CM ESS ABB 59N
CM ESS ABB 59N
CM ESS ABB 59N
Characteristics
–– Monitoring of DC and AC voltages (3-600 V)
–– TRMS measuring principle
–– One device includes 4 measuring ranges
–– Over- or undervoltage monitoring configurable
–– Hysteresis adjustable (3-30 %) Approvals
–– 3 supply voltage versions A UL 508, CAN/CSA C22.2 No.14
–– Precise adjustment by front-face operating controls C GL (pending)
–– Screw connection technology or
D GOST
Easy Connect Technology available
–– Housing material for highest fire protection classification K CB Scheme
UL 94 V-0 E CCC
–– Tool-free mounting on DIN rail as well as demounting L RMRS
–– 1 c/o (SPDT) contact
–– 22.5 mm (0.89 in) width
Marks
–– 3 LEDs for status indication
a CE
b C-Tick
Order data
Accessories
Type Description Order code
ADP.01 Adapter for screw mounting 1SVR 430 029 R0100
MAR.12 Marker label for devices with DIP switches 1SVR 730 006 R0000
COV.11 Sealable transparent cover 1SVR 730 005 R0100
Connection technology
Maintenance free Easy Connect Technology with Approved screw connection technology with
Push-in terminals double-chamber cage connection terminals
Type designation CM-xxS.yyP Type designation CM-xxS.yyS
2CDC 253 026 F0011
–– Tool-free connection of rigid and flexible wires with –– Terminal spaces for different wire sizes:
wire end ferrule according to DIN 46228-1-A, fine‑strand with/without wire end ferrule:
DIN 46228-4-E 1 x 0.5-2.5 mm² (2 x 20 - 14 AWG),
Wire size: 2 x 0.5-1.5 mm², (2 x 20 - 16 AWG) 2 x 0.5-1.5 mm² (2 x 20 - 16 AWG)
–– Easy connection of flexible wires without wire end rigid:
ferrule by opening the terminals 1 x 0.5-4 mm² (1 x 20 - 12 AWG),
–– No retightening necessary 2 x 0.5-2.5 mm² (2 x 20 - 14 AWG)
–– One operation lever for opening both connection –– One screw for opening and closing of both cages
terminals –– Pozidrive screws for pan- or crosshead screwdrivers
–– For triggering the lever and disconnecting of wires according to DIN ISO 2380-1 Form A 0.8 x 4 mm
you can use the same tool (Screwdriver according to (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm
DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 (0.177 in)
in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in))
–– Constant spring force on terminal point independent
of the applied wire type, wire size or ambient
conditions (e. g. vibrations or temperature changes)
–– Opening for testing the electrical contacting
–– Gas-tight
Both the Easy Connect Technology with Push-in terminals and screw connection technology with double-chamber cage
connection terminals have the same connection geometry as well as terminal position.
Operating controls
Application
The voltage monitoring relays CM-ESS.1 are designed for use in single-phase AC and/or DC systems for over- or
undervoltage monitoring as well as detection of phase loss. The devices are available with different supply voltage ranges
and work according to the open-circuit principle.
Operating mode
The CM-ESS.1 have 1 c/o (SPDT) contact and include 4 measuring ranges: 3-30 V, 6-60 V, 30-300 V and 60-600 V.
The units are adjusted with front-face operating controls. The selection of over- d or undervoltage monitoring c is
made with a DIP switch. Potentiometers, with direct reading scale, allow the adjustment of the threshold value U and of the
hysteresis %. The hysteresis % is adjustable within a range of 3 to 30 % of the threshold value.
Overvoltage monitoring d
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals
A1-A2 is displayed by the glowing green LED.
If the measured value exceeds the adjusted threshold value, the output relay energizes and the red LED (overvoltage) and
the yellow LED (relay energized) glow.
If the measured value drops below the threshold value minus the adjusted hysteresis, the output relay de-energizes and the
red and yellow LEDs turn off.
A1-A2
Threshold
Hysteresis
Measured value
11-14 (15-18)
11-12 (15-16)
Undervoltage monitoring c
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals
A1-A2 is displayed by the glowing green LED.
If the measured value drops below the adjusted threshold value, the output relay energizes, the red LED flashes W
(undervoltage) and the yellow LED (relay energized) glows.
If the measured value exceeds the threshold value plus the adjusted hysteresis, the output relay de-energizes and the red
and yellow LEDs turn off.
A1-A2
Measured value
Hysteresis
Threshold
11-14 (15-18)
11-12 (15-16)
2CDC 252 209 F0205
green LED
red LED
yellow LED
1418 1216 A2
Connection diagram
DIP switches
1 ON Undervoltage monitoring
OFF Overvoltage monitoring
OFF = Default
2CDC 252 275 F0005
Input circuits
Timing circuit
Time delay TV none
Repeat accuracy (constant parameters) ±0.07 % of full scale
Tolerance of the adjusted time delay -
Accuracy within the rated control supply voltage tolerance -
Accuracy within the temperature range -
User interface
General data
MTBF on request
Duty time 100 %
Dimensions (W x H x D) product dimensions 22.5 x 85.6 x 103.7 mm (0.89 x 3.37 x 4.08 in)
packaging dimensions 97 x 109 x 30 mm (3.82 x 4.29 x 1.18 in)
Weight Screw connection Easy Connect Technology
technology (Push-in)
Net weight Version 24-240 V AC/DC 0.135 kg (0.298 lb) 0.126 kg (0.278 lb)
Version 110-130 V AC 0.164 kg (0.362 lb) 0.155 kg (0.342 lb)
Version 220-240 V AC 0.164 kg (0.362 lb) 0.155 kg (0.342 lb)
Gross weight Version 24-240 V AC/DC 0.157 kg (0.346 lb) 0.148 kg (0.326 lb)
Version 110-130 V AC 0.186 kg (0.410 lb) 0.178 kg (0.392 lb)
Version 220-240 V AC 0.186 kg (0.410 lb) 0.178 kg (0.392 lb)
Mounting DIN rail (IEC/EN 60715),
snap-on mounting without any tool
Mounting position any
Material of housing UL 94 V-0
Degree of protection housing IP50
terminals IP20
Environmental data
Isolation data
Standards
Electromagnetic compatibility
V V
300 300
V 200 V 200
resistive load
resistive load
100 100
80 80
60 60
50 50
40 40
30 30
20 20
1.0
Switching cycles
0.9
0.8
F
0.7 250 V
resistive load
0.6
0.5
2CDC 252 192 F0205
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
cos ϕ
Contact lifetime
113.4 4.47”
105.9 4.17” 22.5 0.89”
85.6 3.37”
Accessories
in mm and inches
8 0.32”
22.5 0.89” 4.8 0.19”
68 2.68”
0.453”
11.5
0.256”
62.5 2.461”
6.5
22.2
2CDC 252 008 F0010
0.787”
10
20
4T22
0.309”
7.85
front to back
60 2.362” 19.9 110.5 4.31”
70 2.756” 0.783”
ADP.01 ‑ Adapter for screw mounting MAR.12 ‑ Marker label for devices COV.11 ‑ Sealable transparent cover
with DIP switches
Further documentation
You can find the documentation on the internet at www.abb.com/lowvoltage -> Control Products ->
Electronic Relays and Controls -> Single Phase Monitors
Note:
We reserve the right to make technical changes
or modify the contents of this document without
prior notice. With regard to purchase orders, the
agreed particulars shall prevail. ABB AG does
not accept any responsibility whatsoever for
potential errors or possible lack of information in
this document.