Chapter_2
Chapter_2
Chapter_2
CHAPTER 2
OF AN IPM MACHINE
A model of a 3 phase PM machine is shown in Figure 2.1. Both the abc and the dq
axes are shown in the figure. The magnetizing current, due to the presence of the magnet, is
represented in Figure 2.1 by the current source if . The fictitious current source ( along with
the associated field winding Lmd) will be used in the derivation to follow to obtain an
expression for the flux which is equivalent to the flux created by the presence of the magnet
It is assumed in the following derivation that the rotor speed of the machine is
constant . Thus, no current flows in the damper windings contained within the rotor and
their presence may be ignored. It is also assumed that the machine is balanced.
d
va = λ a + ia r1
dt
d
vb = λ b + i b r 1
dt (2.1)
d
vc = λ c + i c r 1 ,
dt
where va , vb , vc are the a,b,c stator terminal voltages , λa , λb ,λc are the flux linkages in
the abc plane, ia , ib ,ic are the abc stator currents, and r1 is the stator resistance of each phase
14
of the stator winding. Thus, the assumption has been made that the resistances for each
The flux linkages expressed in terms of the stator and terms of the current are
⎡λ a ⎤ ⎡ L aa L ab Lac ⎤ ⎡i a ⎤ ⎡ Lafd 0 0 ⎤ ⎡i f ⎤
⎢ ⎥ ⎢ ⎥⎢ ⎥ ⎢ ⎥⎢ ⎥
⎢ λ b ⎥ = ⎢ Lba Lbb Lbc ⎥ ⎢ib ⎥ + ⎢ Lbfd 0 0 ⎥ ⎢ 0 ⎥ . (2.2)
⎢ ⎥ ⎢ ⎥⎢ ⎥ ⎢ ⎥⎢ ⎥
⎣⎢ λ c ⎦⎥ ⎣⎢ Lca Lcb Lcc ⎥⎦ ⎢⎣ i c ⎥⎦ ⎣ Lcfd 0 0 ⎥⎦ ⎢⎣ 0 ⎥⎦
⎢
The inductances given in Equation (2.2) will be kept in their symbolic form, transformed
into their equivalent dq axis counterparts, and then be defined in terms of the physical
construction of machine.
Due to the salient nature of the rotor, the inductances of Equation (2.2) are functions
of the position of the rotor and (assuming that the rotor is spinning) are functions of time.
This means that the inductance parameters are constantly changing - making the analysis of
the machine very difficult in its present form. A transformation commonly referred to as
Park’s transformation allows the equations describing the machine to be transformed into a
reference frame where the inductances are not functions of time. The reference frame
chosen to accomplish this goal is dependent upon the type of machine being looked at. For a
synchronous machine, this reference frame is that of the rotor. In other words, the stator
voltages, currents, and inductances will be projected onto the rotor side of the machine and,
thus, be rotating at the same speed with which the rotor is spinning. With this
accomplished, the inductances no longer vary with the position of the rotor.
16
The transformation of a 3 phase balanced voltage, current, or flux linkage from the
⎡ ⎤
⎢cos( θ ) 2π 2π ⎥
⎢ cos( θ - ) cos( θ + )⎥
⎢ 3 3 ⎥
2 ⎢ ⎥
T( θ ) = ⎢ sin( θ ) 2π 2π ⎥ ,
3⎢ sin( θ - ) sin( θ +
3 ⎥⎥
)
⎢ 3
⎢ ⎥
⎢ 1 1 1⎥
⎢⎣ 2 2 2 ⎥⎦
where
and θ denotes the reference frame chosen. For the rotor reference frame, θ=θr . Expressing
2 2π 2π
hq = [ ha cos( θ r ) + hb cos( θ r - ) + hc cos( θ r + )]
3 3 3
2 2π 2π
hd = [ ha sin( θ r ) + hb sin( θ r - ) + hc sin( θ r + )] (2.4)
3 3 3
1
h o = [ h a + hb + h c ] ,
3
where, for balanced conditions, h0 = 0 and the o term will, from this point forward, be
ignored. So, using Equation (2.4), the flux linkages may be expressed in the dq plane as
17
2 2π 2π
λ q = [ λ a cos( θ r ) + λ b cos( θ r - ) + λ c cos( θ r + )]
3 3 3
(2.5)
2 2π 2π
λ d = [ λ a sin( θ r ) + λ b sin( θ r - ) + λ c sin( θ r + )] .
3 3 3
d λq 2 dθ 2π dθr 2π dθr
= - [ λ a sin( θ r ) r + λ b sin( θ r - ) + λ c sin( θ r + ) ]
dt 3 dt 3 dt 3 dt (2.6)
2 d λa d λb 2π d λc 2π
+ [ cos( θ r ) + cos( θ r - )+ cos( θ r + )] .
3 dt dt 3 dt 3
Comparing the first bracketed expression of Equation (2.6) with the expression for λd in
Rearranging the voltage equation of (2.1) in terms of the rate of change of flux linkage
gives
d λa
= va - i a r 1
dt
d λb
= vb - i b r 1 (2.8)
dt
d λc
= vc - ic r 1 .
dt
Substituting Equation (2.8) into the second bracketed expression of (2.6) gives
18
d λa d λb 2π d λc 2π
cos( θ r ) + cos( θ r - )+ cos( θ r + )=
dt dt 3 dt 3
2π 2π
[ v a cos( θ r ) + vb cos( θ r - ) + vc cos( θ r + )] -
3 3 (2.9)
2π 2π
[ i a r 1 cos( θ r ) + ib r 1 cos( θ r - ) + i c r 1 cos( θ r + )]
3 3
= v qs - i qs r 1
Substituting the results of Equations (2.7) and (2.9) into (2.6) gives
d λq d θr
= - λd + v qs - i qs r 1 . (2.10)
dt dt
Letting
d dθr
p= , and ω r = ,
dt dt
then
Similarly, taking the derivative of the d-axis flux linkage of Equation (2.5) gives
19
d λd 2 dθ 2π dθr 2π dθr
= [ λ a cos( θ r ) r + λ b cos( θ r - ) + λ b cos( θ r + ) ]
dt 3 dt 3 dt 3 dt
(2.13)
2 d λa d λb 2π d λc 2π
+ [ sin( θ r ) + sin( θ r - )+ sin( θ r + )] .
3 dt dt 3 dt 3
dθr dθ 2π dθr 2π dθr
λq = [ λ a cos( θ r ) r + λ b cos( θ r - ) + λ c cos( θ r + ) ] . (2.14)
dt dt 3 dt 3 dt
Comparing the first bracketed expression in Equation (2.13) with the equation for q axis flux
Substituting the results of Equation (2.8) into the second bracketed expression of Equation
(2.13) gives
d λa d λb 2π d λc 2π
sin( θ r ) + sin( θ r - )+ sin( θ r + )=
dt dt 3 dt 3
2π 2π
[ v a sin( θ r ) + vb sin( θ r - ) + vc sin( θ r + )] -
3 3
2π 2π
[ i a r 1 sin( θ r ) + ib r 1 sin( θ r - ) + i c r 1 sin( θ r + )] (2.15)
3 3
= vds - i ds r 1 .
Substituting the results of Equations (2.14) and (2.15) into Equation (2.13) gives
d λd d θr
= λq + vds - i ds r 1 . (2.16)
dt dt
20
After rearranging Equation (2.16) and substituting Equation (2.10) into it, the final
In order to obtain the individual self and mutual inductance terms ( given in Equation
(2.2 )), the parameters may be defined in terms of the physical construction of the machine ,
i.e. number of windings, physical dimensions, etc. , and then the equations obtained may be
transformed into the dq reference frame. Alternatively, as was done in this thesis, the flux
linkage equations may be transformed directly into the dq rotor reference frame ( θ equals
θr) and the q and d axis inductances may be defined directly in that frame of reference.
Thus,
where
and
⎡ L afd 0 0 ⎤ ⎡ Lmd 0 0⎤
⎢ ⎥ ⎢ ⎥
T( θ ) ⎢ Lbfd 0 0 ⎥ = ⎢ 0 Lmdr 0⎥ .
⎢ ⎥ ⎢ ⎥
⎢⎣ Lcfd 0 0 ⎥⎦ ⎢⎣ 0 0 L mqr ⎥⎦
It is worthwhile to reiterate that the field current if is fictitious and has been used to
represent the flux linkage from the magnet source. From this point forth the term λe will be
used instead of the product term if * Lmd . Since the rotor speed is assumed constant, idr and
λ d = Ld i ds + λ e
(2.19)
λ q = Lq i qs ,
where
Ld = Lls + Lmd
L q = Lls + Lmq ,
and Lmd and Lmq are the d and q axis mutual inductances and L ls is the leakage in the
stator.
22
The d and q axis mutual inductances are given as [12]
Lmq = C q Lm
(2.20)
L md = C d Lm ,
where Lm is the inductance of a machine with a uniform air gap and no magnets. This
inductance is determined from the flux linking with N1 Cw effective turns, and is given as
2
N 1 C w Di L - 8 H ,
L m = 1.273 µ o m1 ( ) 10 (2.21)
P g
where all the terms given in Equation (2.21) are in meter, kilogram, second (MKS) units
P = number of poles
L = core length
Cq and Cd are factors which account for the presence of the magnets and are, for an interior
where
The open circuit magnet flux λe for an IPM machine is given as [12]
4.44 ( π Di L) !
λe = Ni Cw
-8
B f * 10 , (2.23)
2π P
where B!f is the amplitude of the fundamental flux density created by an individual magnet.
In summary, the voltage and flux equations needed to analyze a permanent magnet
v qs = p λ qs + i qs r s + λ ds ω
(2.24)
v ds = p λ ds + i ds r s - λ qs ω ,
where
λ ds = Lds i ds + λ e
λ qs = L qs i qs ,
24
and the subscript s on the q and d axis stator terms has been added, rs has replaced r1 as
the symbol used to represent the stator resistance, and the subscript r has been dropped from
ω. Under steady-state, the derivatives of the state variables of Equation (2.24) are zero so, at
V qs = I qs r s + λ ds ω
(2.25)
V ds = I ds r s - λ qs ω .
A d-q axis schematic diagram representing the equations given in (2.25) is shown in Figure
2.2
Figure 2.2. Schematic diagram representing the steady state q and d axis voltage equations
of a PM machine
25
2.2 Determination of Parameters of the IPM
machine is to find what the parameters of the machine are. Due to the effects of saturation at
heavy load and demagnetization of the magnet at light loads, the parameters of the machine
change significantly as the load presented to it changes. Thus, the parameters (namely the
mutual inductances in the d and q axes and the flux linkage created by the magnet) must be
Generally, when effects due to saturation are included in an analysis, the parameters
are made functions of either the total mutual flux λmm or the total stator current Is. The
decision was made to make the parameters functions of stator peak current because, when
the parameters were plotted as a function of flux, there were regions in which two possible
values of a particular parameter could be obtained for a single value of flux (which could be
The parameters are found by using the equations given in Equation (2.25) and
V qs = r s I qs + ω Lds I ds + ω λ e
(2.26)
V ds = r s I ds - ω Lqs I qs .
26
The stator resistive value rs was found by applying a dc voltage across two terminals
of the stator and measuring both the voltage and the current which flowed through the
terminals ( see Figure 2.3). The stator resistance for a single phase is given as
V dc
rs = . (2.27)
2 I dc
The voltages and currents in Equation (2.26) were found by varying a three phase
balanced resistive load from a high value to a low value and recording the terminal voltage
and the current output from the generator. The measurements made were the line to line
voltages and the phase currents. In order to convert the voltages and currents into their dq
components, the torque angle δ was needed. The power factor of the machine is also needed
in parameter determination, but, since the generator was feeding a resistive load, the current
out of the generator was in phase with the voltage at the terminals, so the power factor was
27
unity. The torque angle was found by measuring the difference in angle of the voltages of
a search coil located across phase “a” of the stator and the terminal voltage appearing at the
stator terminal of phase “a.” This method was not an ideal way to measure the torque angle
because the oscilloscope used to measure the angle between the two voltages gave a varying
readout even though the load and speed of the generator were constant. An average of the
numbers was taken and used as the torque angle. It would have been much easier (and
probably more accurate) to have a commercially available torque angle measuring device;
however, no such device was available. Nevertheless, the strong corroboration between
measured and predicted results suggests that the method used was an acceptable means of
Once the stator voltages, currents, and torque angle are known, the dq voltages and
V qs = V s Cos( δ )
V ds = - V s Sin( δ )
(2.28)
I qs = I s Cos( γ )
I ds = - I s Sin( γ ) ,
where Vs is the peak line to neutral voltage, Is is the peak stator current, and γ is the sum of
the torque angle δ and the power factor angle θ. Since the power factor is unity (since the
With the dq voltages and currents and the stator resistance known, the inductance
V ds - r s I ds
L qs = - . (2.29)
ω I qs
The inductance in the d axis and the magnet flux linkage are not as easy to find as the q axis
inductance. The two terms are contained in the same equation and are, in a sense, coupled
together.
One method of finding the magnet flux involves running a no load test on the PM
machine for a range of frequencies and measuring the terminal voltage of the machine and
the voltage across the terminals of the search coil. An empirical relationship between the
search coil voltage and the magnet voltage (and thus the magnet flux linkage) can be
developed since, at a no load condition, the terminal voltage of the machine is equal to the
magnet voltage. Figure 2.4 shows a plot of the rms voltage of the magnet vs. the air gap
voltage for both the series connection (high voltage) and the parallel connection (low
The low voltage connection was not used in any of the experiments reported in this
thesis (except for the one just described). The main reason for this is that, since the machine
is being operated in generator mode, one would normally like a high terminal voltage and
the low voltage connection is, as one would expect, one half of the terminal voltage of the
This brings up one other point of interest, which is that one would ideally like to
have a generator having a magnet voltage greater than 120 volts rms when operating at 60
29
100
90 + E o h v = . 1 6 8 3 * V a g -. 1 1 2 8
80 o Eo l v =. 0 8 3 9 * Va g +. 1 8 3 5
70
60
Eo (V)
50
40
30
20
10
0
100 200 300 400 500 600
A i r g a p v o l t a g e ( mV )
Figure 2.4. Measured line to neutral rms terminal generator voltage vs air gap voltage for no
load condition for machine connected in high and low voltage stator connections
30
Hertz since most loads were designed to operate at or near that particular voltage.
Although not shown explicitly on Figure 2.4, the machine is operating at 60 Hertz when the
air gap voltage is approximately 520 mv. This operating point corresponds to a magnet
voltage of about 88 volts line to neutral rms which is certainly low if one wanted to drive, for
example an induction motor with it. As will be seen in subsequent chapters, shunt capacitors
placed at the terminals of the PM machine boosts the terminal voltage, but a better method
would be to design a PM machine having a magnet voltage of around 130 volts when
operating at 60 Hertz. Incidentally, the lower voltage of this IPM machine is not an
motor.
The empirical relationship between the air gap voltage (Vag) and the magnet voltage on a per
With this relationship established, the magnet voltage (and thus the magnet flux) could be
approximated under load conditions by measuring the air gap voltage at each operating
condition. While this method is not entirely accurate since, under load conditions, the
voltage across the search coil is also affected by the current flowing in the mutual
inductances of the d and q windings of the stator, the approximation seems reasonable and,
absent the use of finite element analysis, there is little other option but to use this method if
the d axis inductance and the magnet flux terms are to both remain as functions of the
operating conditions.
31
After the magnet flux term has been determined (by λ e = E o / ω), then Lds can be
found by
V qs - r s I qs - ω λ e
L ds = . (2.31)
ω I ds
The plots of Lqs, Lds, and λ e are given in Figures 2.5-2.8. The empirical relationships
1
ln( ) = - .0013 Is4 + .0293 I3s - .2303 Is2 + .8684 Is + .790
Lqs
1
ln( ) = - .0011 Is4 + .0251 I3s - .210 Is2 + .9096 Is + 1.505 (2.32)
Lds
λ e = .0002 I3s - .0041 Is2 + .0208 Is + .1863 .
larger than the q axis inductance; however, comparing the magnitudes of Lqs and Lds in
Figures 2.5 and 2.6, it can be seen that Lqs is larger. This phenomenon, called inverse
saliency, is caused by the magnet depth appearing as basically an air gap in the d-axis. As
the machine is loaded, it can also be seen that the magnet voltage Eo first increases and then
decreases. The initial increase in magnet voltage is due to the fact that, at very light loads,
the bridge becomes highly saturated and much of the magnet flux flows through it and does
It was mentioned earlier in this section that the reason the parameters were made
functions of the peak stator current and not the total flux linkage was that the when the
32
0.3
0.25 + E x p e r i me n t
- Fi t
0.2
Lqs [H]
0.15
0.1
0.05
0 1 2 3 4 5 6 7 8
Is p e a k [ A ]
0.12
+ E xp
0.1
- Fi t
0.08
Lds [H]
0.06
0.04
0.02
0
0 1 2 3 4 5 6 7 8
Is p e a k [ A ]
0.22
0.21
0.2
Ma g ne ti c F lux [Wb ]
+ E xp
0.19 - Fi t
0.18
0.17
0.16
0.15
0.14
0.13
0.12
0 1 2 3 4 5 6 7 8
Is p e a k [ A ]
0.3
0.25
0.2
Lqs (H)
0.15
0.1
0.05
0.18 0.2 0.22 0.24 0.26 0.28 0.3 0.32
M u t u a l F l u x [ Wb ]
Figure 2.8. Measured q axis inductance vs peak mutual flux
36
parameters were plotted as a function of the total mutual flux linkage λmm, there were
regions in which two possible solutions exist. An example of this is shown in Figure 2.8
where the q axis inductance is plotted vs the mutual flux linkage. It can be seen from the
figure why determining Lqs from a given value of λmm would be difficult. For example, if
λmm was given as 0.28 Wb, then Lqs could either be 0.1 or 0.15 H. The same problem was