Technical help
Ecodial AC 4
Contents
Component names
Main changes following the Cenelec TR50480 report
Types of system earthing
Types of transformer losses
Diversity factor Ks
Switchgear status and operating modes
Discrimination of LV protective devices
Check on the thermal stress in cables
Discrimination of residual-current protective devices
Discrimination between MV and LV protective devices
Cascading
Withdrawable circuit breakers and switches
Electrical operating mechanisms for circuit breakers and switches
Remote opening of switches
Visible break
Classification of residual current devices
Type of residual-current protection
High-sensitivity residual-current protection
Medium-sensitivity residual-current protection
Maximum permissible voltage drop for loads
Circuit voltage-drop tolerances
Cable installation method
Maximum, permissible cross-sectional area
Cable sizing according to circuit breaker setting or rating
Number of additional touching circuits
Third-order harmonic distortion
Manual and alternate solutions
Additional derating coefficients for wiring systems
Waiver of overload-protection requirements for safety circuits
Power factor for short-circuits on LV sources
Calculation of LV-source phase impedances, based on Ik3max
Calculation of LV-source neutral impedances, based on Ik1min
Calculation of LV-source PE impedances, based on Ief
Calculation of LV-source PE impedances, based on Ief2min
Consistency of LV-source input parameters
Type of regulation of LV capacitor banks
Types of LV capacitor banks
Reactive power threshold
Technical help Page 2/61
Ecodial AC 4
Component names
The default prefix of component names is defined in accordance with standard IEC 81346-2.
This standard defines the following rules depending on the type of equipment.
ZT
Incomer:
ZSUP = ZC + ZG ZSUP = Z Q + Z C ZQ (ZT + ZC )
ZQ ( ZT + ZC ) Outgoer: ZSUP =
ZSUP = nT
nT − 1
nT is the total number of transformers operating
simultaneously.
Incomer = the conductor between the transformer and the
main switchboard.
Outgoer = the circuits supplying the entire installation
downstream of the main switchboard.
TN-C system
TT system
IT system
Dry-type transformers
Dry-type encapsulated transformers offer two possible loss levels:
normal losses,
reduced losses.
Diversity factor Ks
Standard IEC 61439-1 defines the diversity-factor (Ks) values that may be used if more precise
information on switchboards and busbar-trunking systems (BTS) is lacking.
Ecodial uses these values by default to calculate the design currents for BTSs and busbars.
Switchboard busbars
Number of outgoers Ks
1 1
2-3 0.9
4-5 0.8
6 to 9 0.7
10 and more 0.6
Distribution BTS
Number of outgoers Ks
1 1
2-3 0.9
4-5 0.8
6 to 9 0.7
10 to 40 0.6
Over 40 0.5
When a part of the network is not supplied in a given operating mode, it is shown in blue in the single-line
diagram. Given that the "closed" status condition is the most common in installations, only the "open"
status condition is shown in the single-line diagram.
Tripping curve
Non-tripping curve
If the selectivity limit current is lower than the short-circuit current that can occur on the circuit protected
by the downstream protective device, discrimination is said to be partial.
If the selectivity limit current is higher than the maximum short-circuit current that can occur on the circuit
protected by the downstream protective device, discrimination is said to be total for the given installation.
If the discrimination limit is in the table zone, the rating of the upstream protective device must be
increased. In this case, Ecodial retains the circuit design current Ib as the reference for the thermal
setting of the protective device to avoid oversizing the cable.
Ikmin
i²t phase
i²t neutral
i²t PE
The sensitivity of the downstream device must also meet the condition below:
sensitivity (I∆n) x 2 ≤ fault current (Ief).
≥ 2 → current discrimination OK
Ikmin
Partial discrimination
When the sensitivity discrimination condition is not met, discrimination is said to be partial.
However if the breaking-time discrimination condition is not met, there is no discrimination between the
two residual-current protective devices (even if the sensitivity discrimination condition is met).
Depending if the MV protective device is a fuse or relay the rules to ensure discrimination between MV
and LV are slightly different.
For MV fuse:
all parts of the minimum pre-arcing fuse curve must be located to the right of the CB curve by a
factor of 1.35 or more (e.g. where, at time T, the CB curve passes through a point corresponding
to 100 A, the fuse curve at the same time T must pass through a point corresponding to 135 A, or
more, and so on...),
and all parts of the fuse curve must be above the CB curve by a factor of 2 or more (e.g. where,
at a current level I the CB curve passes through a point corresponding to 1.5 seconds, the fuse
curve at the same current level I must pass through a point corresponding to 3 seconds, or more,
etc.).
The factors 1.35 and 2 are based on standard maximum manufacturing tolerances for MV fuses and LV
circuit-breakers.
Where a LV fuse-switch is used, similar separation of the characteristic curves of the MV protective
device and LV fuses must be respected.
Cascading
Default and individual parameter settings
On the Project parameters tab, in the zone for device selection, it is possible to request that the system
attempt to set up cascading for all final protection devices, i.e. those immediately upstream of the loads. It
is on the final circuits that there is the greatest number of outgoers and consequently that cascading can
provide the greatest benefits.
In addition, there is an individual parameter for each circuit breaker in the installation, among the circuit-
breaker properties, to activate or deactivate system attempts to establish cascading.
Limits on cascading
Certain configurations in electrical installations making cascading impossible:
the circuit breaker selected for cascading is supplied by two parallel circuits,
the circuit breaker selected for cascading and the upstream circuit breaker are on opposite sides of a
LV/LV transformer.
No cascading
No cascading
No search for a
cascading solution
If withdrawability is not required, Ecodial proposes solutions without taking the feature into account.
In the results zone, Ecodial indicates whether a withdrawable version exists for each device.
Drawout Masterpact NT circuit Withdrawable Compact NSX Plug-in Compact NSX circuit
breaker (on a chassis). circuit breaker (on a chassis). breaker (on a base).
If the option is not required, Ecodial proposes solutions without taking the option into account.
In the results zone, Ecodial indicates whether the option exists for each device.
If the option is not requested, Ecodial selects only devices that cannot be remotely opened.
In the absence of an indication (parameter set to Any), Ecodial proposes solutions without taking the
option into account.
In all cases, Ecodial indicates in the results zone whether each device can be remotely opened or not.
Visible break
For certain applications, visible breaking of circuit may be required for safety reasons.
On a device offering visible break, the operator can see via a transparent screen that the contacts are in
fact open. For example, the Interpact INV range offers a double safety function with visible break and
positive contact indication.
If visible break is required on a switch, Ecodial selects only switches offering the function.
If it is not required, Ecodial selects only devices not offering the function.
In the absence of an indication (parameter set to Any), Ecodial proposes solutions without taking the
function into account.
In all cases, Ecodial indicates for each device in the results zone whether the function is available.
Type A
Tripping is ensured for residual sinusoidal alternating currents and specified residual pulsating direct
currents.
Type B
Tripping is ensured for currents identical to those for class A and for residual direct currents produced by
three-phase rectification.
In addition, Schneider Electric offers the following types of residual-current devices in its catalogue:
SI (super immunised) with reinforced immunity to nuisance tripping in polluted networks,
SiE designed for environments with severe operating conditions.
The table below presents the recommended type and immunity level as a function of the external
conditions and the level of disturbances on the electrical network.
Masterpact circuit breaker equipped with Vigicompact NSX iC60 circuit Type M and P
a Micrologic 7.0 control unit circuit breaker breaker with Vigirex relays
add-on Vigi
module
Procedure if the cumulative voltage drop for a load exceeds the permissible value
If the calculated, cumulative voltage drop exceeds the maximum, permissible value, Ecodial displays a
message to signal the error.
To clear the error, reduce the voltage-drop tolerances for the upstream circuits supplying the load (
Circuit voltage-drop tolerances).
In the example below, the calculated voltage Below, the voltage-drop tolerance for cable WD3
drop for load AA7 is 6.06%, i.e. greater than the has been reduced to 3%. Ecodial consequently
maximum permissible value of 6%. The increases the size of the cable and the voltage
tolerance for circuit voltage drops is set to 5%. drop for load AA7 is now less than 6% (4.98%).
∆u ∆u tolerance
+3.86% 5% → 3%
∆u
+ 1.93%
To maintain the maximum voltage drop for AA7 to less than 6%, it is necessary to reduce the voltage
drops on the upstream circuits (WD3 and WD7) by reducing the voltage-drop tolerance(s).
There are two possible methods.
Reduce the tolerances for all upstream circuits, in which case the size (cross-sectional area) of all
upstream circuits will be increased.
Reduce the tolerance for a single upstream circuit, namely the circuit selected by the designer as the best
for an increase in size.
For example in a circuit where the requested design current is 220A, using a Compact NSX250 with
Mircologic 2.2 trip unit the cable sizing can be made taking into account:
In = 250 A, the cable is sized to 95 mm²,
Or Ir = 220 A, the cable is sized to 70 mm².
If the concerned circuit itself contains several conductors per phase, the grouping factor is automatically
set to the right value by Ecodial.
1 cable of 120 mm² per phase, and is installed 2 cables of 120 mm² per phase and is installed
in a cable tray with 2 other circuits in a cable tray with 2 other circuits
The number of additional touching circuit has to The number of additional touching circuit has to
be set to 2 be set to 2
Then the grouping factor will be set by Ecodial for Then the grouping factor will be set by Ecodial for
3 touching circuits (the concerned circuit + 2 4 touching circuits (2 for the concerned circuit + 2
additional circuits) additional circuits)
Many devices in a wide range of fields include this type of circuit. They are the main causes of H3
harmonics.
Field Devices
Residential TV, hi-fi, video, microwave ovens, compact fluorescent lamps (CFL), etc.
Services Microcomputers, printers, photocopiers, fax machines, CFLs, etc.
Industry Switch-mode power supplies, variable-speed drives, CFLs, etc.
THDI ≤ 15% 15% < THDI ≤ 33% 33% < THDI ≤ 45% THDI > 45%
Sneutral = Sphase/2 is Sneutral = Sphase Sphase = Sneutral Sphase = Sneutral
permissible (1) Sphase is decisive Sneutral is decisive Sneutral is decisive
Neutral protected Factor = 0.86 IBneutral = 3 X THDi x IBneutral = 3 X THDi x IBphase
IBphase Factor = 1
Factor = 0.86
Alternate selection
Alternate solutions may be accessed only after a calculation has been validated. If that is the case and
the Select another product command is launched, the selection window automatically opens the
Calculated products window. Then simply select the desired solution using the values proposed in the
selection zone. The results zone is updated with the new solution. When OK is clicked, the solution is
confirmed (locked), i.e. it will be used for future calculations.
Manual selection
A prior, validated calculation is not required to access solutions in the catalogue. If a calculation has not
yet been validated, the selection window automatically opens the Entire catalogue window. If a
calculation has been validated, Ecodial opens the Calculated products selection window. Select Entire
catalogue to access the entire catalogue.
When a product is selected manually from the catalogue, it is "locked" for use in future calculations.
Ecodial includes a function to waiver thermal protection for circuit breakers supplying loads.
In this case, two types of circuit breakers are proposed by Ecodial:
circuit breakers without thermal protection and equipped with an MA trip unit,
circuit breakers equipped with a control unit enabling inhibition of thermal protection (e.g.
Micrologic 5 or equivalent).
In that case, Ecodial sizes the circuit breaker and the cable to accept 1.5 times the design current of the
circuit.
Depending on the type of system earthing, there are a number of dependencies between the different
short-circuit currents (Ik3max, Ik1min, Ief, Ief2min) that must be entered.
Ecodial checks the consistency between the parameters ( Consistency of LV-source input parameters).
These equations are also valid for the impedance of the PEN conductor in the TN-C system (with a
distributed neutral).
Depending on the type of system earthing, there are a number of dependencies between the different
short-circuit currents (Ik3max, Ik1min, Ief, Ief2min) that must be entered.
Ecodial checks the consistency between the parameters ( Consistency of LV-source input parameters).
U U
cmin × r cmax × r
=
3 3
ZPE -
Ief Ik3max
U U
cmin × r cmax × r
R PE = 3- 3 × PF
Ief Ik3max
sc
XPE = ZPE 2 − RPE 2
Depending on the type of system earthing, there are a number of dependencies between the different
short-circuit currents (Ik3max, Ik1min, Ief, Ief2min) that must be entered.
Ecodial checks the consistency between the parameters ( Consistency of LV-source input parameters).
U U
cmin × α × r cmax × r
=
3 3
ZPE -
2 × Ief2min Ik3max
U U
cmin × α × r cmax × r
=
3 3
R PE - × PFsc
2 × Ief2min Ik3max
XPE = ZPE 2 − RPE 2
Depending on the type of system earthing, there are a number of dependencies between the different
short-circuit currents (Ik3max, Ik1min, Ief, Ief2min) that must be entered.
Ecodial checks the consistency between the parameters ( Consistency of LV-source input parameters).
The ratio Gh/Sn is calculated by Ecodial for each capacitor bank, taking into account the loads declared
as harmonic loads.
The ratio Gh/Sn can also be entered directly for each capacitor bank. In this case, the values are locked
and will not be modified by Ecodial in the event of changes in the installation.
Selection criteria
LV capacitor banks are available for 3 levels of harmonic withstand:
Gh/Sn < 15%, "Classic" capacitor banks can be used,
15% ≤ Gh/Sn < 25 %, the capacitor banks must be at least of the "Comfort" type (the "Classic"
type is not allowed),
Gh/Sn ≥ 25%, "Harmony" capacitor banks must be used (the "Classic" and "Comfort" types are
not allowed).
If Gh/Sn exceeds 50%, a special study must be carried out to determine the type of capacitor bank
because harmonic filtering must be installed.
For more information: Electrical Installation Wiki.
Type Definition
Type 1 Deterioration of the contactor and the relay is acceptable under two conditions:
no danger to operating personnel,
no danger to any components other than the contactor and the relay
Type 2 Only minor welding of the contactor or starter contacts is permissible and the contacts
must be easily separated. Following type-2 coordination tests, the switchgear and
controlgear functions must be fully operational.
When the switchgear and controlgear includes both the circuit breaker and contactor functions,
coordination is considered to be total.
Example I’’start/Ir ≤ 19
For an 11 kW motor with direct-on-line starting, the following protection is selected:
Circuit breaker: P25 M 23 A,
Contactor: LC1D25.
The short-circuit currents Ik3max, Ik2max and Ik1max are calculated in compliance with Cenelec
TR50480 technical report.
For the double-fault current, Ecodial check that the breaking capacity at the phase-to-phase voltage is
greater than:
the current Ief calculated in compliance with Cenelec TR50480 technical report
0.15 times the 3-phase short-circuit current at the point considered if this current is less than or
equal to 10 000 A,
0.25 times the 3-phase short-circuit current at the point considered if this current is greater than
10 000 A.
The short circuit set of values stay same across The short circuit set of values vary across tap off
any tap off points points based on there distance from origin.
When designing systems where the details When designing systems where BTS riser needs
about the BTS are not know at the design time, to be used, it is advised to use Non Uniform BTS
it is advised to use Uniform BTS as it will take as the tap off points will not be equidistance from
into consideration derated voltage drop and each other.
short circuit set
Important note: The the busbar trunking system selected by Ecodial will remain the same irrespective of
whether a uniform / non uniform distribution type is chosen as far as the voltage drop is acceptable.
Ecodial does not distinguish between uniform and non uniform from a schematic perspective (SLD).
In case of BTS where feeder distribution is non uniform, the component voltage drop and short circuit set
represented in the report section, shows the total cumulative values of the tap off points along with the
component’s voltage drop and short circuit set.
MV protective device
3 possibilities are available for MV protective device:
“undefined”, in that case Ecodial will not propose any protection device, only the breaking time of
the protection is requested to check the thermal stress of LV connection between transformer and
main switchboard,
“fuse”, in that case Ecodial will select the appropriate fuses for the MV/LV transformer (refer to
MV fuse technology),
“relay”, in that case Ecodial will propose a relay for MV/LV transformer protection (refer to Type of
MV relay).
MV fuse technology
DIN and UTE fuses are available in Ecodial.
DIN technology will results in choosing fuses in Fusarc range.
UTE technology will results in choosing fuses in Solefuse range.
Ecodial selects the fuses rating according to voltage and transformer power in order to:
break short-circuit current across the terminal of the transformer secondary,
prevent unexpected tripping due to transformer inrush current.
Type of MV relay
Digital and self-powered relays are available in Ecodial providing transformer protection against:
internal short-circuits in MV windings,
internal short-circuits in LV windings,
short-circuits on LV cable or busway between transformer and LV circuit-breaker
it’s also a back-up for main LV circuit-breaker.
This type of protection is also known as ANSI 50/51.
Digital relays
Ecodial calculates default settings with 2 definite-time thresholds for short-circuit detection upstream the
transformer.
The lower threshold is set:
20% lower than minimum LV short-circuit current
seen from MV side Ikmin(LV),
time delay to 0,5 s to prevent tripping during
inrush current.
The upper threshold is set:
greater than transformer assigned current,
greater than transformer inrush current,
greater than the greatest LV short-circuit current
seen from MV side,
20% lower than minimum MV short-circuit current
Ik2min,
time delay is set as lower as possible (0,05 s).
With:
Is = current setting,
T = time delay setting at 10 x Is.
k α β
SIT 0,14 0,02 2,97
VIT 13,5 1 1,5
LTI 120 1 13,33
EIT 80 2 0,808
UI 315,2 2,5 1
1000
100
10
t (s)
1
1 10 100 1000 10000 100000
0,1
0,01
0,001
I (A)
The default value proposed by Ecodial depends on the UPS characteristics and power:
for small UPS (low power) the connections are common by default,
for medium and high power UPS the connections are separated by default.
When the default value is “Common” it’s possible to change it to “Separated”, in that case the lock next to
the parameter closes .
Common Normal and Bypass connection Separated Normal and Bypass connection
Here is an example with 2 feeders connected downstream an USP with respective power demand:
- 100 kVA,
- 10 kVA.
Taking into account the diversity factor of 0.9 on bubsar WC15 the total power demand for the UPS is 99
kVA.
The following table shows the solutions proposed by Ecodial depending the requested level of
redundancy.
UPS mode
When UPS inputs connection are separated, Ecodial requests the definition of an operating mode to
describe the operating conditions for bypass input.
Once an operating mode is created for bypass operating condition, the UPS mode parameter has to be
set to “Bypass”.
Number of UPS
This is the total number of UPS unit for the solution including:
UPS to supply power demand,
UPS for redundancy, refer to UPS requested redundancy.
Number of bypass
Depending on the USP technology, in case of multiple unit solution, 2 types of bypass can be proposed:
solution with one bypass per UPS unit,
solution with a bypass common to several units.
In case of a solution with common bypass, the number of bypass displayed by Ecodial will be lower than
the number of UPS unit.
One bypass per UPS unit Common bypass for several units