AC Single Phase Ammeter

User Manual

This manual is applied to the following models:


LNF31

JIANGSU SFERE ELECTRIC CO., LTD


1 Product description
1.1 Overview
This series of digital ac ammeter is suitable for measuring single phase ac current
parameters of low voltage distribution system. This series of meter support
programmable transformation ratio, and can be equipped with communication
function to support Modbus-RTU communication protocol.
This series of meter can be widely used in various control systems, distribution
automation system, industrial automation system and intelligent buildings.

1.2 Model selection


Function LNF31
Display mode LCD
Appearance
Panel size(mm) 72×72
Real-time
Current, frequency ▇
measurement
Note: “▇” Yes.

2 Technical parameters
2.1 Technical specification
Working environment

Working temperature -10°C -- 55°C

Storage temperature -25°C -- 70°C

Relative humidity ≤95% RH, no condensation

Working altitude ≤2500m

Anti-pollution level Non-corrosive gas

Protection degree Front case IP54, rear case IP20.

Between signal, power supply, output terminal to


Insulation
case resistance >100MΩ
Input and power supply ≥ 2kV, input and output ≥
Withstand voltage
2kV, power supply and output ≥ 2kV
Display

Display method LCD

Working power supply

Rated range AC/DC(80~270)V

Power consumption ≤5VA

Input and power supply ≥ 2kV, input and output ≥


Withstand voltage
2kV, power supply and output ≥ 2kV
Current input

Range 5A/1A

Resolution 1 mA

Impedance ≤20mΩ/ per phase

Power consumption ≤0.2 VA/ per phase

Continuous:1.2In
Overload
Instantaneous:10In/5s
Frequency 45 Hz-65 Hz

Communication interface

Physical interface RS-485

Communication speed Up to 9.6 kbps

Communication protocol Modbus-RTU

Isolation voltage 2000 VAC (1 min)

EMC

Electrostatic discharge immunity IEC 61000-4-2-III

Radiated, radio-frequency, electromagnetic


IEC 61000-4-3-III
field immunity

Electrical fast transient/burst immunity IEC 61000-4-4-IV

Impact (surge) immunity IEC 61000-4-5-IV

Immunity to conducted disturbances,


IEC 61000-4-6-III
induced by radio-frequency fields

Power frequency magnetic field immunity IEC 61000-4-8-III

Voltage dips, short interruptions and voltage IEC 61000-4-11-III

-3-
variations immunity

2.2 Measurement parameter


Measurement
Accuracy Instant Demand Sum Unit
variable

I1/I2/I3 0.2 ● ● — [A,kA]


F ±0.01Hz ● — — [Hz]

3 Installation
3.1 Dimension

5(max)
67

A
67
72

72 7.5 44.5

3.2 Installation

Install the meter from the


outside of the panel into the
mounting hole.

-4-
Install it to the end and fix the
meter with a snap spring.

3.3 Wiring