FSL 751
FSL 751
FSL 751
FSL-751
Very Intelligent Early Warning (VIEW) Laser Smoke Detector
Intelligent/Addressable Devices
General
The Notifier FSL-751 VIEW Laser Detector is a revolutionary advance in early warning smoke detection technology. The unique design of this detector, combined with enhanced intelligent sensing algorithms in the Notifier AFP-300, AFP-400, NFS-640, NFS2-640, NFS-320, NFS-3030 or NFS2-3030 control panels, for smoke detection sensitivity that is up to 50 times higher than present photoelectric technology. Because of this high sensitivity, the FSL-751 can provide very early warning of slow smoldering fires. Its performance is comparable to present aspiration technology, at a substantially lower installed cost.
5306p2.jpg
5306p1.jpg
The FSL-751 uses an extremely bright laser diode, combined with special lens and mirror optics (U.S. patent pending), to achieve a signal-to-noise ratio that is much higher than traditional photoelectric sensors. In addition, the tightly focused light beam, combined with the intelligent sensing algorithms, allow the system to differentiate between dust and smoke particles. Because of this differentiation, the FSL-751 can be set to extremely high sensitivity, yet can reject false signals caused by larger airborne particles such as dust, lint, and small insects . The FSL-751 is an intelligent (analog/addressable) detector. Using CLIP mode, up to 99 FSL-751 detectors may be installed per loop. On FlashScan systems (NFS-640/NFS2640/NFS-320/NFS-3030/NFS2-3030), up to 159 addresses are available. The FSL-751 may be mixed in any combination with other Notifier intelligent sensors on the same loop and is quickly installed using the panel autoprogram feature. The FSL-751 has dual bi-color LEDs, which blink green in normal operation and illuminate steady red in alarm. FlashScan (U.S. Patent 5,539,389) is a communication protocol developed by Notifier for high speed communication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other protocols.
Using the enhanced intelligent sensing algorithms, the intelligent sensing system provides drift compensation (meeting UL requirements as a calibrated sensitivity meter), maintenance alert (3 levels), selection of 9 alarm levels and 9 pre-alarm levels, and report of drift compensation used and recent peak values. The system includes a self-learn sensitivity adjustment to set the pre-alarm level just above the peak levels sensed over long periods of time for each detectors actual environment. The system includes multi-detector algorithms that permit one sensor to consider readings from adjacent sensors to provide faster detection of fires.
6714recs.jpg
Features
Very Intelligent Early Warning (VIEW) smoke detection. Advanced laser light source and patented optical design. Sleek low-profile housing (1.66"/42.164 mm height). Notifier Analog Addressable communications protocol provides extremely reliable operation proven in millions of worldwide detector installations. Sensitivity: 0.03% to 1.00% for CLIP Legacy Systems 0.02% to 2.00% for Onyx Series panels. Rotary DECADE address switches. Set 01 99 on legacy systems and 01 159 on FlashScan systems (NFS-640, NFS2-640, NFS-320, NFS-3030, or NFS2-3030). These switches allow quick selection of address without resorting to binary switches, special programmers, or bar coding devices. Dual bi-color (red/green) LEDs flash green when Normal and are steady red in Alarm.
Compatible with the AFP-300, AFP-400, NFS-640, NFS2640, NFS-320, NFS-3030, and NFS2-3030 (all software releases). Dual LED design provides 360 viewing angle. Built-in magnetic test switch, or automatic test commanded from panel. Optional relay, isolator, or sounder bases.
ULC Listed: S911 MEA Listed: 3-02-E; 447-99-E (AFC-600) FM Approved (except NFS2-3030) CSFM: 7272-0028:218 BSMI: CI313066760036 CCCF: Certif. # 2004081801000015 U.S. Coast Guard: 161.002/42/1 (NFS-640)
Specifications
Operating voltage range: 15 to 32 VDC peak. Maximum average standby current: 230 A @ 24 VDC (no communication). 330 A @ 24 VDC (one communication every 5 seconds with LED blink enabled). Maximum alarm current: 6.5 mA @ 24 VDC (LED ON). Operating humidity range: 10% to 93% relative humidity, non-condensing. Operating temperature range: 0 to 38C (32 to 100F). Loop resistance: 40 ohms maximum. Dimensions: Height: 1.66 inches (42.16 mm) installed in B710LP base. Diameter: 4.0 inches (154.94 mm) installed in B710LP base; 4 inches (101.6 mm). Weight: 5.6 oz. (102 g).
Ordering Information
FSL-751: Laser Detector. Intelligent laser sensor with FlashScan capabilities. Mounts to one of the bases listed below.
BASES:
B710LPBP: Standard U.S. flanged low-profile base, package of ten (10). B710LPA: Same as B710LP, but with ULC listing. B501: Standard European Flangeless base. B501BP: Standard European flangeless base, package of ten (10). B501A: Same as B501BP, but with ULC listing. B501BH-2: Sounder base, includes B501 base. B501BH-2A: Same as B501BH-2, but with ULC listing. B501BHT-2: Sounder base assembly. Temporal three-tone. Includes B501 base. B501BHT-2A: Same as B501BHT-2, but with ULC listing. B224RB: Intelligent relay base. B224RBA: Same as B224RB, but with ULC listing. B224BI: Intelligent isolator base. Isolates SLC from loop shorts. B224BIA: Same as B224BI, but with ULC listing.
BASES AVAILABLE:
B710LP: 6.1 inches (154.94 mm) diameter. B501BP: 4.1 inches (104.14 mm) diameter. B501BH-2: Sounder base assembly, constant tone Includes B501BP base. B501BHT-2: Sounder base assembly, temporal three-tone. B224RB Relay Base: Screw terminals: Up to 14 AWG (2.00 mm). Relay type: Form-C. Rating: 2 A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive. Dimensions: 6.2 in. (157.48 mm) x 1.2 in. (30.48 mm). B224BI Isolator Base: Dimensions: 6.2 in. (157.48 mm) x 1.2 in. (30.48 mm). Maximum: 25 devices between isolator bases.
ACCESSORIES
F110: Retrofit replacement flange for BX-501 base. RA400Z: *Remote LED annunciator. 3 32 VDC. Fits U.S. single-gang electrical box. MOD400R: Detector sensitivity test tool. Use with most analog or digital multimeters. Satisfies requirement of NFPA72 for sensitivity testing. SMK400E: Surface mounting kit provides for entry of surface wiring conduit. For use with B501 base only. RMK400: Recessed mounting kit. For use with B501 base only. M02-04-00: Test magnet. M02-09-00: Test magnet with telescoping handle. XR2: Detector removal tool. Allows installation and/or removal of 700 Series detector heads from base in high ceiling installations. XP-4: Extension pole for XR-2. Comes in three 5-ft. (1.524 m) sections. *Supported by B710LP and B501 bases only.
Installation
The FSL-751 plug-in detector uses a separate base to simplify installation, service, and maintenance. A special tool allows maintenance personnel to plug-in and remove detectors without using a ladder. Mount base on a box which is at least 1.5" (38.1 mm) deep. Suitable mounting base boxes include: 4" (101.6 mm) square box. 3-1/2" (88.9 mm) or 4" (101.6 mm) octagonal box. Single-gang box (except relay or isolator base).
Notifier, FlashScan and VIEW are registered trademarks of Honeywell International Inc. 2007 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com
Page 4 of 4 dn-6886:b 02/25/09