20240730_datasheet_easyair_sns212_MC
20240730_datasheet_easyair_sns212_MC
20240730_datasheet_easyair_sns212_MC
EasyAir
SNS212 MC
Datasheet
EasyAir SNS212 MC
The Philips EasyAir SNS212 MC is the ideal solution for per-luminaire control of new
light luminaires. This new generation sensor features all functions of its predecessor
SNS210 MC while providing the technical basis for future innovations. It combines
occupancy and daylight sensing in a single, compact package for easy OEM
luminaire assembly. EasyAir SNS212 MC operates with Xitanium SR or D4i certified
drivers via a simple two-wire connection between sensor and driver, thus
eliminating the need for multiple components and auxiliary devices. The result is a
cost effective and easy to design-in solution ideal for energy savings. An intuitive
app makes configuration and commissioning during and after installation fast and
easy using Philips MasterConnect App.
July 2024
Ordering Information
Product Data
All specific ations are typical and at 25 °C Tcase unless otherwise specified.
Physical Information
Overall Dimensions 50 mm x 19.0 mm x 31.5 mm
Housing (Luminaire Hole) 44 mm x 17 mm (l x w)
Net Weight per Piece 16 gr
Volume required Inside Luminaire (LxWxH) 50 mm x 19 mm x 24 mm
Color White, black and grey
Connectors WAGO 2060/BJB 46.132 2-pole terminal block rated for AWG24 to AWG18 solid or stranded wire
Input wire cross-section (solid conductor wire) 0.25 - 0.75 mm2, 18 - 24 AWG
Input wire cross-section (stranded wire) 0.3 - 0.5 mm2, 20 - 22 AWG
Electrical Information
Input Voltage Powered by SR driver low-voltage interface
Current Consumption 9.5 mA
Nominal Power Consumption 140 mW
Standby Power < 1 W on luminaire level (typically 0.6W), including driver standby power
Frequency 2.4 GHz
Activation Sensors regulate light output out-of-the-box with default settings
Occupancy Sensing
Type Passive infrared (PIR)
Occupancy Based Control Default enabled
Occupancy Mode Auto on/off, Manual on/off, Manual on/auto off; Red LED indicates occupancy detected
Group/Zone Occupancy Sharing Enabled/disabled
Group/Zone light behaviour Background light level, Eco on level
Eco-On Level 1 - 100%
Hold Time 2 - 100 minutes
Viewing Angle X = 62°, Y = 84° ( See detection pattern)
Background Light Level 1 - 100%
Prolong Time 2 - 100 minutes + infinite
Grace Fading 1 - 25 seconds
Fading to Switch On/Off 1 second
Daylight Sensing
Daylight based control Enabled/disabled. Default Enabled with target light level of “~500lux X Eco-ON%”.
Calibration Selectable. Light Level calibrated to “Max light output from fixture X Eco-ON%”.
Viewing Angle 40° (half value sensitivity); 2% cut-off point at 75°
Task Tuning
Field Task Level 0-100%
Tunable White With Philips FlexTune driver, default factory setting: 4000K
Environment & Approbation
Operating Ambient Temperature Range 0 °C to 55 °C
Operating Humidity 0 – 85% non condensing
Storage Temperature -25 °C - 85 °C
Storage Humidity 0-95% non condensing
Ingress Protection IP20
Max Case Temperature (Tcase) 55 °C
Agency Approbations CE, ENEC, RTTE, EMC, RCM, SRRC
Warranty 5 years
Digital Interface Xitanium SR
16.8 MAX
X
43.8 MAX
19.0 MAX
50.0 MAX
7.5 MAX
24.3 MAX
43 43
16.0 16.0
Mounting in cut-out in sheet matal (thickness 0.7 mm to 1.2 mm), tolerance +/-0.2 mm
44.0
2.3
17.0
64 Max.
60 ± 0.2
24 Max.
22 ± 0.2
8 Max.
Easy Air SNS212 MC can be mounted outside of the luminaire using the recessed ceiling mount bracket CMP/w. For cut-
out in the ceiling and mounting, refer the figures below. All dimensions are in mm.
Please note that below accessory CMP/w does not contain a sensor. Assembly of sensor with CMP accessory should be
carried out by OEM or installer. The wiring should be kept <2m from Xi SR Driver or SR Bridge.
74
63
Ø 4
7
Ø
46
Wiring Diagram
Connectors
DA- LED+
EASYAIR LED+
DA+
LED-
GROUND
NC XITANIUM SR LED-
Use 0.75 mm2 solid copper wire,
rated >= 600 V / 90 °C. NC
LED DRIVER LEDset
NEUTRAL GNDset
Strip wire to 8 mm.
LINE
Connectors NFC ANTENNA
(non-polarized)
EasyAir SNS212 MC
Occupancy Sensing
The detection area for the movement sensor can be roughly divided into two parts:
• Minor movement (person moving ≤ 0.9 m/s).
• Major movement (person moving ≥ 0.9 m/s)..
Eco-on level
(configurable)
Hold time
Gr nfig
(co
ac ura
(configurable)
ef
ad ble)
n
ing
switch o
LIGHT LEVEL
Background level
(configurable)
(fixed)
Fade (fixed)
Fade to
Prolong time
to sw
(configurable)
itch o
ff
T1 T2 T3 T4 T5 T6 T7
Task level
(configurable)
Hold time
Gr nfigu
(configurable)
(co
ac
Eco-on level
e f rabl
(configurable)
ad e)
ing
Background level
(configurable)
Fad (fixed
on
Prolong
(fix itch-
e to
Manual time
dim-up (configurable)
ed)
w
swit
command
to s
ch-
)
e
Fad
off
Daylight Sensor
The light sensor measures the total amount of light in a circular field of ≈ 80% of the PIR detection area. The following
aspects should be observed during installation:
As a guideline the formula 0.72 x h can be used to calculate the minimum horizontal distance between the window
and sensor whereby h is the vertical height of the sensor measured from the bottom of the window.
Light Fixture
Window
40˚
Field of View
1.0
Output current (Normalized)
Wavelength (nm)
https://www.lighting.philips.com/prof/led-
electronics/masterconnect-system/
masterconnect-sensors/
LP_CF_9218075_EU/family
This product includes software licensed under terms that require Signify B.V. to display the following notice:
CmBacktrace 1.3
Disclaimer
©2024 Signify Holding B.V. All rights reserved.
Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N.V. All
other trademarks are owned by Signify Holding or their respective owners.
UK importer address: 3 Guildford Business Park, GU2 8XG
07/2024
Data subject to change