APPLICATIONS
The Hochiki ACC-V Multi-Criteria Sensor is particularly suited for
detecting smoke produced by a wide range of combustibles found in
various applications. Temperature monitoring is achieved by a ther-
mistor placed for optimum sensitivity. Hochiki's unique design allows
fast response to flaming fires as well as smoldering fires while mini-
mizing false alarms.
OPERATION
The ACC-V chamber consists of a light-emitting diode (LED) and
photodiode arrangement. The chamber is designed such that light
emitted by the LED cannot normally reach the photodiode. In the
STANDARD FEATURES event of fire, particles of smoke enter the chamber and scatter the
light. As the smoke level increases, the scattering effect increases,
Low profile - only 2.00” high, including base causing more light to hit the photodiode. The chamber contains a
unique design which allows smoke to enter the chamber while pre-
Simple and reliable device addressing venting external light from affecting the photodiode. The photodiode
Automatic compensation for sensor contamination input level is sampled to sense smoke density. When the smoke den-
sity exceeds a preset threshold the sensor transmits an interrupt to
Built-in fire test feature the fire control panel indicating a fire condition. The fire alarm control
panel can adjust the sensor threshold to compensate for contamina-
Uses the noise-immune Digital Communication tion.
Protocol (DCP), which utilizes interrupts for fast The ACC-V heat portion incorporates a highly linear thermistor circuit,
response to fires with two thermistors mounted externally. The specially designed cover
protects the thermistor while allowing maximum air flow. The thermis-
Two built-in power/alarm LEDs tor circuit produces a voltage proportional to temperature which is
Programmable non-polling LEDs scaled, and transmitted as a digitally encoded value to the control
panel. When the ambient temperature exceeds a preprogrammed
Non-directional smoke chamber threshold (fixed temperature), the sensor transmits an interrupt to the
control panel indicating a fire alarm. The fire alarm control panel can
Vandal resistant security locking feature adjust the sensor threshold for different standard's requirements.
Removable smoke labyrinth for cleaning or Up to 127 devices are permitted on each SLC loop. A sensor address
replacement can be set by a hand-held programming unit. The sensor mounts to
an electronics-free base and incorporates a locking mechanism for
SPECIFICATIONS secure installation. The base provides mounting slots, terminals for
Operating Voltage 17-41 VDC field wiring and a third contact for a remote indicator/LED. The sensor
incorporates dual LEDs for easy viewing of sensor status.
Standby Current 450μA
Alarm Current 450μA SENSOR SPACING
Transmission Method DCP - Digital Communication Protocol Smoke sensor spacing shall be in compliance with NFPA 72. For
Maximum Humidity 95% RH Non-Condensing smooth ceilings and in the absence of specific performance-based
design criteria, the distance between smoke sensors shall not exceed
UL Temperature Range 135°F to 150°F a nominal spacing of 30 ft. (9.1m) or all points on the ceiling shall
(57° C to 65° C) have a sensor within a distance equal to or less than 0.7 times the
Operating Temperature 14°F to 122°F nominal 30 ft. (9.1m) spacing. Sensors shall be located within a dis-
tance of one-half the nominal spacing, measured at right angles from
Range (-10°C to 50°C) all walls or partitions extending upward to within the top 15 percent of
Sensitivity Range 0.7-4.0%/FT@300FPM the ceiling height. For additional instructions see NFPA 72.
0.7-3.86%/FT@2000FPM
0.7-2.65%/FT@4000FPM
PRODUCT LISTINGS
Air Velocity Range 0-4000 fpm
Color & Case Material Bone - ABS Blend California State
Weight 4.2oz (5.9 oz. with 4” base) Fire Marshal
Dimensions 3.9”D x 1.8”H 7272-0410:0204
Bases YBN-NSA-4, HSB-NSA-6, S1383 3054858
ASB, SCI-B4, SCI-B6, ASBL
Specifications subject to change without notice. Continued on back.
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install Hochiki's ACC-V (Multi-Criteria Sensor) as indicated on the plans. The multi-criteria sensor
head and twist lock base is UL Listed and it’s compatible with an UL Listed fire alarm control panel.
The base permits direct interchange with the Hochiki ALG-V, ALK-V/ALK-V2, ALN-V photoelectric type smoke sensors, AIE-EA
ionization type smoke sensor, ATG-EA, ATJ-EA heat sensors and the ACA-V, ACC-V multi-criteria sensor.
The sensitivity of the sensor is capable of being measured by the control panel.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature is
optional and can be implemented when required.
BASES
The Hochiki HSB-NSA-6 and the YBN-NSA-4 mounting bases are electronics free and are a simple rugged design with screw
terminals for wiring connections. A common mounting base allows sensor interchange and maintains loop continuity when
sensors are removed. A simple anti-tamper head locking system is provided which is enabled by removing a small plastic tab on
the back of the sensor. Once locked, the head can be removed using a small diameter screwdriver
UL LISTED
POWER
LIMITED
SUPPLY
* HSB-NSA-6
8mA MAX. 8mA MAX.
OUTPUT OUTPUT
*-OPTIONAL WIRING CONFIGURATION FOR REMOTE OUTPUT
UL LISTED
COMPATIBLE
CONTROL
PANEL
8mA MAX.
OUTPUT
UL LISTED
POWER YBN-NSA-4
LIMITED
SUPPLY * 8mA MAX.
OUTPUT
NOTE: Fire alarm control panel compatibility is required for DCP products. DCP communications protocol allows system
components (DCP sensors AIE-EA, ALG-V, ACA-V, ACC-V, ALK-V, ALN-V, ATJEA and ATG-EA, bases and modules)
to be used concurrently on a system's SLC (Signaling Line Circuit).
Hochiki America Corporation ACC-V Multi-Criteria Sensor Specifications subject to change without notice.