Technical data
2000 kWel; 10500 V, 50 Hz; Natural gas, MN = 80
2)
Design conditions Fuel gas data:
Inlet air temperature / rel. Humidity: [°C] / [%] 25 / 60 Methane number: [-] 80
Altitude: [m] 100 Lower calorific value: [kWh/Nm3] 10,17
Exhaust temp. after heat exchanger: [°C] 120 Gas density: [kg/Nm3] 0,79
NOx Emission (tolerance - 8%): [mg/Nm3 @5%O2] 250 Standard gas: Natural gas, MN = 80
Genset:
Engine: CG170-20
Speed: [1/min] 1500
Configuration / number of cylinders: [-] V / 20
Bore / Stroke / Displacement: [mm]/[mm]/[dm3] 170 / 195 / 89
Compression ratio: [-] 13,0
Mean piston speed: [m/s] 9,8
Mean lube oil consumption at full load: [g/kWh] 0,15
Engine-management-system: [-] TEM EVO
Energy balance
Load: [%] 100 75 50
Electrical power COP acc. ISO 8528-1: [kW] 2000 1500 1000
Engine jacket water heat: [kW ±8%] 1043 788 556
Intercooler LT heat: [kW ±8%] 184 132 79
Lube oil heat: [kW ±8%]
Exhaust heat with temp. after heat exchanger: [kW ±8%] 1024 856 655
Exhaust temperature: [°C ±25°C] 415 442 473
Exhaust mass flow, wet: [kg/h] 11422 8724 6060
Combustion mass air flow: [kg/h] 11055 8441 5860
Radiation heat engine / generator: [kW ±8%] 71 / 54 67 / 45 61 / 39
Fuel consumption: [kW+5%] 4690 3628 2556
Electrical / thermal efficiency: [%] 42,6 / 44,1 41,3 / 45,3 39,1 / 47,4
Total efficiency: [%] 86,7 86,6 86,5
1)
System parameters
Ventilation air flow (comb. air incl.) with ΔT = 15K [kg/h] 51500
Combustion air temperature minimum / design: [°C] 5 / 25
Exhaust back pressure from / to: [mbar] 30 / 50
Maximum pressure loss in front of air cleaner: [mbar] 5
Zero-pressure gas control unit selectable from / to: 2) [mbar] 20 / 200
Pre-pressure gas control unit selectable from / to: 2) [bar] 0,5 / 10
Starter battery 24V, capacity required: [Ah] 450
Starter motor: [kWel.] / [VDC] 18 / 24
Lube oil content engine / base frame: [dm3] 300 / 685
Dry weight engine / genset: [kg] 8070 / 17620
Cooling system
Glycol content engine jacket water / intercooler: [% Vol.] 35 / 35
Water volume engine jacket / intercooler: [dm3] 210 / 25
KVS / Cv value engine jacket water / intercooler: [m3/h] 58 / 52
Jacket water coolant temperature in / out: [°C] 80 / 93
Intercooler coolant temperature in / out: [°C] 40 / 44
Engine jacket water flow rate from / to: [m3/h] 60 / 85
Water flow rate engine jacket water / intercooler: [m3/h] 74 / 40 Page 1 / 1
Water pressure loss engine jacket water / intercooler: [bar] 1,6 / 0,6
3332450EB19753
1) See also "Layout of power plants": 2) See also Techn. Circular 0199-99-3017
Frequency band 31,5 40 50 63 80 100 125 160 200 250 315 400 500 630 800 1k 1.25k 1.6k 2k 2.5k 3.15k 4k 5k 6.3k 8k 10k 12.5k 16k
LWA S
25
f [Hz] [dB(A)] [m2]
Air-borne noise 3) 94,9 96,9 98,0 100,0 106,3 111,3 111,7 118,9 113,6 116,3 116,8 112,2 111,6 114,2 111,5 111,1 112,2 110,5 111,3 111,4 109,2 107,2 105,7 105,9 109,4 120,3 104,7 99,1 98,6
123,8
140
LW,Terz [dB(lin)] ±4dB(A)
4) 135,8
Exhaust noise 118,6 117,9 121,4 127,3 126,9 126,8 126,5 140,9 126,3 129,9 130,9 125,2 126,3 126,5 125,9 125,9 125,0 123,3 123,9 123,8 123,2 126,3 116,4 115,5 115,2 114,1 114,6 112,6 110,8 15,55)
LW,Terz [dB(lin)] ±3dB(A)
2
3) DIN EN ISO 3746 (σR0=±4 dB) 4) Measured in exhaust pipe (f ≤ 250Hz: ±5dB; f > 250Hz: ±3db) LW : Sound power level S: Area of measurement surface (S0=1m ) 5) DIN 45635-11, Appendix A