Fsc-851 (A) Intelliquad™: Advanced Multi-Criteria Detector With Four Unique Sensing Elements

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

DN-60412:B

FSC-851(A) IntelliQuad™
Advanced Multi-Criteria Detector
with four unique sensing elements
Intelligent / Addressable Devices

General
This latest addition to Notifier’s Advanced Detection line
combines four complementary technologies into one device to
convey accurate fire sensing information for locations where
absolute certainty is required.
It is designed for use with Notifier’s ONYX series fire alarm
control panels (FACPs).

Features
• Unique ability to detect all four major elements of a fire
• Highest nuisance alarm immunity
• Advanced algorithms interpret and respond to the multiple
inputs
• Six levels of sensitivity
• CO sensing for fastest response to slow developing, smol-

60412cov.tif
dering fires
• Fully integrated infrared sensing to support the fire alarm
decision
• Automatic drift compensation of smoke sensor and CO cell
• Superior EMI protection
• Twin LED indicators providing 360° visibility NOTE: The CO cell is specifically deployed as a component of
• LEDs can be panel controlled to blink, latch on, latch off smoke detection in this device. This device is not listed for applica-
tions in which standalone CO detection is required for life safety.
• Built-in test switch
The IR light sensor recognizes specific situations such as
This plug-in fire detector combines four separate sensing
welding and makes adjustments rapidly to further reduce the
elements in one unit:
potential for nuisance alarms. The thermal detection function
1. Electrochemical cell technology that monitors carbon uses thermistor technology with a software-corrected linear
monoxide (CO) produced by smoldering fires temperature response to offer exceptional nuisance alarm
2. Infrared (IR) sensing that measures ambient light levels immunity and excellent fire detection.
and flame signatures
3. Photo-electric smoke detection Product Line Information
4. Thermal detection for temperature monitoring FSC-851: IntelliQuad Advanced Multi-Criteria Detector
The integration of continual monitoring for all four major FSC-851A: ULC-listed version
elements of a fire has enabled Notifier to create a detector that
responds more quickly to an actual fire with the highest Accessories
immunity to nuisances. This advanced multi-criteria detector B710LP: Flanged mounting base. 6.1” (15.5 cm) diameter.
operates at a high immunity level, changing to become very
sensitive to identify those that should be ignored, reducing B710LPA: Flanged mounting base, ULC Listed.
false alarms. B710LPBP: Flanged mounting base. (Pack of 10)
Its on-board intelligence runs advanced algorithms that B200S: Intelligent sounder base, capable of producing a
dynamically adjust detection parameters to respond to the variety of tone patterns including ANSI Temporal 3.
inputs from the sensors, enabling instant response as ambient Compatible with System Sensor sychronization protocol.
conditions change. B200SA: Intelligent sounder base, capable of producing a
The program changes sensor thresholds, sensor gain, time, variety of tone patterns including ANSI Temporal 3.
delays, combinations, sampling rates, and averaging rates. If Compatible with System Sensor sychronization protocol, ULC-
any sensor fails, the detector automatically adjusts the listed.
sensitivity of the remaining sensors. It also recognizes a fault B200SR: Intelligent sounder base, Temporal 3 or Continuous
condition. tone.
The CO cell has an expected lifetime of approximately six B200SRA: Intelligent sounder base, Temporal 3 or Continuous
years. It is not a field replaceable component. An internal tone, ULC-listed.
timer signals the control panel to indicate the approach of the
CO cell’s end of life. Upon expiration, you should contact the B224RB: Relay base Screw terminals: up to 14 AWG (2.0
system supplier to arrange for replacement of the unit. mm²). Relay type: Form-C. Rating: 2.0 A @ 30 VDC resistive;
Detection is not compromised when the CO cell expires. The 0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive.
algorithms automatically adjust to properly weight the inputs Dimensions: 6.2" (15.748 cm) x 1.2" (3.048 cm)..
from the photo-electric, heat, and IR sensors. B224RBA: Relay base, ULC Listed.

DN-60412:B • 08/25/2010 — Page 1 of 2


B224BI: Isolator base. Dimensions: 6.2" (15.748 cm) x 1.2"
(3.048 cm). Maximum: 25 devices between isolator bases.
B224BIA: Isolator base, ULC Listed.

Listings and Approvals


• UL Listed: S911
• ULC Listed: S1115 (FSC-851A)

60412dia.wmf
• FM Approved
• CSFM: 7272-0028:0255

Specifications 4.0" 2.4"


(10.16 cm) (6.096 cm)
GENERAL SPECIFICATIONS
Size: Height: 2.4" (6.1 cm), Diameter: 4.0" (10.16 cm) FSC-851 IntelliQuad
Shipping Weight: 4.6 ounces Advanced Multi-Criteria Detector
Color: Ivory
Operating Humidity Range: 10 to 93% relative humidity
(non-condensing)
Application Temperature Range: 32°F to 100°F (0°C to
38°C)
ELECTRICAL SPECIFICATIONS
Operating Voltage Range: 15 to 32VDC
Maximum Standby Current: 200μA at 24VDC (no
communications)
Maximum Alarm Current (LED on): 7mA at 24VDC
SENSITIVITY SETTINGS & SUGGESTED APPLICATION
Level 1: 1% per foot (30.48 cm) of smoke. Very clean
environments - Laboratories.
Level 2: 2% per foot (30.48 cm) of smoke. Clean
environments - Offices.
Level 3: 3% per foot (30.48 cm) of smoke. Moderately clean
environments - Hotel Room, Dorm Room.
Level 4: 3% per foot (30.48 cm) of smoke with different
algorithm processing and weighting of sensor elements. Hotel
rooms near a shower, Boiler Rooms.
Level 5: 4% per foot (30.48 cm) of smoke. Equipment rooms,
Kitchens, Paint Shops.
Level 6: Thermal alarm at 135°F (57°C).
NOTE: Once the CO cell has reached the end of life, any device
set to Level 3 or Level 4 will default to Level 5 and Level 5 will drop
to 3%. The following sensitivities apply to devices with expired CO
cells:
Level 1: 1% per foot (30.48 cm) of smoke. Very clean
environments - Laboratories.
Level 2: 2% per foot (30.48 cm) of smoke. Clean
environments - Offices.
Level 5: 3% per foot (30.48 cm) of smoke. Moderately clean
environments - Hotel Room, Dorm Room.
Notifier®, System Sensor®, and FlashScan® are registered trademarks
Level 6: Thermal alarm at 135°F (57°C). and IntelliQuad™ is a trademark of Honeywell International Inc.
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com

Page 2 of 2 — DN-60412:B • 08/25/2010