Part 2 - Regenerator Control Strategies
Part 2 - Regenerator Control Strategies
Part 2 - Regenerator Control Strategies
There are several control strategies for ensuring good amine regenerator performance. As will be
seen, some work better than others, and some do not work at all. But all function by monitoring and
controlling the temperature somewhere in the regeneration system. In the first part of this article, it was
shown that anywhere from the overhead vapour line to just below the feed tray are satisfactory measuring
points. In this Part 2 we address various approaches to control. The article uses specific operating cases
to show the benefits and shortcomings of several strategies. Discussion of the various approaches is made
concrete by using MDEA as a selective solvent in a typical natural gas processing plant; however, most of
the discussion applies equally well to most other amines and gas treating applications.
Reboilers in the amine regeneration section of a treating plant come in a number of varieties,
including kettle, once-through thermosiphon, and recirculating thermosiphon, and they can be steam
heated, hot oil heated, process-gas heated, and direct fired. Regardless of type though, reboilers have the
main purposes of providing:
Sensible heat to raise the rich amine feed to the boiling temperature inside the regenerator,
Heat to reverse the reactions between acid gases and the amine, and
Energy to generate the dilution steam necessary for providing the acid gas partial pressure that
directs dissolved gases from the solvent into the vapour.
Energy requirements to reverse the acid gas-amine reactions are very amine specific. Energy needed to
raise solvent temperature and generate steam are less so because the solvent heat capacity is dominated
by water as is the heat of vapourisation (mostly of water) from the solvent.
Regenerator performance is usually measured in terms of the solvent lean loading(s) produced.
Strategies for controlling lean loading include:
Manipulate reboiler steam or hot oil flow to meet a target regenerator bottoms temperature or
reboiler temperature,
Manual reboiler steam or hot oil flow control,
Maintain a fixed flow ratio of steam or oil to the solvent flow, and
Allow the ratio of steam to solvent flow rates to be biased or reset to control overhead temperature.
Each of these strategies is examined in turn using ProTreat® mass transfer rate based simulation as a
guide to the quantitative response and behaviour of an example amine unit.
0.00020
0.003
H2S Lean Loading
0.001
0.00005
0.000 0.00000
80 90 100 110 120
O/H Temperature, °C
Using a reboiler duty that is directly proportional to the circulation rate allows the unit to respond
well to solvent flowrate changes. The solvent H2S lean loading varies only a little over a tenfold range of
flow rates. In a relative sense, the CO2 lean loading varies by a factor of ten; however, in terms of absolute
loading values the CO2 loading response is quite similar to H2S: both experience a change in loading of
0.0002 to 0.0003 loading units. Reboiler conditions play a large role in determining regenerator
performance because a large fraction of solvent stripping actually takes place there. From the lowest to the
highest solvent rates, reboiler pressure varied from 1.149 to 1.279 barg (16.67 to 18.55 psig) and reboiler
temperature ranged from 127.9 to 129.9°C (262.2 to 265.8°F).
The mass transfer performance of trays improves with both vapour and liquid flow rates. Both are
increasing as the circulation rate through the fixed size regenerator increases. On that basis, one might
expect both the H2S and CO2 lean loadings to improve with solvent rate. The H2S loading does; the CO2
loading does not—instead it grows worse, by about the same number of loading units (0.0002) as H2S
loading improves (0.0003). Although both H2S and CO2 mass transfer rates benefit from the higher mass
transfer coefficients that accompany increased traffic through the regenerator, the effect is stronger on H2S
desorption than on CO2 because of a higher reaction enhancement effect. Somewhat more of the
additional energy, therefore, is used to strip just a little more H2S, leaving slightly less available for
removing CO2. This is the reason for the counteracting effect, and for the relative total stripping remaining
roughly unchanged.
Adjusting Steam-to-Solvent Flow Ratio to Control Overhead Temperature
Maintaining a constant steam-to-solvent ratio allows simple, accurate control of stripping under
varying conditions of solvent flow rate. As also already shown, adjusting the steam flow allows control of
solvent lean loading under varying rich amine loading conditions. Therefore, it only stands to reason that a
combination of the two will allow control of lean loading when both solvent rate and rich loading are
changing. This is done via cascading the control system and, of course, it is used to control the
regenerator’s overhead (or feed tray) temperature as a proxy for lean loading. The two individual controls
have already been discussed and this approach is just a marriage of the two.
As an example, a sudden increase in rich loading will cause overhead temperature (more or less
equivalent to the boiling point) to drop. The physical response should be to increase reboiler steam flow to
bring the temperature back up to the set point value. However, the rich solvent flow has not changed so
the flow-ratio controller wants to keep the same steam rate; thus, a control system with only a simple flow-
ratio controller cannot respond except by violating the prescribed flow ratio. The basic strategy is to
institute a second level of control to override the set flow-ratio controller and allow the steam rate to be
increased, all the while resetting the ratio to the new value needed to maintain the set point temperature.
The reboiler steam flow changes in response to the measured solvent flow, while the steam-to-solvent flow
ratio adjusts in response to rich loading as indicated by the temperature measured at an appropriate
location in the regenerator.
Summary
Most attention is usually focused on the absorber because this is the equipment that actually
processes the gas. However, absorber performance is controlled to a very large extent by the regenerator
and how it performs in providing a satisfactory lean amine solvent. Thus, one could easily take the position
that solvent regeneration is really the key operation, and its accurate and reliable simulation is at least as
important as the absorber’s.
The ProTreat® simulator uses a mass transfer rate-based regenerator model similar in every
respect to that for the absorber, allowing it to predict the performance of the entire amine unit with uncanny
accuracy. This includes the effect of heat stable amine salts (HSSs) on both retarding absorption and
enhancing regeneration, leading to either better or worse overall amine unit performance, depending on the
circumstances.
Satisfactory absorber operation often depends critically on achieving the right solvent lean loading.
Because it is hard to measure on-line, temperature is the usual proxy for lean loading. Part 1 of this article
discussed where the best places are to measure temperature in a regenerator; this article has discussed
several ways to control lean loading by controlling temperature. But probably the most beneficial tool one
can use for analysing and monitoring an amine unit is a truly mass transfer rate-based simulator.