FSP 851
FSP 851
FSP 851
General
6934pho1.jpg
Notifier 851 Series intelligent plug-in smoke detectors with
integral communication provide features that surpass conven-
tional detectors. Detector sensitivity can be programmed in
the control panel software. Sensitivity is continuously moni-
tored and reported to the panel. Point ID capability allows
each detectors address to be set with decade address
switches, providing exact detector location for selective main-
tenance when chamber contamination reaches an unaccept-
able level. The FSP-851 photoelectric detectors unique
optical sensing chamber is engineered to sense smoke pro- FSP-851 with B710LP base
duced by a wide range of combustion sources. Dual electronic
thermistors add 135F (57C) fixed-temperature thermal sens-
ing on the FSP-851T. FSP-851 and FSP-851T detectors are
6935pho1.jpg
compatible with all Notifier intelligent Fire Alarm Control Pan-
els (FACP).
FlashScan (U.S. Patent 5,539,389) is a communication pro-
tocol developed by Notifier engineering that greatly enhances
the speed of communication between analog intelligent
devices. Intelligent devices communicate in a grouped fash-
ion. If one of the devices in the group has new information, the
panels CPU stops the group poll and concentrates on single
points. The net effect is response speed greater than five
FSP-851T with B710LP base
times that of earlier designs.
Features
Sleek, low-profile design. Specification
Addressable-analog communication. Size: 2.1 (5.3cm) high x 4.1 (10.4cm) diameter installed in
Stable communication technique with noise immunity. B501 base, 6.1 (15.5cm) diameter installed in B710LP base.
Low standby current. Shipping Weight: 5.2oz. (147g).
Two-wire SLC connection. Operating Temperature: FSP-851, 0C to 49C (32F to
FlashScan (NFS-640, NFS-3030) and classic CLIP sys- 120F); FSP-851T, 0C to 38C (32F to 100F). Low temper-
tems (AFP-100, AFP-200, AFP-300, AFP-400, NFS-640, ature signal for FSP-851T at 45F +/- 10F (7.22C +/-
AM2020/AFP1010, NFS-3030) compatible. 5.54C).
Rotary, decimal addressing (1-99 on current classic sys- UL Listed Velocity Range: 0-4000 ft/min. (1219.2 m/min.),
tems, 1-159 on FlashScan systems). suitable for installation in ducts.
Optional remote, single-gang LED accessory (RA400Z). Relative Humidity: 10%-93% noncondensing.
Dual LED design provides 360 viewing angle. Thermal Ratings: Fixed-temperature setpoint 135F (57C).
Visible bi-color LEDs blink green every time the detector is
addressed, and illuminate steady red on alarm. DETECTOR SPACING AND APPLICATIONS
Remote test feature from the panel. Notifier recommends spacing detectors in compliance with
Walk test with address display (an address on 121 will blink NFPA 72. In low airflow applications with smooth ceiling,
the detector LED: 12-[pause]-1(FlashScan systems only). space detectors 30 feet (9.144m) for ceiling heights 10 feet
(3.148m) and higher. For specific information regarding
Built-in functional test switch activated by external magnet.
detector spacing, placement, and special applications refer to
Built-in tamper-resistant feature. NFPA 72. System Smoke Detector Application Guide,
Sealed against back pressure. document A05-1003, is available at systemsensor.com
Constructed of off-white Bayblend, designed to commer- FSP-851 and FSP-851T are listed for use in ducts, but they
cial standards, and offers an attractive appearance. are NOT listed for use inside duct smoke detector housings.
94-5V plastic flammability rating. See Duct Application Smoke Detectors Guide, document A05-
SEMS screws for wiring of the separate base. 1004, available at systemsensor.com, for details on pendant-
mount applications.
Optional relay, isolator, and sounder bases.
Backward compatible.
6833addr.wmf
Standby Current (max. avg.): 250A @ 24VDC (with no
communication enabled); 360A @ 24VDC (one communica-
tion every five minutes with LED enabled).
LED Current (max.): 6.5mA @ 24VDC (ON).
BASES AVAILABLE
B710LP: 6.1 (15.5cm) diameter.
B501: 4.1 (10.4cm) diameter.
B501BH or B501BHT: Sounder base assembly. Includes
B501 base.
B224RB Relay Base: Screw Terminals, up to 14AWG Address Dial on back of Detector
(2.0mm2); Relay Type, Form-C; Rating, 2.0A @ 30VDC resis-
tive, 0.3A @ 110VDC inductive, 1.0A @ 30VDC inductive;
Dimensions, 6.2 (15.748cm) x 1.2 (3.048cm) x 1.2
(3.048cm). 4762wir1.tif
Installation
FSP-851 plug-in detectors use a separate base to simplify
installation, service, and maintenance. A special tool allows
maintenance personnel to plug in and remove detectors with-
out using a ladder.
Mount base on an electrical backbox which is at least 1.5
(3.81cm) deep. Suitable mounting base boxes include: Wiring Diagram
4.0 (10.16cm) square box.
3.5 (8.89cm) or 4.0 (10.16cm) octagonal box.
Single-gang box (except relay or isolator base).
With B501BH or B501BHT base, use a 4.0 (10.16cm)
square box.
With B224RB or B224BI base, use a 3.5 (8.89cm) octago-
nal box, or a 4.0 (10.16cm) octagonal or square box.
NOTE: 1) Because of inherent supervision provided by the SLC
loop, end-of-line resistors are not required. Wiring T-taps or
branches are permitted for style 4 (Class B) wiring. 2) When
using relay or sounder bases, consult data sheet DN-2243 (ISO-X)
for device limitations between isolator modules and isolator bases.