SD365 Series
Addressable Photoelectric Smoke Detectors
Addressable Devices
The Fire•Lite® Alarms SD365(A), SD365R(A), and SD365HT(A)
intelligent plug-in smoke detectors are designed for both perfor-
mance and aesthetics, and are direct replacements for the SD355
Series. A new modern, sleek, contemporary design and enhanced
optical sensing chamber is engineered to sense smoke produced by
a wide range of combustion sources in accordance with more strin-
gent code standards.
Exclusively for use with Fire•Lite’s addressable fire alarm control
panels, the SD365(A) Series point ID capability allows each detec-
tor’s address to be set with rotary, decimal address switches, provid-
ing exact detector location for emergency personnel to quickly locate
a fire during its early stages, potentially saving precious rescue time
while also reducing property damage. Two LEDs on each sensor
light to provide a local, visible sensor indication.
The SD365(A) Series also offers 135°F (57°C) fixed temperature
thermal sensing on the SD365T(A) and a remote test capable detec-
tor on the SD365R(A) for use with DNR(A)/DNRW duct smoke
detector housings.
Features • Plugs into separate base for ease of installation and maintenance
SLC LOOP: • Separate base allows interchange of photoelectric, ionization and
thermal sensors
• Two-wire SLC loop connection
• Unit uses base for wiring OPTIONS:
• Compatible with LiteSpeed™ and CLIP protocol systems • Optional relay, isolator, and sounder bases
• Stable communication technique with noise immunity
Installation
ADDRESSING: SD365 Series plug-in intelligent smoke detectors use a detachable
• Addressable by device base to simplify installation, service and maintenance. Installation
• Rotary, decimal addressing instructions are shipped with each detector.
(Refer to the Fire•Lite panel manuals for device capacity.) Mount detector base (all base types) on an electrical backbox which
ARCHITECTURE: is at least 1.5" (3.81 cm) deep. For a chart of compatible junction
boxes, see DF-60059.
• Sleek, low-profile, stylish design
NOTE: Because of the inherent supervision provided by the SLC loop,
• Unique single-source design to respond quickly and dependably end-of-line resistors are not required. Wiring “T-taps” or branches are
to a broad range of fires permitted for Class “B” wiring only.
• Integral communications and built-in device-type identification When using relay or sounder bases, consult the I300(A) installation
• Built-in tamper resistant feature sheet I56-3626 for device limitations between isolator modules and isola-
tor bases.
• Remote test feature from the panel
• Walk test with address display (an address on 121 will blink the Construction
detector LED: 12-[pause]-1(LiteSpeed systems only)
These detectors are constructed of fire-resistant plastic. The SD365
• Built-in functional test switch activated by external magnet Series plug-in intelligent smoke detectors are designed to commer-
• Removable cover and insect-resistant screen for simple field cial standards and offer an attractive appearance.
cleaning
• Expanded color options Operation
Each SD365 Series detector uses one of the panel’s addresses
OPERATION:
(total limit is panel dependent) on the Fire•Lite Signaling Line Circuit
• Designed to meet UL 268 7th Edition (SLC). It responds to regular polls from the control panel and reports
• Factory preset at 1.5% nominal sensitivity for panel alarm thresh- its type and the status. If it receives a test command from the panel
old level (or a local magnet test), it stimulates its electronics and reports an
• LED “blinks” when the unit is polled (communicating with the fire alarm. It blinks its LEDs when polled and turns the LEDs on when
panel) and latches in alarm. commanded by the panel. The SD365 Series offers features and
performance that represent the latest in smoke detector technology.
• Low standby current
MECHANICALS: Detector Sensitivity Test
• Sealed against back pressure Each detector can have its sensitivity tested (required per NFPA 72,
• SEMS screws for wiring of the separate base Chapter 14 on Inspection, Testing and Maintenance) when installed/
connected to an Fire•Lite addressable fire alarm control panel. The
• Designed for direct-surface or electrical-box mounting
results of the sensitivity test can be printed for record keeping.
For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX:(877) 699-4105. Country of Origin: Mexico