAN
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861
INFO@VIDALENGINEERING.COM
H.VIDAL
& ASSOCIATES VIDALENGINEERING.COM
P-0A
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
MAINTENANCE MAINT.

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


STAIRS

RAMP UP

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
MAINTENANCE
ROOM

ELEV.

VESTIBULE
ELEV.

STAIRS
SEAL Henry A. Vidal, P.E.
PE #56204

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

JACUZZI

POOL EQUIPMENT DESIGNED DRAWN


G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
Project No.: 18217
EXISTING STANDARD PARKING THIS LEVEL = 120 SPACES
Date: 04-01-2021
EXISTING PARKING THIS LEVEL = 120 SPACES
Scale: AS SHOWN
Sheet Title:
PLUMBING GAS
CONSULTING ENGINEERS
241 N.W. SOUTH RIVER DRIVE GARAGE PLAN
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861
INFO@VIDALENGINEERING.COM
H.VIDAL
& ASSOCIATES VIDALENGINEERING.COM
P-1
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
MAINTENANCE MAINT.

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING


STAIRS

RAMP UP

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
MAINTENANCE
ROOM

ELEV.

VESTIBULE
ELEV.

STAIRS
SEAL Henry A. Vidal, P.E.
PE #56204

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

POOL

JACUZZI

POOL EQUIPMENT DESIGNED DRAWN


G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
Project No.: 18217
EXISTING STANDARD PARKING THIS LEVEL = 120 SPACES
Date: 04-01-2021
EXISTING PARKING THIS LEVEL = 120 SPACES
Scale: AS SHOWN
Sheet Title:
BASEMENT PARKING PLAN - GAS CONSULTING ENGINEERS
NATURAL GAS
SCALE: 3/32"=1'-0" 241 N.W. SOUTH RIVER DRIVE BASEMENT PLAN
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861
INFO@VIDALENGINEERING.COM
H.VIDAL
& ASSOCIATES VIDALENGINEERING.COM
P-1A
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


A.1 B.1 D E H I K L M 8.130
N O O.1 Q

8777 COLLINS AVENUE


CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
REPAIR & RESTORATION
SEAL Henry A. Vidal, P.E.
PE #56204

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions

DESIGNED DRAWN
G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
Project No.: 18217

Date: 04-01-2021
1.
Scale: AS SHOWN
Sheet Title:
PLUMBING - FIRST FLOOR
CONSULTING ENGINEERS
R S T A.1 B.2 D.1 F.1 G.1 I 241 N.W. SOUTH RIVER DRIVE PARKING PLAN
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861

H.VIDAL
& ASSOCIATES
INFO@VIDALENGINEERING.COM

VIDALENGINEERING.COM
P-2
SOUTH CONDOMINIUM
CHAMPLAIN TOWERS

SURFSIDE, FLORIDA 33154


8777 COLLINS AVENUE
1.1

2.1

CHAMPLAIN TOWERS SOUTH 40-YEAR BUILDING

PHASE IIC: OVERALL BUILDING


REPAIR AND RESTORATION
5

REPAIR & RESTORATION


8.1

10.1

SEAL Henry A. Vidal, P.E.


PE #56204

12.1

14

Structural Engineers | Remediation & Parking Consultants


206 Via Condado Way | Palm Beach Gardens, FL 33418-1701
561.316.7660 | www.morabitoconsultants.com
© Copyright Morabito Consultants, Inc.

No. Date Revisions


14.1

1.
DESIGNED DRAWN
G.V. / H.O. G.V. / H.O.
CHECKED APPROVED
H.V. H.V.
R S T A.1 B.2 D.1 F.1 G.1 I
Project No.: 18217

Date: 04-01-2021

Scale: AS SHOWN
Sheet Title:
FIRST FLOOR PARKING PLAN - GAS CONSULTING ENGINEERS
NATURAL GAS - FIRST
SCALE: 3/32"=1'-0" 241 N.W. SOUTH RIVER DRIVE FLOOR PARKING PLAN
MIAMI, FL 33128
HENRY VIDAL, P.E., PE #56204
CERTIFICATION OF AUTHORIZATION #9056
Sheet No.:
PHONE: (305) 571-1860 FAX: (305)571-1861

H.VIDAL
& ASSOCIATES
INFO@VIDALENGINEERING.COM

VIDALENGINEERING.COM
P-2A
88th STREET

1A)
2

DA
F.F.E.= 10.89'
3
GARAGE

OA
ELEV.: -0.28

ER
AT
(S T

MULTISTORY BUILDING
4 No. 8777
UE

8777 Collins Avenue, Surfside, FL 33154


N
VE

F.F.E.= 11.08'
SA

F.F.E.= 10.89'
6
LIN

7 8

TREE DISPOSITION PLAN


F.F.E.= 10.83'
L
CO

13

F.F.E.= 10.91'
9

11
10

12

Landscape Architecture-Planning, P.A.


412 North Andrews Avenue
Fort Lauderdale, FL 33301
Flo r id a L ic e ns e Nu mb er LA 39 3
Fax 954 / 462-0722
Phone 954 / 462-0704

87th TERRACE rrla@rhettroy.com

NOTE: ALL BASE INFORMATION


TREE DISPOSITION LEGEND
INDICATES EXISTING CONDITIONS FROM
LOCATION OF EXISTING PALM
SURVEY BY J. BONFILL & ASSOC. 8/7/2020

3 TREE NUMBER

NORTH
0 16' 32'
GRAPHIC SCALE
LS. HARDSCAPE MATERIALS LEGEND
PAVER CONCRETE PAVERS BY BELGARD -2 3/8" THICK, SAND
BORDER SET ON CONCRETE SLAB (UNLESS NOTED OTHERWISE)
SERVICE LANDSCAPE
LS. DRIVEWAY / PARKING / PLAZA - HOLLAND STONE 4"x8"
LANDSCAPE GARAGE ACCESS C A HERRINGBONE PATTERN FIELD, COLORS CHARCOAL,
PRIVATE PATIO SLATE & GRAY (33% EA.) WITH 4"x8" SOLDIER COURSE
LANDSCAPE A BORDERS, RANDOM EVEN COLOR DISTRIBUTION.

POOL DECK - MODULINE 3"X12" STAGGERED RUNNING


B BOND PATTERN, COLORS 40% WHITE, 30% PEWTER,
30% GRAY, WITH 4"x8" SOLDIER COURSE BORDERS
RANDOM EVEN COLOR DISTRIBUTION.

PRIVATE PATIOS - OCEANSIDE 8"x8" STACKED BOND


D C PATTERN FIELD, COLOR CREAM WITH 4"x8" SOLDIER
COURSE BORDERS.

STEPS / RISERS - COPING 4"x9" TREAD WITH CUT


D HOLLAND STONE INFILL & RISERS, COLOR CREAM .
PAVER MUD SET ON SLAB
BORDER
C E STEPS / RISERS - COPING 4"x9" TREAD WITH CUT
HOLLAND STONE INFILL & RISERS, COLOR PEWTER.
LS. MUD SET ON SLAB

LANDSCAPE NOTE: CONTRACTOR SHALL INSTALL A 4' MIN. SQ. AREA OF EACH
PAVER TYPE A, B & C FOR OWNER APPROVAL PRIOR TO ORDER
AND INSTALL. SAMPLES OF STEP TREADS SHALL ALSO BE
PROVIDED FOR APPROVAL BY OWNER.
A
SLOPED WALKWAY
D

LS.
LS.
C
PRIVATE PATIO
A
A

8777 Collins Avenue, Surfside, FL 33154


PLAZA
PORTE COCHERE LS. C PRIVATE PATIO EAST GARDEN (NOT
IN CONTRACT)
LS.
E B
E
LS.
B LS.
D LS. LS.
LANDSCAPE
D

RESIDENTIAL TOWER POOL DECK

PAVER
BORDER
ENTRY DRIVE

HARDSCAPE PLAN
A
B

B POOL DECK

PAVER
BORDER

LANDSCAPE PAVILION -
SEE SWIMMING POOL
SKETCH
RAISED A
SIGN WALL SPA
PARKING B

LS.

Landscape Architecture-Planning, P.A.


412 North Andrews Avenue
Fort Lauderdale, FL 33301
Flo r id a L ic e ns e Nu mb er LA 39 3
Fax 954 / 462-0722
Phone 954 / 462-0704
rrla@rhettroy.com

NORTH
1 PAVILION SKETCH (FOR BIDDING ONLY) 0 16' 32'
LH-1 SCALE: NONE GRAPHIC SCALE
34
FGI
2
PHT
3 4
SP FGI
80 45
NER CES VENT

FUEL
VENT
TANK
84 GARAGE ACCESS
SCH
1 PRIVATE PATIO
PE
46
FGI
54
FGI
B 12 1
CLU CS
B 22 67
B 7 FGI SCT
1 7
CLU CS CLU
2 132
CS SCT
44 19 37
RAP CLU CES
11
MOUND UP TO 3' SOIL FGI
27
DEPTH -TYP. AT TREE FGI
ROOTBALLS 21
B B SCT
11
41 B FGI
FGI 10
59
FGI
RAP
1
VM

34
SAN
7
57
CLU
FGI 2
2
CS
PHT 44
RUE EAST GARDEN (NOT
13
IN CONTRACT)

8777 Collins Avenue, Surfside, FL 33154


SCH

PRIVATE PATIO
22
SCT 17
1
107 LJ 25 SCT
PORTE COCHERE PRIVATE PATIO FGI
NER 15
1
VM SCT
57
FGI VENT 11
8 1 6
SCT SCT
B VENT
VM FGI 13 7
B SCT FGI
5
B
FGI
1 6
VM FGI 4
65

LANDSCAPE PLAN
RESIDENTIAL TOWER 2 BEDS SCT 6 36
SAN
21 VM FGI 6 BEDS
CLU
97
44
RUE
ENTRY DRIVE 72 SCT
1
2 SAN
TR
3
CS
69 SP
101
FGI
1 SCH
2
PE
66 B B CS POOL DECK
85 1
RUE B SCH
3 TR
21
SP SCT
92
RAP

MOUND UP TO 3' SOIL PAVILION SWIMMING POOL


DEPTH -TYP. AT TREE
ROOTBALLS
3 36
TR FGI
SPA
6 BEDS

2 EQ. PLANT NOTES


PHT
22 1. ALL PLANTS TO BE FLORIDA NO. 1 GRADE OR BETTER.
COD 2. NO SUBSTITUTIONS WILL BE ACCEPTED WITHOUT PRIOR WRITTEN
24
FGI 58 APPROVAL BY THE LANDSCAPE ARCHITECT.
CLU 3. ALL LANDSCAPE AREAS TO RECEIVE 100% IRRIGATION COVERAGE
WITH A MINIMUM 50% OVERLAP BY AN AUTOMATIC IRRIGATION SYSTEM.
SYSTEM SHALL INCLUDE A RAIN SENSOR DEVICE. USE OF NON-POTABLE
NOTE: INSTALL SPECIFIED SOIL TO WATER (IF AVAILABLE) SHALL BE USED FROM A RUST FREE SOURCE.
18" DEPTH, 36" DEPTH 4. QUANTITIES ON PLANT LIST ARE FOR CONVENIENCE ONLY. THE
LANDSCAPE CONTRACTOR IS RESPONSIBLE FOR ALL PLANTS SHOWN ON Landscape Architecture-Planning, P.A.
SURROUNDING TREE ROOT BALLS. PLANTING PLAN(S). WHEN DISCREPANCIES OCCUR BETWEEN THE PLANT 412 North Andrews Avenue
LIST AND PLANTING PLANS, THE PLANS ARE TO OVERRIDE THE PLANT LIST IN Fort Lauderdale, FL 33301
Flo r id a L ic e ns e Nu mb er LA 39 3
ALL CASES. Fax 954 / 462-0722
SPREAD (SPR) 5. CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL UNDERGROUND Phone 954 / 462-0704
rrla@rhettroy.com
OVERALL HT. (OA)
TREE TRUNK WHERE APPLICABLE
UTILITIES PRIOR TO COMMENCING WORK.
IN 4' DIAMETER SAUCER
6. ALL SHRUB AND GROUNDCOVER BEDS SHALL BE LAID OUT IN A
REMOVE 1/2 OF LOWER
SOD / MULCH LINE UNIFORM AND CONSISTENT PATTERN AND SET IN A PERPENDICULAR LINE
FRONDS, TIE REMAINING 1/2 OC SPACING OF WHEN ABUTTING PAVEMENT OR BUILDINGS.
FRONDS TO PROTECT BUD. ADJACENT PLANT
(12" MIN) STRUCTURE, PAVEMENT, 7. ALL TREES AND PALMS TO BE STAKED AND GUYED AS INDICATED ON
A CURB, FENCE, ETC.
DEAD 'BOOTS' MAY WHERE APPLICABLE. DETAILS.
REMAIN 1-2' BELOW LIVE
CLEAR TRUNK HT. (CT) FRONDS. 8. ALL PLANTING AREAS TO RECEIVE 3" LAYER OF GRADE B SHREDDED
GROUNDCOVER (12"-18"
OC TYP) ALL EUCALYPTUS MULCH. TOP OF MULCH SHALL BE 1" BELOW ANY ADJACENT
DIMENSIONS 'B' EQUAL
PAVEMENT OR TOP OF WALL.
CLEAR TRUNK (CT) (3) 2"x4" BATTENS 9. ALL PLANTERS TO BE BACKFILLED WITH 30% PEAT / 20% SAND / 20%
120° APART MEDIUM SHRUBS (24" OC
TYP) ALL DIMENSIONS 'C' RICE ROCK / 20% PERLITE PLANTING MIXTURE. 18" DEPTH, 36" DEPTH
TRUNK FLARE SHALL BE (3) 2"W BLACK MESH POLY EQUAL
VISIBLE ABOVE EXISTING STRAPS, TIE SECURELY TO
(3) 2"x4" BRACES SURROUNDING TREE ROOT BALLS.
GRADE TOENAIL INTO BATTENS B
TREE & STAKES 10. FERTILIZER SHALL BE APPLIED AS PER MANUFACTURERS
2'R LARGE SHRUBS (30"-36"
TRUNK FLARE SHALL BE BANDING IN TWO PLACES OC TYP) ALL
3" MULCH AS SPECIFIED (3) #4 REBAR, 24"L DRIVEN VISIBLE ABOVE
PLAN C DIMENSIONS 'D' EQUAL RECOMMENDATIONS AS FOLLOWS:
BELOW GRADE EXISTING GRADE 5 LAYERS OF BURLAP D SOD 8-8-8
6" EARTHEN SAUCER
3" MULCH AS SPECIFIED ANNUALS / GROUNDCOVER OSMOCOTE SIERRA BLEND 14-14-14
SHRUBS, TREES, PALMS AGRIFORM 20-10-5- TABLETS
6" EARTHEN SAUCER A C D D 3" LAYER OF MULCH AS
FINISH GRADE SPECIFIED 11. ALL SOD SHALL BE SOLID WEED-FREE PANELS, LAID ON ONE INCH
WATERED-IN PREPARED
WATERED-IN FIN. GRADE DEPTHS OF DEPTH OF TOPSOIL WITH STAGGERED JOINTS.
PLANTING SOIL AS PLANTING SOIL
SPECIFIED PREPARED PLANTING FINISH GRADE 12. ALL MECHANICAL EQUIPMENT SHALL BE SCREENED ON THREE SIDES
SOIL AS SPECIFIED 8"
12" PLANTING SOIL
UNDISTURBED SOIL 16"
BACKFILL & FERTILIZER
WITH APPROVED HEDGE.
UNDISTURBED SOIL
AS SPECIFIED
PLANTING PIT 13. ALL TREES PLANTED ADJACENT TO OVERHEAD POWER LINES SHALL
2X ROOTBALL EXISTING SUB-GRADE
PLANTING PIT SECTION
PLANTING PITS TO BE 2X
CONFORM TO F.P.L 'RIGHT TREE RIGHT PLACE' GUIDELINES
2X ROOTBALL
THE SIZE OF THE 14. LANDSCAPE SHALL NOT OBSCURE FIRE HYDRANTS OR STANDPIPES.
SMALL TREE PLANTING DETAIL SABAL PALM PLANTING DETAIL SHRUB PLANTING DETAIL ROOTBALL.
15. ALL PLANT MATERIAL SHALL BE WARRANTEED FOR ONE YEAR
NORTH
N.T.S. N.T.S.
N.T.S.
0 16' 32'
GRAPHIC SCALE
LEGEND
SYMBOL MODEL NO. DESCRIPTION * EST. QUANTITY
TYPICAL ZONE SUMMARY
CW - CONTROLLER PA8S-5CST-B RAINBIRD STREAM BUBBLER 06
1 - STATION
3/4" 1" 1" 1"
2Q PA8S-SQ-QTR RAINBIRD SPRAY BUBBLER 06
40 - EST. WATER USE 3/4" 3/4" 3/4"
2H PA8S-SQ-HLF RAINBIRD SPRAY BUBBLER 145
1 1/2" - VALVE SIZE
VENT RCS
8V PA8S-8V RAINBIRD SHRUB SPRAY 02
3/4" 15V 15Q 8V 10Q 10Q
8Q 10Q
3/4" 10H
10Q 8Q PA8S-8Q RAINBIRD SHRUB SPRAY 01
CW1 - 40 GPM (1 1/2") 10H 10H 10H 10H
1" FUEL 3/4" 1" 3/4"
8F PA8S-8F RAINBIRD SHRUB SPRAY 01
3/4" VENT 3/4" 10F 3/4" 10F 10F TANK 10F 10F SST 10H PA8S-10H RAINBIRD SHRUB SPRAY 08
10H 10H
CW2 - 36 GPM (1 1/2") 10H 10H 10H 3/4" 10H
15V 15F 3/4" 1" GARAGE ACCESS 10F PA8S-10F RAINBIRD SHRUB SPRAY 06
1"
15H 2" 1"R 2" 1 1/4"R 1 1/2" 1 1/2" 1 1/4"R
1"X 1" 12Q PA8S-12Q RAINBIRD SHRUB SPRAY 05
WIRE CONDUIT X X X X X X X X X X X X X X X X X X PRIVATE
X PATIO
1" 1 1/2" 12H PA8S-12H RAINBIRD SHRUB SPRAY 02
12V 12Q 10Q 10Q 10Q
RAIN SENSOR 15Q SST
12TQ PA8S-12TQ RAINBIRD SHRUB SPRAY 01
3/4" 10Q 10H 10H 10H 10H 10H

X
LOCATION SHALL BE 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 1"
12F PA8S-12F RAINBIRD SHRUB SPRAY 03

X
SELECTED ON SITE 10V 15F 3/4" 15V PA8S-15V RAINBIRD SHRUB SPRAY 02
15H
EXISTING IRRIGATION METER 12Q 15Q PA8S-15Q RAINBIRD SHRUB SPRAY 02
1" 2"
PA8S-15T RAINBIRD SHRUB SPRAY 01

X
10Q 15T
LOCATED AT GRADE IN 3/4" 15Q SST

X
VAULT BELOW SIDEWALK 1 1/2"SL 15H PA8S-15H RAINBIRD SHRUB SPRAY 01
X
X

3/4" 3/4" 15TQ PA8S-15TQ RAINBIRD SHRUB SPRAY 01

X
X

X
X

10V

X
X

X
X

X
X

3/4"
X

5Q

X
X

15Q
X

X
X

X
X

X
1"R
X

X
X

X
X

X
X

X
X

X
X

X
X

PA8S-15F

X
RAINBIRD SHRUB SPRAY
X

04
X

X
X

15F

X
X

X
X

1 1/2"R

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

15H
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

1 1/2"

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

5Q
X

X
X

X
X

X
X

X
X

2"
X

X
X

X
X

1812-5Q RAINBIRD 12" POP-UP SPRAY


X

X
24
X

X
X

5Q
X

3/4"
X
X

X
X

X
X

X
1 1/2"R
X

10Q
X
X

X
X

X
X

X
X

X
X

LCS
X
MOUND UP TO 3' SOIL
X

LCS
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

1812-8Q RAINBIRD 12" POP-UP SPRAY


X

29
X

X
X

8Q
X

12V
X

X
X

X
X

X
X

DEPTH -TYP. AT TREE


X

X
X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

12Q
X

X
X

X
X

X
X

X
X

X
X

ROOTBALLS
X
X

2"R
X

X
X

1812-8H RAINBIRD 12" POP-UP SPRAY


X

03
X

X
X

8H
X

X
X

3/4"
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

10V
X

X
X

12H
X

X
X

10V 1812-10V RAINBIRD 12" POP-UP SPRAY 08


12Q 1 1/2"SL SST
3/4" 10Q 1812-10Q RAINBIRD 12" POP-UP SPRAY 18
RS 12Q
10F 2" 3/4" 3/4" 10H 1812-10H RAINBIRD 12" POP-UP SPRAY 05
8Q
8F LCS
CW
12V 1812-12V RAINBIRD 12" POP-UP SPRAY 01
2" PVC RISER RCS 1812-12Q RAINBIRD 12" POP-UP SPRAY
2" 5Q 08

8777 Collins Avenue, Surfside, FL 33154


12Q
3/4"
CONNECTED TO EXISTING PIPE 12Q 3/4" 5Q 12T 1812-12T RAINBIRD 12" POP-UP SPRAY 02
PENETRATION THROUGH GARAGE WALL 3/4" RCS 3/4"

IRRIGATION PLAN AND LEGEND


12H 1812-12H RAINBIRD 12" POP-UP SPRAY 04
X

X
X

X
X

X
X

X
X
X

X
X
X

X
X
X

X
X

X
X

X
X

X
X
X

X
X
X

12V
X

X
X

X
X

X
X
X

2" GATE VALVE


X

12H
X
X

12Q
X
X

X
X

X
X

X
X

X
X
X

5Q 5Q
X

X
X
X

X
X

X
X

X
X

X
X
X

X
X
X

X
X
X

X
X

X
X

2"R 2"
X
X

X
X
X

X
X
X

X
X

X
X

X
X

X
X

1812-15RCS RAINBIRD 12" POP-UP SPRAY


X

X
X

05
X

3/4"
X
X
X

RCS
X
X

X
X

X
X

X
X
X

X
X
X

X
X

X
X

X
X

X
X
X

X
X
X

X
X
X

X
X

X
X

X
X

X
X
X

X
X
X

2"R
X

X
X

X
X

X
X

X
X
X

X
X
X

X
X
X

10Q
X
X

X
X

X
X

X
X
X

X
X
X

X
X

X
X

X
X

X
X
X

X
X
X

X
X
X

X
X

X
X

1 1/2"SL
X
X

X
X
X

X
X
X

X
X

X
X

X
X

X
X
X

X
X
X

1812-15LCS
X

RAINBIRD 12" POP-UP SPRAY


X
X

06
X
X

X
X

X
X

LCS
X
X

X
X
X

X
X

8Q
X
X

X
X

X
X
X

X
X
X

X
X
X

2"
X

AUTO. CONTROLLER 8Q
X
X

X
X

X
X
X

X
X
X

X
X

X
X

X
X

X
X
X

X
X
X

X
X
X

1" 2"
X

X
X

X
X

X
X

X
X
X

X
X
X

X
X

X
X

X
X

X
X
X

X
X
X

X
X
X

X
X

X
X

X
X

X
X
X

X
X
X

X
X

X
X

X
X

X
X
X

X
X
X

X
X

1812-15SST RAINBIRD 12" POP-UP SPRAY


X

X
X

06
X
X

X
X

X
X

SST
X

X
X
X

X
X

X
X

X
X

X
X
X

X
X
X

LOCATION SHALL BE SELECTED


X

10Q
X

X
X

8Q
X

8Q
X
X

3/4"R EAST GARDEN (NOT


X
X

X
X

X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
X

X
X

X
X

X
X

X
X

10Q
X

X
X

3/4"
X

3/4"
X

ON SITE. 120 POWER REQUIRED.


X
X

X
X

1812-15V RAINBIRD 12" POP-UP SPRAY


X
X

01
X

15V
X
X

X
X

X
X

X
X

X X
X
X
X

X
X
X
X
X

X
X
X X
X

X X
X
X
X

X
X
X
X
X

X
X X
X
X
X

8Q
X

IN CONTRACT)
X
X
X X

X
X
X
X

X
X X
X
X

X X
X
X
X

X
X
X X
X

X
X

X
X
X
X
X
X
X
X

X
X X
X

X
X X
X
X

X
X
X
X
X
X

X
X
X

X
X

X X
X
X
X
X

X
X
X X
X

X
X X
X
X
X
X
X
X
X
X
X
X
X
X

X
X X
X
X

X
X
X
X
X

X
X
X

X
X

X X
X
X
X
X
X
X
X X

X
X
X X
X

X
X

X
X
X

X
X
X
X
X
X

X
X X
X
X

X X
X
X
X X

X
X
X X
X

X
X

X
X

X X
X
X
X

X
X

1812-15Q RAINBIRD 12" POP-UP SPRAY


X X
X

X
X

X
X
X

06
X
X
X
X
X X

X
X X

8Q
X
X

15Q
X X
X
X
X
X

X
X
X
X

X
X
X

X
X

X X
X
X
X

X
X
X
X X
X

X
X X
X
X
X

X
X
X
X X

X
X
X

X
X X
X

3/4"R
X

X
X
X
X
X

X
X
X X
X

X X
X
X
X
X
X
X
X
X

X
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
X

X
X

X
X

3/4"R
X
X

X
X

X
X

X
X

X
X

CW3 - 44 GPM (1 1/2")


X
X

X
X

X
X

X
X

X
X

X
X

1812-15H RAINBIRD 12" POP-UP SPRAY


X

07
X

10Q 15H
X

X
X

X
X

X
X

X
X

X
X

X
X

2"
X
X

X
X

X
X

PRIVATE PATIO
X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

2"
X

X
X

X
X

X
X

X
X

X
X

150 PEB
X

04
X

10Q
X

RAINBIRD 1 1/2" SOLENOID VALVE


X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

CW4 - 48 GPM (1 1/2")


X

X
X

X
X

15Q
X

X
X

10Q
X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

ESP-4ME
X

RAINBIRD AUTO. CONTROLLER


X

CW
X
X

X
X

01
X
X

5Q
X
X

X
X

5Q
X

X
X

X
X

X
X

X
X

1 1/2"SL
X
X

X
X

X
X

X
X

X
X

X
X

15H
X

X
X

X
X

X
X

3/4"
X

LCS 5Q
X
X

X
X

X
X

X
X

X
X

X
X

PORTE COCHERE
X

X
X

PRIVATE PATIO
X

3/4" ESP-SM3
X

3/4"R
X
X

RAINBIRD EXPANSION MODULE


X
X

5Q
X

2"R 3/4"
X

NOT SHOWN
01
X
X

X
X

1"
X

X
X

2"
X
X

X
X

X
X

X
X

X
X

X
X

X
X

3/4"R
X

X
X